PSI-REP-PROFIBUS/12MB



Similar documents
MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

MINI MCR-SL-R-UI(-SP)

Redundancy Module QUINT-DIODE/40

Extract from the online catalog

PSI-MOS-RS485W2/FO 850 T

PSI-DATA/FAX-MODEM/RS232

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

Telephone- and leased line modem for industrial applications TD-36

Modular I/O System Analog and Digital Interface Modules

PHOENIX CONTACT - 01/2007

Rack mounted telephone- and leased line modem for industrial applications

PHOENIX CONTACT Features

Serial Bluetooth Converter for V.24 (RS-232), RS-422, and RS Wire Bus Systems PSI-WL-RS232-RS485/BT

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

My first Hirschmann: The SPIDER family of switches.

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

NC-12 Modbus Application

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Digital input modules

RM4TG20 three-phase network control relay RM4-T - range V

ABB Drives. User s Manual HTL Encoder Interface FEN-31

PHOENIX CONTACT - 03/2007

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Safety technique. Emergency stop module BO 5988 safemaster

PCS0100en Persy Control Services B.V. Netherlands

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Provides one channel for Ethernet over existing

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

PLC-RS /21. PLC INTERFACE With PDT Relay, Universal Version. INTERFACE Data Sheet _en_02. 1 Description

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Product Information. Gateway For Connecting EnDat Encoders to PROFIBUS-DP

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

DMX2PWM 9 Channel Dimmer Setup Manual

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

DS 600. A contact free flux gate based current measurement sensor 600A rms

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Power Supplies 3. SDN-P DIN Rail Series

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

TX OPEN RS232/485 module

PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version ( )

HARTING mcon 1000 Introduction and features

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.:

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Voltage Regulator SPAU 341 C. Product Guide

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Waveguide Access Point WGA631. Product Guide

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

is then retained absolutely without interruption.

Duct Humidity Transmitter

ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide

Product and functional description

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Practical steps for a successful. PROFIBUS Project. Presented by Dr. Xiu Ji Manchester Metropolitan University

80 Series - Modular timers 16 A. Features

SYSTEM DESCRIPTION Termination Boards

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date:

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

Provides one channel for Ethernet over existing

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

J TB/TW Temperature limiter, temperature monitor

LevelOne IFE Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

Analog signal converters CC-E I/I Current / current isolators

MCR1900 Media Converter 19-Slot Chassis

Rosemount 333 HART Tri-Loop

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm

HARTING econ 3000 Introduction and features

APD / Outputs 19" DC/DC Converter, 50 Watt

I STAR COMPUTER CO., LTD

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Options for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface

xepi 2 Installation Guide Diagnostic Unit and Configuration Interface Doc. Version 4.0 English

Moxa EtherDevice Switch

Quick Connect. quick - simple - efficient.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Technical data. General specifications. Signal voltage V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

Three-phase monitoring relay CM-PFE

8-port 10/100Base-TX +2-port 100Base-FX Switch. User s Guide

E-STOP relays, safety gate monitors

Application. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Description. Dimensions. Features. precision works better

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment

T0118 T2118 T3118. Instruction Manual

Transcription:

Repeater for PROFIBUS Systems up to 12 Mbps INTERFACE Data Sheet 102986_02_en PHOENIX CONTACT - 03/2007 1 Description The PSI-REP-PROFIBUS/12MB DIN rail-mountable modular PROFIBUS repeater is designed to meet the high requirements associated with the use of PROFIBUS systems. The device is snapped onto standard EN DIN rails in the control cabinet and supplied with 24 V. The main areas of application are: Electrical isolation/bus segmentation Increasing system availability Increasing the range Increasing transmission speeds Extending the number of devices to n x 32 Implementing hybrid/network structures Modular PROFIBUS hubs The following features of the repeater are particularly outstanding: Transmission speed of up to 12 Mbps Automatic transmit/receive changeover High-quality 4-way isolation Integrated surge protection with transient discharge to the DIN rail 24 V DC control cabinet supply voltage, with user-friendly connection via COMBICON plug-in screw terminals Bit retiming Bit oversampling Modular station structure, even with PSI-MOS-... fiber optic converters If you have any technical problems, which you cannot resolve with the aid of this documentation, please contact us during the usual office hours at: PSI hotline: +49-52 35-31 98 90 Fax: +49-52 35-33 09 99 E-mail: interface-service@phoenixcontact.com Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf.

1.1 Bit Retiming PROFIBUS signals with a bit distortion of up to 35% can be reliably detected using the bit retiming function and are converted to their original bit form before being transferred to the next segment. This data processing function means that a virtually unlimited number of repeaters can be aligned without an impermissible level of bit distortion. 1.2 Bit Oversampling The bit oversampling function can be used to detect and filter malfunctions so that they are not transferred to the next segment. 2 Ordering Data Repeater Description Type Order No. Pcs./Pck. Modular PROFIBUS repeater, for electrical isolation and increasing the range in PROFIBUS systems, 4-way isolation, DIN-rail mountable PSI-REP-PROFIBUS/12MB 2708863 1 Accessories Description Type Order No. Pcs./Pck. System power supply unit for supplying a modular star coupler configuration MINI-SYS-PS 100-240AC/24DC/1.5 2866983 1 End bracket CLIPFIX 35 3022218 50 DIN rail connector, power supply and data (2 per device) ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 10 PROFIBUS cable, Fast Connect type, up to 12 Mbps PSM-CABLE-PROFIB/FC 2744652 1 Small, angled PROFIBUS connector with screw connection SUBCON-PLUS-PROFIB/SC2 2708232 1 Small, angled PROFIBUS connector with screw connection and additional PG connection SUBCON-PLUS-PROFIB/PG/SC2 2708245 1 3 Technical Data Interface Power supply Frequency Nominal current consumption Ready-to-operate indicator 24 V DC (±20% via COMBICON plug-in screw terminal) DC 90 ma (at 24 V DC) "VCC" LED (green) Maximum star coupler expansion 10 Serial RS-485 Interface PROFIBUS according to IEC 61158, 2-wire Transmission channels Operating mode Data format/encoding Data direction changeover Transmission speed (manual adjustment) Transmission length Transmission medium Connection General Data Bit distortion input ±35%, maximum Bit distortion output < 6.25% Bit delay 11 bits Electrical isolation Test voltage 2 (1/1), TD, RD Half duplex UART (11, NRZ) Automatic, minimum station response time 2 bits 9.6/19.2/45.45/93.75/187.5/500/1500/3000/6000/12000 kbps; autobaud 1200 m, maximum (depending on transmission speed, bus system, and cable type) 2-wire twisted pair, shielded 9-pos. D-SUB female connector PROFIBUS (A) // PROFIBUS (B) // power supply // DIN rail connector 1.5 kv rms, 50 Hz, 1 min. 102986_02_en PHOENIX CONTACT 2

General Data (Continued) Alarm output 60 V DC/42 V AC, 1 A, maximum Status and diagnostic indicators Power supply (VCC), transmit/receive data (port A) Housing material PA V0, green Conductor cross section 0.2 mm 2... 2.5 mm 2 Ambient temperature Operation Storage/transport -20 C... +60 C -40 C... +85 C Humidity 10%... 95%, no condensation Dimensions (W x H x D) 35 mm x 99 mm x 105 mm Degree of protection IP20 Weight 200 g, approximately MTBF according to Telcordia standard Ambient temperature 25 C Ambient temperature 40 C 878,000 h 489,000 h Chloroform test Free from substances which would hinder coating with paint or varnish (according to VW/Audi/Seat specification) Vibration resistance 5g according to IEC 60068-2-6, 2.5 h each in x, y, and z direction, criterion A Shock resistance 15g according to IEC 60068-2-27 with 11 ms pulse length, criterion C Free fall 1 m without packaging according to IEC 60068-2-32 Air and creepage distances DIN EN 50178, DIN EN 60950 Tests/Approvals CE UL Ex c In preparation X II 3G Ex nac IIC T4 X Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC Noise Immunity Test According to EN 61000-6-2 1 Electrostatic discharge (ESD) EN 61000-4-2 Criterion B 2 8 kv air discharge 6 kv contact discharge Electromagnetic HF field Amplitude modulation Pulse modulation EN 61000-4-3 Criterion A 3 10 V/m 10 V/m Fast transients (burst) Signal Power supply EN 61000-4-4 Criterion B 2 2 kv/5 khz 2 kv/5 khz Surge current load (surge) Signal Power supply EN 61000-4-5 Criterion B 2 1 kv/12 Ω 0.5 kv/2 Ω Conducted interference Amplitude modulation EN 61000-4-6 Criterion A 3 10 V 80% AM 1 khz Noise Emission Test According to EN 61000-6-4 Noise emission of housing EN 55011 4 Class A 5 1 EN 61000 corresponds to IEC 61000 2 Criterion B: Temporary adverse effects on the operating behavior, which the device corrects automatically. 3 Criterion A: Normal operating behavior within the specified limits. 4 EN 55011 corresponds to CISPR11 5 Class A: Industrial application, without special installation measures. 102986_02_en PHOENIX CONTACT 3

Block Diagram 24V (1) 0V (2) V P GND DATA (P) DATA (N) 6 5 3 8 DC DC DC DC gn DIN rail connector DIN rail bus Retiming gn ye Bus management Retiming Retiming DATA RATE Port B 6 5 3 8 V P GND DATA (P) DATA (N) Figure 1 Block diagram 24V 0V GND D(P) D(N) DIN DIN rail rail connector bus Housing Dimensions 105 35 PSI-REP-PROFIB/12MB Ord.-No. 27 08 863 99 VCC TD RD ERR A ERR B PORT B 102986A001 Figure 2 Housing dimensions (in mm) 102986_02_en PHOENIX CONTACT 4

4 Safety Instructions Installation, operation, and maintenance may only be carried out by qualified electricians. When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. Notes on Explosion Protection The device is a category 3 item of electrical equipment. Follow the instructions provided here during installation. The device must be installed in housing with IP54 protection according to EN 60529. The specified limits for mechanical strain or thermal loads for the device must not be exceeded. Temporary malfunctions (transients) must not exceed the rated voltage by more than 40%. Repairs must not be carried out by the user. Cables may only be snapped on and connected in potentially explosive areas when the power is disconnected. 5 Function Elements 5 6 7 9 1 2 3 4 PSI-REP-PROFIB/12MB Ord.-No. 27 08 863 VCC TD RD ERR A 8 1 24 V DC supply voltage connection 2 0 V DC supply voltage connection 3 Switch contact connection 1 4 Switch contact connection 2 5 "VCC" LED: Ready-to-operate 6 "TD" LED: Transmit data dynamic port A (yellow) 7 "RD" LED: Receive data dynamic port A (green) 8 9-pos. D-SUB: PROFIBUS interface port A 9 "ERR A" LED: Transmission error port A 10 "ERR B" LED: Transmission error port B 11 9-pos. D-SUB: PROFIBUS interface port B 10 ERR B Port B 11 102964A002 Figure 3 Function elements 102986_02_en PHOENIX CONTACT 5

6 Applications The PSI-REP-PROFIBUS/12MB repeater can be used to create network topologies that are ideally adapted to the relevant application. The limits set by the PROFIBUS standard, which specifies the electrical properties of PROFIBUS, are thus extended. This standard defines the following basic specifications: 1. Maximum of 32 devices per potential segment 2. Only (linear) bus structure permitted 3. Maximum bus cable length 1200 m 4. Maximum branch line length of 5 m without termination resistor (depending on the transmission speed) 5. Bus cable termination at the start and end of the bus cable Example Applications for Repeaters A segment can be created as an active branch, which can comprise the full bus cable length and a maximum of 31 devices. Electrical isolation and bus segmentation using repeaters enables the permissible bus cable length to be multiplied and the number of devices to be extended to n x 32, since the total number of devices of the PROFIBUS specification applies in each potential segment. The repeater supports higher transmission speeds by subdividing into shorter segment lengths. For example, a 200 m PROFIBUS system can only be operated at a transmission speed of 1.5 Mbps. The use of a repeater after 100 m means that 8 times the performance can be achieved, i.e., 12 Mbps. Hybrid/network structures, star, and tree structures can be created using the PSI-REP-PROFIBUS/12MB modular repeater. A freely selectable installation concept, independent of the restrictive linear structure, is thus possible. The repeaters can be extended using PSI-MOS-PROFIB/FO... fiber optic converters for PROFIBUS systems. In addition, the repeaters can be combined and thus configured to form a modular PROFIBUS hub. Stub line PROFIBUS 12 MBit/s 100m 100m Max. 31 devices = Switch on bus termination resistor Linear structure Max. 30 devices Max. 30 devices = Switch on bus termination resistor Star structure = Switch on bus termination resistor Tree structure = Switch on bus termination resistor 102986_02_en PHOENIX CONTACT 6

7 DIP Switches The DIP switches (1) are located under the cap (2) on the port B interface (see Figure 4). Insert a small screwdriver into the slot on the bottom of the cap and lever it off. Setting the Transmission Speed Set the transmission speed using DIP switches 1 to 4. Transmission DIP Switch Speed (kbps) 1 2 3 4 AUTO (default) OFF OFF OFF OFF 12000 OFF OFF OFF ON 6000 OFF OFF ON OFF 3000 OFF OFF ON ON 1500 OFF ON OFF OFF 500 OFF ON OFF ON 187.5 OFF ON ON OFF 93.75 OFF ON ON ON 45.45 ON OFF OFF OFF 19.2 ON OFF OFF ON 9.6 ON OFF ON OFF Figure 4 1 2 3 4 5 6 ON S1...S6 TD ERR B ERR A ON PORT B 1 2 3 4 5 6 102986B003 DIP switches (default upon delivery: all DIP switches set to OFF) DIP switches 5 and 6 are reserved and have no function. 102986_02_en PHOENIX CONTACT 7

8 Connection Notes Only mount and remove devices when the power supply is disconnected. Warning Disregarding this warning may result in damage to equipment and/or serious personal injury. Only qualified personnel may start up and operate this device. According to the safety instructions in this text, qualified personnel are persons who are authorized to start up, to ground, and to mark devices, systems, and equipment according to the standards of safety technology. In addition, these persons must be familiar with all warning instructions and maintenance measures in this text. PSI-REP-PROFIBUS/12MB devices are designed exclusively for SELV operation according to IEC 60950/EN 60950/ VDE 0805. 8.1 Combined Assembly With a System Power Supply (Modular Star Coupler) 1. Connect together the required number of DIN rail connectors for the connection station. Two DIN rail connectors are required for each device (see A in Figure 5). A maximum of ten devices are permitted in a connection station. 2. Push the connected DIN rail connectors onto the DIN rail (B and C). 3. Place the device onto the DIN rail from above. The upper holding keyway of the device must be hooked onto the top edge of the DIN rail (see Figure 6 on page 9). Make sure that it is aligned correctly with the DIN rail connectors. 4. Once the device has been snapped on properly, check that it is fixed securely on the DIN rail. A Install the device on a 35 mm DIN rail according to DIN EN 60715. To avoid contact resistance only use clean, corrosion-free DIN rails. End brackets should be mounted on both sides of the device to stop the devices from slipping on the DIN rail (for ordering data see page 2). B C 101973A003 Figure 5 Combined assembly 102986_02_en PHOENIX CONTACT 8

8.2 Assembly as an Individual Device in the Control Cabinet (Stand-Alone) 1. Place the device onto the DIN rail from above. The upper holding keyway of the device must be hooked onto the top edge of the DIN rail (see Figure 6). 2. Push the device from the front towards the mounting surface. 3. Once the device has been snapped on properly, check that it is fixed securely on the DIN rail. 9 Cabling Notes 9.1 Connecting the Supply Voltage The device is operated with a +24 V DC SELV. Operation as an Individual Device Supply the supply voltage to the module via terminal blocks 1 (24 V) and 2 (0 V). Individual supply Redundant supply 24 V 0 V 24 V 0 V 24 V 0 V 102964A006 Figure 7 Individual/redundant supply Figure 6 Assembly in the control cabinet 102964B005 8.3 Removal 1. Pull the locking latch down using a screwdriver, needle-nose pliers or similar. 2. Pull the bottom edge of the module away from the mounting surface. 3. Pull the module diagonally upwards away from the DIN rail. 4. If removing a complete star distributor, remove the DIN rail connectors from the DIN rail as well. Operation in a Star Coupler Configuration When the devices are operated in a star coupler configuration, the supply voltage must only be supplied to the first device in the station. The remaining devices are supplied via the DIN rail connector. A redundant supply concept can be created by connecting a second power supply unit to another device in the configuration. Using the MINI-SYS-PS-... System Power Supply Unit As an alternative, the star coupler configuration can also be supplied using the MINI-SYS-PS 100-240AC/24DC/1.5 power supply unit (Order No. 2866983). It is connected via two DIN rail connectors. Usually the system power supply unit is mounted as the first device in a configuration. A second power supply unit can be used to create a redundant supply concept. 102986_02_en PHOENIX CONTACT 9

9.2 Wiring the Switch Contact PSI-REP-PROFIBUS/12MB repeaters are equipped with a floating switch contact for error diagnostics (connection terminal blocks 3 and 4 in Figure 3 on page 5). This contact opens on the relevant device in the event of a transmission error at port A or port B. 24 V DC The switch contact is an N/C contact and can be linked to a local digital input, e.g., on the PLC, to support error detection. If devices are combined (in a modular star coupler configuration), the individual contacts can be linked to separate input points (Figure 8) or the individual contacts can be looped to generate a group message (Figure 9). The maximum load capacity of the relay contact is 60 V DC/42 V AC, 1 A. Figure 8 Individual message 101973A006 24 V DC Group message 101973A007 Figure 9 Group message 102986_02_en PHOENIX CONTACT 10

9.3 Connecting the Data Cables Attention Use shielded twisted pair data cables. Connect the cable shielding at both ends of the transmission path. 1. Use a suitable connector (e.g., SUBCON-PLUS- PROFIB..., see page 2) to connect the bus cable to the D-SUB connection on the repeater. 2. If the repeater is located at the start or end of an electrical PROFIBUS segment, activate termination in the connector. PSI-REP-PROFIB/12MB Ord.-No. 27 08 863 VCC RD TD ERR A ERR B Port B Pin Signal Meaning 3 RxD/TxD-P Receive/transmit data, positive B cable 5 DGND Data transmission potential/ (reference potential to VP) 6 VP Supply voltage, positive (P5V) (50 ma, maximum) 8 RxD/TxD-N Receive/transmit data, negative A cable Figure 10 PORT B D-SUB connections for port A and port B 102986A004 PHOENIX CONTACT 03/2007 102986_02_en PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 11 Phone: +49-52 35-30 0 Fax: +49-52 35-34 12 00 www.phoenixcontact.com