THE USE OF OZONE IN COOLING TOWERS



Similar documents
Best Practice in Boiler Water Treatment

Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources

2014 Service Technician Training Program Closed Loop Systems

Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower

Hardness ions also interfere with many chemical processes such as chemical compounding and aqueous cleaners.

Ozone in Cooling Towers : Hygiene for us

Scale and Deposit Formation in Steam Assisted Gravity Drainage (SAGD) Facilities

EXTRACTION OF METALS

Factors Affecting Precipitation of Calcium Carbonate

Guidelines for Selecting and Maintaining Glycol Based Heat Transfer Fluids

ALS TRIBOLOGY Engine Coolant Reference Guide

NALCO WT-1000 Closed System Corrosion Inhibitor

WATER CHEMISTRY AND POOL WATER BALANCE

Industrial Water Reuse and Wastewater Minimization

WATER TREATMENT GLOBAL PRODUCT SELECTION GUIDE

BASIC WATER TREATMENT OF STEAM BOILERS

FINAL EVENT LIFE+ BIOMOMI BIO-MONITORING AND AUTOMATIC MICROBIOLOGICAL CONTAMINATION CONTROL SYSTEM OF INDUSTRIAL HYDRAULIC CIRCUITS

Cooling Water. Watertreatment and chemical conditioning of open and closed cooling systems. Dr. K. Nachstedt, Weidner Wassertechnik, Herten

Technical Information for Cooling Towers Using Recycled Water

Cooling Water Management. Basic Principles and Technology

Cooling Towers: Understanding Key Components of Cooling Towers and How to Improve Water Efficiency

NORKOOL Industrial Coolants

The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation

Dispelling the Myths of Heat Transfer Fluids. Kevin Connor The Dow Chemical Company

COOLING WATER MANAGEMENT

Ion Exchange Softening

Water Softening for Hardness Removal. Hardness in Water. Methods of Removing Hardness 5/1/15. WTRG18 Water Softening and Hardness

A Guide to Trouble-Free Cooling Towers

Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation

ENE 806, Project Report 3 CHEMICAL PRECIPITATION: WATER SOFTENING. Grégoire Seyrig Wenqian Shan

Ion Exchange Design Hand calculation. Brian Windsor (Purolite International Ltd)

Sulfites for Oxygen Control

The National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio

Silica Over-Saturation, Precipitation, Prevention and Remediation In Hot Water Systems Edited By Dave Peairs, Cal Water, Technical Director

Design of Purified Water and Water For Injection Systems. Hugh Hodkinson Engineers Ireland Chemical & Process Division

Scale and Deposit Control Polymers for Industrial Water Treatment

C. Provide temporary water treatment for chilled, hot and condenser water until facility has final connections.

GUIDELINES FOR LEACHATE CONTROL

Thermo Siphon Solar Systems

Cooling Water Problems and Solutions

HVAC Energy Conservation through Cooling Water Treatment

5.0 EXPERIMENT ON DETERMINATION OF TOTAL HARDNESS

Total Suspended Solids Total Dissolved Solids Hardness

Removing Heavy Metals from Wastewater

D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:

Cooling Tower Sidestream Filtration A Green, Proven Cost Reduction Technology

Technical Presentation IMPORTANT TOPICS

Metals and Non-metals. Comparison of physical properties of metals and non metals

Control of legionella bacteria in water systems

Corrosion Inhibitors in Antifreeze Coolants

RO Reverse Osmosis equipments

A Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE

Cooling Tower Efficiency Guide Property Managers

Guidelines for Produced Water Evaporators in SAGD

TREATMENT OF PHOSPHATE FERTILIZER PLANT WASTE WATER IN FLORIDA FOR DISCHARGE AND RE USE PURPOSES

Complexometric Titrations

A SHORT INTRODUCTION TO CORROSION AND ITS CONTROL

Domestic Chemical Water Treatment Manufacturers Association

Storage-stable Aqueous Solutions of Chlorine Dioxide

Sustained growth in the demand

Calcium Carbonate Scale Formation, Prediction and Treatment (Case Study Gumry Oilfield-PDOC)

The chemical components of detergents and their roles in the washing process

Hydrochemistry. Deacidification. Junianti Roslinda Sihombing. Practical Date : Monday, Report Delivery : Monday,

The Use of Phosphates For Potable Water Treatment

Subject: Technical Letter 22 April 1977 Removal of Water Supply Contaminants -- Copper and Zinc

THE PHOSPHATE METHOD FOR PRODUCING QUALITY DRINKING WATER!

NON-HAZARDOUS CHEMICAL TREATMENTS FOR HEATING AND COOLING SYSTEMS

WATER TREATMENT THE NEED FOR CONTROL COMMON IMPURITIES FOUND IN WATER. CALCIUM CARBONATE (CaCO3) CALCIUM SULFATE (CaSO4) MAGNESIUM SULFATE (MgSO4)

Ionic and Metallic Bonding

The role of CO 2 in pool water

Best Management Practice and Guidance Manual for Cooling Towers

Hardness - Multivalent metal ions which will form precipitates with soaps. e.g. Ca 2+ + (soap) Ca(soap) 2 (s)

Pure Water. Isn t Hard to Find

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities

DEIONIZATION IN A "NUT SHELL"

Molarity of Ions in Solution

COOLING TECHNOLOGY INSTITUTE

Estimation of Hardness of Water by EDTA Method

Feasibility study of crystallization process for water softening in a pellet reactor

CONVERTING A CLOSED-LOOP WATER SYSTEM TO A GLYCOL SYSTEM

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

Testing Water for Gardening and Lawn Irrigation

Conductivity and TDS Meters

Biocorrosion Risk Assessment

Environmentally Friendly Solutions for Industry MEXEL 432 CASE STUDY - GEOTHERMAL POWER GENERATION

Wire Drawing Soap Lubrication: Principles And Factors Affecting Selection

INTAC PARTS & SERVICES ( H)

Dissimilar Metal Corrosion

NALCO BT-25 Boiler Internal Treatment

SODIUM CATION EXCHANGE (ZEOLITE) WATER SOFTENING PROCESS

Amiad s AMF² pre-treatment technology ensures efficient and reliable nanofiltration of Scottish Highland loch water

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

conductivity emulsification saponification wetting peptizing dispersion rinsability controlling mineral deposits Sequestration chelation

Fertigation. This project is supported by Growcom, through funding from the Australian Government.

SUGAR MILL BOILER CYCLE CHEMISTRY: AN UPDATE ON BEST PRACTICES DAVID RODMAN. Nalco Australia Pty Ltd, Townsville

Trichloramine and Asthma in Swimming pools & spas Problem solved

Cooling Water Treatment

Predictive modeling of scale, corrosion, & inhibitor dosages for Cooling Waters. French Creek

Optimization of Cleaning-In- Place (CIP) processes in bottled water industry

Transcription:

THE USE OF OZONE IN COOLING TOWERS Paul D. McNicholas Ozonia Ltd Duebendorf, Switzerland Abstract Ozone has been successfully applied to industrial cooling water systems with the resultant improvement in operational efficiency due to increased heat transfer, reduced system corrosion, improved environmental impact and reduced on-going chemical expenditure. The aim of this paper is to provide practical advice on the options available for the application of ozone and the potential benefits which can be realised. Introduction Open evaporative cooling systems are used extensively throughout industry to remove heat from process systems and modern buildings for the purpose of air conditioning. Heat is dissipated to atmosphere by the evaporation of water and energy removed due to the latent heat of vaporisation of water, achieved by bringing the cooling water into direct contact with the surrounding air. As a result, open type evaporative cooling systems are subject to potential biofouling problems as a result of micro-organisms from the surrounding environment. They are also prone to corrosion due to the establishment of corrosion cells within the system fabric in contact with the aqueous medium and to scale formation due to the increasing concentration of scale forming hardness salts as a result of the cycling of mineral salts present in the system make up water due to the evaporation of pure water from the cooling circuit. For optimum performance the above problems must be minimised, heat transfer surfaces maintained in a clean condition, corrosion controlled to maintain system integrity and to avoid unexpected outages and microbial activity controlled to prevent the build-up of biofilm and the proliferation of legionella bacterium. Traditional methods utilise a chemical programme incorporating chemical inhibitors and biocides which, in themselves, also present particular problems of storage and handling and potential environmental impact issues. Practical Ozone Scaling Index ( POSI) The normal convention used to determine the degree of scale forming potential of a cooling water at differing cycles of concentration is the Langelier saturation Index (LSI). The LSI uses the calcium concentration (ppm CaCO 3 ), alkalinity concentration (ppm CaCO 3 ), TDS and temperature of the cycled-up cooling water to determine the maximum ph at which calcium carbonate will be stabilised. This is then compared to the actual ph of the cooling system which, if greater, will exhibit scale forming potential. Scale inhibitors are then dosed to retain calcium carbonate in solution at positive LSI and typically a maximum LSI of say +3 can be achieved and is controlled by system bleed to achieve the maximum cycles of concentration possible under the chemical treatment programme. VS/PMcN/Cooling Towers/10-10-02

This is to be compared to virtually zero blow-down systems using ozone, where the cooling water is cycled up many more times, realising calcium loss within the cooling system but also without the deposition of hardness scale on heat transfer surfaces. Sandy calcium carbonate precipitates can be found in cooling tower sumps rather than on heat exchanger surfaces indicating the involvement of surface-active biopolymers. Several mechanisms have been proposed to explain the observed scale reduction in ozonated water including chelation of scale forming cations by oxidation products of biofilm and organic compounds to liberate bio-polymers, carboxylic acids and other organic compounds. Alginates, polysaccharides and other bio-polymers released are known to be surface active and may function as dispersants for suspended solids, including small crystalline scale particles and corrosion products. This approach also gives excellent corrosion inhibition within the cooling system probably due to the cathodic protection afforded by calcium carbonate. Thus the water conditions establish a non-corrosive environment. In order to quantify the parameters for ozone to operate at high cycles of concentration without scale deposition the POSI index was developed which gives the maximum conductivity at which the tower can operate without scale deposition. As calcium is lost from solution this also leads to a reduction in the conductivity (TDS) of the cooling water this is expected and allowed for in this index. This maximum conductivity can then be compare to the conductivity of the cooling tower make-up water to then determine the actual maximum concentration factor. As this mechanism also provides corrosion protection it is important that the cycles of concentration are not allowed to go too low. Maximum cooling water conductivity = 10 (1/log((Ca x Mg)/(Na + Cl))/log(Alk/10) x conductivity of make up water Ca = Calcium hardness of make-up, ppm CaCO 3 Mg = Magnesium Hardness of make-up, ppm CaCO 3 ALK = Total alkalinity of make-up, ppm CaCO 3 CI = Chlorides in make-up, ppm Cl Na = Sodium in make-up, ppm Na For example, with a make-up water quality with the following parameters: ph 8.4 Conductivity 130 µs Calcium hardness 30 ppm CaCO 3 Magnesium hardness 10 ppm CaCO 3 Sodium 10 ppm Na Chloride 7 ppm Cl Total alkalinity 39 ppm CaCO 3 Temperature 55 deg. F The maximum conductivity using POSI = 10 (1/log ((30 x 10) / (7 + 10)) / log (39/10) x 130 = 2964 µs maximum concentration factor = 2964 130 = 22.8 cycles VS/PMcN/Cooling Towers/10-10-02 2

This would compare to a chemical treatment programme maximum cycles of concentration for this water of some 10 cycles. The water is supersaturated with calcium thereforeany chemical species entering the cooling system which would react with calcium to form a very insoluble salt would cause significant scaling. Such species are phosphate and borate and could be present in a chemical water treatment programme. The guidance note recommends a maximum of 1 ppm total phosphate in the make-up water to the cooling system. Minimum cycles of concentration To establish the minimum cycles of concentration needed to afford corrosion protection the alkalinity and silica concentrations within the make-up water are used: Theoretical silica concentration should exceed 150mg/l SiO 2 Theoretical alkalinity should exceed 450mg/l CaCO 3 For example: Make-up water silica = 20mg/l Make-up water alkalinity = 60 mg/l Minimum cycles of concentration required based on chloride analysis = 7.5 SiO 2, 20 x 7.5 = 150 mg/l SiO 2 Alkalinity, 60 x 7.5 = 450 mg/l CaCO 3 Recommended ozone concentrations There is general agreement in the literature as to the recommended residual ozone concentrations required. These range from: Cooling tower basin 0.025 to 0.250 ppm Recirculating pump inlet 0.075 to 0.150 ppm Heat exchanger inlet 0.040 to 0.080 ppm Return line to tower 0.010 to 0.040 ppm We calculate the size of the ozone generator based upon a dose rate of 0.2 ppm with respect to the recirculation rate of the system. The recommended residuals should be achieved at this dose rate, as we have found from actual applications. For small systems (less than 20 minute turnover time) an application dose rate of 0.1 ppm based upon the recirculation rate is likely to be sufficient. Using an injector system we can achieve 95% mass transfer in a pressurised side stream strong water line which can be used to provide multi-point dosing around the tower system to ensure that the recommended reserves are achieved. The main dosage point being after the recirculation pumps. When corrosion has occurred it is typically linked to higher ozone concentrations so care should be taken to ensure that the maximum recommended residual ozone concentrations are not exceeded. VS/PMcN/Cooling Towers/10-10-02 3

Use of ozone with chemicals Under some circumstances it may be required to utilise chemical treatment in addition to ozone. In these conditions care should be taken not to compromise the treatment programme integrity. Many modern programmes utilise inhibitors which are stable to the typical ozone application rates given above, however, the system parameters, such as the concentration factor, must be operated in line with the requirements of the chemicals utilised. In this instance ozone is used as a complimentary product to control microbiological fouling and to achieve low planktonic counts. Whilst the water treatment specialist should be consulted with respect to the compatibility of his product with ozone, the following actives have been evaluated and found to be compatible: PBTC Molybdate Silicate TTA / BTA Zinc based Phosphate Phosphonate scale and corrosion inhibitor to protect against hardness scale deposition. (HEDP and AMP are unstable to oxidising compounds including ozone) Corrosion inhibitor for soft waters Corrosion inhibitor at system calcium concentrations < 200 ppm. Yellow metal inhibitors can be effectively used due to their relatively slow oxidation by ozone (72h to completion), copper and brass alloy protection. Corrosion inhibitor. Used in di-anodic application with dispersant and acid dosing ozone stable dispersants. Ozone compatible materials The following materials are considered suitable for use with ozone: Pipe work: Vessels: Gaskets: 316 Stainless steel Teflon/PTFE Kynar/PVDF 316 stainless steel (welds to be ground smooth internally) Teflon/PTFE FPM/Viton Off-Gas Venting Off-gas venting can be achieved by either using a contacting vessel or by installing a degassing valve at the highest point in the recirculation system near the injection point. A VOD may be utilised in either case or alternatively it is feasible to take the off gas into the area of the cooling tower sump to make use of any small traces of ozone which may be present to provide additional protection for the cooling tower sump. VS/PMcN/Cooling Towers/10-10-02 4

Economic comparison Each case must be evaluated individually and will depend upon the chemical programme utilised and the reasons for utilising ozone from an improved performance and possibly an improved environmental perspective. Some indication can however be given: Cooling Tower: System volume 4 000 m 3 Recirculation rate 21 000 m 3 /h Temperature differential 10 F Evaporation rate 210 m 3 /h Programme Type Chemicals Ozone only Concentration factor 3 10 Bleed rate (m 3 /h) 105 23 Water usage (m 3 /h) 315 238 Savings: Water cost savings - Make-up ($0.06 m 3 ) $40 471.00 / year - Discharge ($0.1 m 3 ) $67 452.00 / year Chemical programme cost savings - Inhibitor at 25ppm $115 000.00 / year - Biocides $100 000.00 / year - Dispersant $50 000.00 / year Maintenance savings Total on-going savings $20 000.00 / year $342 923.00 / year Unquantified cost savings Energy savings as a result of improved operational efficiencies due to the increased heat transfer resulting from biofilm removal from heat exchange surfaces. These savings could realise the greatest benefit from the use of ozone for cooling water treatment as typically approach temperature performance improves dramatically. A reduction of 3 C in cooling water temperature would give an associated energy saving of approximately 1%. Administrative cost savings resulting from eliminating the need for chemical inventory management. VS/PMcN/Cooling Towers/10-10-02 5

Ozone treatment costs A complete ozone solution incorporates the following equipment: Feedgas supply equipment -in this case air fed with a compressor and air dryer. Ozone generator proper Contacting system - consisting of side stream injector and motive water pump. The equipment would be installed in a suitable room/enclosure fitted with appropriate health and safety devices. An off-gas venting degassing valve would be installed in a suitable location. Total cost of the equipment for the above example is estimated at $ 370 000.00 including monitoring and control equipment. The total electrical running cost at $0.06 / kwh would be $ 59 524.00 per year. In addition to the above costs allowance must be made for installation. For many cooling water systems ozone provides an efficient treatment solution which is easier to manage, provides on-going cost savings and supports environmental improvement objectives. Keywords Ozone, Cooling Water, Cooling Towers, Inhibitors, Chemical treatment, Biocide 1) To be added 2) References VS/PMcN/Cooling Towers/10-10-02 6