Technical Information for Cooling Towers Using Recycled Water
|
|
|
- Simon Owens
- 10 years ago
- Views:
Transcription
1
2 Using Recycled Water Why Use Recycled Water? Introduction In today s highly competitive markets, businesses and institutions must make wise use of available resources. Increasingly the most forward-thinking companies are partnering with local utilities to reduce their demands for energy and water, both to save costs and improve the long-term sustainability of their business. Using highly treated recycled water for non-potable purposes is an effective way to reduce the demand for precious fresh-water resources. It is also a recognized green building practice. Recycled water has been used in industrial settings throughout California and the arid west for nearly 100 years. Locally, Biogen Idec, a company specializing in the development of therapeutic products for the medical field, worked with the County and City of San Diego in 2006 to convert their cooling towers to recycled water. The cooling towers at Biogen Idec are the largest users of water in the facility. Conversion to recycled water has allowed Biogen Idec to realize significant cost savings through discounted rates and has provided Biogen Idec with a drought-proof source of water. Elsewhere in Southern California, Orange County s Irvine Ranch Water District provides recycled water for cooling tower and toilet-flushing use in over 40 high-rise office buildings. Los Angeles County s West Basin Municipal Water District delivers service to the cooling towers at Cal State Dominguez Hills and the American Honda Campus. In Riverside County, Inland Empire Utilities Agency s headquarters building secured 52 LEED points to achieve Platinum Certification from the U.S. Green Building Council. Among these points was credit in the Innovation and Design Process category because of indoor recycled water use. There is approximately 13,000 acre-feet of recycled water reused annually within the San Diego County Water Authority (SDCWA) service area. Roughly 70% of the recycled water is used for agriculture, landscape irrigation, and other municipal and industrial uses. The annual beneficial reuse of recycled water in San Diego County is projected to increase to over 53,000 acre-feet by the year By converting to recycled water, cooling tower customers can secure a drought-proof water supply that can protect future growth potential even when water supply shortages loom. Converting to recycled water enhances overall water use efficiency and helps customers comply with their green building goals. Purpose of this Guide The purpose of this guide is to provide information tailored specifically for customers planning to use recycled water in evaporative cooling tower applications. Evaporative cooling systems, which don t need potable water, are a good use of recycled water. By focusing on water quality and optimizing system control, customers can reduce their demand for potable water without compromising the performance of their systems. SDCWA has published this document to assist customers, who are considering converting to recycled water by providing detailed information on water quality and system management together with cost saving potential. For additional information or questions concerning water recycling, contact the SDCWA s recycled water information line at (858)
3 Operational road map to converting cooling towers The steps for establishing an operational regime for a cooling tower are outlined below. These steps can be performed by the system owner or, as is often the practice, by its maintenance contractor. Step 1: Determine the materials used in the cooling system and the temperature, flow rates and hours of operation. By understanding these factors, system owners can narrow the list of water quality constituents that cause concern. For example, if a system contains 304 SS, chloride levels are an important concern. However if the system is constructed of fiberglass, this water quality parameter is less of a problem. Step 2: Evaluate the source water quality in order to understand if treatment is necessary to make the water compatible with your system materials. Step 3: Select a treatment system if source quality is problematic. Step 4: Establish the desired cycles of concentration to minimize water and chemical use, without compromising system performance. While pretreatment can condition water to acceptable standards, each cycle of concentration will increase the TDS, Conductivity and Chlorine concentration in the water and at some point, these constituents will affect system performance. This point limits the cycles of concentration and establishes when blowdown should occur and make-up water added. The system manufacturer s recommendations for conductivity and system performance with respect to TDS will likely be the limiting factors on cycles of concentration Step 5: Potable water back-up is necessary. This will provide increased reliability and assist with blending during conversion. Step 6: Monitor Makeup and Blowdown water quality to confirm that the system is behaving as anticipated. Step 7: Reset chemical dosing and/or cycles of concentration as necessary to achieve desired performance. 2
4 1Cooling System Basics These guidelines focus specifically on evaporative cooling units. Due to the nature of evaporative cooling units, water lost from evaporation and blowdown has to be replenished. In regions where potable supply is plentiful, cooling towers use potable water for making up the water losses in the cooling tower. However, as California s water supplies are increasingly constrained, businesses and institutions can consider converting to recycled water to supply the makeup water. Evaporative cooling systems are composed of two components: a heat exchanger (chiller) and a cooling unit (cooling tower). The heat exchanger or chiller allows cooling water to transfer heat from production source (facility equipment or fluids) without direct contact, creating heated water. The main purpose of the cooling tower is to expel the heat from the heated water efficiently. Heat is removed by transferring it to air through evaporation. Cooling tower packing material or fill optimizes the contact of air and water, improving the heat transfer and efficiency of the tower. Splash and film fill types are the two types of packing materials inside the cooling towers. The figures below illustrate evaporative cooler configurations. In counter flow induced draft cooling towers, the water being cooled moves from the top down through the tower, while air is pulled in the counter direction from the bottom up. Evaporative Cooling System Overview COUnTER FLOW InDUCED DRAFT COOLIng TOWER 3
5 In cross flow induced draft cooling towers, the water being cooled moves from the top down through the tower, while air moves across the water flow and then out the exhaust. Air is moved by fans, blowers or natural draft. CROSS FLOW InDUCED DRAFT COOLIng TOWER In forced draft cooling towers, air is pushed through the tower from an inlet to an exhaust. Downward direction for movement of the water being cooled is shown here. FORCED DRAFT COOLIng TOWER 4
6 EvAPORATIve ConDEnSER COOLIng TOWER In evaporative condenser cooling units, the fluid that removes heat from the process is kept isolated from the water used for evaporative cooling. The cooling water is never circulated to the process it cools. Some systems use condensable fluids as refrigerants for transferring heat. Because the cooling system relies on evaporation, the total dissolved solids in the cooling tower water are concentrated. In a well-designed and operated cooling tower, even with a good water quality control system, a portion of this water in the cooling tower is constantly flushed to make sure that solids buildup does not damage the equipment. This blowdown water is replaced with new makeup water that has lower dissolved solids concentration. The combination of evaporation, blowdown and makeup creates the cooling tower water demand and it is this demand that can be served by recycled water. Water Use in Cooling Towers Evaporation The purpose of a cooling tower is to expel heat from water to the air by evaporation. As a general rule of thumb, for each 10º F that the water needs to be cooled, one percent of the cooling water is evaporated. Depending on the cooling needs, the evaporative water demand can be substantial. The table on the right provides an example of the water used to achieve 10º F, 20º F, and 30º F changes in temperature. 5
7 Makeup Water and Blowdown All water has some concentration of dissolved or suspended solids. When water evaporates, as it does in a cooling system, the dissolved solids are left behind increasing the concentration in the remaining water. Concentrated solids can build up in the form of scale and cause blockages or corrosion to the cooling system materials. Also the growth of algae and other biological matter can lead to corrosion, plugging of film fill, and eventually collapse of film fill. Water treatment can reduce the impact of the solids and biological matter, however, after a certain point impurities become too concentrated and solids and biological matter must be removed from the system to avoid serious damage. To stay below this maximum acceptable concentration and to maintain the tower s water balance, fresh makeup water is added and concentrated blowdown water is discharged. The maximum acceptable levels for solids and biological matter are site specific and depend on both local water quality and cooling tower construction. Cycles of Concentration A cycle of concentration occurs when the water balance of evaporation, makeup water and other losses concentrates solids by multiples of the makeup water. For example, when the solids concentration in the cooling tower water has doubled that of the makeup water, it is described as two cycles of concentration. When the solids concentration in the cooling tower water is triple that of the makeup water, it is described as three cycles of concentration. Increasing the cycles of concentration is a very common water conservation measure for cooling towers. It can also reduce treatment chemical costs, because when less water is used, fewer pounds of treatment chemicals are required. Determining the optimum number of cycles of concentration is a balancing act between savings in water, sewer and chemical costs and the increased risk of scale, plugging and film fill failure that can occur with water that has higher dissolved solids. Usually, cooling towers using makeup water with low dissolved solids can be operated at the higher cycles of concentration. Because recycled water typically is higher in dissolved solids than potable water, converting to recycled water for makeup water may require operational changes, including reducing cycles of concentration to manage the different quality of recycled water. 6
8 2Water Quality Considerations Matching the cooling system materials, design, and operation with water quality allows users to develop the water treatment program and operation cycles that meet their needs. It is not the water source, but the effect the water source s constituents have on the cooling system that matters. Protecting the cooling system is the first priority. Optimizing the performance of the cooling system requires: Evaluating the cooling system to determine the materials that can be affected by water quality Evaluating the water quality constituents Evaluating the water treatment options Establishing the treatment and operational cycle regime for the system Cooling System Component Considerations Material Water Quality Effects Management Considerations Wood N/A Protect from decay or chemical attack. Mild Steel Galvanized Iron (Cu and Zn coating) Stainless Steel 304-SS Evaluating the Cooling System Matching the cooling system materials, design, and operation with the water treatment program and water quality is essential for protecting the cooling water contacted equipment. Thus, the water quality within the cooling system will determine what water treatment program should be used. This table below describes materials commonly found in cooling towers, the affect of water quality on the material, and recommended management considerations. Susceptible to corrosion from high total dissolved solids, suspended solids, biomass, scale and heavy metals. Susceptible to corrosion from high dissolved solids and ph levels below 6.5 or above 8.5. Susceptible to corrosion from chlorides when deposit-forming conditions exist. Biomass deposits can cause rapid pitting. Corrodes at chloride levels of 200 mg/l when deposit-forming conditions exist. Tolerates chlorides levels of 1,000 mg/l on clean surfaces. Chemical water treatment minimizes this potential. Increased flow rates and periodic flushing of heat exchangers minimizes this potential. Reduce cycles of concentration. Adjust ph with chemical treatment. Chemical water treatment minimizes this potential. Maintaining a positive oxidant level will benefit the integrity of the protective oxide film on stainless steels and will reduce biomass accumulation. Nitrates, which occur in higher levels in recycled water, are known to reduce stainless steel corrosion. 7
9 Cooling System Component Considerations Stainless Steel 316-SS Copper alloys Plastics Similar to 304-SS with higher chloride tolerances. Tolerates chloride levels of 5,000 mg/l when deposit-forming conditions exist. Tolerates chloride levels up to 30,000 mg/l on clean surfaces. Susceptible to corrosion from ammonia and high dissolved solids. Ammonia above 0.5 mg/l as NH3 can cause cracking and corrosion and contributes to biomass that can cause corrosion to copper alloy under deposits. Coppernickel alloys (90/10 and 70/30) are resistant to cracking. Similar to 304-SS. Water treatment can minimize this potential. Copper corrosion inhibitors such as TTA (Tolytriazole or BZT (Benzotriazole) and BBT (Butylbenzotriazole) reduce but do not totally eliminate cracking. BBT is most effective. Coppernickel alloys (90/10 and 70/30) are resistant to cracking. Keep clean and free of deposits to prevent clogging. Keep plastic film free of biomass buildup. Evaluating the Water Quality Constituents All water, regardless of its source contains various constituents at different concentrations. Some constituents can be very beneficial, while others need to be handled by specific water conditioning or chemical treatment. Knowledge and understanding are needed to assure successful water conservation and use. The chemistry of any given source of water will impact the structures and operation of all types of cooling towers. Operations at higher cycles of concentrations increase the potential for equipment scaling, corrosion, and fouling unless some type of treatment is implemented. The table below describes common water quality parameters and their effects on cooling systems. Impact of Water Quality Parameters on Cooling Systems Water Quality Parameter Hardness (Measure of combined calcium and magnesium concentrations) Alkalinity (Measure of water s ability to neutralize acids.) Impact on Cooling Water System Contribute to scale. Calcium salts exhibit inverse solubility which increases precipitation with water temperature. Magnesium is troublesome when silica levels are also high and can result in magnesium silicate scale in the heat exchangers. Alkalinity is an important means of predicting calcium carbonate scale potential. 8
10 Impact of Water Quality Parameters on Cooling Systems Silica Stainless Steel 304-SS Water Quality Parameter Total Suspended Solids (TSS) (Consists of undissolved material such as silt, sand, fine clay, and vegetation.) Ammonia Phosphate Chloride Iron Impact on Cooling Water System Can produce difficult-to-remove scale deposits. Pretreatment or sidestream filtration is often required if the silica levels are above 150 ppm (as SiO2). Susceptible to corrosion from chlorides when depositforming conditions exist. Biomass deposits can cause rapid pitting. Corrodes at chloride levels of 200 mg/l when depositforming conditions exist. Tolerates chlorides levels of 1,000 mg/l on clean surfaces. Can enter the system with makeup water and can be generated in the system from corrosion and scale byproducts or from air/water contact. Suspended solids can adhere to biofilms and cause under-deposit corrosion. TSS can be controlled through pretreatment, sidestream filtration or through use of deposit control agents. Promotes biofilm development in the heat exchangers and cooling tower fill. Corrosive to copper alloys at concentrations as low as 2.0 ppm. Combines with chloride to form chloramines which can negate the disinfecting effect of chlorine and some nonoxidizing biocides such as glutaraldehyde. Bromine is a more cost-effective biocide if ammonia is present. At concentrations of 4.0 mg/l or less and ph is controlled between 7.0 and 7.5, phosphate may provide corrosion protection because it is an anionic inhibitor. At concentrations greater than 20 mg/l, combined with calcium greater than 1,000 mg/l, there is a potential for calcium phosphate scaling. Acts as a nutrient for biofilms. Corrosive to most metals. Limit concentrations to 300 ppm for stainless steel: up to 1,000 ppm for other metals. Can combine with phosphate to form foulants. May deactivate specialized polymers used to inhibit calcium phosphate scaling. Recycled water has concentrations over 0.1 mg/l of iron and specialized treatment for iron may be required. 9
11 Impact of Water Quality Parameters on Cooling Systems Water Quality Parameter Biological Oxygen Demand (BOD) Nitrates and Nitrites Zinc Organics Fluoride Heavy Metals (e.g. Cu, Ni, and Pb) Impact on Cooling Water System Reflects the organic content and associated demand for oxidizing biocide. Can provide additional mild steel corrosion control at levels above 300 mg/l. Can contribute to reductions in stainless steel cracking and pitting erosion. Nitrates do not attack copper alloys or protect them from corrosion. Can assist phosphates and nitrates in reducing mild steel corrosion rates and pitting tendencies. Levels in cooling water above 0.5 mg/l are beneficial, but levels above 3.0 mg/l can contribute to deposits. Acts as fertilizer for microorganisms. Water-soluble cationic polymers can react with some anionic treatment biocides, as well as some scale and corrosion inhibitors. At 10 ppm or more can combine with calcium to cause scale formation. Copper and nickel can plate out on steel, causing localized galvanic corrosion that can rapidly penetrate thin steel heat exchanger tubes. Evaluating Water Treatment options Cooling tower water treatment can be both chemical and physical. New physical treatment systems based on electromagnetic energy are presenting opportunities to manage cooling tower water quality without dependence on chemical systems. Because of CDPH s requirements for biocide addition to recycled water used in cooling towers, combined systems that use physical treatment for corrosion and depositional control and chemical treatment for microbiological control can provide an effective hybrid system. Chemical Treatment It is most common for chemical treatment programs to be used for controlling corrosion, deposition, and microbiological growths. Prior to installing a chemical treatment system, or introducing a new chemical treatment agent, contact your local fire department s hazardous materials unit for regulatory, reporting, and permitting requirements. Corrosion Control (Inhibitors) Corrosion is an electrochemical process in which metals are oxidized by transferring electrons from an anodic site to a cathodic site. Cathodic inhibitors reduce the amount of cathodic surface available and anodic inhibitors reduce the amount of anodic surface available. Sometimes both types of inhibitors are needed to prevent corrosion. Phosphates, zinc salts, molybdates, and polysilicates are typical mild steel corrosion inhibitors, while organic nitrogen-based compounds (azoles) are copper alloy corrosion inhibitors. 10
12 Deposition Control Several different types of deposits can form in cooling water systems, necessitating different approaches for control: Depositional Inhibitor Control focuses on either solubilizing agents to prevent scale from precipitating or crystal modifiers to alter the nature of precipitate to prevent adhesion to surfaces. Dispersants and Surfactants are charged molecules that adsorb suspended solids and cause a mutual repulsion, which keeps solids as smaller particles. Acid, Phosphonates and Water-Soluble Polymers are typical mineral scale inhibitors. Deposition control is particularly critical in systems with high levels of calcium hardness. Microbiological Growth Controls The hydroxyl radicals, hydrogen peroxide and hypochlorite (bleach), and chlorine gas are oxidizers that kill microbiological growths. CDPH requires the use of microbiological growth controls when recycled water is used for cooling tower applications The table below illustrates common conditioning chemicals, their use and their recommended maximum concentrations. Conditioning Chemical Additives Conditioning Chemical Use Recommended Maximum Concentration** Organophosphates (phosphates)* Control scaling for steel 20 mg/l as PO4 Orthophosphates, Polyphosphates Inhibit corrosion and control scaling 20 mg/l as PO4 Sodium silicate Inhibit corrosion 100 mg/l as SiO2 Aromatic triazoles Inhibit corrosion 2-4 mg/l Molybdates*** Inhibit corrosion 40 mg/l as molybdenum Non-Oxidizing Biocides such as: Isothialozin**** Dibromoitrilopropionamide Quaternary amines Inhibit biological growth See notes. Oxidizing Biocides Chlorine Bromine Inhibit biological growth 0.5 mg/l * Requires close monitoring of blowdown and dispersant to prevent calcium phosphate scale. ** If corrosion protection of the cooling system require high chemical dosing rates that result in concentrations of inhibitors that exceed these recommended maximum levels, the system should be thoroughly investigated to determine the cause. *** Molybdates discharged to treatment plants may be prohibited in certain service areas. ****Copper is often used as a stabilizer in isothiazolin biocides. Because the presence of copper is not typically noted on the Material Safety Data Sheet (MSDS), chemical analysis data should be obtained before use. Such data may be obtained from the vendor or other industrial dischargers. Copper containing additives must not be used. 11
13 Physical Treatment (Electromagnetic Systems) The operating principles of these devices are based on four essential methods of action: electromagnetic signal; interaction of the induced electric field with colloidal particles; control of microbial populations; and corrosion control. Pulsed-power systems work by changing how calcium carbonate and other dissolved minerals precipitate from solution. Pulsed-power fields activate colloidal nucleation sites in the bulk solution. These activated sites become the preferential nucleation sites for precipitation. The amorphous precipitate, generated by a pulsed-power system, does not adhere to the pipe wall but remains with the bulk solution and is removed via blowdown and/or side-stream filtration. The systems use colloidal science instead of inorganic chemistry to control scaling. Pulsed power systems are a bacteriostatic product rather than a true bactericide. Although the bacteria are not killed, they are controlled through two mechanisms. The first relates to the well-established effect in water treatment that coagulation and calcium carbonate precipitation will result in a microbial reduction. The second mechanism involves sub-lethal injury that controls bacteria even when there is no precipitation occurring. This mechanism is based on the interaction of the low frequency radiation generated by the pulsing with the bacteria. In California, CDPH requires that biocides be used in cooling towers with recycled water feedwater regardless. Corrosion inhibition is accomplished indirectly by maintaining sufficient cycles of concentration to force the system into the alkaline mode at the saturation point of calcium carbonate, which is a cathodic corrosion inhibitor. In this type of water system, the expected corrosion rate on mild steel is 2 to 5 mils per year (mpy). The Cooling Technology Institute Guideline WTP-130 lists corrosion rates in cooling towers on mild steel of 2 to 5 mpy as good and 0 to 2 mpy as excellent. In many municipal water systems, phosphates or silicates are used as corrosion inhibitors to meet EPA s copper/lead requirements. Where these systems are cycled up, the corrosion rate on mild steel is typically less than 2.0 mpy. 12
14 3Green Building Considerations and Leed Certification LEED is a third-party certification program and the nationally accepted benchmark for the design, construction and operation of high performance green buildings. LEED gives building owners and operators the tools they need to have an immediate and measurable impact on their buildings performance. LEED promotes a whole-building approach to sustainability by recognizing performance in five key areas of human and environmental health: sustainable site development, water savings, energy efficiency, materials selection and indoor environmental quality. Utilizing recycled water in your building can assist you in achieving certification. The Inland Empire Utilities Agency (IEUA) received 2 LEED Credits in the Innovation and Design Process Category for its indoor use of recycled water. The first credit was for water use efficiency, recycled water combined with conservation efforts reduced the building s water use by 73%. The second credit was for its Green Building Education program. IEUA included signage in its building and provides tours and education publications about the sustainable nature of its building. 13
15 14
16 4 Regulatory Considerations Converting to recycled water use means complying with requirements set forth by the California Department of Public Health and San Diego County Department of Environmental Health as well as complying with guidance established in the Uniform Plumbing Code. This section provides an overview of the various requirements. Recycled Water Regulators California Department of Public Health The CDPH is responsible for protecting public health and safety by regulating both the potable and recycled water supplies. CDPH s authority around water quality and treatment is outlined Title 22 of the California Code of Regulations. CDPH s authority around backflow prevention is outlined in Title 17 of the California Code of Regulations. For each recycled water use, CDPH must review and approve both an Engineering Report and the project design documents. San diego county department of environmental health The San Diego County Department of Environmental Health (DEH) regulates the use of recycled water through a delegation agreement with CDPH. Land and Water Quality Division staff review recycled water use plans, and conduct site inspections to ensure drinking water supplies are not contaminated with recycled water. Staff also monitor spray irrigation sites to ensure the recycled water irrigation does not present a risk to the public. Recycled water sites must also pass an initial cross-connection control shut down test and retesting every four years thereafter. This test should be coordinated with the agency supplying the recycled water. Local Building Officials Whether you are constructing a new facility or re-plumbing your facility to change the source water for your cooling system, contact your local building official for permits or requirements. In some instances there may be special requirements for reusing process water in cooling systems. Complying WIth the cdph Requirements As noted above, CDPH through Title 17 and Title 22 of the California Code of Regulations sets forth a number of specific requirements for users employing the recycled water supply. Most of these requirements can be satisfied with a thoughtful design process. Several of the requirements are specific to operations and reflect practices that are common to any facility where a potable and a nonpotable water supply are employed. The EnGIneering Report The Engineering Report is a very important tool for explaining the project to both your water district and CDPH. The Report should provide the detail and explanation necessary to allow regulatory agencies to understand your project and your strategy for complying with regulatory requirements. The Engineering Report should be submitted as early as possible in the design process in order to allow for comment and revision before detailed site plans, mechanical plans and plumbing plans are complete. 15
17 The Engineering Report should include a description of the proposed projects and recycled water use area and enough detail and graphics to allow the project to reviewed. Typical components of the Engineering Report include: Description/location of recycled water use areas Site piping diagram illustrating compliance with all separation requirements Description of the pipe/valve labeling scheme Description and location of backflow prevention Description and location of signage Description (manufacturer s cut sheet and specifications) for the drift eliminator(s) Description of proposed bacteriological control system including schematic flow diagrams if appropriate Description and plan of back-up water supply Location of connection(s) to the sanitary sewer system PIPe Separation and Labeling CDPH requires that recycled water pipelines be separated from potable water pipelines. CDPH also requires that recycled water pipelines, valves and other devises be clearly labeled and identified. The Engineering Report should include enough detail on the Site Plan to illustrate the separation requirements can be met. The Engineering Report should describe the pipe/valve identification system that will be used. If recycled water is used inside your building for uses beyond cooling (i.e. non-potable domestic uses such as toilet flushing), your building is considered dual-plumbed. The plumbing system design requirements for dual-plumbed buildings are outlined in Chapter 16 of the International Association of Plumbing & Mechanical Officials (IAPMO) Uniform Plumbing Code. This Chapter has not been officially adopted in California, although its provisions are followed by recycled water utilities throughout the state. For sites that intend to use recycled water only for industrial or irrigation purposes, it is recommended that dedicated lines be located outside the building (or in an approved, dedicated pipe-chase) in order to avoid the need for project-specific dual-plumbing review; this design concept is illustrated on the next page. Signage Title 22 requires the use of advisory signs to inform workers and the general public of recycled water use, when there is a probability of coming into contact with the water. The figure below illustrates common signage for industrial use. For many industrial applications, the actual signage requirements may be quite minimal since industrial and cooling facilities are typically not accessible to the public. The Site Plan included in the Engineering Report should illustrate the location of proposed signage. The Engineering Report should provide a brief description of the rationale for location of signage. 16
18 Locating Recycled Water Lines Outside of Building Minimizes Cross-Connection Testing Day Tank Cooling Tower Cooling Tower Day Tank Fill Line Inside Pipe Chase Fill Line Inside Building Walls This design does not require shut-down testing because pipeline can be observed for its full length This design requires shutdown testing because of potential to cross-connect potable and recycled water pipes behind closed walls 17
19 Cross-Connection Control Title 17 requires that the public water system be protected at all times from cross-connection. Typical enforcement of Title 17 includes: Requiring a backflow prevention device on potable water connections to sites where recycled water is in use. Typically this includes a reduced pressure backflow prevention device (RP); Requiring cross-connection prevention between the recycled water supply line and the cooling water system. Typically this is achieved by an air gap between the recycled water supply lines; any back-up potable supply lines and the basin of the cooling tower (see illustration below). Requiring a cross-connection control test at system startup. Requiring annual visual inspection and subsequent cross-connection control testing if the situation warrants. The Engineering Report should illustrate the location and type of all backflow prevention devices. Air Gaps Between the Water Supply Lines and the Day-Tank are an Effective Cross- Connection Control Strategy This gap between the pipe and the water surface protects the water system Day Tank Cooling Tower Recycled Water Fill Line Potable Water Backup Line 18
20 At system start-up all recycled water systems must be subject to a cross-connection control test performed by an American Water Works Association (AWWA) certified cross-connection control specialist, to assure that there are no connections between the potable and non-potable water systems. Subsequent cross-connection control tests may be required if the user installs new equipment or significantly modifies its recycled water use patterns. A visual inspection through cross-connection review of the recycled water system should be conducted by the Site Supervisor annually and the results should be included in the annual self-monitoring report. All on-site backflow preventers should be tested annually by an AWWA certified backflow tester. The results of these tests should be included in the annual self-monitoring report. Dual-plumbed buildings (those that cannot provide a dedicated pipe chase or supply line), must have a cross connection control test performed every four years to verify that there are no cross-connections between the potable and non-potable water systems. The test must be performed by an AWWA certified cross-connection control specialist and the report must be filed with the appropriate agencies. Drift Control Title 22 allows the use of tertiary treated recycled water in cooling towers but the regulations seek to limit the contact that employees or members of the public have with mist generated from the system. All new or retrofitted cooling towers must include a high efficiency drift eliminator that serves to collect and condense fine mist. The Engineering Report shall include a description (manufacturer s cut-sheet and specifications) for the drift eliminator. The sketches provided in Section 1 Cooling System Basics illustrate the use of drift eliminators. BacterioloGIcal Control and Biocides Title 22 requires that when recycled water is used in a cooling tower, the system must be designed so that the cooling system recirculating water is treated with chlorine or another biocide to minimize the growth of Legionella and other micro-organisms. CPDH currently does not permit electromagnetic water treatment devices (such as Clearwater s Dolphin System) to be used in lieu of biocides. CDPH has permitted specific installations of electromagnetic water treatment devices, without mandatory biocide treatment, if the system design allows for emergency biocide dosing and the biocides are stored on site. The Engineering Report shall include a clear description of the proposed bacteriological control system including, where appropriate, schematic flow diagrams. Back-Up Water supplies When recycled water is used for cooling system it is necessary to have a back-up potable water supply to the site. The potable water supply is used during the required cross connection tests and can also provide an important element of reliability for the industrial customer. Many industrial users employ a day-tank on both their potable and recycled water supplies to further enhance overall system reliability. The Engineering Report shall include a clear description of the proposed back-up water supply and the Site Plan should illustrate the major features of the system. 19
21 20
22 5Resources San Diego County Water Authority 4677 Overland Avenue San Diego, CA (858) (858) Recycled water Information line Contact information Resources Acknowledgments The Water Authority would like to extend its thanks to Eric Rosenblum at South Bay Water Recycling for providing important information for this guide. 21
23 JULY 2009
2014 Service Technician Training Program Closed Loop Systems
1/20/14 2014 Service Technician Training Program Closed Loop Systems Daniel S. Krack, CWT 2 Closed Loop Cooling and Heating The Closed Loop Cooling Advantages High Efficiency Chillers, Heat Exchangers,
THE USE OF OZONE IN COOLING TOWERS
THE USE OF OZONE IN COOLING TOWERS Paul D. McNicholas Ozonia Ltd Duebendorf, Switzerland Abstract Ozone has been successfully applied to industrial cooling water systems with the resultant improvement
Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources
Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources Matthew L. Haikalis Veolia Water Solutions & Technologies April 24, 2013 Operational Priorities
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
Best Practice in Boiler Water Treatment
Best Practice in Boiler Water Treatment Boiler Water Treatment Part 2 Internal Treatment Objectives of Internal Water Treatment 1 To control the level of total dissolved solids (TDS) within the boiler
COOLING WATER MANAGEMENT
COOLING WATER MANAGEMENT Intent To minimize the carbon-footprint, water usage and environmental impact of HVAC cooling systems and process cooling systems, generally by optimizing the control of water
Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower
Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower Device Evaluated "The Dolphin HYTRONIC Series 1000" pulsed power water treatment device (Dolphin) manufactured by Clearwater
Industrial Water Reuse and Wastewater Minimization
Technical Paper Industrial Water Reuse and Wastewater Minimization Author: James P. McIntyre, P.E. Abstract Many industrial users of fresh water are under increasing pressure to reuse water within their
Cooling Towers: Understanding Key Components of Cooling Towers and How to Improve Water Efficiency
FEDERAL ENERGY MANAGEMENT PROGRAM Cooling Towers: Understanding Key Components of Cooling Towers and How to Improve Water Efficiency Source: Paul Johnston-Knight Introduction Federal laws and regulations
Removing Heavy Metals from Wastewater
Removing Heavy Metals from Wastewater Engineering Research Center Report David M. Ayres Allen P. Davis Paul M. Gietka August 1994 1 2 Removing Heavy Metals From Wastewater Introduction This manual provides
EVAPCO ENGINEERING. Commercial HVAC. District Energy. Industrial Process. Industrial Refrigeration. Power
Since its founding in 1976, EVAPCO, Incorporated has become an industry leader in the engineering and manufacturing of quality heat transfer products around the world. EVAPCO s mission is to provide first
The National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio 43229 614.888.8320
TheNationalBoardofBoilerandPressureVesselInspectors 1055CrupperAvenue Columbus,Ohio43229 614.888.8320 NB-410, Revision 3 Sept, 2015 1 1.0 GENERAL The purpose of this document is to provide basic guidelines
Cooling Water Management. Basic Principles and Technology
Cooling Water Management Basic Principles and Technology By: Timothy Keister, CWT Fellow, American Institute of Chemists Certified Water Technologist, Certificate #90 ProChemTech International, Inc. Apache
SYNERGISTIC APPLICATION OF ADVANCED PRIMARY AND SECONDARY WASTEWATER TREATMENT SYSTEMS
SYNERGISTIC APPLICATION OF ADVANCED PRIMARY AND SECONDARY WASTEWATER TREATMENT SYSTEMS Published in Water and Waste Digest membrane issue, November 2008 Miroslav Colic; Chief Scientist, Clean Water Technology
Silica Over-Saturation, Precipitation, Prevention and Remediation In Hot Water Systems Edited By Dave Peairs, Cal Water, Technical Director
Silica Over-Saturation, Precipitation, Prevention and Remediation In Hot Water Systems Edited By Dave Peairs, Cal Water, Technical Director Background Silica scaling becomes a problem when any hot water
Testing Water for Gardening and Lawn Irrigation
wellcare information for you about Testing Water for Gardening and Lawn Irrigation Within a household, water may serve many functions beyond everyday household uses such as drinking, cooking, laundry,
Total Suspended Solids Total Dissolved Solids Hardness
Total Suspended Solids (TSS) are solids in water that can be trapped by a filter. TSS can include a wide variety of material, such as silt, decaying plant and animal matter, industrial wastes, and sewage.
GUIDELINES FOR LEACHATE CONTROL
GUIDELINES FOR LEACHATE CONTROL The term leachate refers to liquids that migrate from the waste carrying dissolved or suspended contaminants. Leachate results from precipitation entering the landfill and
Chemistry at Work. How Chemistry is used in the Water Service
Chemistry at Work How Chemistry is used in the Water Service WATER TREATMENT Everyday, more than 100 water treatment works in Northern Ireland put approximately 680 million litres of water into the supply
Wastewater Reuse. Typical treated wastewater is:
Wastewater Reuse Most metal finishing industries have in-house wastewater treatment to economically dispose of the acids, alkali, oils, and dissolved metals in the rinse water and occasional tank solution
Ion Exchange Softening
Ion Exchange Softening Ion-exchange is used extensively in small water systems and individual homes. Ion-exchange resin, (zeolite) exchanges one ion from the water being treated for another ion that is
Cooling Water Treatment
NALCO S PHILOSOPHY: BUILDING VALUE We create value for our customers by developing and implementing innovative, differentiated solutions that are financially, technically, and environmentally sustainable.
Corrosivity of Water Supplies
WD-DWGB-3-4 2009 Corrosivity of Water Supplies What is meant by Corrosivity? Corrosive water can be defined as a condition of water quality which will dissolve metals from metallic plumbing at an excessive
WASTEWATER TREATMENT OBJECTIVES
WASTEWATER TREATMENT OBJECTIVES The student will do the following: 1. Define wastewater and list components of wastewater. 2. Describe the function of a wastewater treatment plant. 3. Create a wastewater
Technical Presentation IMPORTANT TOPICS
BOILER WATER TREATMENT FOR KILN DRY OPERATIONS Technical Presentation IMPORTANT TOPICS PRETREATMENT TEMPERATURE VS OXYGEN FEED WATER / DA BOILER WATER CONDENSATE 1 Boiler Water Pretreatment Purpose - Statistically
Sulfites for Oxygen Control
If you would like a more detailed version of this report, please request SOS from [email protected] along with your e-mail address. A. Introduction Sulfites for Oxygen Control Robert R. Cavano
Guidelines for Selecting and Maintaining Glycol Based Heat Transfer Fluids
Guidelines for Selecting and Maintaining Based Heat Transfer Fluids David Berry Engineering Manager, Chem-Aqua Canada Allan Browning Technical Marketing Manager, Chem-Aqua, Inc. Based Heat Transfer Fluids
Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities
Water Efficiency Water Management Options Boilers for Commercial, Industrial and Institutional Facilities Boiler Water Impurities All boiler make-up water contains impurities. As clean steam is released
8 Chemicals from water treatment and distribution
8 Chemicals from water treatment and distribution 8.1 Introduction Chemicals from water treatment and distribution reach drinking-water by the most direct route. They fall into three broad categories:
AIR-CONDITIONERS CONDENSATE RECOVERY SYSTEM FOR BUILDINGS
AIR-CONDITIONERS CONDENSATE RECOVERY SYSTEM FOR BUILDINGS Kelum Siriwardhena Mercury International Electro-Mechanical LLC - UAE Telephone: 00971507518423; Fax: 0097126270087 E-mail: [email protected];
1. Inspection and monitoring... 3
1 Index 1. Inspection and monitoring... 3 1.1 Handling of new elements... 3 1.1.1 Storage of original packaged RO elements... 3 1.1.2 Packing... 3 1.2 Initial start- up checks of a plant... 3 1.2.1 Preparation
NON-HAZARDOUS CHEMICAL TREATMENTS FOR HEATING AND COOLING SYSTEMS
NON-HAZARDOUS CHEMICAL TREATMENTS FOR HEATING AND COOLING SYSTEMS Vincent F. Hock and Susan A. Drozdz U.S. Army Construction Engineering Research Laboratory What Are Green Chemical Treatments? Reduce corrosion,
Subject: Technical Letter 22 April 1977 Removal of Water Supply Contaminants -- Copper and Zinc
STATE OF ILLINOIS Department of Registration and Education JOAN G. ANDERSON DIRECTOR. SPRINGFIELD BOARD OF NATURAL RESOURCES AND CONSERVATION JOAN G. ANDERSON CHAIRMAN BIOLOGY THOMAS PARK CHEMISTRY H.
A SHORT INTRODUCTION TO CORROSION AND ITS CONTROL
A SHORT INTRODUCTION TO CORROSION AND ITS CONTROL CORROSION OF METALS AND ITS PREVENTION WHAT IS CORROSION Corrosion is the deterioration of materials by chemical interaction with their environment. The
Iron and manganese are two similar elements
L-5451 2-04 Drinking Water Problems: Iron and Manganese Mark L. McFarland, Associate Professor and Extension Soil Fertility Specialist Monty C. Dozier, Assistant Professor and Extension Water Resources
Treatment options for hydrogen sulfide. Testing for hydrogen sulfide
Sometimes hot water will have a sour smell, similar to that of an old damp rag. This smell often develops when the thermostat has been lowered to save energy or reduce the potential for scalding. Odor-causing
BRAZED PLATE INSTALLATION MANUAL
www.brazedplate.com BRAZED PLATE INSTALLATION MANUAL S.E.C. Heat Exchangers P.E.I. CANADA C0A 1A0 tel; 902-659-2424 fax; 902-659-2800 Table of Contents Description...2 Mounting position...3 Piping connections......3
WATER CHEMISTRY AND POOL WATER BALANCE
C R6 H A PT E WATER CHEMISTRY AND POOL WATER BALANCE LEARNING OBJECTIVES After completely studying this chapter, you should be able to: Understand and list the parameters upon which water balance is based.
Cooling Tower Efficiency Guide Property Managers
Cooling Tower Efficiency Guide Property Managers IMPROVING COOLING TOWER OPERATIONS How to Use This Guide This guide is structured in two Parts. Part I outlines the steps necessary to improve cooling tower
Iron and Manganese BACTERIA AND IRON AND MANGANESE
Iron and Manganese Iron and manganese control is the most common type of municipal water treatment in Minnesota. Iron and manganese occur naturally in groundwater. Neither element causes adverse heath
Food Protection Services
Food Protection Services dairy processing plants Guidelines For the Cleaning of Dairy Plant Processing Equipment TABLE OF CONTENTS PART I...1 INTRODUCTION... 2 PART II GENERAL PRINCIPLES OF CLEANING AND
Cooling Water Problems and Solutions
Cooling Water Problems and Solutions Course No: M05-009 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
RO / NF Cleaning Guidelines
Nanostone Water, Inc. Carlsbad Office 2463 Impala Dr. Carlsbad, CA 92010 USA T: +1 (844) 765-7377 www.nanostone.com RO / NF Cleaning Guidelines 2015 Nanostone Water, Inc. www.nanostone.com RO/NF Cleaning
A Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE
The following article was published in ASHRAE Journal, December 2002. Copyright 2002 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:
SECTION 232500 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following HVAC water-treatment systems: 1. Open Loop Chemical Treatment Systems. 2. Closed Loop Chemical Treatment Systems. 3.
Best Management Practice and Guidance Manual for Cooling Towers
Best Management Practice and Guidance Manual for Cooling Towers Prepared by JEA for the control of pollutants discharged to the sanitary collection system. August 2005 Table of Contents Introduction...3
C. Provide temporary water treatment for chilled, hot and condenser water until facility has final connections.
SECTION 23 25 00 - HVAC WATER TREATMENT PART 1 -GENERAL 1.1 SUMMARY A. This Section includes the following: 1. HVAC water-treatment systems. 2. Chemical treatment test equipment. 3. HVAC water-treatment
TREATMENT OF PHOSPHATE FERTILIZER PLANT WASTE WATER IN FLORIDA FOR DISCHARGE AND RE USE PURPOSES
TREATMENT OF PHOSPHATE FERTILIZER PLANT WASTE WATER IN FLORIDA FOR DISCHARGE AND RE USE PURPOSES JOHN F. BOSSLER, SIEMENS Water Technologies Corp., Hoffman Estates, IL RONALD TRAVIS, SIEMENS Water Technologies
PROPAK AquaBio Complete Water Restoration Systems
PROPAK AquaBio Complete Water Restoration Systems Conserving natural resources and lowering operating expenses is no longer an option, it is a necessity. Water, sewer and discharge fees are continuing
WISCONSIN WASTEWATER OPERATORS ASSOCIATION
Integrity. People. Knowledge. WISCONSIN WASTEWATER OPERATORS ASSOCIATION ANNUAL CONFERENCE GREEN BAY Resources. MEETING LOW LEVEL PHOSPHORUS LIMITS BY CHEMICAL ADDITION WHAT IS PHOSPHORUS Atomic # 15 Electron
BASIC WATER TREATMENT OF STEAM BOILERS
BASIC WATER TREATMENT OF STEAM BOILERS Steve Kenny and Dave Pope Chemco Water Technology Vancouver, WA This is a brief discussion on low-pressure steam boiler chemistry. It provides dry kiln boiler operators
Cooling Water. Watertreatment and chemical conditioning of open and closed cooling systems. Dr. K. Nachstedt, Weidner Wassertechnik, Herten
Cooling Water Watertreatment and chemical conditioning of open and closed cooling systems Dr. K. Nachstedt, Weidner Wassertechnik, Herten Recirculation of process water volume of utilization is increasing
INDUSTRIAL WATER TREATMENT OPERATION AND MAINTENANCE
UNIFIED FACILITIES CRITERIA (UFC) INDUSTRIAL WATER TREATMENT OPERATION AND MAINTENANCE APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UNIFIED FACILITIES CRITERIA (UFC) INDUSTRIAL WATER TREATMENT OPERATION
Development of Advanced Wastewater Treatment and Reclamation System
14 Development of Advanced Wastewater Treatment and Reclamation System TAKESHI TERAZAKI *1 HOZUMI OTOZAI *2 KOSUKE SHIGIISHI *2 HIDEO SUZUKI *3 HIROSHI NAKASHOJI *4 HIROYUKI KAWAMOTO *5 Recycling and the
WHAT IS IN FERTILIZER OTHER THAN NUTRIENTS?
WHAT IS IN FERTILIZER OTHER THAN NUTRIENTS? Raymond C. Ward Ward Laboratories Inc. Kearney, NE Commercial fertilizer is a source of plant nutrients that can be applied to soil to nourish crops when the
HVAC Energy Conservation through Cooling Water Treatment
HVAC Energy Conservation through Cooling Water Treatment Course No: M05-013 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800
The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation
The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation Introduction The importance of keeping cooling tower water in proper chemical
CONTROL OF LEGIONELLA AUDIT PROFORMA
CONTROL OF LEGIONELLA AUDIT PROFORMA This document is an audit sheet designed to assist persons in control of cooling systems which incorporate cooling towers or evaporative condensers, to assess their
Water System Disinfection
Water System Disinfection Document Number Revision 1 Approved By Ric Morris All 6/2/04 Active Divisions/Departments FEMC Raytheon Polar Services Company HARD COPY NOT CONTROLLED-CONTROLLED COPY AVAILABLE
Characterizing Beauty Salon Wastewater for the Purpose of Regulating Onsite Disposal Systems
Characterizing Beauty Salon Wastewater for the Purpose of Regulating Onsite Disposal Systems Fred Bowers 1,2, Ph.D. New Jersey Department of Environmental Protection Division of Water Quality August 14,
Cooling Tower Sidestream Filtration A Green, Proven Cost Reduction Technology
Cooling Tower Sidestream Filtration A Green, Proven Cost Reduction Technology TAB0411 Typical crossflow cooling tower installation Due to the large air-water interface needed to obtain good evaporative
IMPACT OF CHEMICALS ADDITION IN WATER/WASTEWATER TREATMENT ON TDS CONCENTRATION AND SLUDGE GENERATION Jurek Patoczka, PhD, PE Hatch Mott MacDonald 27 Bleeker Str., Millburn, NJ 07041 (973) 912 2541 [email protected]
Troubleshooting tips Key. What colour is the water? Reddish-orange. Yellowish-brown or tea-coloured
Appendix 9: Troubleshooting tips These troubleshooting tips provide basic guidance on how to rectify some common water quality problems. Conduct a risk assessment and seek further information before making
I N C O R P O R A T E D
BIOSOLUTIONS I N C O R P O R A T E D WATER SOFTENERS & WASTEWATER FOR MORE INFORMATION CALL (818) 991-9997 http://www.biosolutions.org Water Softeners and Wastewater Treatment Systems Across North America,
PREPARING INDUSTRIAL ENGINEERING REPORTS
PREPARING INDUSTRIAL ENGINEERING REPORTS EARLE HARTLING, LOS ANGELES COUNTY SANITATION DISTRICT JOHN ROBINSON, JOHN ROBINSON CONSULTING, INC WateReuse LA Chapter December 2, 2014 Presentation Overview
Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX
Cooling Systems Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX Cooling Water Systems Water is used for cooling because of its capacity to remove and store heat and availability. Cooling water is used in
Ozone in Cooling Towers : Hygiene for us
Ozone in Cooling Towers : Hygiene for us Dr. Matthias Hoffmann BWT Wassertechnik GmbH, Industriestrasse 7, D-69198 Schriesheim, Germany Keywords: Ozone, Cooling Tower, Legionella, Hygiene, Air conditioning,
Storage-stable Aqueous Solutions of Chlorine Dioxide
White Paper Storage-stable Aqueous Solutions of Chlorine Dioxide Tom McWhorter November 14, 2014 Abstract Chlorine dioxide is a powerful, selective biocide. Aqueous solutions of chlorine dioxide have many
SECTION 15041 DISINFECTION OF PIPE AND WATER STORAGE FACILITIES
SECTION 15041 DISINFECTION OF PIPE AND WATER STORAGE FACILITIES PART 1 GENERAL 1.01 DESCRIPTION This section describes requirements for disinfection by chlorination of potable water mains, services, pipe
Biocorrosion Risk Assessment
Biocorrosion Risk Assessment Andrew M.Pritchard European Summer School on Biologically Influenced Corrosion, University of Portsmouth 7-13 July 2002 Contents T Management and assessment of risks T A definition
Environmental Technology March/April 1998
Treating Metal Finishing Wastewater Sultan I. Amer, Ph.D. AQUACHEM INC. Environmental Technology March/April 1998 Wastewater from metal finishing industries contains high concentrations of contaminants
Outdoor Storage of Raw Materials SC-33
Objectives Cover Contain Educate Reduce/Minimize Description Raw materials, by-products, finished products, containers, and material storage areas exposed to rain and/or runoff can pollute stormwater.
THE PHOSPHATE METHOD FOR PRODUCING QUALITY DRINKING WATER!
THE PHOSPHATE METHOD FOR PRODUCING QUALITY DRINKING WATER! Answers to Frequently Asked Questions Phosphates have a long history of successful application in drinking water treatment, providing both primary
ALS TRIBOLOGY Engine Coolant Reference Guide
ALS TRIBOLOGY Engine Coolant Reference Guide Engine coolants are a mixture of, inhibitors, and water. Each formula is designed for specific protection and engine requirements. Mixing different coolants
Facilities Maintenance Standards rev 9-1-2015
Facilities Maintenance Standards rev 9-1-2015 Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will
Water Quality For Poultry
Water Quality For Poultry Amy E. Halls, M.Sc. Monogastric Nutritionist Shur-Gain, Nutreco Canada Inc. January 2008 Water Quality For Poultry Amy E. Halls, M.Sc. Monogastric Nutritionist Shur-Gain, Nutreco
Removing Thallium from Industrial FGD Scrubber Water with Sorbster Adsorbent Media
Case History MAR Systems Inc. Removing Thallium from Industrial FGD Scrubber Water with Sorbster Adsorbent Media Trace thallium levels in process and wastewater streams pose a human toxicity threat. Tidwell
More inside :: Tackle even the toughest water treatment piping challenges with
More inside :: Tackle even the toughest water treatment piping challenges with Corzan Industrial Systems Corrosion to pipes, valves and fittings caused by chemicals and microbes can greatly impact the
TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Anode Rods, Cathodic Protection and the Porcelain (glass) Lining
Corrosion can be defined as the destructive attack of a metal by an electrochemical reaction with its environment. Steel exposed to moisture and oxygen will rust and corrode. Corrosion is defined as the
Question Bank Electrolysis
Question Bank Electrolysis 1. (a) What do you understand by the terms (i) electrolytes (ii) non-electrolytes? (b) Arrange electrolytes and non-electrolytes from the following substances (i) sugar solution
Trichloramine and Asthma in Swimming pools & spas Problem solved
1 Trichloramine and Asthma in Swimming pools & spas By Dr.Howard T Dryden October 2006 In recent years there have been many reports in the press regarding trichloramine and its potential implications as
Troubleshooting Your RO
Troubleshooting Your RO Summary: There can be many reasons why a RO system suffers a loss in performance, and is unable to produce the proper quantity and/or quality of permeate water. Similar to a doctor
Crevice Corrosion on Stainless Steel Propeller Shafts
Crevice Corrosion on Stainless Steel Propeller Shafts A Quick Summary: What is it? How to Prevent it. How to Repair it. Stainless steel propeller shafts and running gear are subject to pitting & crevice
Boiler Blowdown. Boiler Blowdown Benefits. Best Operating Practices for Boiler Blowdown
Boiler Blowdown Even with the best pretreatment programs, boiler feedwater often contains some degree of impurities, such as suspended and dissolved solids. The impurities can remain and accumulate inside
ROSS Technology Removal of Oil, Solids and Scale Formers
ROSS Technology Removal of Oil, Solids and Scale Formers Frac Flowback and Produced Treatment for Reuse WATER TECHNOLOGIES Treatment for Reuse and Enhanced Oil Recovery ROSS Technology is a an effective
Amiad s AMF² pre-treatment technology ensures efficient and reliable nanofiltration of Scottish Highland loch water
technical article Document Ref: 0411001-NFPT-text-RevG Status: Re-issued to Elsevier Science Company: Amiad Filtration Systems Limited Issue Date: 10 February 2006 Copy Deadline: 10 February 2006 Publication:
Reverse Osmosis Membranes for Wastewater Reclamation By Craig R. Bartels, PhD Hydranautics, 401 Jones Road, Oceanside California, USA 92054
Reverse Osmosis Membranes for Wastewater Reclamation By Craig R. Bartels, PhD Hydranautics, 401 Jones Road, Oceanside California, USA 92054 Abstract Wastewater reclamation has become a viable alternative
INTAC PARTS & SERVICES (001308835-H)
DESCALING AND RUST REMOVAL SERVICES FOR TWIN SCREW EXTRUDER BARRELS Scale or lime-scale is a hard, rock-like deposit of calcium or magnesium salts that forms in heat exchangers, machinery cooling channels
CATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
LOS ANGELES UNIFIED SCHOOL DISTRICT INDUSTRIAL WASTEWATER MANAGEMENT PROCEDURES
LOS ANGELES UNIFIED SCHOOL DISTRICT INDUSTRIAL WASTEWATER MANAGEMENT PROCEDURES Office of Environmental Health and Safety 333 S. Beaudry Avenue, 20 th Floor Los Angeles, California 90017 (213) 241-3199
Water Recycles poster
Water Recycles poster The "Water ReCycles" poster is designed for students of all ages. It shows the natural water cycle and humans influence on water resources. Raincloud illustration The raincloud in
Thermo Siphon Solar Systems
Thermo Siphon Solar Systems Thermo Siphon Solar Systems are a very cost effective way of producing hot water due to their simplicity in design and installation requirements. Usually more common in hotter
WATER TREATMENT IN AUCKLAND
WATER TREATMENT IN AUCKLAND Auckland's water (like water throughout New Zealand) is a combination of water from dams and water from underground springs. Depending on the source of the water, it has different
Heat Exchanger Care and Water Quality Guide
Heat Exchanger Care and Water Quality Guide l 015-164-000 C Copyright information Trademark information 2005 MTS Systems Corporation. All rights reserved. MTS is a registered trademarks of MTS Systems
AMEC 6007: Linear Velocity and Acceleration Learning Outcome. CHEM 6012: Oil and Gas Compositions and Sales Specifications Learning Outcome
s/objectives Level F ADMN 6044: Post Job Management It is important to know the proper procedures for closing out a job so that rigging and equipment is maintained for future use and personnel are adequately
Evaluation of Alternatives to Domestic Ion Exchange Water Softeners. Mara Wiest Dr. Peter Fox Dr. Lee Wontae, HDR Tim Thomure, HDR
Evaluation of Alternatives to Domestic Ion Exchange Water Softeners Mara Wiest Dr. Peter Fox Dr. Lee Wontae, HDR Tim Thomure, HDR April 26, 2011 OUTLINE Water Quality and reuse in the Southwest US Ion
CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS
CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS Natural gases either from natural production or storage reservoirs contain water, which condense and form solid gas hydrates to block pipeline flow