Multileaf dampers Type JZ-* / WG-JZ-*



Similar documents
PLASTIC VOLUME CONTROL DAMPERS OVERVIEW TYPE: GGB

Weather Resistant Louvres

CEILING CASSETTE FAN COIL UNIT

Pneumatic Control and Shut-off Butterfly Valve Pfeiffer Type BR 14b/31a and Type BR 14c/31a

DIAMOND Retractable Rodding Robot Model SPRAYROD-R

Solenoid valves 2/2-way direct-operated Type EV210A

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER

39HQ Airovision Air Handling Units

SISTO-16TWA/HWA/DLU. Type Series Booklet

Installation Instructions

Accessory Manual Ventilation Section Model Comfort Circle

AMD-33 Air Measuring Station with VCD-33 Control Damper

15GAL STEEL OIL DRAIN WITH 110V PUMP

Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Fisher 249 Caged Displacer Sensors

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

Installation Instructions For Slider Casement Air Conditioners

Cooktop Low-Profile Ventilation Hoods

Instruction Manual Differential Pressure Transmitter

S GATE KNIFE GATE VALVE WITH PNEUMATIC ACTUATOR

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT

Cable Drum Machine. Operation Manual BC260 SERIES. Cleans 1 1/4" to 3" lines up to 50'

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

1. SAFETY RULES WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR PERSONAL INJURY, MOUNT FAN TO OUTLET BOX MARKED "ACCEPTABLE FOR FAN SUPPORT".

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.

WE-350 Series ¼ Turn Electric Actuator

Butterfly Valves PN 6/10/16 for flanged connection

Installation and safety instructions for AC/DC built-in devices

SELECTION, APPLICATION AND MAINTENANCE

ADM1TE 5/30A DIN rail single phase two wire energy meter

Compensation Unit in X-, Y-, and Z-Direction AGE-S-XYZ

System 8. ü ( System 8

PEDAL CAR - GO CART ASSEMBLY & OPERATING INSTRUCTIONS

UV100A Ultraviolet Air Treatment System

1. SAFETY RULES. 8. Avoid placing objects in the path of the blades.

Installation Instructions

Mounting Instructions. Torque Transducer. A en

1000-LB. TRAILER JACK OWNER S MANUAL

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

Ball valve C 16 valve ball completely moulded in place, extremely low clearance volume, high k v value

INFRARED QUARTZ WALL HEATER

FIRE DAMPER APPLICATION GUIDE

Load Limiter ULS-60 ULS-80 ULS-100 ULS-125. Table of Contents. Assembly Instructions Load Limiter ULS-60, -80, -100, -125

1.1 DOOR'S SYSTEM INTRODUCTION - IRIZAR'S I6 DOOR SYSTEM

PBX Series Quick Fit Connector Bimetallic Steam Traps

Rapide Inline Ceiling Extractor Fan, White Fascia Rapide Inline Ceiling Extractor Fan, Chrome Fascia

TECHNICAL BULLETIN. Meritor WABCO Cab Leveling Valves and Chassis Leveling Valves. How the Cab Leveling and Chassis Leveling Valves Work

Operating Instructions Drill rig DRU160

Elektromotoren und Gerätebau Barleben GmbH

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

Vacuum Gate Valve DN 100 and DN 150

8" BENCH GRINDER OWNER'S MANUAL

PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: AW 120 / AW 122 / AW 125 AWD 120 / AWD 121 / AWD 129

Installation. Smart-UPS VT MGE Galaxy Maintenance Bypass Panel kva 400 V

2003 ACCORD - Automatic Transmission Removal

Diaphragm Actuators Favorable Variety Pneumatic Diaphragm Actuators Electric Actuators Hydraulic Actuators

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Direct steam injection humidifiers

Proportional pressure regulators VPPE

Class 5 to 7 Truck and Bus Hydraulic Brake System

MODEL J SERIES CONVERTER

Float and Thermostatic Traps Series H, C and X

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions

POWERS Controls No. 4 Pneumatic Damper Actuator

Speed-Mat Rectangle Cutter

Hydraulic control unit series

Operating instructions. SCORP 220 Plus SCORP 360. Pipe Cutter. Code Machine-no.:

Operating Instructions

Application Tooling Specification Sheet

MBSAW. Meat Cutting Band Saw With Meat Grinder Assembly & Operating Instructions

Spetec Laminar Flow Systems. Operating Instructions

Unique DV-ST UltraPure - Manuel: for valve sizes DN8 to DN80 (¼ to 3 )

DIAMOND Gear Company, LTD. an ERIKS Company. Installation, Maintenance, & Operation Manual Declutchable Worm Gear

Rotary actuator for 2 and 3-way (control) ball valves Torque 5 Nm Nominal voltage AC V Control: Open/close or 3-point Auxiliary switch

LUCCI AIRFUSION QUEST II CEILING FAN

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Unit 24: Applications of Pneumatics and Hydraulics

Installation Instructions

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

security products metric sizes Redefine your comfort zone.

Installation Detailed installation instructions are provided which should be strictly followed.

Auto Feed Screwdriver

225C-024T-05. Continuous control rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Assisted lift operated 2/2-way solenoid valves Type EV250B

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

VdS en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS en : (01)

ONE OF THE SMALLEST SNAP-ACTION SWITCHES IN THE WORLD. FEATURES Superminiature type, light-weight snap action switch PC board terminal type (0.

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

IMPORTANT SAFETY NOTICE

ATEX-Specific Supplementary Operating Instructions

3. Loosen 3 x grub screws in the Dec end cap and unscrew the cap and counterweight shaft. NEQ6 Belt Modification Kit.

3/2-way Solenoid Valve, direct-acting, NC or NO

SELECTION, APPLICATION AND MAINTENANCE

Compact pressure switch Flameproof enclosure Ex d Model PCA

Diaphragm Control Valves FLUXOTROL Series I and Series 25 Installation and Maintenance Instructions

Type 3353 Angle Seat Valve

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

Transcription:

Installation manual GB/en Multileaf dampers Type JZ-* / WG-JZ-* TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de http://www.troxtechnik.com Product overview A00000049740, 04/2016, TROX GmbH 2015 Fig. 1: Schematic illustration of JZ-HL and WG-JZ ① ② ③ ④ ⑤ ⑥ Casing Opposed blades (JZ-P*: parallel blades) Blade tip seal (JZ-HL*, JZ-LL-* only) Travel stop (angle section with seal) (JZ-HL*, JZ-LL-*, only) Actuator (optional) Transverse link ⑦ ⑧ ⑨ ⑩ ⑪ External linkage Wire mesh, with or without insect screen WG border WG bottom blade WG regular blades 1

Important notes Important notes Information on the installation manual This manual enables operating or service personnel to correctly install the product described below and to use it safely and efficiently. It is essential that these individuals read and fully understand this manual before starting any work. The basic prerequisite for safe working is to comply with the safety notes and all instructions in this manual. The local regulations for health and safety at work and general safety regulations also apply. Qualified staff The work described in this manual has to be carried out by individuals with the qualification, training, knowledge and experience described below: HVAC technician HVAC technicians are individuals who have sufficient professional or technical training in the field they are working in to enable them to carry out their assigned duties at the level of responsibility allocated to them and in compliance with the relevant guidelines, safety regulations and instructions. HVAC technicians are individuals who have indepth knowledge and skills related to HVAC systems; they are also responsible for the professional completion of the work under consideration. HVAC technicians are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to work on HVAC systems, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved. Skilled qualified electrician Skilled qualified electricians are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to work on electrical systems, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved. Limitation of liability The information in this manual has been compiled with reference to the applicable standards and guidelines, the state of the art, and our expertise and experience of many years. The manufacturer does not accept any liability for damages resulting from: Non-compliance with this manual Incorrect use Operation or handling by untrained individuals Unauthorised modifications The actual scope of delivery may differ from the information in this manual for special constructions, additional order options or as a result of recent technical changes. Copyright This document, including all illustrations, photos, etc., is protected by copyright. Any use of this document without the written consent of the manufacturer is an infringement of copyright; this applies in particular to disclosing this document to third parties, to publishing, copying, microcopying, or translating content, and to saving content on electronic systems or modifying it. Violators will be held liable for any damage. The right to further claims remains reserved. Personal protective equipment Personal protective equipment must be worn for all work in order to reduce health or safety hazards to the minimum. The appropriate protective equipment for a job must be worn for as long as the job takes. Correct use The multileaf damper is used as an acting element in the volume flow and pressure control in air conditioning systems, e.g. in ventilation plant rooms or ducts. 2

Transport and packaging Incorrect use WARNING! Danger due to incorrect use! Incorrect use of the unit can lead to dangerous situations. Never use the unit: in areas with potentially explosive atmospheres for process air control or shut-off outdoors without sufficient protection against the effects of weather in humid rooms in rooms with aggressive or dust-laden air Storage temperature: 10 to 50 C Relative humidity: 95 % max., non-condensing Installation General safety notes CAUTION! Danger of injury from sharp edges, sharp corners and thin sheet metal parts! Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes. Be careful when carrying out any work. Wear protective gloves, safety shoes and a hard hat. Transport and packaging Transport CAUTION! Danger of injury from sharp edges, sharp corners and thin sheet metal parts! Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes. Be careful when carrying out any work. Wear protective gloves, safety shoes and a hard hat. NOTICE! Contamination or damage will impair the function of the multileaf damper. Protect the multileaf damper from contamination and damage. Use only lifting and transport gear designed for the required load. Always secure the load against tipping and falling. Upon delivery, carefully remove the packaging and check the unit for transport damage and completeness. Storage Please note: Store the unit only in its original packaging Protect the unit from the effects of weather Protect the unit from humidity, dust and contamination 3

Installation Personnel: HVAC technician General installation information CAUTION! Danger of injury! Danger of injury when reaching into the blades or the linkage of the multileaf damper. Once the multileaf damper has been installed, people must be prevented from reaching into the damper, for example by a cover grille. NOTICE! Temperatures below the dew point Temperatures below the dew point should be avoided as they lead to condensation which may cause damage to the building structure. Fig. 2: Installation types 1 2 3 4 Ducts on both sides Without duct (air transfer) Duct on one side (air outlet) Duct on one side (air inlet) The multileaf damper is installed away from walls (in ducts), or adjacent to or on the face of walls and ceiling slabs. Please note: Installation should be vertical and without torsion Installation in vertical or horizontal ducting Installation with the blades vertical or horizontal; JZ-LL only with the blades horizontal Any airflow direction Duct connection on one side or on both sides The function of the damper must be checked before installation. Duct installation Fig. 3: Duct installation Use screws (by others) to fix the multileaf damper to the duct. Due to its weight the multileaf damper must be supported, e.g. by a suspension system. 4

Installation Wall/ceiling installation Screw fix installation Fig. 6: Wall installation with installation subframe (aluminium construction) Fig. 4: Wall installation Use suitable screws (by others) to attach the multileaf damper to the wall or ceiling slab. Installation with installation subframe Fig. 7: Wall installation with installation subframe (steel/stainless steel construction), height subdivided H 1 See Fig. 20 Fig. 5: Wall installation with installation subframe (steel/stainless steel construction) 1 2 3 Threaded stud Fixing tab Installation subframe Items 1 to 3 are included in the installation subframe supply package 5

Installation Fig. 8: Wall installation with installation subframe (steel/stainless steel construction), width subdivided B 1 See Fig. 21 Fig. 10: Bend and spread the fixing tabs before installation Installation with external weather louvre Assembling the installation subframe and damper Fig. 11: Wall installation with external weather louvre (WG-JZ) Fig. 9: Installation subframe and damper assembly 1 Threaded stud 2 Washer 3 Hexagonal nut 4 Fixing tab 5 Hexagon head screw 6 Installation subframe 7 Casing of the multileaf damper * with installation subframe ** without installation subframe 1 Fixing tab 2 Hexagon head screw with washer 3 Installation subframe The gap between the frame of the external weather louvre and the building envelope has to be professionally sealed (by others) to prevent the ingress of humidity or rain. Connecting the duct Use screws to attach the damper to the ducting. The damper casing has flange holes for duct connection. 6

Electrical/pneumatic connection Seal the joint between the casing flange and the duct in order to avoid pressure loss. Use sealing tape, for example, and clamps or additional screws, if necessary. The movement of the damper blades must not be obstructed by any attachment. CAUTION! Danger of injury when reaching into the multileaf damper. If only one end is to be ducted on site, the other end must have a cover grille (galvanised steel, mesh aperture 20 mm) or an external weather louvre. Electrical/pneumatic connection Actuators provided by others If actuators are provided by others, please note: Minimum torque of the actuator Maximum differential pressure for the multileaf damper Remove the lever (if any) that locks the quadrant stay during transport before you install the actuator Install the actuator according to the manufacturer's instructions For technical data refer to the technical leaflet. Connecting electric actuators Personnel: Skilled qualified electrician Any leads must be designed for the supply voltage for which they will be used. The power rating is given on the actuator rating plate. The length and cross section as well as any contact resistance may increase voltage losses. The sizing of leads and the selection of lead types must be performed by a skilled qualified electrician. DANGER! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. Connect the actuator according to the terminal connections indicated on the actuator or in the manufacturer's product documentation. NOTICE! The blade mechanism must not be used as a travel stop for the actuator; if necessary, use a separate travel stop device. TROX cannot guarantee leak-free dampers if the actuators are provided and installed by others. 7

Electrical/pneumatic connection Electric open/close actuators Limit switch Fig. 14: Connecting cable core identification for limit switch S2A Fig. 12: 1-wire control 1 Actuator 2 Spring return actuator (safe damper blade position as an option) S1 closed: Direction of rotation 1 open: Direction of rotation 2 S1 Common contact S2 Mechanical stop 1 < x S3 Mechanical stop 1 > x S4 Common contact S5 Mechanical stop 2 < x S6 Mechanical stop 2 > x Modulating actuators Fig. 15: Variable control Fig. 13: 2-wire control 1 2-wire control (3-point) S1 open and S2 open: Actuator has stopped (any position) S1 closed: Direction of rotation 1 S1 open, S2 closed: Direction of rotation 2 2 2-wire control (open/close) S3 not actuated: Direction of rotation 1 S3 actuated: Direction of rotation 2 1 2 Setpoint adjuster: U = voltage signal 0-10 V DC or 2-10 V DC Modulating actuator 8

Electrical/pneumatic connection Connecting pneumatic actuators Personnel: Skilled qualified electrician Required Control medium: Dry air which is free from dust and oil, or inert gases. Supply voltage, depending on the solenoid valve, see rating plate. Operating pressure, depending on the actuator, see rating plate. DANGER! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. 1. Connect the solenoid valve according to the terminal connections indicated on the valve or the manufacturer's product documentation. 2. Connect the tubes according to the tubing diagram. Fig. 17: Pneumatic actuator without solenoid valve 1 2 3 4 Double acting pneumatic actuator Single acting pneumatic actuator Throttle valve Flow reducer (noise reduction) Limit switch Fig. 18: Connecting cable core identification for limit switch 1 Common contact 2 NC contact 4 NO contact Fig. 16: Pneumatic actuator with solenoid valve 1 2 3 Throttle valve Flow reducer (noise reduction) Double acting or single acting actuator 9

Commissioning and maintenance Commissioning and maintenance Commissioning Personnel: HVAC technician As part of commissioning, the multileaf damper must be tested for correct functioning. Technical data Multileaf dampers are manufactured according to the width (B) height (H) ordered. Multileaf dampers must be installed according to B H; turning them is not usually possible, Ä General installation information on page 4. Dimensions of JZ-* NOTICE! JZ-LL-AL / JZ-HL-AL with quadrant stay JZ-LL-AL / JZ-HL-AL multileaf dampers have a quadrant stay which functions as a travel stop (open/close). Using the damper without the quadrant stay may cause damage to the blades. Do not use multileaf dampers JZ-LL-AL / JZ-HL- AL without the quadrant stay. Before commissioning, loosen the nut of the lever that locks the quadrant stay during transport. Maintenance The multileaf damper and the actuator are maintenance-free with regard to wear but multileaf dampers must still be included in the regular cleaning of the ventilation system. Fig. 19: JZ-* T 180 mm for steel/stainless steel construction, 120 mm for aluminium construction 10

Technical data Dimensions of WG-JZ-* Fig. 22: WG-JZ Fig. 20: JZ with height subdivided H 1 = 2 H + 76 mm Fig. 23: WG-JZ with actuator Fig. 21: JZ with width subdivided B 1 = 2 B + 150 mm Attachments Z12 - Z 51, ZF01 - ZF15, ZS21 - ZS22, ZS99 Dimension X [mm] 180 Z60 - Z77 200 11

Technical data JZ-S JZ-P JZ-S- A2 JZ-P- A2 JZ-AL JZ-LL JZ-HL JZ-LL- A2 JZ-LL- AL JZ-HL- AL Steel, galv. Stainless steel Aluminium Parallel Opposed Closed blade air leakage 3-4 1-2 3-4 4 2 to EN 1751 (class) 1 Casing air leakage to EN 1751 (class) C Temperature resistance (temperature of the medium) -20...100 C 2-20...150 C 3 0... 90 C 0...100 C 10... 50 C 0... 90 C 1) Not for actuators provided by others, Ä 7 2) With plastic bearings 3) With brass bearings For more technical data see the technical leaflet. 12