A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps



Similar documents
TROUBLESHOOTING GUIDE

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

MODEL INSTALLATION INSTRUCTIONS

Chapter 7 Hydraulic System Troubleshooting

101 / 105 SERIES INSTALLATION INSTRUCTIONS

Compressor Service & Maintenance Manual

Technical Guide 08/15/14

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Hydraulic Trouble Shooting

SERIES 101 / 105 INSTALLATION INSTRUCTIONS

Oil and Coolant Circulating Heating System. Model - OCSM

Wilo SP Series Submersible Sump Pumps ECS. ECS ECS ECS Installation and operating instructions

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Trouble Shooting. Pump

INSTALLATION & OPERATING INSTRUCTIONS

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

Redi-Flo4. Stainless Steel Submersible Pumps for Environmental Applications GRUNDFOS INSTRUCTIONS. US Installation and operating instructions

Pump Maintenance - Repair

SunMaxx Solar Filling Station Operating Instructions

SPA BUILDERS LX-10 STANDARD TROUBLESHOOTING APPROACH

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

S33 Sump Pump INSTRUCTIONS AND SERVICE MANUAL VERTICAL FLOAT SWITCH S33V1 & S33V1C AUTOMATIC S33P1 & S33PC-1 (CONTROL WITH SERIES PLUG) NOT SHOWN

Hydraulic Troubleshooting PRESENTED BY

, User s Manual

MAINTENANCE INSTRUCTIONS FOR THE CLEAN-FLO CONTINUOUS LAMINAR FLOW INVERSION / OXYGENATION SYSTEM

Hydraulics Trouble Shooting Guide. TS-Guide_R.doc

PC1130 Electric Air Compressor

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

Heat Pump Water Heater IOM Manual

PC1131 Electric Air Compressor

BOWIE PUMPS OPERATION - MAINTENANCE


Packaged Boiler Feed Systems Installation, Operation, and Maintenance

Electrical Resistance Resistance (R)

TROUBLESHOOTING GUIDE

SERVICE SERVICE MANUAL FOR ALDE ELECTRICAL HEATER

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Trouble Shooting BD & TW Compressor Systems 12 and 24 Volt

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

accidents which arise due to nonobservance and the safety information herein.

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:


TROUBLESHOOTING PRELIMINARY

COMPRESSOR REPLACEMENT PROCEDURE

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page Phase Simplex Page 8-13

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

14. Troubleshooting Guide

Troubleshooting Your Refrigerator

Owner s Manual. Models: 2S5P & 3S5P OPERATION AND MAINTENANCE OF SELF-PRIMING CENTRIFUGAL TRASH PUMPS PEDESTAL DRIVE

12 Volt 30 Amp Digital Solar Charge Controller

1/3 HP Submersible Sump Pump with Vertical Float Switch

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

ENERGY SMART TROUBLESHOOTING GUIDE TABLE OF CONTENTS:

Rotary Lift Trouble Shooting Guide

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

CARING FOR YOUR WATER HEATER

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

CPJ SERIES JET PUMPS

12-Volt Negative Ground Installation Instructions

CPL SYSTEMS / GROENEVELD AUTOMATIC GREASING SYSTEM COMPLETE SYSTEM CHECK PNEUMATIC PUMP

T-Series Air Conditioner T62 Model

Not required for most applications Not required for most applications High pressure ( provided) High pressure ( provided)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

BOSCH D-JETRONIC Volkswagen: Type 3 & 4

COMPRESSED AIR DRYER

Dealer Sales & Service Guide

Aquamax Australia Pty Ltd ABN

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

OPERATION AND INSTALLATION MANUAL

Single-Phase AC Synchronous Generator

OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE

SERVICE DIAGNOSIS Modine heating & ventilating equipment

HEAT SIPHON ANSWERBOOK

LOBOY 16 AIR CONDITIONERS

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM


SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

OPERATING AND MAINTENANCE INSTRUCTIONS CLIMATE CONTROL/INDUSTRIAL

TECHNICAL GUIDE TO FUEL TRANSFER PUMP TROUBLESHOOTING

Thermo Top - Troubleshooting Tree

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Troubleshooting Salt Generators

Before repairing your toilet, you must determine

Koldwave Kompac Installation & Operation Manual For models 4WK07, 4WK14, 4WK16, 4WK23, 4WK26

FUEL-16, Troubleshooting Fuel Supply Problems

Transcription:

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line voltage terminals in the control box (or connection box in the case of the 2 wire models) with a voltmeter. Make sure that the voltage is within the minimum-maximum range prescribed by the manufacturer. If the voltage is incorrect, contact the power company to have it corrected. 2. Defective control box: (a) Defective wiring. (b) Incorrect components. (c) Defective starting capacitor (skip for 2 wire models). (d) Defective relay (skip for 2 wire models). 3. Incorrectly wired pressure switch. 4. Defective motor winding or cable: a. Shorted or open motor winding. b. Grounded cable or winding. 5. Pump locked. Check out all motor and power-line wiring in the control box, following the wiring diagram found inside the box. See that all connections are tight and that no short circuits exist because of worn insulation, crossed wires, etc. Check all control box components to see that they are the type and size specified for the pump in the manufacturers literature. In previous service work, the wrong components may have been installed. Using an ohmmeter, X1000 scale, determine the resistance across the disconnected starting capacitor. When contact is made, the ohmmeter needle should jump toward 0, and then drift back slowly toward infinity. No movement indicates an open capacitor, Iow resistance means that the capacitor is shorted. Using an ohmmeter, check the relay coil and contacts. Their resistance should be as shown in the manufacturer s literature. Check the wiring at the pressure switch. Check the resistance of the motor winding by using an ohmmeter on the proper terminals in the control box (see manufacturer s wiring diagram). The resistance should match the ohms specified in the manufacturer s data sheet. If it s too low, the motor winding may be shorted; if the ohmmeter needle doesn t move, indicating high or infinite resistance, there is an open circuit in the motor winding or cable. Ground one lead of the ohmmeter onto the drop pipe or well casing, then touch the other lead to each motor wire terminal. If the ohmmeter needle moves appreciably when this is done, there is a ground in either the cable or the motor winding. Check the line amps before the trip. If amps are twice normal, or higher, pump is probably locked. Rewire any incorrect circuits. Tighten loose connections. Replace worn wires. Replace any incorrect component with the size and type recommended by the manufacturer. Replace defective starting capacitor. If coil resistance is incorrect or contacts defective, replace relay. Make sure all line, load and ground connections in the switch match the diagram. If the motor winding is defective shorted or open the pump must be pulled and the motor repaired. Pull the pump and inspect the cable for damage. Replace damaged cable. If cable checks OK, the motor winding is grounded. Pull pump, disassemble from motor and check which one is locked. Replace one, or both, if defective. 11-2 (11/00)

Troubleshooting Submersible Pumps Pump operates but delivers little or no water 1. Pump may be air locked. Stop and start the pump several times, waiting about one minute between cycles. If the pump then resumes it s normal delivery, air lock was the trouble. If this test fails to correct the trouble, proceed as below. 2. Water level in well too low. 3. Discharge line check valve installed backward. 4. Leak in drop pipe. 5. Pump check valve jammed by drop pipe. 6. Pump intake screen blocked. 7. Pump parts worn. 8. Motor shaft uncoupled. Well production may be too low for pump capacity. Restrict the low of pump output, then wait for well to recover, and start pump. Examine check valve on discharge line to make sure that the arrow indicating direction of flow points in the right direction. Raise the pipe and examine for leaks. When pump is pulled after completing Step 4 above, examine connection of drop pipe to pump outlet. If threaded section of drop pipe has been screwed in too far, it may be jamming the pump s check valve in the closed position. The intake screen on the pump may be blocked by sand or mud. Examine the screen. The presence of abrasives in the water may result in excessive wear on the impeller, casing and other close-clearance parts. Before pulling the pump, reduce setting on pressure switch to see if the pump shuts off. If it does, worn parts are probably at fault. Coupling between motor and pump shaft may have wom out or worked loose. Inspect for this after pulling the pump and looking for worn components, as in Step 7 above. If partial restriction corrects trouble, leave valve or cock at restricted setting. Otherwise, lower pump in well if depth is sufficient. Do not lower if sand clogging might occur. Reverse the valve if necessary. Replace the damaged section of drop pipe. Unscrew the drop pipe and cut off the portion of threads. Clean the screen and when reinstalling the pump, make sure that it is located several feet above the well bottom preferably 10 feet or more. Pull the pump and replace worn components. Tighten all connections, setscrews, etc. Replace parts if wom out. Pump starts too frequently 1. Pressure switch defective or out of adjustment. 2. Leak in pressure tank above water level. 3. Leak in plumbing system. 4. Discharge line check valve leaking. Check the setting on the pressure switch and examine for defects. For discharge or bladder captive air tanks, drain the tank and check the precharge pressure. It should be equal to or 2 psig below pump cut-in pressure. If lower, check welds, braze joints, mechanical joints and valve core with a soap solution. If defective, replace. DO NOT ATTEMPT TO REPAIR BY WELDING. Examine the service line to the house and distribution branches for leaks. Remove and examine. Adjust the pressure setting or replace switch. Replace tank. Repair leaks. Replace if defective. (11/00) 11-3

Troubleshooting Submersible Pumps Pump starts too frequently (continued) 5. Air volume control plugged. Remove and inspect the air volume control. Clean or replace. 6. Snifter valve plugged. 7. Captive air tank has lost charge. Remove and inspect the snifter valve. Check tank. Clean or replace. Recharge or replace tank. Fuse, overload or circuit breaker trips when motor is running 1. Incorrect voltage. Check the line voltage terminals in the control box If voltage is incorrect, (or connection box in the case of 2 wire models) contact the power company with a voltmeter. Make sure that the voltage is for service. within the minimum-maximum range prescribed by the manufacturer. 2. Overheated control or starter. If sunlight or other sources of heat makes the box too hot, overload may trip or fuses may blow. If box is hot to the touch, this may be the problem. Ventilate or shade the box, or remove it from the source of heat. 3. Detectlve control box components (skip this for 2 wire models). Using an ohmmeter, X1000 scale, determine the resistance across the disconnected running capacitor. When contact is made, the ohmmeter needle should jump toward 0, and then drift back slowly toward infinity. No movement indicates an open capacitor; low resistance means the capacitor is shorted. Using an ohmmeter, check the relay coil. its resistance should be shown in the manufacturer s literature. Check amps in red motor lead with motor running. If amps are much higher than the manufacturer specifies, start relay contacts are failing to open. If amps are much lower, run capacitor is defective or motor is overloaded. Replace defective components. 4. Defective motor winding or cable. Check the resistance of the motor winding by using an ohmmeter on the proper terminals in the control box (see manufacturer s wiring diagram). The resistance should match the ohms specified in the manufacturer s data sheet. If it s too low the motor winding may be shorted; if the ohmmeter needle doesn t move, indicating high or infinite resistance, there is an open circuit in the motor winding. Ground one lead of the ohmmeter onto the drop line or well casing, then touch the other lead to each motor wire terminal. If the ohmmeter needle moves appreciably when this is done, there is a ground in either the cable or the motor winding. If neither cable or winding is defective shorted, grounded, or open the pump must be pulled and serviced. 5. Pump is overloading. If the fuses blow or overloads trip while the pump is operating, check the line amps. If it s more than 5 percent above the manufacturer s nameplate value, the pump is overloading, which indicates a defective pump and/or motor. Pull pump, disassemble from motor and replace one or both, if defective. 11-4 (11/00)

Troubleshooting Submersible Pumps Pump won t shut off 1. Defective pressure switch. Check the pressure switch to insure contacts are open at the correct pressure. Adjust or replace switch. 2. Water level in well too low. Well production may be too low for the pump capacity. Restrict the flow of pump output, wait for the well to recover, and then start pump. If partial restriction corrects trouble, leave the valve or cock at restricted setting. Otherwise, lower pump into the well if depth is sufficient. Do not lower if sand clogging might occur. 3. Leak in drop line. Raise the pipe and examine it for leaks. Replace the damaged section of the drop pipe. 4. Pump parts worn. The presence of abrasives in the water may result in excessive wear on the impeller, casing and other close-clearance parts. Before pulling pump, reduce setting on pressure switch to see if the pump shuts off. If it does, worn parts are probably at fault. Pull pump and replace wom components. Motor does not start, but fuses don t blow 1. Overload protectlon tripped. Check overloads and circuit breaker to see if they are operable. Reset overloads or circuit breaker. 2. No power. Check power supply to control box (or overload protection box) by placing a voltmeter across the incoming power lines. Voltage should approximate nominal line voltage. If no power is reaching the box, contact power company for service. 3. Defective pressure switch. Check whether contacts are closed and the same voltage is present between load terminals as line terminals. If the line voltage is not on the line terminals, replace the switch. 4. Defective control box. Examine the winding in the control box to make sure all of the contacts are tight. With a voltmeter, check voltage at line and motor terminals. If no voltage is shown at terminals, wiring is defective from pressure switch or in control box. With a voltmeter, check the voltage across the pressure switch while the switch is closed. If the voltage drop is equal to the line voltage, the switch is not making contact. Correct faulty wiring or tighten loose contacts. Clean the contacts or replace the switch. (11/00) 11-5

Troubleshooting Jet Pumps Pump won t start or run CAUSE OF TROUBLE 1. Blown fuse. 2. Low line voltage. 3. Loose, broken or incorrect wiring. 4. Defective motor. 5. Defective pressure switch. 6. Tubing to pressure switch plugged. 7. Impeller or seal 8. Defective start capacitor. HOW TO CHECK Check to see if the fuse is OK. Use voltmeter to check pressure switch or the terminals nearest pump. Check the wiring circuit against diagram. See that all of the connections are tight and that no short circuits exist because of worn insulation, crossed wires, etc. Check to see that the switch is closed. Check the switch setting. Examine the switch contacts for dirt or excessive wear. Remove the tubing and blow through it. Turn off the power, then use a screwdriver to try to turn the impeller or motor. Use an ohmmeter to check the resistance across a capacitor. The needle should jump when contact is made. No movement means an open capacitor; no resistance means the capacitor is shorted. HOW TO CORRECT If blown, replace with a fuse of proper size. If voltage is under the recommended minimum, check the size of wiring from the main switch on the property. If OK, contact the power company. Rewire any incorrect circuits and tighten connections, replace defective wires. Repair or take it to the motor service station. Adjust the switch settings. Clean contacts with an emery cloth if it s dirty. Clean or replace if it s plugged. If the impeller won t turn, remove housing and locate the source of binding. Replace the capacitor or take the motor to the service station. 9. Motor shorted out. If the fuse blows when the pump is started (and external wiring is OK), the motor is shorted. Motor overheats and overload trips out CAUSE OF TROUBLE HOW TO CHECK Replace the motor. HOW TO CORRECT 1. Incorrect line voltage. 2. Motor wired incorrectly. 3. Inadequate ventilation. 4. Prolonged low pressure delivery. Use a voltmeter to check at pressure switch or terminals nearest pump. Check the motor wiring diagram. Check the air temperature where the pump is located. If over 100 F, overload may be tripping on external heat. Continuous operation at very low pressure places heavy overload on pump. This can cause overload protection to trip. If voltage is under the recommended minimum, check size of wiring from main switch on property. If OK, contact power the company. Reconnect for proper voltage as per wiring diagram. Provide adequate ventilation or move the pump. Install the globe valve on the discharge line and throttle it to reduce flow and to increase the pressure. 11-6 (11/00)

Troubleshooting Jet Pumps Pump starts and stops too often 1. Leak in pressure tank. 2. Defective air volume control. 3. Faulty pressure switch. 4. Leak on discharge side of system. 5. Leak on suction side of system. 6. Leak in foot valve. For discharge or bladder captive air tanks, drain the tank and check the precharge pressure. It should be equal to or 2 psig below pump cut-in pressure. If it s lower, check welds, braze joints, mechanical joints, and valve core with a soap solution. If it s defective, replace. DO NOT ATTEMPT TO REPAIR BY WELDING. This will lead to a water-logged tank. Make sure the control is operating properly. If it s not, remove and examine for plugging. Check the switch setting. Examine the switch contacts for dirt or excessive wear. Make sure all of the fixtures in the plumbing system are shut off. Then check all of the units (especially ballcocks) for leaks. Listen for the noise of water running. On shallow well units install the pressure gauge on suction side. On the deep well systems, attach a pressure gauge to the pump. Close the discharge line valve. Then, using a bicycle pump or air compressor, apply about 30 psi pressure to the system. If the system will not hold this pressure when the compressor is shut off, there is a leak on the suction side. Pull the piping and then examine foot valve. Replace the tank. Clean or replace the defective control. Adjust the switch settings. Clean the contacts with an emery cloth if dirty. Repair leaks as necessary. Make sure above ground connections are tight. Then repeat the test. If necessary, pull the piping and repair the leak. Repair or replace the defective valve. Pump won t shut off 1. Wrong pressure switch setting or setting drift. Lower the switch setting. If the pump shuts off, this was the trouble. Adjust the switch to the proper setting. 2. Defective pressure switch. 3. Tubing of pressure switch plugged. 4. Loss of prime. 5. Low well level. 6. Plugged ejector. Arcing may have caused the switch contacts to weld together in a closed position. Examine the points and other parts of the switch for defects. Remove the tubing and blow through it. When no water is being delivered, check the prime of the pump and well piping. Check the well depth against the pump performance table to make sure the pump and the ejector are properly sized. Remove the ejector and inspect it. Replace the switch if it s defective. Clean or replace the tubing if it s plugged. Reprime if necessary. If undersized, replace pump or ejector. Clean and reinstall if dirty. (11/00) 11-7

Troubleshooting Jet Pumps Pump operates but delivers little or no water 1. Low line voltage. 2. System incompletely primed. 3. Air lock in suction line. 4. Undersized piping. 5. Leak in air volume control or tubing. 6. Pressure regulating valve stuck or incorrectly set; (deep well only). 7. Leak on suction side of system. 8. Low well level. 9. Wrong pump-ejector combination. 10. Low water level in well. 11. Plugged ejector. 12 Defectlve or plugged foot valve and/or strainer. 13. Worn or defective pump parts or plugged impeller. Use a voltmeter to check at the pressure switch or the terminals nearest pump. When no water is being delivered, check prime of pump and the well piping. Check the horizontal piping between the well and pump. If it does not pitch upward from the well to the pump, an air lock may form. If the system delivery is low, the discharge piping and/or plumbing lines may be undersized. Refigure the friction loss. Disconnect the air volume control tubing at the pump and plug hole. If the capacity increases, a leak exists in the tubing of control. Check the valve setting. Inspect the valve for defects. On shallow well units, install a pressure gauge on suction side. On deep well systems, attach a pressure gauge to the pump. Close the discharge line valve. Then, using a bicycle pump or air compressor, apply about 30 psi pressure to the system. If the system will not hold this pressure when the compressor is shut off, there is a leak on the suction side. Check well depth against pump performance table to make sure the pump and ejector are properly sized. Check the pump and ejector models against the manufacturer s performance tables. Shut off the pump and allow the well to recover. Restart the pump and note whether delivery drops after continuous operation. Remove the ejector and inspect. Pull the foot valve and inspect. Partial clogging will reduce delivery. Complete clogging will result in no water flow. A defective foot valve may cause pump to lose prime, resulting in no delivery. Low delivery may result from wear on the impeller or other pump parts. Disassemble and inspect. If the voltage is under the recommended minimum, check the size of wiring from the main switch on the property. If OK, contact the power company. Reprime if necessary. Rearrange the piping to eliminate an air lock. Replace the undersized piping or install a pump with higher capacity. Tighten all the fittings and replace control if necessary. Reset, clean, or replace the valve as needed. Make sure above ground connections are tight. Then repeat the test. If necessary, pull the piping and repair the leak. If undersized, replace the pump or ejector. Replace ejector if wrong model is being used. If well is weak, lower the ejector (deep well pumps), use a tail pipe (deep well pumps), or switch from shallow well to deep well equipment. Clean and reinstall if it s dirty. Clean, repair or replace as needed. Replace worn parts or the entire pump. Clean parts if required. 11-8 (11/00)