1 762 1761P03 1762P01 Mounting flange AQM630 QAM21 Symaro Duct Temperature Senss QAM2161040 QAM2171040 Active senss f acquiring the air temperature in air ducts Operating voltage AC 24 V DC 13535 V Signal output DC 010 V 420 ma Use The QAM duct temperature senss are f use in ventilation and air conditioning plants as: Supply extract air temperature senss Limit senss, eg f minimum limitation of the supply air temperature Reference senss, eg f compensation of the room temperature as a function of the outside temperature Dew point temperature senss Measuring senss, eg f measured value indication f connection to a building automation and control system Type summary Type reference Probe length Measuring range Operating voltage Output signal QAM2161040 04 m 50+50 C AC 24 V ±20 % / DC 010 V DC 13535 V QAM2171040 04 m 50+50 C DC 13535 V 420 ma CE1N1762en 2014-07-30 Building Technologies
Ordering and delivery When dering, please give name and type reference, eg: Duct temperature sens QAM2161040 The sens is supplied complete with mounting flange AQM630 and cable entry gland M16 Equipment combinations All systems devices capable of acquiring and handling the sens s DC 010 V 420 ma output signal Function Burden diagram The sens acquires the air temperature via its sensing element whose resistance value changes as a function of the temperature This change is converted to a DC 010 V 420 ma output signal, depending on the type of sens The output signal cresponds to the selected temperature range Output signal, terminal I1 Mechanical design Burden [Ohm] 900 800 700 600 500 400 300 200 100 Inadmissible range! Admissible range 0 0 10 20 30 40 Operating voltage [DC V] 1762D02en Setting element The duct temperature sens consists of housing, printed circuit board, connection terminals and probe The 2-sectional housing is comprised of base and removable cover (snap-on design) The measuring circuit and the setting element are located on the printed circuit board inside the cover, the connection terminals on the base Cable entry is made via the M16 cable entry gland (IP 54) supplied with the sens which can be screwed into the housing Probe and housing are rigidly connected The sens is designed f screwed flanged mounting It can be fitted as follows: With the mounting flange supplied with the sens (recommended), which is to be fitted to the sens and then secured in accdance with the required immersion length, Without mounting flange (making use of the maximum immersion length) F that propose, the housing has 4 holes f fitting the sens directly to the air duct Range 1 2 3 Measuring range 1 2 3 Test function active U1 I1 10 V 5 V 0 V 20 ma 12 ma 4 ma 5 V 12 ma 1762Z01 2/6 Siemens Duct temperature senss QAM2161040, QAM2171040 CE1N1762en
Fault Engineering notes Cable routing and cable selection The setting element is located inside the cover It consists of 6 pins and a shting plug It is used to select the required measuring range and to activate the test function The different plug positions have the following meaning F the temperature measuring range: Shting plug in the left position (R1) = 050 C Shting plug in the mid position (R2) = 50+50 C (facty setting) Shting plug in the right position (R3) = 35+35 C F activating the test function: Shting plug in the hizontal position: The values accding to the table "Test function active" will be made available at the signal output In the event of fault, the output signal will reach 0 V (4 ma) after 60 seconds To power the sens, a transfmer f safety extra low-voltage (SELV) with separate windings f 100 % duty is required When sizing and electrically protecting the transfmer, local safety regulations must be observed When sizing the transfmer, the power consumption of the temperature sens must be taken into consideration F crect wiring, refer to the Data Sheets of the devices with which the sens is used The permissible cable lengths must be observed When laying the cables, it must be observed that the longer the cables run side by side and the smaller the distance between them, the greater the electrical interference Twisted pair cables are required f the secondary supply lines and the signal lines Mounting notes Mounting location F supply air temperature control: Downstream from the fan, if the fan is located after the last air handling unit Otherwise, after the last air handling unit with a minimum distance of 05 m F extract air temperature control: Always upstream of the extract air fan As a limit sens f the supply air temperature: As close as possible to the air outlet into the room F dew point control: Immediately after the spray trap of the air washer Manually bend the probe so that it lies diagonally across the duct in equally spaced windings across the entire duct cross-section The probe must not touch the duct wall Mounting Instructions are printed on the packaging Mounting positions Permitted: Not permitted: 1761Z03 Mounting examples min 200 mm max 70 mm 1 2 1761Z05 1761Z07 Siemens Duct temperature senss QAM2161040, QAM2171040 CE1N1762en 3/6
Disposal The devices are considered electronics devices f disposal in term of European Directive 2012/19/EU and may not be disposed of as domestic waste Dispose of the device via the channels provided f this purpose Comply with all local and currently applicable laws and regulations Technical data Power supply Power supply Operating voltage (QAM2161040 Safety extra-low voltage (SELV) AC 24 V ±20%, DC 13535 V AC/DC 24 V class 2 (US) Line lengths f measuring signal Functional data Degree of protection Electrical connections Environmental conditions Operating voltage (QAM2171040) Frequency External supply line protection (EU) Power consumption Perm cable lengths Copper cable 06 mm dia Copper cable 1 mm 2 Copper cable 15 mm 2 Measuring range Probe Probe length Minimum bending radius DC 135 35 V DC 24 V class 2 (US) 50/60 Hz at AC 24 V Fuse slow max 10 A Circuit breaker max 13 A Characteristic B, C, D accding to EN 60898 Power source with current limitation of max 10 A 1 VA 50 m 150 m 300 m 50+50 C (R2 = facty setting), 050 C (R1), 35+35 C (R3) 04 m 10 mm Sensing element Pt 1000 Time constant 30 s at 2 m/s Dead time <1 s Measuring accuracy in the range of 25+25 C 50+50 C ±075 K ±09 K Output signal, linear (terminal U1) DC 010 V 50+50 C 35+35 C 050 C, max ±1 ma Output signal, linear (terminal I1) 420 ma 50+50 C 35+35 C 050 C Burden refer to "Function" Protection degree of housing IP54 accding to EN 60529 Protection class III accding to EN 60730-1 Connection terminals f 1 x 25 mm 2 2 x 15 mm 2 Cable entry gland (enclosed) M 16 x 15 Operation Climatic conditions Temperature (housing) Humidity (housing) Transpt Climatic conditions Temperature Humidity Mechanical conditions IEC 721-3-3 class 3K5 40+70 C 595 % r h IEC 721-3-2 class 2K3 25+70 C <95 % r h class 2M2 4/6 Siemens Duct temperature senss QAM2161040, QAM2171040 CE1N1762en
Materials and cols Directives and Standards Environmental compatibility Weight Probe Base Cover Mounting flange Cable entry gland Packaging copper, polyolefine polycarbonate, RAL 7001 (silver-grey) polycarbonate, RAL 7035 (light-grey) PA 66 (black) PA, RAL 7035 (light-grey) crugated cardboard Product standard EN 60730-1 EU Confmity (CE) CET1762xx *) RCM Confmity CE1T1864en_C1 *) UL Automatic electrical controls f household and similar use UL 873, http://ulcom/database The product environmental declaration CE1E1762 *) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal) Incl packaging QAM2161040 QAM2171040 approx 017 kg approx 017 kg *) The documents can be downloaded from http://siemenscom/bt/download Connection terminals QAM2161040 G G0 R1 = 050 C / R2 = 50+50 C / R3 = 35+35 C U1 1762G01 QAM2171040 G1 R1 = 050 C / R2 = 50+50 C / R3 = 35+35 C I1 1762G02 G, G0 Operating voltage AC 24 V (SELV) DC 13535 V G1 I1 U1 Operating voltage DC 13535 V Signal output 420 ma f measuring range 50+50 C (facty setting), 050 C 35+35 C Signal output DC 010 V f measuring range 50+50 C (facty setting), 050 C 35+35 C Siemens Duct temperature senss QAM2161040, QAM2171040 CE1N1762en 5/6
Dimensions ø 6 ø 20 Typ QAM2161040 L1 400 L2 max min 97 37 80 ø 40 80 QAM2171040 400 97 37 106 39 3,7 60 28 50 M16 x 1,5 L2 L1 21 60 1762M01 Drilling plan Dimensions in mm 6/6 2004 2014 Siemens Switzerland Ltd Subject to change Siemens Duct temperature senss QAM2161040, QAM2171040 CE1N1762en