Fisher 377 Trip Valve



Similar documents
Fisher FIELDVUE DVC6200 Digital Valve Controller / Magnet Assembly Dimensions

Baumann Way Bronze or Stainless Steel Control Valve

Fisher 377 Trip Valve

Baumann Flexsleev Sanitary Control Valve

Baumann Mikroseal Control Valve

Fisher 2625, 2625SST, and 2625NS Volume Boosters

Fisher 657 and 667 Diaphragm Actuators

Baumann Little Scotty Bronze Control Valve

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

M Series Manual Handwheel Gear Actuators for Fisher Butterfly Valves

Fisher FIELDVUE DVC6200 SIS Digital Valve Controller for Safety Instrumented Systems (SIS)

Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability

4310/4320 Wireless Position Monitor

1805 Series Relief Valves

Fisher CV500 Rotary Globe Control Valve

167D Series Switching Valves

Fisher FIELDVUE DVC6200p Digital Valve Controller Device Setup and Accessing Communication and Calibration using Siemens SIMATIC Manager/PDM

Fisher 1061 Pneumatic Piston Rotary Actuator with Style F & G Mounting Adaptations

289 Series Spring-Loaded Relief Valves

Fisher GX Control Valves

Fisher D3 Control Valve

Fisher ENVIRO-SEAL and HIGH-SEAL Packing Systems for Sliding-Stem Valves (Live-Loaded)

Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator

ValveLink Mobile Software

1301 Series High-Pressure Regulators

ValveLink Software Quick Start Guide

Types 66R and 66RR Low-Pressure Relief Valves

Baumann 24000SB Barstock Control Valve

Type 119 Control Valve

ENVIRO-SEAL. Valve Packing Systems Extending service life. Meeting environmental requirements.

SLAM-SHUT VALVE. Type OSE. Europe, Middle East, Africa and Asia Pacific Documents Only. Process Management TM

Fisher V500 Rotary Globe Control Valve

Fisher GX 3-Way Control Valve and Actuator System

Fisher 8580 Rotary Valve

Fisher 3710 and 3720 Positioners and 3722 Electro-Pneumatic Converter

Bristol Series 5453 Indicating Pneumatic Pressure Controllers/Transmitters

4310/4320 Wireless Position Monitor Burst Configuration and Diagnostics

SIS. Fisher FIELDVUE DVC6200 Series Digital Valve Controllers. Contents. Before You Begin... 2

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

Fisher 4320 Wireless Position Monitor, with On/Off Control Option

MP8000 Series Pneumatic Valve Actuators

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

Simulation of Process Conditions for Calibration of Fisher Level Controllers and Transmitters Supplement to 249 Sensor Instruction Manuals

Type 92S Pilot-Operated Steam Regulator

Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications

Uncompromising Customer Service. Baumann TM Sanitary and Aseptic Process Valves

Scraper Passage Indicator. Electrical Indicator. Features

Experience In Motion. Valtek Spring Cylinder Linear Actuators

Fisher 249 Caged Displacer Sensors

BULLETIN OCTOBER DeZURIK ROTARY DIAPHRAGM ACTUATORS

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

POWERS Controls No. 4 Pneumatic Damper Actuator

Fisher FIELDVUE DVC6200f Digital Valve Controller for FOUNDATION fieldbus

Index Page. Pumping Systems Intensifiers Gas Boosters High Pressure Generators

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

Fisher 646 Electro Pneumatic Transducer

Fisher 3610J and 3620J Positioners and 3622 Electro-Pneumatic Converter

Fisher FIELDVUE DVC2000 Digital Valve

Shut-off & Lockout Valves 1/4" to 1-1/2" port size

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4" to 1" NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

Fisher A11 High-Performance Butterfly Valve

Valv-Powr Series VPVL Stainless Steel Model D Double-Acting and Spring-Return Rack-and-Pinion Compact Pneumatic Actuators

Fisher 846 Electro-Pneumatic Transducer

PRESSURE REDUCING CONTROL VALVE

Fisher C1 Pneumatic Controllers and Transmitters

Fisher FIELDVUE DVC6200 Digital Valve

Damcos. LPU-D for double-acting actuator. Product Data Sheet November 2014 SD E06

Eurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump

Fisher Vee-Ball V150, V200, and V300 Rotary Control Valves

AMS ValveLink SNAP-ON Application

WILROY. Operation. Optional Diaphragm Rupture Detection HYDRAULICALLY ACTUATED DIAPHRAGM PUMP

Fisherr 8510 and 8510B Eccentric Disc Control Valves (EMA)

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

Type EZR Relief Valve or Backpressure Regulator

G-Series Pneumatic and Hydraulic Actuators. Next Generation Valve Automation Solutions

*Rated to 207 Bar/3000 PSI with Aluminum Body. Catalog HY /US SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO.

Basic Fundamentals Of Safety Instrumented Systems

TECHNICAL DATA. Dry 122a. November 12, 2013

BERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features

PRESSURE REGULATOR SERIES R 4100 R 2100 R 5100 VIRTUAL CATALOGUE FAIL TO OPEN REGULATOR BALANCED VALVE HIGH FLOW COEFFICIENT

*Rated to 207 Bar/3000 PSI with Aluminum Body. Denotes New Winner s Circle Product Line. Catalog HY /US

Fisher Vee-Ball Rotary Control Valves Highly efficient rotary valves to meet a variety of applications

TN2000 Series Pneumatic Piston Actuators for DN125 to DN300 SPIRA-TROL Series Control Valves

Type 99 Pressure Reducing Regulator

Automatic Self-Cleaning Strainers

3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223

Micro Motion 3098 Gas Specific Gravity Meter

ValveLink DTM ValveLink PLUG IN for PRM

T-4000 Series Room Thermostat Adjusting Instructions*

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Fisher GX Control Valve and Actuator System

Micro Motion Model D and DL Coriolis Flow and Density Meters

INSTALLATION INSTRUCTIONS

Actuators & Positioners LP - Linear Pneumatic Piston Actuator. Cylinder Actuators. High resolution, sensitivity, and fast response

SELECTION, APPLICATION AND MAINTENANCE

Pneumatic Actuators. Crafted without compromise, to make your life easier. The Leader in Actuator Technology

V47 Series Temperature Actuated Modulating Water Valves

3M Housings DS Series

VG7000 Series Bronze Control Valves

Transcription:

377 Trip Valve Product Bulletin Fisher 377 Trip Valve Fisher 377 pressure sensing trip valves are for control applications where a specific valve/actuator action is required when supply pressure falls below a specific point. When supply pressure falls below the trip point (see figure 1), the trip valve causes the actuator to fail up, lock in the last position, or fail down. When the supply pressure rises above the trip point, the 377 trip valve automatically resets, allowing the system to return to normal operation. The trip valve can be top mounted on a manifold, yoke mounted, or bracket mounted to match the application requirements. 377 trip valves can be used with Fisher 480, 585C, 685, 1061, 1066, 1069, and Bettis G Series piston actuators. W4292 1 Features Cost Effective Single trip valve construction reduces costs and spare part requirements of those systems using three separate switching valves to perform the failure functions. A single trip valve greatly simplifies piping requirements. Ease of Mode Conversion Conversion to any of the fail modes requires only minor hookup changes. Adjustable Trip Valve The trip point is adjustable for specific supply pressure requirements. Reliable Operation The trip valve design includes large diaphragm areas and few moving parts for efficient performance, minimum maintenance, and long service life. W8435 1 Fisher 377 Trip Valve Mounted on Size 130 585C Actuator www.fisher.com

Product Bulletin 377 Trip Valve Specifications Available Configurations When supply pressure falls below the trip point, 377D Trip Valve: Fails actuator piston down. Includes check valve and volume tank. 377L Trip Valve: Locks actuator piston in the last position. 377U Trip Valve: Fails actuator piston up. Includes check valve and volume tank. 377CW Trip Valve: Fails fully clockwise to close the valve. Requires check valve and volume tank. Trip valve moves piston to either up/down position and requires actuator configuration for actual clockwise movement. 377CCW Trip Valve: Fails fully counterclockwise to close the valve. Requires check valve and volume tank. Trip valve moves piston to either up/down position and requires actuator configuration for actual counterclockwise movement. All 377 trip valves can be converted to any of the above fail modes with minor hookup changes Allowable Supply Pressure for Trip Valve (1) Maximum: 10.3 bar (150 psig) Minimum: 3.8 bar (55 psig) Outlet Pressure (1) Normal Operation: Pressure from control device Fail Up or Fail Down Mode: Maximum volume tank pressure Lock In Last Position: Respective cylinder pressure Trip Point (2) Adjustable from a minimum of 2.8 bar (40 psig) to a maximum of 72 percent of supply pressure; see figure 1 Reset: 12.5 to 33 percent above adjusted trip point -Continued- Flow Coefficients (C v ) (3) Depends on flow path (shown in figure 3) as follows: Port A to Port B and Port D to Port E: 0.5 Port B to Port C and Port E to Port F: 0.6 Body Connections 1/4 NPT internal Temperature Capabilities (1) Nitrile Diaphragms and O Rings: -40 to 82 C (-40 to 180 F) Fluorocarbon Diaphragms and O Rings: -18 to 104 C (0 to 220 F) Volume Tank Maximum Internal Working Pressure (for 377D, 377U, 377CW and 377CCW trip valves) Standard: 10.3 bar (150 psig) for non ASME approved applications (4) ASME Approved Applications: Rated 10.3 bar (150 psig), maximum; 9.3 bar (135 psig), recommended Volume Tank Sizing See sizing section Hazardous Area Classification Complies with the requirements of ATEX Group II Category 2 Gas and Dust 377 SST Safety Instrumented System Classification SIL 3 capable - certified by exida Consulting LLC Table of Contents Features... 1 Safety Certification... 3 Principle of Operation... 4 377D Trip Valve... 4 377L Trip Valve... 6 377U Trip Valve... 7 377CW and 377 CCW Trip Valves... 7 Volume Tank Sizing... 8 Installation... 9 Ordering Information... 10 Application... 10 Trip Valve... 10 2

377 Trip Valve Product Bulletin Specifications (continued) Mounting Top Mounted: Manifold mounted between a 3570 positioner and a 480 actuator (manifolds cannot be supplied with 585C, 685, 1061, 1066, and 1069 piston actuators) Side Mounted: Yoke mounted or bracket mounted for use with a FIELDVUE DVC6200, DVC6200f, DVC6200p, DVC6000, or DVC6000f digital valve controller Approximate Weight Trip Valve Aluminum: 0.95 kg (2.1 pounds) Stainless Steel: 2.31 kg (5.1 pounds) Mounting Manifold: 0.5 kg (1.2 pounds) Volume Tank: Varies between 5.4 and 363 kg (12 and 800 pounds) depending on size Construction Materials Housing: Aluminum or Stainless steel Cover: 25% mineral filled thermoplastic polyester O Rings: Nitrile or fluorocarbon Diaphragms: Nitrile or fluorocarbon Interior parts Aluminum construction: Brass, aluminum, steel, and stainless steel Stainless Steel construction: Stainless steel 1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded. 2. If the trip point is not specified, the trip point is factory set at 72 percent of supply pressure or 2.8 bar (40 psig), whichever is higher. 3. Values represent nominal C v measures for each port pair using a trip valve/actuator combination. 4. This tank is rated at 14.5 bar (240 psig) in LP service. When used with air, the rating should be considered to be 10.3 bar (150 psig), consistent with the maximum pressure allowed for the 377 trip valve. Figure 1. Maximum Trip Point Settings TRIP POINT, PSIG A2779 2 110 100 90 80 70 60 50 40 SUPPLY PRESSURE, BAR 4 5 6 7 8 9 10.3 10 7.6 55 60 70 80 2 90 100 110 120 SUPPLY PRESSURE, PSIG MAXIMUM TRIP POINT SETTING TO ENSURE RESET 1 130 140 7 6 5 4 3 150 TRIP POINT, BAR Safety Certification The 377 SST is certified for use in Safety Instrumented System (SIS) applications. Certification is by exida Consulting LLC, a global provider of functional safety and control system security (see figure 2). SIS certification is identified on the product by a label affixed to the pilot body. The functional safety assessment was performed to the requirements of IEC 61508: ed2, 2010, SIL3 for mechanical components. Figure 2. exida Certificate 1 Trip point may be set to any value between 2.8 bar (40 psig) and the maximum trip point line. 2 Reset occurs a 12.5 to 33 percent above adjusted trip point. 3

Product Bulletin 377 Trip Valve Principle of Operation Figure 3. Simplified Sectional View of Trip Valve 377D Trip Valve In normal operation, supply pressure loads the upper diaphragm (see figure 3) of the unit. The valve plug spring keeps the exhaust port closed. Supply pressure also loads the lower diaphragm through the restriction, causing the plug assemblies to move down and isolate ports C and F while connecting port A to B and port D to E. UPPER Normal actuator control pressure flows from the control device to the top of the cylinder through ports A and B and to the bottom of the cylinder through ports D and E. A volume tank is charged to maximum supply pressure through a check valve in order to retain maximum supply pressure in the volume tank if supply pressure drops. VALVE PLUG SPRING SUPPLY CONNECTION PORT D PORT E EXHAUST PORT RESTRICTION PORT A PORT B When supply pressure falls below the trip point pressure in the fail down mode (see figure 4), the exhaust port opens, venting the supply pressure that is loading the lower diaphragm. This causes the upper ports of the plug assemblies to close and shut off normal pressure flow from the control device to the actuator. Volume tank pressure then flows through ports C and B to the top of the actuator cylinder, while pressure in the bottom of the actuator cylinder is vented through ports E and F. The pressure imbalance created forces the actuator piston down. W4303 1 PORT F PORT C PLUG ASSEMBLIES When supply pressure is restored, it loads the upper and lower diaphragms, causing the trip valve to reset. The exhaust port closes. The upper ports of the plug assemblies open, and the lower ports close. Normal actuator control pressure flow from the control device is restored through ports A and B and ports D and E. The check valve opens and recharges the volume tank to the maximum supply pressure. 4

377 Trip Valve Product Bulletin Figure 4. Fisher 377D Trip Valve Shown Tripped MAIN SPRING SPRING ACTUATOR VALVE PLUG UPPER VENT EXHAUST PORT CONTROL DEVICE SUPPLY PRESSURE DVC6200 PORT D PORT E PORT A PORT B UPPER PORTS CHECK VALVE PORTS PORT F PORT C PLUG ASSEMBLIES VOLUME TANK GE08412-A A6905-1 SUPPLY PRESSURE CONTROL PRESSURE TO TOP OF CYLINDER (BLOCKED) CONTROL PRESSURE TO BOTTOM OF CYLINDER (BLOCKED) PRESSURE TO TOP OF CYLINDER (FROM VOLUME TANK) PRESSURE FROM BOTTOM OF CYLINDER (VENTING) LOADING PRESSURE (BEING VENTED) 5

Product Bulletin 377 Trip Valve Figure 5. Fisher 377L Trip Valve Shown Tripped MAIN SPRING SPRING VALVE PLUG UPPER EXHAUST PORT VENT ACTUATOR SUPPLY PRESSURE PORT D PORT A DVC6200 CONTROL DEVICE PORT E PORT B PORTS PORT F PORT C UPPER PORTS PLUG ASSEMBLIES GE08414-A A6906-1 SUPPLY PRESSURE CONTROL PRESSURE TO TOP OF CYLINDER (BLOCKED) CONTROL PRESSURE TO BOTTOM OF CYLINDER (BLOCKED) PRESSURE TO TOP OF CYLINDER (STATIC) PRESSURE FROM BOTTOM OF CYLINDER (STATIC) LOADING PRESSURE (BEING VENTED) 377L Trip Valve When supply pressure falls below the trip point in the lock in last position mode (see figure 5), the exhaust port opens, venting supply pressure from the lower diaphragm. This causes the upper ports of the plug assemblies to close and the lower ports to open. Since ports C and F are plugged, no pressure change occurs on either side of the actuator piston, and the piston is pressure locked in position upon loss of supply pressure. No volume tank is necessary in this mode. When supply pressure is restored, the plug assemblies move back into the normal operating position, and supply pressure flows from the control device through ports A and B to the actuator. 6

377 Trip Valve Product Bulletin Figure 6. Fisher 377U Trip Valve Shown Tripped MAIN SPRING SPRING VALVE PLUG UPPER EXHAUST PORT VENT ACTUATOR CONTROL DEVICE SUPPLY PRESSURE PORT D PORT E PORT A PORT B DVC6200 CHECK VALVE PORTS PORT F PORT C UPPER PORTS PLUG ASSEMBLIES VOLUME TANK GE08413-A A2284-6 SUPPLY PRESSURE CONTROL PRESSURE TO TOP OF CYLINDER (BLOCKED) CONTROL PRESSURE TO BOTTOM OF CYLINDER (BLOCKED) PRESSURE TO TOP OF CYLINDER (VENTING) PRESSURE FROM BOTTOM OF CYLINDER (FROM VOLUME TANK) LOADING PRESSURE (BEING VENTED) 377U Trip Valve The fail up mode of operation (figure 6) is similar to the fail down mode of operation except that connections to port C and F are reversed. When supply pressure falls below the trip point, the top of the actuator cylinder vents, and volume tank pressure loads the bottom of the actuator cylinder. The pressure imbalance created forces the actuator piston up. 377CW and 377CCW Trip Valves Makes use of the 377D or 377U trip valve configurations, a piston actuator, and volume tank with check valve to move the piston actuator to either the up or down position. Requires the actuator and valve configuration for actual clockwise or counterclockwise movement. 7

Product Bulletin 377 Trip Valve Volume Tank Sizing Note State and local regulations may require the use of ASME approved volume tanks. It is the user's responsibility to determine requirements and applicable regulations for proper volume tank selection. Several different tanks of varying capacities are available. The volume tank must be selected so that its pressure at any time is greater than the minimum percentage of maximum supply pressure required to stroke the actuator (see figure 7). Figure 7. Volume Tank Sizing Graph 1. Size the volume tank as indicated below: For Actuators on Sliding Stem Valves, Determine: Where: For Actuators on Rotary Shaft Valves, Determine: Y = F/AP x 100 Y = P r /P x 100 Y = Minimum failure positioning percentage F = Actuator thrust required in normal operation to position the valve at the desired limit of travel A = Effective piston area (from the appropriate actuator bulletin) P = Maximum supply pressure available P r = Highest pressure required by the actuator to stroke the valve (from the appropriate actuator sizing technique) 2. With the minimum failure positioning percentage obtained in step 1, enter the value on the abscissa of the graph in figure 7. Locate the corresponding point on the curve, and read across to find the volume ratio, R. VOLUME RATIO, R A2281 1 MINIMUM FAILURE POSITIONING PERCENTAGE, Y 3. Determine: V T = (XA)/R Where: X = Maximum actuator travel from the appropriate actuator bulletin. For rotary actuators, substitute total displacement (XA). Actuator displacement can be found in the product bulletin, or contact your Emerson Process Management sales office. V T = Minimum volume tank size required R = Volume ratio from step 2 8

377 Trip Valve Installation The 377 trip valve may be mounted in any position without affecting normal operation. Dimensions are shown in figure 8 and tables 1 and 2. Table 1. Standard Volume Tank Dimensions Tank Volume J L Liters Inch 3 /Gal mm Inches mm Inches 11.8 721/3.1 309 12.16 318 12.5 21.6 1315/5.7 310 12.19 451 17.75 32.3 1970/8.5 309 12.16 595 23.43 42.9 2615/11.3 309 12.16 737 29.00 65.6 4001/17.3 309 12.16 1095 43.12 131.1 8002/34.6 Requires two 65.6 liter (4001 inch 3 / 17.3 gal) volume tanks Product Bulletin Table 2. ASME Approved, Canadian Registered Volume Tank Dimensions Tank Volume J L Liters Inch 3 /Gal mm Inches mm Inches 8.5 518/2.2 208 8.19 337 13.25 24.9 1520/6.6 305 12 427 16.81 30 1831/7.9 254 10 684 26.94 42.8 2609/11.3 305 12 681 26.81 68.8 4199/18.1 360 14.19 792 31.19 71.6 4371/18.9 305 12 1087 42.81 143.3 8742/37.86 Requires two 71.6 liter (4371 inch 3 / 18.9 gal volume tanks 114 6930/30 406 16 965 38 227 13860/60 508 20 1219 48 303 18480/80 610 24 1600 63 454 27720/120 610 24 1702 67 908 55440/240 762 30 2134 87 Figure 8. Dimensions of Trip Valve with Manifold (also see tables 1 and 2) 57 (2.25) CAP REMOVAL CLEARANCE 1/4 18 NPT SUPPLY CONNECTION 154 (6.06) PORT D 100 (3.94) 46 (1.81) PORT E PORT C PORT F 141 (5.56) L J STANDARD TANK 1 L J ASME APPROVED TANK 1 AF4605 K 19A7995 A A2778 4 76 90 (3.00)(3.56) 54 (2.12) 1/4 18 NPT VENT CONNECTION mm (INCH) 1 Refer to table 1 and 2 for J and L dimensions 9

Product Bulletin 377 Trip Valve Ordering Information When ordering specify: Application 1. Available supply pressure 2. Actuator type number and size 3. Aluminum or stainless steel construction 4. Input signal range 5. Operating ambient temperature 6. Trip point (If the trip point is not specified, the unit is factory set to trip at 72 percent of supply pressure or 2.8 bar (40 psig), whichever is higher.) 7. Volume tank size Trip Valve Refer to the specifications. Review the information under each specification and in the referenced figures. Specify the desired choice wherever there is a selection to be made. Be sure to specify the type number as described in the Available Configurations specification. Refer to table 3 for guidelines on specifying the correct trip valve. Table 3. Guidelines for Specifying Fisher 377 Trip Valve Actuator Type Fail Mode Valve Action (1) Trip Valve PDTC 377U Fail Open PDTO 377D Sliding Stem PDTC 377D Fail Closed PDTO 377U Rotary: Fully Clockwise 377CW Clockwise 1035 Fully to Close 377CCW Bettis G Series Counterclockwise Fully Clockwise 377CW Rotary: Fully 1069 377CCW Counterclockwise 1. PDTC Push Down to Close; PDTO Push Down to Open 10

377 Trip Valve Product Bulletin 11

Product Bulletin 377 Trip Valve Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Process Management Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore www.fisher.com 121985, 2014 Fisher Controls International LLC. All rights reserved.