Completion of Hitachinaka Thermal Power Station Unit No. 1



Similar documents
Completion of High-efficiency Coal-fired Power Plant

Design and Operating Experience of the Latest 1,000-MW Coal-Fired Boiler

Latest Low-NOx Combustion Technology for Pulverized-coal-fired Boilers

New-generation Integrated Monitoring and Control System

Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant:

Development of Tandem-Compound 1,000-MW Steam Turbine and Generator

Recent Technologies in Nuclear Power Plant Supervisory and Control Systems

Latest Power Plant Control System

Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal

Operating Performance and Latest Technology of DeNOx Plants for Coal-Fired Boilers

R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler

Development Study of Nuclear Power Plants for the 21st Century

HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3

REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS

525-MVA Generator-motor and Thyristor Starter Put into Service at the Tokyo Electric Power Co., Inc. s Kannagawa Hydroelectric Power Station

DeNOx, DeSOx, and CO2 Removal Technology for Power Plant

Boiler Preparation, Start-Up and Shutdown

OROT RABIN POWER STATION UNITS x 350 MW

ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -

Completion of SCR System for Ninghai Power Plant Unit 4 in China

Current state of plant Functioning as a peak and emergency centre. Statistics Accumulated operating hours:

A Review on Power Generation in Thermal Power Plant for Maximum Efficiency

Efficiency on a large scale CFB Steam Boilers

Best Choice BENSON BOILER. Excellent performance features make the Benson boiler the most widely used type of once-through boiler

Originators of the Flexible Water Tube design

SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA. Matthias Fränkle Siemens Power Generation (PG), Germany

High-efficient gas boiler CompactGas

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

LMS The modular management system for condensing boilers. Control Products & Systems OEM. Answers for infrastructure.

Operational Flexibility Enhancements of Combined Cycle Power Plants. Dr. Norbert Henkel, Erich Schmid and Edwin Gobrecht

Routine and Emergency Boiler Operation

ORGANIC SAMPLE PREPARATION


Absorption. LG HVAC Solution.

Steam Generator Boilers Compact Steam Boilers. Rapid Start-Up Safe in Operation

Factory owners must ensure the boiler is:

HC900 for Boiler Control Applications

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

ELECTRODE BOILERS VAPOR POWER INTERNATIONAL

Indirect fired heaters

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

Control of Boiler Operation using PLC SCADA

Power Plants. BENSON Once-Through Heat Recovery Steam Generator. Power Generation

Performance Improvement of Pump-turbine for Large Capacity Pumped Storage Power Plant in USA

A Practical Guide to Free Energy Devices

Online Infrared Flue Gas Analyzer Gasboard 3000

Cooking at the Speed of light!

Supercritical boiler technology for future market conditions

MC (Multi-Circulation) f o r S A G D a n d I n d u s t r i a l A p p l i c a t i o n s

Thermodynamical aspects of the passage to hybrid nuclear power plants

SuperIOr Controller. Digital Dynamics, Inc., 2014 All Rights Reserved. Patent Pending. Rev:

NAWTEC CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED BOILER AND INCINERATION TECHNOLOGY

Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla

Steam Power Plants as Partners for Renewable Energy Systems

Boiler NOx Emissions and Energy Efficiency

Development of Grid-stabilization Power-storage Systems Using Lithium-ion Rechargeable Batteries

JASE-world Waste to Energy Sub WG Masanori Tsukahara Hitachi Zosen Corporation

5. State the function of pulveriser. The pulverisers are the equipments which are used to powdered coal.

Combined Cycle Control Overview

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

Performance Analysis of Thermal Power Station: Case Study of Egbin Power Station, Nigeria

Development of Coal Gasification System for Producing Chemical Synthesis Source Gas

Committed to make a better world

Heavy Fuel Oil supply units. The world s best selling HFO supply unit. The right choice for any conditions

How To Reduce Coal Power Plant Emissions

Siemens Steam Turbine SST-600

Making power plants energy efficient

FLUID CIRCULATION PUMP PRESSURE

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district

Steam turbines for solar thermal power plants. Industrial steam turbines. Answers for energy.

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Commercial Semi-Instantaneous Water Heaters

Motors and Inverters for Environmentally Friendly Industrial Equipment

Natural Gas Conversions of Existing Coal-Fired Boilers

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Thermal Coupling Of Cooling and Heating Systems

Energy Saving Solutions. Bob Montgomery Technical Solutions Specialist Waterloo Manufacturing

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Advantage of Using Water-Emulsified Fuel on Combustion and Emission Characteristics

Hitachi s Involvement in Nuclear Power Plant Construction in Japan

Permissible ambient temperature Operation Storage, transport

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

4 th EU Sout Africa Clean Coal Working Group Meeting

Rainwater Harvesting

Implementation of Emergency Repair Work for Steam Turbine at Himeji No. 2 Power Station, Kansai Electric Power Co., Inc.

Building Energy Systems. - HVAC: Heating, Distribution -

Making power plants energy efficient ABB, integrated power and automation solutions

I. STEAM GENERATION, BOILER TYPES

INTEC Engineering GmbH Heating Solutions for the Marine Industry

RELIABLE AND EFFICIENT STEAM GENERATION SYSTEMS FOR MODERN UTILITY SERVICE

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

SOLARPACES: Development of an integrated solar thermal power plant training simulator

Key Technologies of Mitsubishi LNG Carriers - Present and Future -

Gas Turbine Combustor Technology Contributing to Environmental Conservation

BOILER OPERATORS HANDBOOK

Guidelines for Preparing for a Temporary Steam Plant

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES

PERFORMANCE EVALUATION OF NGCC AND COAL-FIRED STEAM POWER PLANTS WITH INTEGRATED CCS AND ORC SYSTEMS

Transcription:

Completion of Hitachinaka Thermal Power Station Unit No. 1 1,000-MW Power Generating Plant of The Tokyo Electric Power Co., Inc. 104 Completion of Hitachinaka Thermal Power Station Unit No. 1 1,000-MW Power Generating Plant of The Tokyo Electric Power Co., Inc. Nobuyuki Matsumoto Hideaki Iwamoto Takao Kaneda Koichi Shigihara OVERVIEW: In recent years, from the viewpoint of environmental conservation, it has become a top priority to improve the heat efficiency of thermal power plants. Under such circumstances, in December 2003, a 1,000-MW coal-fired power plant with the world s highest efficiency Unit No. 1 of Hitachinaka Thermal Power Station of The Tokyo Electric Power Co., Inc. was put into service. This generator consists of a coal-fired boiler with an extremely high critical pressure and a main steam temperature of 600 C as well as a state-of-the-art steam turbine with 41-inch-long (about 104 cm) final-stage turbine blades. Hitachi, Ltd. was in charge of the design and construction of the facilities for these two main components (i.e. the boiler and turbine) of Unit No. 1. Upon completing the plant design, Hitachi drew upon its collective strengths and latest technologies to develop these components. That is, by introducing the large-capacity, coal-fired boiler which can handle many varieties of coal and meet the optimum steam conditions through increased pressure and temperature and the highefficiency steam turbine, both plant efficiency and reliability have been improved. Furthermore, a newly developed remote-monitoring system installed in the central control room of the plant utilizes expanded-display devices [large-size LCD (liquid crystal display) displays] and wider-scope operation by means of highly functional CRT (cathode ray tube) displays. As a result of this system set-up, plant operation in terms of labor saving and monitorability is improved. In addition, the remote-monitoring system is directly connected to the switchgear for auxiliary electrical equipment; consequently, the amount of cable materials used is reduced and the construction cost is lowered. INTRODUCTION CONSTRUCTION of the boiler of Unit No. 1 of Hitachinaka Thermal Power Station of The Tokyo Electric Power Co., Inc. was started in July, 1999, and the unit went into commercial operation in December 2003. Regarding the main facilities of this power plant, Hitachi, Ltd. took charge of the design and construction of the boiler and turbine generator of Unit No. 1. Taking full advantage of its collective strength in terms of plant engineering and technical skills, Hitachi Fig. 1 View of Completed Hitachinaka Thermal Power Station. Located at Hitachinaka Thermal Power Station, Hitachinaka Port north quay Ibaraki Prefecture, Japan, Unit No. 1 a 1,000-MW powergeneration plant was completed in December, 2003.

Hitachi Review Vol. 53 (2004), No. 3 105 TABLE 1. Comparison of Design Specifications of Two Powergeneration Plants By adopting higher steam pressure and temperature conditions, thermal efficiency of Hitachinaka Unit No. 1 is 4.5% higher than Shinchi Unit No. 1. Item Unit Shinchi Unit No. 1 Hitachinaka Unit No. 1 Rated power MW 1,000 1,000 Basic MPa 24.1 24.5 design Steam conditions (main/reheat) C 538/566 600/600 conditions Fuel Coal Coal Ultra-high critical pressure, variable through flow Boiler Steam pressure MPa 25.0 25.4 Steam temperature C 542/567 604/602 Main Evaporation volume t/h 3,080 2,870 machine Two-axis four-flow discharge spec. Turbine Revolution speed min 1 3,000/1,500 3,000/1,500 Discharge vacuum pressure kpa 97.06 (728 mmhg) 96.26 (722 mmhg) Generator Horizontal-cylinder revolving magnetic field Capacity MVA 634.8/519.9 675.0/488.0 Thermal efficiency % 41.89 43.78 successfully completed construction of these two key facilities of this 1,000-MW power-generation plant and achieved world-leading thermal efficiency and reliability. In the following sections, the main features of the two facilities designed and constructed by Hitachi namely, the boiler and turbine generator and the technologies applied are described. OVERVIEW OF PLANT DESIGN Table 1 compares the specifications of the new Hitachinaka No. 1 Unit and that of an existing unit with the same rated output power (i.e. No. 1 Unit of Shinchi Thermal Power Station (hereafter referred to simply as Shinchi Unit No. 1) developed in collaboration with Soma Kyodo Power Co., Ltd.). As regards the basic design of Unit No. 1 of Hitachinaka Thermal Power Station (hereafter referred to simply as the Hitachinaka Unit No. 1), it is clear that the Hitachinaka Unit No. 1 seeks higher thermal efficiency and optimized economic efficiency through increased steam pressure and temperature conditions. That is, compared to the design thermal efficiency of the Shinchi Unit No. 1, that of Hitachinaka Unit No. 1 (under a main steam pressure of 24.5 MPa and main/ reheat steam temperatures of 600 C) is 4.5% higher. NEW BOILER TECHNOLOGY As for the high-efficiency operation of the new boiler facility, by applying high-temperature, highelevated temperature strength materials adapted to high-temperature, high-pressure steam under so-called maximum-level conditions, high reliability can be sustained. And improving combustion performance by means of utilizing the latest pulverized-coal-firing technology further improves efficiency. Boiler Design As for the boiler furnace specification, since hightemperature steam at 600/600 C is used, a variablepressure-operation Benson boiler with a highreliability spiral water wall is adopted. A schematic cross section of Hitachinaka Unit No. 1 is shown in Fig. 2. As for the boiler design, streamlining the facility led to improvement in operation characteristics and maintainability. Fig. 2 Side Structural View of Boiler of Hitachinaka Thermal Power Station Unit No. 1. The plant design combines the latest high-strength materials in the high metal-temperature range to attain high reliability and high economical efficiency.

Completion of Hitachinaka Thermal Power Station Unit No. 1 1,000-MW Power Generating Plant of The Tokyo Electric Power Co., Inc. 106 The main features of the boiler are listed below: (1) Hitachi s latest pulverized-coal burner (NR3) improves burning efficiency and decreases NOx emission. (2) By aligning all boiler reheater horizontally, controllability of steam temperature in the parallel gas damper is improved, so a gas-recirculation system is not required. (3) Enlarging the heat-absorption in the furnace results in non-uniform temperature distribution in the water wall; therefore, a mixing bottle is located at the outlet of the spiral water wall to mitigate the non-uniform temperature distribution. (4) Large-scale modular design using a sling-type tube support for the horizontal heating surface is used for the first time. As a result, using various module designs shortens construction time and, thus, improves efficiency. High-efficiency Combustion Technology In recent years, to simplify combustion facilities, the capacity of burners has been increased. In the new plant facility, 36 Hitachi-NR3 burner units are installed providing the maximum capacity in Japan. Regarding the Hitachi NR3 burner, in addition to the denitration technology used in Hitachi s standard low-nox pulverized-coal (NR2), a guide sleeve and flame stabilizing ring with a baffle plate are applied. As a result of this, a flow pattern of the secondary and tertiary air is optimized; consequently, a hightemperature reducing flame is enlarged and the NOx emission is reduced. NEW STEAM TURBINE AND SYSTEM TECHNOLOGIES By applying the latest technologies under hightemperature conditions for the main steam and reheat steam, the steam turbine attains high efficiency and high reliability. Furthermore, in the construction phase of the plant facilities, the steam turbine was made more compact. New Steam Turbine Technology Since the steam turbine operates under hightemperature-steam conditions, the main parts must handle temperatures of 600 C. Accordingly, the mainsteam stop valve, regulator valve, and combined reheat valve are made of 9Cr-1Mo steel; the inside casing of the high-pressure turbine is made of Cr-Mo-V-B steel; and the inside casing of the intermediate-pressure turbine is made of 12Cr steel. Moreover, on top of the improved combustion efficiency brought by the increased steam temperature, overall efficiency is improved as a result of the implementation of the latest AVN (advanced vortex nozzle). A photograph of the completed steam turbinegenerator is given in Fig. 4. Characteristics of System Configuration In regards to the configuration of the system for the heat cycle (steam extraction, charging, and condensation), a structure that works well in a 1,000- MW power generator is used. Moreover, from the viewpoint of compactness, various features of the auxiliary equipment have been elaborately designed. The main features of the system configuration are listed as follows: (1) Steam extraction, charging, and condensation Powdered coal plus primary air Guide sleeve 3D flow 2D flow Powdered-coal concentrator Baffle plate 2D: two-dimensional 3D: three-dimensional Fig. 3 Structure of Hitachi-NR3 Burner. By utilizing Hitachi s low-nox NR3 burner, even lower NOx emission, along with better combustibility and flame stability, is attained. Fig. 4 View of Steam Turbine-generator Facility. Completed steam turbine-generator applying the latest technology is shown.

Hitachi Review Vol. 53 (2004), No. 3 107 The feedwater heater consists of a low-pressure, four-step deaerator and a high-pressure, four-step deaerator. The condensate pump and its booster pump are comprised of two units, each with 50% capacity; while the feedwater pump is comprised of two 50%- capacity turbine-driver units and one low pump-head motor-driver unit feedwater pump for plant start-up and shutdown. (2) Simplified deaerator Compared to a conventional deaerating chamber for removing dissolved oxygen from the boiler feedwater which has a flush tank for the boiler water made from two blow molds the new steam-turbine system has a enlarged flush tank made from a single mold. Accordingly, this monohull-type flush tank with a built-in deaeration capability is more compact and takes up less space. (3) Cleaning filter Up till now, the steam condenser has utilized a sixvalve-switching backwash method. The new condenser, however, features a large-size cleaning filter at the input of the water chamber of the condenser. As well as improving the operation of the steam-condenser cooling system, introduction of this filter makes setting up the circulating water system more efficient. REMOTE PLANT-MONITORING CONTROL SYSTEM The facilities of the above-described 1,000-MW large-capacity coal-fired power plant are monitored by a large-scale remote-control system consisting of 700 auxiliary units for coarse control and monitoring points for collecting data (2,200 analog and 20,000 digital). This large-scale system coverage is provided by the Hitachi Integrated Automatic Control System (HIACS). The HIACS is composed of distributed computer (RS-90/400) with automization and control functions, FA (factory automation) PCs with operation monitoring functions, and a high-speed, large-capacity controller series with control and safety functions. All these devices are connected via high-speed network called µ -100 to form an all digital system. The characteristic features of this large-scale remote-control system, HIACS, are outlined in the following sections. Human-machine Interface (1) As well as integrating and sharing information, the HMI (human-machine interface) achieves excellent operability and controllability by utilizing a fourscreen multi-window system provided by 110-type expanded-display devices [large-size LCDs (liquid crystal displays)]. A view of the main operator s control panel of the central control room is shown in Fig. 5. (2) CRT operation is achieved by the distributed FA PCs and expanded-display devices by PC mouse operation. As well as covering the conventional range of control devices, it also extends to auxiliary electrical devices, so the main operator s control panel of the Metal-cable system Direct-remotecommunication system Control device HIACS Controller (automization logic) PCM (auxiliary protection logic) Metal cable Input/output interface device Metal cable Switchgear Control device Communication cable HIACS Controller (automization logic) PCM (auxiliary protection logic) Switchgear Direct-remotecommunication system Fig. 5 View of Main Operator Control Panel and Expanded- Display Devices in Central Control Room. An HMI centered on 110-type expanded-display devices is adopted, and the integration of data enables the central control room to be streamlined. Plant auxiliaries PCM: programmable control module Plant auxiliaries Fig. 6 Interface between Control Devices and Switchgears. By utilizing remote-communication methods, the control system can be significantly streamlined.

Completion of Hitachinaka Thermal Power Station Unit No. 1 1,000-MW Power Generating Plant of The Tokyo Electric Power Co., Inc. 108 central control room can be made more compact. Interface between Control Devices and Switchgears The conventional interface between control devices and switchgears utilizes metal cables; however, the new plant-control system uses remote communication between these devices as shown schematically in Fig. 6. Each switchgear is fitted with a communication function so that it can communicate directly with a corresponding control device. As a result, the operating control panel is made more compact and the cableengineering work is made significantly more efficient. Improving Reliability of Boiler and Turbinegenerator Safety Systems Regarding the boiler and turbine safety panel, to assure higher reliability than that attainable up till now, a triple system consisting of a PCM equipped with a ROM (read-only memory) and CPU (central processing unit) is connected to a protection circuit. And a dual system is set up to cover abnormal-state detection and alarm monitoring by the detection elements and calculation circuitry. In conjunction with a digital protective relay board for protecting the generator machinery and main transformer, the abovedescribed configuration has enabled the protection circuit to be completely digitized. CONCLUSIONS This paper described the main features of the boiler and turbine-generator of Unit No. 1 of Hitachinaka Thermal Power Station of The Tokyo Electric Power Co., Inc., and outlined the latest technologies applied in these facilities. Applying these new technologies enables stable operation of these coal-burning-powerplant facilities at high efficiency and large capacity. In the future, Hitachi Group intends to apply these technical achievements in other thermal power plants. In particular, focusing on development of technologies for even higher efficiency and more plant streamlining, we are striving toward construction of sustainable thermal power plants. ACKNOWLEDGMENTS The authors would like to express their sincere thanks to all those concerned at The Tokyo Electric Power Co., Inc., for their considerable assistance from planning, to construction and testing, and up to final commissioning in developing the Unit No. 1 of Hitachinaka Thermal Power Station. REFERENCES (1) R. Okura et al., Completion of a High-efficiency Coal-fired Power Plant; Hitachi Hyoron, 85, pp. 163-166 (Feb. 2003) in Japanese. (2) K. Umezawa et al., Kin No. 1 1220 MW Thermal Power Station, Hitachi Hyoron, 85, pp. 167-170 (Feb. 2003) in Japanese. ABOUT THE AUTHORS Nobuyuki Matsumoto Joined Hitachi, Ltd. in 1979, and now works at the Electrical and I&C System Engineering Section, the Thermal Power Plant Engineering Department, Hitachi Works, the Power Systems. He is currently engaged in basic planning of instrumentation and control of thermal power plants. Mr. Matsumoto can be reached by e-mail at nobuyuki_matsumoto@pis.hitachi.co.jp. Hideaki Iwamoto Joined Babcock-Hitachi K.K. in 1994, and now works at the Boiler Design Section of the Thermal Engineering Department of Kure Office. He is currently engaged in basic planning and development of commercial boilers. Mr. Iwamoto can be reached by e-mail at iwamoto-h@kure.bhk.co.jp. Takao Kaneda Joined Hitachi, Ltd. in 1971, and now works at the Power Generation Control Systems Planning Department, the Information Control Systems Division of the Information & Telecommunication Systems. He is currently engaged in drawing up plans for thermal-power control systems. Mr. Kaneda can be reached by e-mail at takao_kaneda@pis.hitachi.co.jp. Koichi Shigihara Joined Hitachi Engineering Co., Ltd. in 1992, and now works at the No. 1 Engineering Division of the Electrical Power Systems Headquarters. He is currently engaged in engineering work on thermal power systems. Mr. Shigihara can be reached by e-mail at kouichi_shigihara@pis.hitachi.co. jp.