PERFORMANCE OF PV INVERTERS



Similar documents
Solar Power at Vernier Software & Technology

Solar Photovoltaic Frequently Asked Questions

Application Note: String sizing Conext CL Series

Auburn University s Solar Photovoltaic Array Tilt Angle and Tracking Performance Experiment

Small PV Systems Performance Evaluation at NREL's Outdoor Test Facility Using the PVUSA Power Rating Method

Solar Matters III Teacher Page

Application Note - How to Design a SolarEdge System Using PVsyst

Solar Electric Power System Owner s Manual

ANALYSIS 2: Photovoltaic Glass Replacement

Renewable Energy. Solar Power. Courseware Sample F0

Fronius IG Plus. The next generation grid-connected PV inverter

NBF. Electrical. WHY GO SOLAR? NBF ELECTRICAL EXPLAINS WHY

Photovoltaic Systems II EE 446/646

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

EFFICIENT EAST-WEST ORIENTATED PV SYSTEMS WITH ONE MPP TRACKER

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

Solar radiation data validation

Replacing Fuel With Solar Energy

Impact of Reflectors on Solar Energy Systems

Solar Energy Systems. Matt Aldeman Senior Energy Analyst Center for Renewable Energy Illinois State University

EVALUATING SOLAR ENERGY PLANTS TO SUPPORT INVESTMENT DECISIONS

REDUCING UNCERTAINTY IN SOLAR ENERGY ESTIMATES

As we look at the PV array in a PV system, we find that many. by John Wiles

Running the Electric Meter Backwards: Real-Life Experience with a Residential Solar Power System

UPS Applications and VRLA Battery Sizing

Monitoring System Performance

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Solar Power Frequently Asked Questions

The Solar Power Specialists. Elm Park House, Elm Park Court, Pinner, Middlesex, HA5 3NN Solutions House, Unit A19, 20 Heron Road, Belfast, BT3 9LE

Photovoltaic Incentive Program

THE SUPERFLEX DESIGN OF THE FRONIUS SYMO INVERTER SERIES

Design of Grid Connect PV systems. Palau Workshop 8 th -12 th April

Consumer guide. be brighter. actewagl.com.au/solar

Stand Alone PV System Sizing Worksheet (example)

INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 3, ISSUE 4, APRIL 2014 ISSN

Satcon Solstice 100 kw System Solution

Design of a Photovoltaic Data Monitoring System and Performance Analysis of the 56 kw the Murdoch University Library Photovoltaic System

2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams Sunteams 4000 Sunteams 5000

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

8 Ways Power Optimizers are Better by Design

Photovoltaic String Inverters and Shade-Tolerant Maximum Power Point Tracking: Toward Optimal Harvest Efficiency and Maximum ROI

PLC Based PV Module Tracking with Microcontroller Backup

Additional Solar System Information and Resources

Dual Axis Sun Tracking System with PV Panel as the Sensor, Utilizing Electrical Characteristic of the Solar Panel to Determine Insolation

Green Education through Green Power: Photovoltaics as a Conduit to Interdisciplinary Learning

Performance ratio. Contents. Quality factor for the PV plant

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

5 Things to Understand When Going Solar It s Pretty Simple

SOLAR PV INFORMATION. January, 2015

Solar Tracking Application

INTRODUCTION WARNING S!!! VOC SHOULD BE BETWEEN MUST NOT EXCEED 96 VOC USE DC CIRCUIT BREAKER/ISOLATOR BETWEEN SOLAR PANELS & CONTROLLER

The Basics of Solar Power for Producing Electricity An excellent place to start for those just beginning. The basics of solar power: 1000 W/m²

How oversizing your array-to-inverter ratio can improve solar-power system performance

SOLAR TECHNOLOGY CHRIS PRICE TECHNICAL SERVICES OFFICER BIMOSE TRIBAL COUNCIL

FREQUENTLY ASKED QUESTIONS

Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System

Exploration of Solar Power for the Modern Poultry Farm

A. Hunter Fanney Kenneth R. Henderson Eric R. Weise

The Planning and Design of Photovoltaic Energy Systems: Engineering and Economic Aspects. William Nichols Georgia Southern University Atlanta, GA

Frequently Asked Questions SOLAR ENERGY:

Solar Power HourSM. Solar educa on for your community.

SOLAR ENERGY. Solar Energy, Kit #6A: Efficiency of Solar Cells. Solar Energy, Kit #6B: Solar Extension Activities INSTITUTE FOR SCHOOL PARTNERSHIP

PERFORMANCE OF MPPT CHARGE CONTROLLERS A STATE OF THE ART ANALYSIS

Photovoltaic (PV) Tutorial

ACTIVITY 6: Series and Parallel Wiring

SOLAR ChARge CONTROLLeRS

Method to Calculate Uncertainties in Measuring Shortwave Solar Irradiance Using Thermopile and Semiconductor Solar Radiometers

Fundamentals of Photovoltaic solar technology For Battery Powered applications

PVWATTS DERATING FACTORS FOR SOLARBRIDGE PANTHEON MICROINVERTERS AND ACPV SYSTEMS

PERFORMANCE EVALUATION OF SOLAR ENERGY DEVICES BY USING A DATA LOGGING SYSTEM

INVERTER WITH MULTIPLE MPP TRACKERS: REQUIREMENTS AND STATE OF THE ART SOLUTIONS

Irradiance. Solar Fundamentals Solar power investment decision making

A SOLAR GUIDE - EVERYTHING YOU NEED TO KNOW

Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet'

ABB central inverters PVS to 1000 kw

For millennia people have known about the sun s energy potential, using it in passive

Siting of Active Solar Collectors and Photovoltaic Modules

FLOW DIAGRAM OF FIVE DIFFERENT TYPES OF INVERTER SYSTEMS

Understand Hybrid Generator Battery Systems

Solar Energy Conversion using MIAC. by Tharowat Mohamed Ali, May 2011

Optimum Solar Orientation: Miami, Florida

Solar Energy. Airports Going Green Aimee Fenlon

Application Information Improving Efficiency in Smart Grid Applications With Fully Integrated Current Sensing ICs

An Introduction to Solar Energy. Applications for Agriculture. State of New York. George E. Pataki, Governor

EXPLANATION OF WEATHER ELEMENTS AND VARIABLES FOR THE DAVIS VANTAGE PRO 2 MIDSTREAM WEATHER STATION

Solar panels combined with LED lighting - Case study from Finland

Green Energy Solutions

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:

CUTES Solar Power System

measurements at varying irradiance spectrum, intensity and module temperature

High Power Programmable DC Power Supplies PVS Series

Bankable Data and Interoperability Standards

Solar Up NH. Frequently Asked Questions

Transcription:

ABSTRACT Frank Vignola Solar Radiation Monitoring Laboratory Department of Physics 1274 University of Oregon Eugene, OR 9743-1274 fev@uoregon.edu The inverter is a major component of photovoltaic (PV) systems either autonomous or grid connected. It affects the overall performance of the PV system. Any problems or issues with an inverter are difficult to notice unless the inverter totally shuts down. In this article, the characteristics of inverters are discussed along with some of the problems that can occur but are not often spotted. It is also shown that high resolution time monitoring may aid in identifying issues that otherwise would go unnoticed. The data have been collected under actual operating conditions and different times of the year allowing for a better overview of their performance as a function of irradiance or temperature. 1. INTRODUCTION For any grid tied photovoltaic (PV) system, the inverter is the essential piece of equipment that changes the direct power (DC) from the PV array to alternating power (AC) used in the electrical grid. Not only does the inverter convert DC to AC power but it also regulates the PV system. The electronics that perform this task utilize special algorithms known as maximum power point tracking (MPPT) algorithms. The inverter affects the overall performance of the photovoltaic (PV) systems and problems concerning inverters are difficult to notice unless the inverter totally shuts down. In this article, the characteristics of several inverters are discussed along with some of the problems encountered when monitoring PV systems. Some of the inverters covered in this article are several PERFORMANCE OF PV INVERTERS Jim Krumsick Alternative Energy Consortium 1 West 13th Avenue Eugene, OR 9741 jpkrumsick@aol.com Fotis Mavromatakis Department of Sciences Technical Educational Institute of Crete P.O. Box 1939 Heraklion, Crete, Greece fotis@stef.teiher.gr years old and have already been replaced by new models with improved technologies. We hope to get access to new models for comparison. First, the data used in this study are discussed followed by a brief overview of inverters. The characteristic performance of the inverters is then described followed by a discussion of issues that have occurred. 2. THE DATA The Alternative Energy Consortium (AEC) PV test facility consists of eight PV systems with four different inverter and a variety of photovoltaic modules. The PV systems range in size from 2.5 to 3.6 kilowatts. The purpose of the facility is to learn how the various modules perform with a variety of inverters and to learn about the performance of grid-tied photovoltaic systems. AEC teamed with the University of Oregon Solar Radiation Monitoring Laboratory (UO SRML) to monitor and analyze the performance of the systems [1]. The data monitoring equipment consists of two Kipp & Zonen SP Lite pyranometers, one horizontal and one in the plane of array. The meteorological measurements are the wind speed and ambient temperature. The DC current and voltage into the inverters and AC power output are measured using Ohio Semitronics transducers. The temperature of one of the modules is also monitored. The data are recorded by a Campbell Scientific data logger that samples the data on a one second basis and stores the data in 5-minute averages. The pyranometers were calibrated at the UO SRML in Eugene against instruments with calibrations traceable to

Current (Amps) 3 2.5 2 1.5 1.5 I sc Generic IV Plot V mp, I mp V oc 2 4 6 8 1 12 14 16 18 2 Voltage (Volts) IV Curve Power (scaled) Fig. 1: Inverters at the AEC PV Test Facility. Two SMA 25s, one Fronius 25, two SunVista 35s, and three PV Powered 28s. NREL and hence to international standards. The absolute accuracy of the pyranometers is ± 5% with the largest uncertainties coming at large zenith angles. The Ohio Semitronics voltage and current transducers have a specified uncertainty of ±.25% at full scale and the AC power output has an uncertainty of ±.5% at full scale. The temperature transducers have an uncertainly of ±.5ºC. The data logger has an accuracy of ±.5% of full scale range. The AEC PV test facility is located within a mile of the UO SRML solar monitoring station. This station collects high quality solar radiation data and this data can be used to calibrate the pyranometers at AEC during clear days. Data from other sites are also presented in this article and the equipment is similar to that used at the AEC PV Test Facility. The values reported do have uncertainties of a percent or two as these are field measurements and there can be many factors that affect the measurements. In addition, the findings are for individual inverters and do not necessarily correspond to all similar models. However, the overall trends that are reported in this article are similar between the individual inverters monitored. More information about the data and the data itself can be found at http://solardata.uoregon.edu/solardata.html. 3. INVERTER BASICS Inverters transform DC power from the PV array into AC power for the grid. Since solar arrays behave like batteries powered by the sun, inverters have to manipulate the DC voltage and current to maximize the power produced by the arrays. Power is the product of current times voltage and the maximum power is obtained when the product of the current and voltage is the greatest. A generic I-V curve Fig. 2: Generic IV curve for a photovoltaic module. Module power equals current times voltage. The dotted line is the DC power (scaled to fit on plot) plotted for various voltages. The max power point is labeled and can be considered as the rectangle with the largest area that can be obtained using the current and voltage values on the curve. is shown in Fig. 2 where the maximum power point is easily identified along with the open circuit voltage (V oc ) and short circuit current (I sc ). Several MPPT algorithms are available for this purpose and each manufacturer may apply any of them (e.g. Hohm and Ropp [3], Yu et al. [2]). As the voltage increases or decreases from the max power point, the power from the array decreases as compared to the maximum power output possible. Software or hardware in the inverter senses when the maximum power specification output of the inverter is about to be exceeded, and instructions are sent to the max power point tracker to decrease the amount of power produced. The inverters use the grid to synchronize their AC output power and to set the AC output voltage. Inverters are constructed so that if the AC voltage sensed by the inverter from the grid gets outside a specified range, the inverter will shut down immediately. Typically an inverter shuts down for about 5-minutes if it senses the grid going down. This is a safety precaution but not the only one that prevents inverters from sending power into the grid if the grid fails. Inverters carry several anti-islanding features that are of paramount importance for safety reasons (Xu et al. [4]) Inverters may operate indoors or outdoors. If inverters are located outdoors, they should be provided some shade from direct sunlight. Often inverters will have heat fins that help cool the inverters and good airflow over these heat fins should be maintained.

Fig. 3: DC to AC conversion efficiency of a Fronius 25 inverter plotted against incident solar radiation. The data in the plot comes from the AEC PV Test Facility in July, 27. The 5-minute AC output power data values are divided by input DC power values. 4. PERFORMANCE OF INVERTERS Inverters convert DC power from the PV array into AC power that is compatible with the utility grid. Inverter manufacturer s published data generally lists the efficiency of the conversion of DC power to AC power in the 92-95% range (see Figs. 3 and 4). These are efficiencies under optimal operating conditions for a system in which the array is properly sized for the inverter. Inverter manufacturers sometimes also quote an average efficiency that is more appropriate since inverters don t always operate at their nominal rating (e.g. Islam et al. [5]). 4.1 Characterizing inverter performance Peak efficiencies are not maintained over the whole range 1% 8% 7% 6% 5% 4% 3% 2% 1% % Efficiency of Fronius 25 Inverter AEC PV Test Facility -- July 27 2 4 6 8 1 12 14 Incident Solar Radiation (W/m 2 ) Efficiency of Fronius 25 Inverter in January and July - AEC PV Test Facility 98% 97% 96% 95% 94% 93% 92% 91% 2 4 6 8 1 12 Incident Solar Radiation (W/m 2 ) July efficiency January efficiency Fig. 5: Efficiency of the Fronius 25 Inverter in January and July, 27. Note that the efficiency is the same in either month. The inverter is located inside an unheated mechanical room. 1% 8% 7% 6% 5% 4% 3% 2% 1% % Efficiency of PV Powered 28 Inverter AEC PV Test Facility -- July 27 Inverter Efficiency - PV Powered 8 Inverter Efficiency - PV Powered 7 Inverter Efficiency - PV Powered 6 2 4 6 8 1 12 14 Incident Solar Radiation (W/m 2 ) Fig. 4: Efficiency of three PV Powered 28 inverters plotted against incident solar radiation using 5-minute data. Plot shows the efficiency of turning DC Power into AC Power on July 27, at the AEC PV Test Facility. of operation, but inverters generally operate at greater than over much of the range. Examples of PV inverter efficiency are plotted for a Fronius 25 and three PV Powered 28 inverters in Figs. 3 and 4. The efficiency was determined by dividing the AC power output from the inverter by the DC power input to the inverter. For incident radiation below 2 to 3 Watt/m 2 the inverter efficiency begins to decline. When the incident solar radiation is between 5 and 1 Watts/m 2 the efficiency of converting DC to AC power falls off to around 7%. This is a considerable improvement over older inverters. It is worthwhile to note that the inverter efficiency very slowly declines after peaking with incident energy levels around 4-7 Watts/m 2. This is partially related to the temperatures increases inside the inverter when it handles loads with more power. Efficiency of SMA 25 Inverter January & July 26 - Klamath Falls 98% 97% 96% 95% 94% 93% 92% 91% 2 4 6 8 1 12 Incident Solar Radiation (W/m 2 ) SMA 25 June January Efficiency Fig. 6: Efficiency of SMA 25 Inverter in January and June, 26. Note that the efficiency of the inverter improves in January. The inverter is located outdoors.

Efficiency of SMA 25 Inverter Klamath Falls, OR, June, 26 98% 97% 96% 95% 94% 93% 92% 91% 4 6 8 1 12 14 16 18 2 Fig. 7: Efficiency of an SMA 25 inverter at Klamath Falls, Oregon in June. The data are from 5-minute averaged data. Efficiency of SunVista 35 Inverter Grants Pass, OR Oct. 23 1% 8% 7% 6% 5% 4% 3% 2% 1% % 5 1 15 2 25 AC Power Output (W) Fig. 8: SunVista 35 inverter efficiency. Inverter combined three 1 kw arrays, one facing east, one south, and one west. 4.2 Effect of ambient temperature To check for seasonal variations of the DC to AC conversion efficiency, the efficiency for January and July are plotted in Fig. 5 for the Fronius 25 inverter at the AEC PV Test Facility. In general, the efficiency curves fall on top of one another and there is no affect of season visible. However, as shown in Fig. 1, the inverter is in a mechanical room under the roof and the temperature differences between winter and summer are not as drastic as they would be for inverters located outside. In Fig. 6, January and June inverter efficiency data are compared an SMA 25 inverter installed in Klamath Falls that is located outdoors. Fig. 6 shows that the efficiency of inverters located outside can change with season. The inverter s efficiency in a cold month of January appears to be slightly greater than the efficiency in June, a much warmer month. If there is a small performance improvement in January compared to June related to temperature, this difference should also show up during the day when the morning temperatures are lower than the afternoon temperatures. Indeed, the highest inverter efficiency occurs during the morning hours (see Fig. 7). From Figs. 5 and 6, one can see that the peak efficiency occurs when the incident solar radiation is about 6 W/m 2. As the incident solar radiance increases, the inverter efficiency slowly decreases. Hence the 2-3% dip in efficiency during the middle of the day in Fig. 7 is related to the decrease in efficiency with increasing solar radiation above its optimum operating point. To more clearly see the effects of temperature on inverter performance, it is necessary to make comparisons with similar irradiance ranges. Using June data from Klamath Falls, the average inverter efficiency was calculated for irradiance between 65 and 7 W/m 2 in the morning and the afternoon. In the morning, the average inverter efficiency is 94.4% and the average ambient temperature is 15.6 ºC. In the afternoon, the average efficiency is 93.5% and the average ambient temperature is 26.2 ºC. Assuming this is typical, then the inverter efficiency falls about 1% for about every 12 ºC rise in ambient temperature. This explains why the inverter efficiency is about 1% lower in the afternoon than the morning in Fig. 7. 4.3 Array size and inverter efficiency An important design issue is to construct the PV system so that the inverter will be operating in its optimum range most of the time. However there are times when one would like to add a few more panels to an array or that conditions don t allow for the optimal number of panels to be installed. This leads to the following question: What happens if the system is undersized or oversized with respect to the inverter specifications? The performance of a SunVista 35 inverter is shown in Fig. 8. The inverter is powered by three 1 kw arrays, one facing east, one south, and one west. The SunVista inverter is designed to blend output for up to three different input strings, each with their different MPPT requirements. Only when the arrays are near maximum power production is the inverter efficiency above. Because the arrays are facing different directions, the inverter is never operating near at its full capacity and the average DC to AC conversion is below. Therefore the overall inverter efficiency would be greater if all three arrays created more power.

In Bend, a PV Powered 2 was installed on a 1.12 kw DC PV system. This system is extremely undersized for the inverter. At the AEC PV Test Facility in Eugene, 3.6 kw DC of modules were connected with a PV Power 28 inverter. This was an attempt to see what happens when the array size is larger than the optimum for the inverter. Fig. 9 plots the inverter efficiency against the system output divided by the system rating. The inverter efficiency is approximately the same for the two PV Powered inverters except that the Bend system never generates more than 5% of the rated output. On DC Voltage (Volts) 1% 8% 7% 6% 5% 4% 3% 2% 1% % Inverter Efficiency vs % Rated Output Bend & AEC PV Test Facility - Sept. 27 Efficiency PV Powered 28 Efficiency PV Powered 2 % 2% 4% 6% 8% 1% % of Rated Output Fig. 9: Plot of inverter efficiency against rated output power for September 27. Data for the PV Powered 28 come from the AEC PV Test Facility. Data for the PV Powered 2 come from a site in Bend. Note that the PV Powered 28 and the PV Powered 2 follow the same efficiency curve even though the PV system at the AEC PV Test Facility has 36 W DC in modules is occasionally over powered and the PV system in Bend is significantly underpowered and only has 1125 W DC of modules. DC Voltage when Power Is Dumped AEC PV Test Facility, OR July 31, 27 35 3 25 2 15 1 5 4 6 8 1 12 14 16 18 2 DC Voltage: PV Powered #6 DC Voltage: PV Powered #7 Fig. 11: Inverter moves off max power point by increasing DC voltage. PV Powered inverter #6 operates normally while PV Powered inverter #7 dumps power (increases DC voltage) to keep AC power from exceeding specifications. Power Output (Watts) Irradiance (Watts/m 2 ) 35 3 25 2 15 1 5 Irradiance and Power Output AEC PV Test Facility, OR -- July 31, 27 5 7 9 11 13 15 17 19 Total 3º South AC Power: PV Powered #7 DC Power: PV Powered #7 Fig. 1: Plot of DC and AC output of PV array connected to a PV Powered 28 inverter. Note the maximum AC output is about 28 watts. Also note that the DC power also plateaus. average, the PV system in Bend will never be as efficient as the PV system at the AEC PV Test Facility because the PV system at best is operating in the 2 to 4% range of rated output and hence is operating in the 87 to 91% efficiency range during the sunniest periods. Therefore, tests of inverter efficiency should be conducted with properly sized arrays. It also means that daily efficiencies will be weighted over the whole range and is not necessarily a reliable number on which to gauge the performance of an inverter. Also, there can be a problem if the inverter is overpowered. Inverter manufacturers often include the maximum AC output in their names, like the SMA 25 or the PV Powered 28. The inverter ratings represent the DC Current (Amps) DC Current when Power Is Dumped AEC PV Test Facility, OR July 31, 27 14 12 1 8 6 4 2 4 6 8 1 12 14 16 18 2 DC Current: PV Powered #6 DC Current: PV Powered #7 Fig. 12: Inverter moves off max power point by increasing DC voltage and hence decreasing current. PV Powered inverter #6 operates normally while PV Powered inverter #7 dumps power to keep AC power from exceeding specifications.

AC Power Output (W) Irradiance (W/m 2 ) 3 25 2 15 1 5 AC Power Output Dropouts AEC PV Test Facility, OR -- July 8, 27 5 7 9 11 13 15 17 19 AC Power: PV Powered #8 Total 3º South Fig. 13: Plot of power dropout on July 8, 27 at the AEC PV Test Facility. Note that other inverters did not drop out and the problem is likely related to the calibration of sensors monitoring the utility power. maximum AC output power from the array. Sometimes PV arrays are designed with an additional module that could cause the output to exceed design specification or incident solar radiation can occasionally exceed the 1 W/m 2 standard used for the design. If excess power could be generated that would exceed the designated output limit, then the system has to shed that power so that it does not exceed its maximum specifications. These specifications are to protect the inverter or circuitry from being damaged. To prevent the power rating to be exceeded, the inverter either decreases or increases the DC voltage so that the AC output power does not exceed the specifications. DC and AC power output plotted in Fig. 1 shows that the AC power specification of the PV Powered 28 is not exceeded. This is typical of other inverters also. What happens is that the inverter moves off the max power point by increasing the DC voltage so that the AC power does not exceed 28 watts. Fig. 11 shows the DC voltage of two PV Powered 28 inverters, one of which has enough panels to exceed the 28 AC watt output limit. The max power point tracker makes an adjustment to increase the DC voltage slightly so that the AC power output does not exceed specifications. At the same time as the DC voltage is increased, the DC current is decreased (see Fig. 12), as expected (see the IV curve in Fig. 2). Providing slightly more power to the inverter than the inverter s loaded nameplate value has not significantly affected the performance of the inverter over the three years of this study However, system designers should follow inverter specifications. Software tools that estimate system performance are usually based on DC rating of the panels and do not take into account the energy lost if the PV arrays produce more power that the inverter is designed to handle. With hourly or shorter time predictions, periods when predicted performance exceeds inverter specifications can be lowered to maximum power allowed and thus more accurately reflect that actual performance. More sophisticated estimation programs should have algorithms built for specific inverters. Generic PV performance models do not incorporate specific inverter performance curves, and in fact are based on the performance of older style inverters. Since most of the energy is produced when systems are operating with clear or nearly clear skies, the efficiencies are within a few percent of peak operating efficiency. By making slight changes, such as an inverter operating at 91% instead of 92% or vice versa, the overall performance of the system can be adequately estimated. However, some inverter manufacturers are beginning to supply software with their inverters to ensure more accurate performance estimates. 4.4 Grid related shutdowns Inverters sense the utility frequency and voltage and will shut down if the inverter senses conditions outside the range expected for utility power. This feature of inverters is designed to prevent the PV system from feeding power back onto the grid when the grid goes down. For example, if a tree limb falls and breaks a power line, it would be unsafe for the PV system to power the line from the house side of the line. Some of the older inverters had trouble restarting when the grid went down and had to be restarted manually. We have not seen this problem with new models of inverters. However, we have seen inverters shut down when the gird power is still available. When the inverters shut down for short periods of times, it is often impossible to see without monitoring the inverter and having short interval data. A problem can occur if the inverter senses the voltage from the utility is outside specified levels. This is a design feature of grid connected inverters to ensure that the inverters are not dumping power onto the utility grid if the utility power goes down. However, if the inverter is not properly calibrated or if the utility voltage goes outside the specified limits, such shutdowns do occur. The data points that are far from the typical distribution in Figs. 3 and 4 are the result of the PV system shutting down when the system should be producing power. The dropouts are illustrated in Fig. 13, a plot of 5-minute data from July 8, 27. Dropouts take less that a second

and typically last at least 5-minutes before the inverter tries to re-sync with the utility grid. The dropouts don t look sharp in 5-minute data plots because the dropouts rarely happen on the exact minute and some normal performance values are averaged in data when the problem starts or ends. Sometimes this problem can persist over hours, but shorter time intervals are more typical. With very short time interval data, one can see that the power actually goes to zero within about a cycle and the inverter takes five minutes or more before it attempts to start operating again. 5. SUMMARY OF RESULTS The article shows results from several inverters. The characteristics and issues discussed have occurred in several different brands and to some degree are generic with inverters. The following assertions can be made: In general, grid tied inverters convert DC power to AC power with an efficiency of or more most of the time. Inverters can even work to some extent when irradiance levels are down to 4 or 5 Watts/m 2, but performance starts to drop off dramatically when irradiance levels reach the 1-2 W/m 2 level. Inverters reach their maximum efficiency when they operate about 5% of the maximum rated output. Above their peak efficiency the performance drops off slowly and is only down about 1% at 8% of the maximum rated output. Between 1% and 2% of maximum rated output, the efficiency of the inverters starts to drop dramatically. This behavior is better in newer inverters than older inverters and fortunately most of the incident energy occurs when the solar radiation is above these levels. The performance of inverters located indoors is not significantly affected by seasonal weather changes. Systems located outdoors perform slightly better in the colder winter temperatures than during the hot summer weather. A closer look in June showed that the inverter efficiency dropped approximately 1% for every 12 ºC increase in temperature. This is not significant, but it is worthwhile to mount the inverter where it can get a nice cooling breeze in the summer. Photovoltaic systems that are oversized or undersized do not perform as well as properly sized systems. This is particularly true for undersized systems which operate in a region of the efficiency curve where inverters don t perform as well. For oversized arrays, it is probably not cost effective to add extra panels to an array if the total power is going to exceed the nameplate rating of the inverter, since the excess power will be dumped during the sunniest part of the year. Of more concern is the effect of the added stress that might be put on the inverter associated with excess inverter loading. So far, that hasn t seemed to be a problem. A big concern is when inverters shut down when they falsely conclude that the grid power is down and it isn t. Some inverters seem to have this problem more than others even within the same model lines and when connected to the same utility line. This problem can go unnoticed as the system is working most of the time. The source of this problem can be that the utility grid voltage is operating too close to the edge of the range acceptable to the inverter. Solutions to this problem can range from re-calibrating the inverter window, installing a different gauge of wire to reduce the voltage drop, or replacing an overloaded utility transformer that is unable to maintain voltage within the tolerances of utility specifications. The solar market has now become large enough to attract a steady stream of new and improved inverters. Several of the inverters in this report are no longer being manufactured. New and improved models are on the market and inverter prices also are coming down. However, it is still important that the inverters perform reliably over time and be easy to maintain. Monitoring of new inverters is important to ensure that their quality and performance is maintained and that any problems that do occur are identified quickly. 6. ACKNOWLEDGEMENTS We would like to thank the Alternative Energy Consortium for the use of their facility and Energy Trust of Oregon for the support of this project and the Eugene Water and Electric Board, Bonneville Power Administration, and the Emerald People s Utility District for their support of the University of Oregon Solar Radiation Monitoring Laboratory. 7. REFERENCES (1) J. Krumsick, F. Vignola, R. Kessler, AEC Photovoltaic Test Facility First Year Test Data, Proceedings of the 35 th ASES Annual Conference, 26 (2) G. J. Yu, Y. S. Jung, J. Y. Choi and G. S. Kim, A novel two-mode MPPT control algorithm based on comparative study of existing algorithms, Solar Energy, Volume 76,

Issue 4, April 24, Pages 455-463 (3) D. P. Hohm, M. E. Ropp, Comparative study of maximum power point tracking algorithms, Progress in Photovoltaics: Research and Applications, Volume 11, Issue 1, Date: January 23, Pages: 47-62 (4) Mei Xu, Roderick V. N. Melnik and Uffe Borup, Modeling anti-islanding protection devices for photovoltaic systems, Renewable Energy Volume 29, Issue 15, December 24, Pages 2195-2216 (5) Saiful Islam, Achim Woyte, Ronnie Belmans, P.J.M. Heskes and P.M. Rooij, Investigating performance, reliability and safety parameters of photovoltaic module inverter: Test results and compliances with the standards, Renewable Energy, Volume 31, Issue 8, July 26, Pages 1157-1181