ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE



Similar documents
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

MODEL ESP-V SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Air Conditioning Sign-Off Sheet

, User s Manual

Table Z. Troubleshooting Chart for Air Conditioners. Cause

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

E2 Series Electric Furnaces

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

LOBOY 16 AIR CONDITIONERS

Troubleshooting Your Refrigerator

Quest 105, Dry155, and 205 Dual

123 street Salt Lake City, Utah 84092

HVAC-02, Air Conditioning Troubleshooting and Repair

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes


Evaluate, Clean, and Tune Guidance

STATEMENT OF WORK FOR MAINTENANCE OF AIR CONDITIONERS

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

Fan Coil EC Motor Control

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Owner s Manual Phoenix 300

ECM. Service Guide.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SWIMMING POOL HEAT PUMP

ON-VEHICLE INSPECTION

T-Series Air Conditioner T62 Model

COMMISSIONING OF HVAC SYSTEMS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

HI-E Dry DRY 195. quest. Read and Save These Instructions. Installation, Operation and Maintenance Instructions. HI-E Dry 195:

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Owner s Manual Phoenix Arctic Max

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS

Oil and Coolant Circulating Heating System. Model - OCSM

Important Safety Information. Operating Instructions The Controls on Your Zoneline Care of Product

Heat Pump Water Heater IOM Manual

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

AFE424 SERVICE PARTS

MDT5N25 & MTD5N40 SERVICE PARTS

T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Hydraulic Trouble Shooting

Panel Mounted Air Conditioners by Dantherm, Inc.

Chapter 7 Hydraulic System Troubleshooting

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

SERVICE Manual AIR CONDITIONER AWH090ZE0K. 1. Precautions. 2. Product Specifications. 3. Installation and Operating Instructions

AIR CONDITIONER INSTALLATION MANUAL

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

READ AND SAVE THESE INSTRUCTIONS. INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC, NEC AND LOCAL ELECTRICAL CODES.

Models: WA182, WA242. Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List Control Panel.

Owner s Manual Phoenix R175 LGR Dehumidifier

ECM SERVICE GUIDE. A Regal Brand Regal-Beloit Corporation

Failure code manual. content

WINDOW ROOM AIR CONDITIONER

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs:

OWNER S GUIDE OPERATION & INSTALLATION

TYPE. MODEL B3200 Roof-Top Air Conditioner used with Mechanical Air Distribution Box INSTALLATION & OPERATING INSTRUCTIONS Air Conditioner

Operating & Maintenance Manual for Islandaire Packaged Terminal Thru-Wall Air Conditioners & Heat Pumps

Lien Rd. Madison, WI Owner s Manual Phoenix R200 LGR Dehumidifier

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

forair optimal air environments ResidentialPresentation

Owner s Manual Phoenix 200 MAX

forair optimal air environments Service Partner Plan

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

How To Install An Evaporator Coil

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

SERVICE MANUAL FOR 6700, 7000, 8000 & 9000 SERIES AIR CONDITIONERS (MECHANICAL CONTROLS ONLY)

AABC Specifications for Testing and Balancing HVAC Systems

INSTALLATION INSTRUCTION

T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

TROUBLESHOOTING PRELIMINARY

Customized Assessment Blueprint

High School Graduation years 2013, 2014, Unit/Standard Number

How to Maintain an Air Conditioner

CB29M Bulletin # February 1996

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING

Central Air Conditioner

SL280UHV SERIES GAS FURNACE WARNING

Owner s Manual Phoenix Solution. LGR Performance Amplifier

User s Information/Installation Instructions

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

PREVENTATIVE MAINTENANCE

Transcription:

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and Canadian Patents: 891,292; 923,935; 923,936)

Systematic troubleshooting is a logical series of steps to follow in analyzing a problem in the Space-Pak central air conditioning system with a minimum amount of lost time or call backs. Although the owner s initial complaint, most of the time, will be NO COOLING, INSUFFICIENT COOLING or NOISE, there are certain visible and audible symptoms which you can use to pinpoint the problem. This troubleshooting guide provides you with step-by-step procedures, written in the proper sequence for each condition, for solving the situation which you may observe. Depending on the situation involved, upon arrival at the service call, we recommend checking these three most obvious items first: 1. Check that thermostat is calling for cooling and fan switch is in the AUTO position. 2. Check that thermostat is set below room temperature. 3. Check for tripped circuit breaker or blown fuse at main fuse box and at condensing unit disconnect box. In addition to the usual assortment of refrigeration system service tools, Space-Pak troubleshooting also requires the use of a volt-amp-ohmmeter and a U-tube manometer. SERVICE CALL CONDITIONS Page ESP-D Unit & Condensing Units Run, But Cooling Insufficient...2 ESP-D Unit & Condensing Unit Will Not Start...3 ESP-D Unit Will Not Start, But Condensing Unit Runs...3 ESP-D Unit Runs, But Condensing Unit Will Not Start...4 ESP-D Unit Will Not Start, But Condensing Unit Cycles...4 ESP-D Unit Cycles, But Condensing Unit Cycles...4 ESP-D Unit Runs, But Condensing Unit Cycles...5 Sweating At ESP-D Unit Supply Outlet...5 Excessive Air Noise At Terminator...5 Excessive Noise At Return Air Grill...6 Excessive Vibration At ESP-D Unit...6 CONDITION: ESP-D & CONDENSING UNITS RUN, BUT COOLING INSUFFICIENT Low Suction Pressure Check blower motor as described on If defective, replace motor. page 6 Check that filter in return air box is Clean air filter. clean. Check system refrigerant charge. Charge to proper subcooling according to manufacturer s instructions. Check for dirty evaporator coil. Clean evaporator coil. High Suction Pressure Check for air bubbles in system Charge to proper subcooling accordrefrigerant. ing to condensing unit manufacturer s instructions. Install sight glass near indoor unit and monitor. Check calculated heat gain to be Take necessary action. sure that equipment is sized properly. Check for obstructions near Remove obstructions. condensing unit which could cause recirculation of air. Low Head Pressure Check system refrigerant charge. Charge to proper subcooling according to condensing unit manufacturer s instructions. Check calculated heat gain to be sure Take necessary action. that equipment is sized properly. 2

ESP-D & CONDENSING UNITS RUN, BUT COOLING INSUFFICIENT (Continued) High Head Pressure Check condenser fan motor accord- If defective, replace fan motor. ing to condensing unit manufacturer s instructions. Check for dirty condensing unit coil. Clean condensing unit coil. Check system refrigerant charge. Charge to proper subcooling according to condensing unit manufacturer s instructions. Check for dirty evaporator coil. Clean evaporator coil. Check for obstructions near Remove obstructions. condensing unit which could cause recirculation of air. Check for restricted liquid lines. Remove restrictions and kinks from lines. Distribution System Air Leaks Check all joints in air distribution Make sure all joints are air tight. system. Verify static pressure as described on page 6 CONDITION: ESP-D UNIT & CONDENSING UNIT WILL NOT START Thermostat Not Level Check level of thermostat If necessary, level thermostat. Defective Thermostat With volt meter, check resistance of If resistance, thermostat is O.K. thermostat contacts. If no resistance, replace thermostat. Loose Low Voltage Wiring Check all wiring connections for Tighten all loose connections. Defective Blower Relay Check relay as described on page 6 If defective, replace relay. Defective Low Voltage Transformer Check transformer as described on If defective, replace transformer. page 6 Inadequate Electrical Service Check electrical service against Replace electrical service with minimum requirements. adequately sized service. CONDITION: ESP-D UNIT WILL NOT START, BUT CONDENSING UNIT RUNS Shorted Or Broken Wiring Check wiring. If necessary, repair or replace wiring. Loose Low or High Voltage Wiring Check all wiring connections for Tighten all loose connections. Defective Blower Motor Check motor as described on page 6 If defective, replace motor. 3

CONDITION: ESP-D UNIT RUNS, BUT CONDENSING UNIT WILL NOT START Defective Thermostat With volt meter, check resistance of If resistance, thermostat is O.K. thermostat contacts. If no resistance, replace thermostat. Loose Low Or High Voltage Wiring Check all wiring connections for Tighten all loose connections. Float Switch (If Used) And Anti-Frost Thermostat fan ON. With volt meter, If no voltage, fan relay is defective. Switch (Switches are wired in series) check for 24v across terminal 1 on Replace it. the fan relay and terminal 7 on low If read 24v, relay is O.K. voltage terminal strip. With volt meter, check for 24v If no voltage, check coil for ice across terminals 1 and 7 on low and drain pan for excessive water. voltage terminal block. If ice check air filter, return air duct & blower motor for air flow. If excessive water check and clean condensate drain lines. If no ice on coil and water level in drain pan is normal, check each switch for continuity. If switch has no continuity, replace it. If 24v, switches are O.K. Shorted Or Broken Wiring Check wiring. If necessary, repair or replace wiring. Condensing Unit Check according to manufacturer s Repair or replace as directed by instructions. manufacturer. CONDITION: ESP-D UNIT WILL NOT START, BUT CONDENSING UNIT CYCLES Incorrect Low Voltage Connections Check low voltage connections Correct low voltage connections. against wiring diagram. Loose Low Voltage Connections Check all wiring connections for Tighten all loose connections. Defective Blower Relay Check relay as described on page 6 If defective, replace relay. Defective Blower Relay Check motor as described on page If defective, replace motor. 6 CONDITION: ESP-D UNIT CYCLES, BUT CONDENSING UNIT RUNS Blower Motor Check motor as described on page 6 If defective, replace motor. Check motor amps and compare to If excessive, the motor may be nameplate ratings. overloaded. Check supply duct for breaks or leaks. 4

CONDITION: ESP-D UNIT RUNS, BUT CONDENSING UNIT CYCLES Anti-Frost Switch & Float Switch Thermostat fan ON. With volt meter, If no voltage, fan relay is defective. (optional). Switches Are Wired in check for 24v across terminal 1 on Replace it. Series. the fan relay and terminal 7 on low If read 24v, relay is O.K. voltage terminal strip. With volt meter, check for 24v across If no voltage, check oil for ice and terminals 1 and 7 on the low voltage drain pan for excessive water. If ice terminal block. check air filter, return air duct & blower motor for air flow. If excessive water check and clean condensate drain lines. If no ice on coil and water level in drain pan is normal, check each switch for continuity. If switch has no continuity, replace it If 24v, switches are O.K. Thermostat in Wrong Location Check that thermostat is in vicinity of If necessary, relocate thermostat. return air box. Loose Low Or High Voltage Wiring Check all wiring connections for Tighten all loose connections. Defective Blower Motor Check motor as described on page 6. If defective, replace motor. Condensing Unit Refer to manufacturer s instructions. Repair or replace per manufacturer s instructions. CONDITION: SWEATING AT ESP-D UNIT SUPPLY OUTLET Air Leak At Supply Air Plenum Check taped joint at receiving collar. Tape joint properly. Flange Insulation at Outlet Not Installed Check for insulation at outlet. Install insulation. CONDITION: EXCESSIVE NOISE AT TERMINATOR High Supply Air Plenum Static Check static pressure as described Check for and add flow restrictors Pressure on page 6 as necessary in supply runs. If necessary, add additional outlets. Sound Attenuating Tube Not Check for installation of sound Where necessary, install sound Installed attenuating tubing. attenuating tubing. Tight Radius In Sound Attenuating Check all tubing for tight radius. Where necessary, correct radius. Tubing Or In Supply Tubing Incorrect Supply Tubing Length Check that all supply tubing runs Where necessary, correct supply are 6 minimum. tubing length. Improperly Balanced System Check that correct size orifices Properly orifice supply tubing runs. have been installed. 5

CONDITION: EXCESSIVE NOISE AT RETURN AIR GRILL Return Air Duct Not Installed Check for minimum 90 bend in Correct bend in return air duct Properly return air duct. to minimum 90. Dirty Return Air Filter Remove and inspect. Clean air filter. CONDITION: EXCESSIVE VIBRATION AT ESP-D UNIT Noisy Blower Motor Assembly Check blower motor assembly. Tighten all fasteners. Check blower motor for bearing Replace motor. noise. Check for loose or damaged blower Tighten or replace blower wheel wheel. as necessary. CHECKING ESP-D BLOWER MOTOR 1. With volt meter, check voltage at terminals L1 and L2 on line voltage terminal block. Voltage should be ±10% of ESP-D unit nameplate rating. 2. Disconnect power to the ESP-D unit at the disconnect switch. 3. Disconnect motor lead at terminal L1. 4. With an ohmmeter, check continuity between the disconnected motor lead and terminal 4 on the fan relay. a. If continuity, precede to Step 5 below. b. If no continuity, feel the motor to see if it is excessively warm which would indicate the internal over- load may be open. When motor has cooled, check again to make sure you did not get a false reading. If no continuity, motor is defective. 5. With an ohmmeter, check each motor lead to ground to be sure motor is not grounded. a. If not grounded, precede to Step 6 below. b. If grounded, motor is defective. 6. Check capacitor, if capacitor is suspect, replace it with a capacitor of similar rating of motor operates normally, make a permanent capacitor replacement. 7. Reconnect all electrical leads, restore electrical services to the ESP-D unit, and place thermostat fan switch in the ON position. 8. With an ampmeter, check that amp draw compares with ESP-D unit rating plate. Amp draw shown on plate is the actual running amps for a cooling-only installation with an external static pressure of 1.5 W.C. CHECKING ESP-D BLOWER RELAY The ESP-D unit is equipped with a time-delay blower relay. Wait one full minute after turning on power for relay to close. 6 1. With a volt meter, check 24v across terminals 5 and 7 on the low voltage terminal block. a. If read 24v, precede to Step 2. b. If no voltage, check low voltage transformer. 2. With a volt meter, check 24v across terminals 5 and 6 on the low voltage terminal block. a. If read 24v, precede to Step 3. b. If no voltage, check thermostat fan circuit. 3. Check for 230v* across terminal 4 on blower relay and terminal L1. a. If reading is 230v, blower relay is O.K. b. If no reading, replace the relay. * 208v on 208 line volt systems. CHECK ESP-D LOW VOLTAGE TRANSFORMER 1. With volt meter, check for 230v across terminals L1 & L2 on the line voltage terminal block. a. If reading 230v, precede to Step 2. b. if no voltage, check the power supply to the unit. 2. With volt meter, check for 24v across terminal 5 and terminal 7 on the low voltage terminal block. a. If read 24v, transformer is O.K. b. If no voltage, replace transformer. CHECK EXTERNAL STATIC PRESSURE You can use a U-tube manometer to check the external static pressure on the duct system. 1. Puncture a 1/4 hole in the plenum duct at least 18 (or after the tee on ESP-4860D systems) from the fan coil unit. 2. Insert one manometer tube into the hole until the end of the tube is flush with the inside wall of the plenum duct.

BN BLK 3. System static pressure should be between 1.0 and 1.5 W.C. a. If greater than 1.5 W.C. add additional supply runs. b. If less than 1.0 W.C. check the return air filter is clean and return air duct is not collapsed or kinked. c. Check supply air plenum for leaks. d. If more supply runs than recommended are used, check that flow restrictors are in place. L1 BLK BLK 5 4 FAN MOTOR SUPPLY VOLTAGE L2 H.VOLTAGE T.BLOCK WHT ORG FR1 208V INPUT WHT FAN CAPACITOR 208/230/60/1 RD EQUIP. GRD. TRANSFORMER 208/230/24v GRD. LEAD TO MOTOR BASE 24V L. VOLTAGE YEL OUTPUT BLU T. BLOCK R G 7 6 5 YEL BLK BLU FR BRN OUTDOOR UNIT Y 4 3 2 1 YEL 3 FR2 CONTROL BOX 1 BRN AFS FS WIRING LEGEND FIELD NEC CL-1 FIELD NEC CL-2 FACTORY NEC. CL-1 FACTORY NEC. CL FR FS AFS FAN RELAY FLOAT SWITCH (OPTIONAL) ANTI-FROST SWITCH G R Y COOL T'STAT TERM. NOTES: 1. FAN MOTOR FURNISHED WITH INHERENT THERMAL PROTECTION 2. TO BE WIRED IN ACCORDANCE WITH NATIONAL ELECTRIC CODES (NEC) AND LOCAL CODES. 3. USE COPPER CONDUCTORS ONLY. 4. TRANSFORMER IS WIRED FOR 230V SUPPLY. IF 208V IS USED CHANGE TRANSFORMER PRIMARY WIRING. ESP-D WIRING SCHEMATIC 7

260 NORTH ELM ST. WESTFIELD, MA 01085 (800) 465-8558 FAX (413) 564-5815 5211 CREEKBANK RD. MISSISSAUGA, ONTARIO L4W 1R3 CANADA (905) 625-2991 FAX (905) 625-6610