Substation Communications Design - Legacy to IEC 61850



Similar documents
1. Introduction Communication in Substation

1. Communication Network Requirements

Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards

Leveraging the Industrial Internet of Things (IOT) to Optimize Renewable Energy

CONTROL LEVEL NETWORK RESILIENCY USING RING TOPOLOGIES. Joseph C. Lee, Product Manager Jessica Forguites, Product Specialist

Reducing the Risk, Cost and Frequency of Production Stoppages Using Network Redundancy

Industrial Requirements for a Converged Network

IEC 61850: Communication Networks and Systems in Substations

Objectives. The Role of Redundancy in a Switched Network. Layer 2 Loops. Broadcast Storms. More problems with Layer 2 loops

Welcome. People Power Partnership PROFIdag 2013 Peter Van Passen Sales & Business Development Manager HARTING Electric 1/44

IP and Ethernet Communication Technologies and Topologies for IED networks

Redundant Serial-to-Ethernet Data Connections for Mission-critical Devices

John Ragan Director of Product Management. Billy Wise Communications Specialist

Hirschmann Networking Interoperability in a

Automation Unit TM 1703 ACP Flexible automation and telecontrol

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

Substation Automation based on IEC 61850

IES-P3073GC Series. Industrial IEC port managed Ethernet switch with 7x10/100Base-T(X) and 3xGigabit combo ports, SFP socket.

White Paper. Executive Summary. Substation Communications Design Legacy to IEC Best Practices

1Industrial Ethernet Switch

IES-3080/3062 Series. Industrial 8-port managed Ethernet switch. Features. Introduction

Siemens ENEAS solutions for substation automation and protection

Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper

EtherDevice Switch EDS-726 Series

Systems Integration Track: Network Topology

Overview of Routing between Virtual LANs

Wide Area Monitoring, Control, and Protection

Quality of Service in Industrial Ethernet Networks

Chapter 3. Enterprise Campus Network Design

Verifying the IEC Configuration and Assessing the Communication Network during Commissioning

PHASOR MEASUREMENT UNIT (PMU) AKANKSHA PACHPINDE

JetNet 5428Gv2. Features. Industrial 24FE+4G Gigabit Managed Ethernet Switch INDUSTRIAL ETHERNET RACKMOUNT SWITCH

Multicast (Group) Addresses for Layer 2 (Ethernet) Transport of IEEE 1588 PTP Messages, with Application to AVB

48 GE PoE-Plus + 2 GE SFP L2 Managed Switch, 375W

Redundant Gigabit Backbone Adds Speed and Reliability to Industrial Networks

The ABCs of Spanning Tree Protocol

UNLOCK YOUR IEC TESTING EXCELLENCE

SICAM PAS - the Key to Success Power Automation compliant with IEC and your existing system

Efficient remote access to machines and plants with SIMATIC

HARTING mcon 1000 Introduction and features

FOUNDATION Fieldbus High Speed Ethernet Control System

Welcome. Enabling Wide Area Monitoring, Protection, and Control (WAMPAC) Systems with and the Importance of Time Synchronization

Introduction to Ethernet

Choosing the correct Time Synchronization Protocol and incorporating the 1756-TIME module into your Application

ABB PSPS Erich Steinmann; Generator control-2013

HARTING Ha-VIS Management Software

Performance of Redundant Ethernet Networks for Electric Substation Instrumentation and Control

Linear Motion and Assembly Technologies Pneumatics Service. Industrial Ethernet: The key advantages of SERCOS III

Voice Over IP. MultiFlow IP Phone # 3071 Subnet # Subnet Mask IP address Telephone.

B&B ELECTRONICS WHITE PAPER. Managed Ethernet Switches - Key Features for a Powerful Industrial Network

Siemens AG Fieldbus solutions with the SIMATIC PCS 7 distributed control system. Brochure April 2010 SIMATIC PCS 7. Answers for industry.

Hybrid Simulation von Kommunikationsnetzen für das Smart Grid

DIGITAL CONTROL SYSTEM PRODUCT SOLUTIONS

8x10/100/1000Base-T(X) ports and 12x100/1000Base-X, SFP socket

A New Approach to Developing High-Availability Server

2. What is the maximum value of each octet in an IP address? A. 128 B. 255 C. 256 D. None of the above

EVOLVING ENTERPRISE NETWORKS WITH SPB-M APPLICATION NOTE

CHAPTER 6 DESIGNING A NETWORK TOPOLOGY

Network Design. Yiannos Mylonas

Hirschmann. Simply a good Connection. White paper: Security concepts. based on EAGLE system. Security-concepts Frank Seufert White Paper Rev. 1.

Turning Copper into Gold

Abstract. MEP; Reviewed: GAK 10/17/2005. Solution & Interoperability Test Lab Application Notes 2005 Avaya Inc. All Rights Reserved.

Local Area Networks (LANs) Blueprint (May 2012 Release)

Supports O-Ring (recovery time < 30ms over 250 units of connection) and MSTP(RSTP/STP compatible) for Ethernet

Management Software. Web Browser User s Guide AT-S106. For the AT-GS950/48 Gigabit Ethernet Smart Switch. Version Rev.

LAN Switching and VLANs

Ha-VIS FTS 3000 Introduction and features

Square D Model 6 Motor Control Centers

DEMVE a Multi-Vendor Laboratory Environment for Research and Education Related to IEC 61850

What You Will Learn About. Computers Are Your Future. Chapter 8. Networks: Communicating and Sharing Resources. Network Fundamentals

CCNP SWITCH: Implementing High Availability and Redundancy in a Campus Network

Technical Specification Of Substation Protection & Control System with IEC BHEL s Perspective

Basics in Energy Information (& Communication) Systems Substation Automation

Power over Ethernet technology for industrial Ethernet networks

ISIO 200. Binary Input/Output (I/O) Terminal with IEC Interface

Addressing Scaling Challenges in the Data Center

CYBER SECURITY: SYSTEM SERVICES FOR THE SAFEGUARD OF DIGITAL SUBSTATION AUTOMATION SYSTEMS. Massimo Petrini (*), Emiliano Casale TERNA S.p.A.

Module 5. Broadcast Communication Networks. Version 2 CSE IIT, Kharagpur

Basics in Energy Information (& Communication) Systems Summary Substation Automation

IP SAN BEST PRACTICES

THE OSI REFERENCE MODEL LES M C LELLAN DEAN WHITTAKER SANDY WORKMAN

16x10/100/1000Base-T(X) ports and 8x100/1000Base-X, SFP socket

Overview and Applications of PROFINET. Andy Verwer Verwer Training & Consultancy Ltd

RGPS-7084GP-P. Industrial 12-port rack-mount managed Gigabit PoE Ethernet switch with 8x10/100/1000Base-T(X) P.S.E. ports and 4x1000Base-X, SFP socket

How To Understand and Configure Your Network for IntraVUE

Layer 3 Network + Dedicated Internet Connectivity

Supports O-Ring (recovery time < 30ms over 250 units of connection) and MSTP(RSTP/STP compatible) for Ethernet

Data Center Networking Designing Today s Data Center

IGS-9812GP. Industrial 20-port managed Gigabit Ethernet switch with 8x10/100/1000Base-T(X) ports and 12x100/1000Base-X, SFP socket.

IEC TRAINING PROGRAM

EVALUATING INDUSTRIAL ETHERNET

Understanding Device Level Connection Topologies

4-Port 10/100Mbps with PoE + 1-Port 100FX Industrial Ethernet Switch Wide Temperature

Contents. Connection Guide. What is Dante? Connections Network Set Up System Examples Copyright 2015 ROLAND CORPORATION

GROUP OF SPANISH ELECTRICITY COMPANIES FOR STUDIES ON IEC 61850

June Bridge & Switch. Pietro Nicoletti Piero[at]studioreti.it. Bridge-Switch-Engl - 1 P. Nicoletti: see note pag. 2

Waveguide Access Point WGA631. Product Guide

Transcription:

Substation Communications Design - Legacy to IEC 61850 Part 2/3: Practical Application Tim Wallaert Chris Jenkins

Your Utility Customer Tells You We re doing our first IEC 61850 substation and we want you to design the communication infrastructure to support it 2014 Belden Inc. belden.com @BeldenInc 2

What What Do do You you Do do Now? now??? A. Take the job B. Panic C. Try to talk them out of it D. Tell them you know how to design them a great communication infrastructure for IEC 61850 (with help from presentations such as this!) E. All of the above 2014 Belden Inc. belden.com @BeldenInc 3

Topics Here s Covered What We in Are this Going Presentation to Cover (and (and Why) Why) Why the utility is implementing IEC 61850 (so you know what they hope to get out of it!) IEC 61850 Overview (so you can speak their language) Environmental Conditions (so you can understand why the environmental requirements are important in selecting a switch) Communication Requirements (so you can design a solution that will work) Network Architectures (so you can select the right one for the job) 2014 Belden Inc. belden.com @BeldenInc 4

What is is IEC 61850? IEC 61850 is A standard for communication networks and systems for power utility automation Defines an application-focused architecture Defines environmental conditions Translates all information into data models based on standard naming convention Efficient engineering process of an application and integration of devices from multiple vendors Much more than just a communication protocol IEC 61850 is NOT A guarantee of interoperability among different vendors 2014 Belden Inc. belden.com @BeldenInc 5

Why Does the Utility Care?? Project Stage Design Install Startup Operate IEC 61850 Feature Substation Configuration Language (SCL) Data available to all devices on LAN Reduced manual configuration of devices Data available to other substations Utility Benefit Eliminates procurement ambiguity get accurate quotes Reduces wiring costs (no more point to point wiring) Lower commissioning costs Wide area protection schemes are now possible Maintain Device status data Prevent unplanned downtime Upgrade Same naming convention in similar devices New devices added without costly rework Bottom line: Utilities can do more with their substation automation for less 2014 Belden Inc. belden.com @BeldenInc 6

Topics? IEC 61850 Environmental Conditions Communication Requirements Network Architecture 2014 Belden Inc. belden.com @BeldenInc 7

Historical Substation Protocols Vendor-based Alstom Courier ABB SPA Siemens Profibus Schneider Modbus Standard DNP3 (mostly North America) IEC 60870 (mostly Europe) Problem Proprietary structures Different functionality No interoperability 2014 Belden Inc. belden.com @BeldenInc 8

IEC 61850 and UCA2 GOAL: One International Standard IEC 61850 2014 Belden Inc. belden.com @BeldenInc 9

International Electro Technical Commission The IEC is the world's leading organization that prepares and publishes International Standards for all electrical, electronic and related technologies collectively known as electro technology IEC 61850: COMMUNICATION NETWORKS AND SYSTEMS FOR POWER UTILITY AUTOMATION 2014 Belden Inc. belden.com @BeldenInc 10

IEC TC57 System Reference Architecture 61970/968 Application communication 62351 Security Power Utility control system reference architecture from IEC TC 57 Source: IEC61850-1 2014 Belden Inc. belden.com @BeldenInc 11

What is IEC 61850? A standard for communication networks and systems for power utility automation Defines an application-focused architecture Defines environmental conditions Translates all information into data models based on standard naming convention Efficient engineering process of an application and integration of devices from multiple vendors Much more than just a communication protocol 2014 Belden Inc. belden.com @BeldenInc 12

What is IEC 61850? Scope of application of IEC 61850 Source: IEC61850-1 2014 Belden Inc. belden.com @BeldenInc 13

Modeling Basic Idea: Complete description of a technical system (e.g. Substation) based on an object-oriented model Not new, but in this dimension and kind of application very innovative Reference model for information flow in the configuration process Source: IEC61850-6:2010 2014 Belden Inc. belden.com @BeldenInc 14

The Substation Configuration Language Engineer develops Tool creates:.ssd <.ssd> Source: UTInnovation & NettedAutomation <.scd> Tool creates:.scd + + + <.icd> = Siemens ssd: substation specification description icd: ied capability description scd: substation configuration description <.icd> = ABB <.icd> = Areva 2014 Belden Inc. belden.com @BeldenInc 15

The Standard IEC 61850 - Edition 1 International standard since 2003 MMS: Manufacturing Massaging Specification 2014 Belden Inc. belden.com @BeldenInc 16

The Standard IEC 61850 - Edition 2 IEC 61850 ongoing work in IEC TC57 Extensions of the existing standards (Edition 2) Addresses additional topics: part 7-410 Hydroelectric power plants - Communication for monitoring and control part 7-420 Communications systems for distributed energy resources (DER) part 80-1 Guideline to exchange information from a CDC based data model using IEC 60870-5-101/104 part 90-1 Using IEC 61850 for the communication between substations part 90-2 Using IEC 61850 for the communication between substations and control centres part 90-3 Condition Monitoring part 90-4 Communication Network Engineering Guideline part 90-5 Use of IEC 61850 to transmit synchrophasor information Target: approval in 2012-2013 IEC 61400-25: Communications for monitoring and control of wind power plants based on IEC 61850 2014 Belden Inc. belden.com @BeldenInc 17

Hirschmann Is an Active Contributor IEC 61840 Communication Network Engineering Guideline Provides definitions and specifications for the Ethernet network architecture of IEC 61850 based systems. 2014 Belden Inc. belden.com @BeldenInc 18

Network Engineering Guideline 2014 Belden Inc. belden.com @BeldenInc 19

Network Engineering Guideline IEC 61850 Traffic Classes MMS, GOOSE, SV Station Bus and Process Bus 2014 Belden Inc. belden.com @BeldenInc 20

Network Network Engineering Engineering Guideline Guideline Criteria to be considered when planning a substation network 2014 Belden Inc. belden.com @BeldenInc 21

Network Network Engineering Engineering Guideline Guideline Introduction to Ethernet specific aspects (cabling, physical layer, filtering, QoS, VLANs, redundancy) 2014 Belden Inc. belden.com @BeldenInc 22

Network Network Engineering Engineering Guideline Guideline Reference Topologies for station bus and process bus (star, ring, bus, mesh, ) 2014 Belden Inc. belden.com @BeldenInc 23

Network Network Engineering Engineering Guideline Guideline IP addressing schemes 2014 Belden Inc. belden.com @BeldenInc 24

Network Network Engineering Engineering Guideline Guideline Latency and delay aspects 2014 Belden Inc. belden.com @BeldenInc 25

Network Engineering Guideline Traffic management (multicast control, segmentation, VLAN management) 2014 Belden Inc. belden.com @BeldenInc 26

Network Engineering Guideline Time synchronization (use of NTP, PPS, IRIG-B, PTP) 2014 Belden Inc. belden.com @BeldenInc 27

Network Engineering Guideline Network management (use of SNMP, 61850 services) 2014 Belden Inc. belden.com @BeldenInc 28

Network Engineering Guideline Testing the communication network 2014 Belden Inc. belden.com @BeldenInc 29

Network Engineering Guideline Case studies: IEC 61850 project examples 2014 Belden Inc. belden.com @BeldenInc 30

Hirschmann Contributes to Many Standards Hirschmann is actively working in many standardization organizations: Member of DKE K 952 (German national committee Netzleittechnik ) Member of IEC TC57 WG10 (Power system IED communication and associated data models) Member of IEC SC65C WG 15 (High Availability Automation Networks) Member of IEEE1588 (Standard for a Precision Clock Synchronization Protocol for Networked Measurement and Control Systems) Contributing to IEEE PSRC H7 (IEEE 1588 Profile for Protection Applications) Working in IEEE802.1 (LAN/MAN Standards Committee) 2014 Belden Inc. belden.com @BeldenInc 31

Contents IEC 61850 Environmental Conditions Communication Requirements Network Architecture 2014 Belden Inc. belden.com @BeldenInc 32

Substation Environmental Conditions Electric fields Magnetic fields Electrostatic discharge High energy power surges Ground potential rise during ground faults Temperature & humidity Vibration Condensation 2014 Belden Inc. belden.com @BeldenInc 33

Some More Examples 2014 Belden Inc. belden.com @BeldenInc 34

RFI Immunity Requirements IEC 61850-3 Communications Systems and Networks in Substations (Section 5.7) IEEE 1613 - IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric Power Substations 2014 Belden Inc. belden.com @BeldenInc 35

EMI for Substations IEC 61850-3 Communications Networks and Systems in Substations Part 3: General Requirements. General immunity standard: IEC 61000-4-x series basic immunity standard IEC 61000-6-2/-4 for industrial devices IEC 61000-6-5 special enhancements for substations 2014 Belden Inc. belden.com @BeldenInc 36

EMI Immunity Requirements IEC 61850-3 Communications Networks and Systems in Substations Part 3: General Requirements IEC 61000-6-5 Immunity for Power Station and Substation Environments IEC 61000-6-2/-4 for industrial devices IEC 61000-4-x Series Basic Immunity Standards 2014 Belden Inc. belden.com @BeldenInc 37

Climatic Requirements IEC 61850 1. Class A: air-conditioned locations 2. Class B: heated or cooled enclosed conditions 3. Class C: sheltered locations 4. Class D: outdoor locations Class C Operating Temperature Ranges: 1. Class C1: -5 to +45 C 2. Class C2: -25 to +55 C 3. Class C3: -40 to +70 C 4. Class Cx: Special (defined by manufacturer) 2014 Belden Inc. belden.com @BeldenInc 38

What about the network equipment? No standard substation switch The network should not be the weakest link Switches must pass the same EMI tests as the IEDs 2014 Belden Inc. belden.com @BeldenInc 39

Transmission Media Fibre Immunity to electrical interference Avoidance of ground loops Large bandwidth Extended distances Copper Control room cabinets Links to IEDs 2014 Belden Inc. belden.com @BeldenInc 40

Contents IEC 61850 Environmental Conditions Communication Requirements Network Architecture 2014 Belden Inc. belden.com @BeldenInc 41

Logical communication substation Source: Working Draft IEC TR 61850-90-4 2014 Belden Inc. belden.com @BeldenInc 42

Logical communication substation Vertical Bay to Substation level Control and monitoring Client / Server Low priority Horizontal Time critical data between IEDs Automation High priority 2014 Belden Inc. belden.com @BeldenInc 43

Communication- conventional cabling (yesterday) Source: UT Innovation, Netted Automation 2014 Belden Inc. belden.com @BeldenInc 44

Communication - Station bus LAN Process bus conventional (today) Substation Station bus LAN / Process level conventional (today) 2014 Belden Inc. belden.com @BeldenInc 45 Source: UT Innovation, Netted Automation

Communication- Station and Process LAN (future) Substation Station and Process LAN (tomorrow) 2014 Belden Inc. belden.com @BeldenInc 46 Source: UT Innovation, Netted Automation

Power Distribution - In the Past 60-800kV 3-30kV Power ------------ T&D Network --------------- Generation Consumer 2014 Belden Inc. belden.com @BeldenInc 47

Power Distribution - In the Future (present) Power Plants Conventional Power Plants Solar Conventional Wind Solar Fuel Cell Wind Fuel Cell Distribution network Distribution network Generation / Consumer Generation / Consumer Consumer Consumer Industry Household Industry Household 2014 Belden Inc. belden.com @BeldenInc 48

Decentralized Power Generation and Smart Grid Decentralized power generation is increasing strongly Photovoltaic Wind energy Combined heat and power Fuel cells Biomass Hydro power Strong fluctuations of produced energy results in need of Decentralize Energy Management System to balance supply and demand in real time = SMART GRID IT and communication are necessary not influenceable consumer Consumer with energy management system switchable consumer Source: EWE AG 2014 Belden Inc. belden.com @BeldenInc 49

IEC 61850 Communication Management Fast Event MMS: monitoring device information MMS: Reports Ethernet: IEC 61850 GOOSE Sensor data Ethernet: Sampled Values MMS = Manufacturing Messaging Specification GOOSE = Generic Object Oriented Substation Event 2014 Belden Inc. belden.com @BeldenInc 50

IEC 61850 Communication today Sampled Values and GOOSE: High MAC Multicast traffic Today: GOOSE Multicasts on Station level approx. 10-20 devices network uncritical Source: UTInnovation & NettedAutomation 2014 Belden Inc. belden.com @BeldenInc 51

Adaptive GOOSE Transmission Time 2014 Belden Inc. belden.com @BeldenInc 52

Adaptive GOOSE Transmission Time Status sent New status sent Status sent 1s 1s 1ms 1ms 1ms 10ms 100ms 1s 1s Event occurs Settings application specific Shortest GOOSE transmission time 1ms (triple-goose) Timing requirement 12ms: application application event reaction lightning strike open protection relay 2014 Belden Inc. belden.com @BeldenInc 53

GOOSE protocol Fast and efficient communication Prioritization multicast GOOSE (Generic Object Oriented Substation Event) 2014 Belden Inc. belden.com @BeldenInc 54

IEC 61850 Communication future Future: Sampled Values and GOOSE communication via Ethernet network new technology necessary need for intelligent Multicast control (MMRP) to handle SV and GOOSE Working group (61850-90-4) Source: UTInnovation & NettedAutomation 2014 Belden Inc. belden.com @BeldenInc 55

IEC 61850 Communication Sensor data: Sampled Values Synchronized using IEEE1588 Sensors Merging Unit Voltage, current, phasing, Source: UTInnovation & NettedAutomation 2014 Belden Inc. belden.com @BeldenInc 56

IEC 61850 Communication IEEE1588 Time Synchronization cascaded boundary clocks synchronises synchronises synchronises synchronises GM BC BC BC OC cascaded transparent clocks synchronises GM TC TC TC OC BC: point to point synchronization, cascading of control loops TC: corrects only residence time, transparent for end devices (Grandmaster, Master, Ordinary Clock) A TC causes less jitter in highly cascaded networks 2014 Belden Inc. belden.com @BeldenInc 57

IEC 61850 Communication Sensor data: Sampled Values Each sensor data packet should reach the destination! (at least each second) Special requirements for the redundancy No data loss because of recovery times! No recovery time is acceptable RSTP, MRP or any other available technology does not fulfill the requirements. up to now 2014 Belden Inc. belden.com @BeldenInc 58

Contents IEC 61850 Environmental Conditions Communication Requirements Network Architecture 2014 Belden Inc. belden.com @BeldenInc 59

Network topologies 2014 Belden Inc. belden.com @BeldenInc 60

Network topologies The standard describes several topologies: These reference topologies were chosen based on common practice in substation automation systems ranging from small distribution systems to large multi-voltage level substations. They are representative of the various networking issues described in this document. There is no best network topology and no best redundancy protocol. They all have strengths and weaknesses and the correct choice for a given application depends on many factors. Source: IEC61850 Network Engineering Guideline Included in the Guideline are Topologies: Star, Ring / Multi-Ring and double networks. There is no clear recommendation but a trend to ring structures. Redundancy technologies: RSTP IEC 62439-1 PRP HSR 2014 Belden Inc. belden.com @BeldenInc 61

Cascade Architecture 2014 Belden Inc. belden.com @BeldenInc 62

Ring Architecture 2014 Belden Inc. belden.com @BeldenInc 63

Star Architecture 2014 Belden Inc. belden.com @BeldenInc 64

Hybrid Architecture Star Ring 2014 Belden Inc. belden.com @BeldenInc 65

Ring Extension: Sub-Ring Concept Based on RSTP MRP + SRM? 2014 Belden Inc. belden.com @BeldenInc 66

STP RSTP CRP Protocol Most current Standard Typical re config Spanning Tree Protocol IEEE 802.1d Rapid Spanning Tree Protocol IEEE 802.1D 2004 Cross Network Redundancy Protocol IEC 62439 4:2010 BRP Beacon Redundancy Protocol IEC 62439 5:2010 Distributed Redundancy DRP Protocol IEC 62439 6:2010 MRP Media Redundancy Protocol IEC 62439 2:2010 Fast MRP Media Redundancy Protocol IEC 62439 2:2010 Optimized RSTP HSR Comparison of Redundancy Protocols defined in IEC62439 IEEE 802.1D 2004 (configuration requirements described in IEC 62439 1:2010) 5...20ms per switch Available since Remark any topology/mesh, diameter 30s limited 1990 any topology/mesh, diameter 2s limited 2004 1s worst case for 512 end any topology/ duplicated nodes networks 2007 4...8ms worst case for 500 Two top level switches with star, end nodes line or ring topologies 2007 100ms worst case for 50 switches ring, double ring 2010 200ms worst case for 50 switches ring 1998/2007 30ms worst case for 50 switches 10ms worst case for 15 switches ring 2010 Rapid Spanning Tree Protocol ring 2010 High Availability Seamless Redundancy IEC 62439 3:2012 07 0ms ring 2010 PRP Parallel Redundancy Protocol IEC 62439 3:2012 07 0ms (1) pre-standard Hiper Ring since 1998, MRP since 2007 (2) pre-standard Fast Hiper Ring since 2007 any toplogy/ duplicated networks 2010 2014 Belden Inc. belden.com @BeldenInc 67

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks No packet loss 2014 Belden Inc. belden.com @BeldenInc 68

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks No packet loss PRP Sender Red Box 1 Lan A PRP Receiver Red Box 2 Port A Port B Lan B Two redundant networks By doubling the packets no data loss if one packet fails PRP-Redundancy-Box = bidirectional splitter and combiner 2014 Belden Inc. belden.com @BeldenInc 69 6 9 69

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks No packet loss 2014 Belden Inc. belden.com @BeldenInc 70

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks DAN - - Dual attached node implementing PRP Single attached nodes DAN DAN 2014 Belden Inc. belden.com @BeldenInc 71

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks example standard LAN with RSTP No packet loss 2014 Belden Inc. belden.com @BeldenInc 72

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks example standard LAN with MRP No packet loss 2014 Belden Inc. belden.com @BeldenInc 73

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks example standard LAN with MRP No packet loss MRP MRP 2014 Belden Inc. belden.com @BeldenInc 74

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks example standard LAN with wireless No packet loss BAT-R Wireless LAN BAT-R MRP 2014 Belden Inc. belden.com @BeldenInc 75

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks example standard LAN with wireless No packet loss BAT-R Wireless LAN 2.4 GHz WLAN BAT-R RSP RSP BAT-R Wireless LAN 5 GHz WLAN BAT-R 2014 Belden Inc. belden.com @BeldenInc 76

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Zero failover duplicated networks example standard LAN with MRP and several Red boxes No packet loss MRP MRP 2014 Belden Inc. belden.com @BeldenInc 77

IEC62439 Redundancy PRP (Parallel Redundancy Protocol) Net 6 No packet loss Net 1 Net 5 Net 2 Net 4 communication connections: net 1,2,4,5 net 1,2,3,4,5,6 net 3 net 1,2,3,4,5 not 6 net 6 net 1,2,4,5,6 not 3 Net 3 2014 Belden Inc. belden.com @BeldenInc 78

HSR (High Available Seamless Ring) Zero failover Redundant Ring No packet loss 2014 Belden Inc. belden.com @BeldenInc 79

HSR (High Available Seamless Ring) No packet loss PRP Packet PRP Packet 2014 Belden Inc. belden.com @BeldenInc 80

IEC 61850 Integration in Switches Management of Switches by use of IEC 61850 Mechanisms IEC 61850 Services IEC 61850 Server IEC 61850 SCADA Workstation 2014 Belden Inc. belden.com @BeldenInc 81

Additional Resources & Assistance 1. Obtain further Substation Communication resources from our website: www.belden.com/power-td/ This webpage includes substation communication diagrams and other useful tools 3. Contact a Belden representative for assistance: Call 510-438-9071 if you are in the U.S. or Canada Or complete the form at www.belden.com/contact/ Thank you for your interest in this presentation! 2014 Belden Inc. belden.com @BeldenInc 82