BRANCH SOLUTION. Fire protection for wind turbines. Safe for certain



Similar documents
Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230

BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.

GAS EXTINGUISHING SYSTEMS INERT GAS EXTINGUISHING SYSTEMS. Argotec Liquid Argon Gas Extinguishing Technology (LAR)

- Save lives and reduce material damage

- Save lives and reduce material damage

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

INERGEN - EXTINGUISHING SYSTEMS

CO 2. fire extinguishing systems

COMITÉ EUROPÉEN DES ASSURANCES

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

Early Fire Detection & Condition Monitoring

Data Centre alwas protected always up and running.

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

This is how you solve burning problems on forklift trucks and construction machines

Fire Extinguishers Water Extinguishers

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

VAD Variable Area Desuperheaters

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

Safer.Smarter.Tyco. Watermist fire protection Technology you can trust

Siemens D3 platform 3.0-MW, 3.2-MW, 3.3-MW, and 3.4-MW direct drive turbines. Reduced complexity, increased profitability. siemens.

HAZARD CONTROL TECHNOLOGIES, INC. Coal Silo-Bunker Firefighting Procedures

ECHM Recommendations for Safety in multiplace medical hyperbaric chambers

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

EACH CLASS of fire A, B, C, or D has a different source. Some

SPECIAL APPLICATIONS

Control and Indicating Equipment

Fire Protection of Data Centres

Fire suppression system for engine compartments USER MANUAL

Alarm and Detection/Suppression

V MW & V MW (OFFSHORE)

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems

Screw Compressors ESM Fixed Speed & VS Variable Speed

Automatic Fire Fighting Monitors

Maximum uptime and optimum fire safety for your data center

Risk Engineering Guideline

Leveraging the Industrial Internet of Things (IOT) to Optimize Renewable Energy

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

PORTABLE FIRE FIRE SOLUTIONS 1. Portable Fire Equipment Solutions COPY ONLY

Data center solutions from Siemens. For the factories of the 21 st century. siemens.com/datacenters

Nordex SE. Capital Markets Day Products & Sales - Lars Bondo Krogsgaard

DATACENTER COLOCATION. Flexible, Secure and Connected

Peasouper Operator s Manual

FIRE SAFETY FOR OFFICE WORKERS

melbourne//australia data center specifications internet + intellectual property + intelligence tel: fax:

Case Study 5 Use of Wind Turbine Technology

The ABB i-bus KNX Room Master Concept Your first step into the KNX world

Watermist fire suppression systems for commercial low hazard occupancies

DCSS (DCL) Data Center Fire Suppression Procedures

VAD. Variable Area Desuperheaters

Fire Safety Risk Assessment Checklist for Residential Care Premises

Screw Compressors 11-22kW

Maximum uptime and optimum fire safety for your data center

Natural Gas Emergencies

FIRE DETECTION AND ALARM SYSTEMS

Extract of the White paper Reduce energy costs in compressed air systems by up to 60%

FIRE-FIGHTING DESIGN BRIEF REPORT

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS

V kw The turbine that goes anywhere

THE SMARTER WAY RAIL SYSTEMS ENGLISH

Fire Alarm system Installation Guide

Portable Compressors MOBILAIR M 270 With the world-renowned SIGMA PROFILE Free air delivery 20.0 to 26.9 m³/min.

Monitoring of Natural Hazards With the ImpactSentinel Alarming System An Intelligent Solution

How intelligent must an extinguishing solution be to keep fire virtual?

An inventory of hazardous materials used in your workplace will prove useful.

4000 Series 4008TAG2A Diesel Engine ElectropaK rpm

SUPERYACHT SPARES. Nozzles and portable monitors. / info@superyachtspares.com /

Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation

Siemens D7 platform 6.0-MW and 7.0-MW direct drive wind turbines. The new standard for offshore. siemens.com/wind

The Smarter Way of Fire Fighting Fire Fighting with Water Mist

One Seven... the future of firefighting

Top Technology for Industry, Agriculture, Business and Communities

FIRE EXTINGUISHER TRAINING

Car and commercial cial air conditioning service solutions

HAZARD COMMUNICATION: NEW LABEL ELEMENTS AND SAFETY DATA SHEET (SDS) FORMAT

Diesel Engine Driven Generators Page 1 of 6

Brochure. Electric generators to power the world

Advanced Fire Protection in Data Centres

The Smarter Way of Fire Fighting Fire Fighting with Water Mist

Ultrasonic Gas Leak Detection

THM Gas Turbines Heavy duty gas turbines for industrial applications

Vehicle Fire Suppression Systems COPY ONLY

POLYREX EM Page 1 of 6

High-efficient gas boiler CompactGas

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction

IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Fire protection in archives and storage vaults

More efficiency in schools with HVAC, lighting and security

On-Line Fire Extinguisher Training

Wind turbines Fire protection guideline

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

Do you remove fumes from robotic welding and laser cutting?

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Volkswagen Jetta, Golf, GTI 1999, Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Emergency Response Guide

Flashover. Newsletter by Vincent Dunn-July 2000

Transcription:

BRANCH SOLUTION Fire protection for wind turbines Safe for certain

RISKING A FIRE IS RISKING YOUR INVESTM Over the last few years, the generation of electricity from wind energy has become a major technology showing huge growth rates and excellent opportunities for the future. Today's highly efficient wind power stations are a far cry from traditional windmills. Offshore installation and the production of the latest highperformance wind turbines require considerable investment, which must be secured against downtimes and potential loss. Until recently, manufacturers, operators and firefighters were unable to reduce the risk of damage by fire. Underestimated risk The nacelle is at the heart of wind turbines, as it contains the essential elements such as the generator, the gearbox, brakes, control panels, the transformer and the converter. It also poses a particularly high risk of fire. If a fire breaks out, for instance as a result of overheated components, electrical faults or a bolt of lightning, the fire can spread easily as the nacelle contains combustible materials such as mineral oils, lubricants, plastics and electrical components. Effective intervention is hampered by long response times on the part of the emergency services, remote location with poor roads and wind turbines with extreme hub heights. As access to the seat of the fire is crucial for a successful intervention, fire-fighters are often unable to intervene, as standard fire ladders can only be extended to a height of approximately 30 metres. Under such circumstances, fire-fighting measures are thus reduced to protecting the immediate vicinity and watching the station on fire burn down. In offshore plants, intervention from the shore is in any case far too slow to make a difference. The consequences: Downtimes or total loss of the unit, with considerable economic consequences for operators, manufacturers and insurance companies. Minimax is the only supplier in Europe providing mobile and fixed fire protection solutions. For more than 100 years, Minimax has offered planning, design, installation, maintenance and training in the field of fire protection.

ENT BRANCH SOLUTION Loss of corporate image and uneasiness on the part of investors and the general public. Minimax fire protection solutions Minimax, the market leader in fire protection solutions, has developed effective systems specifically designed for wind turbines, based on proven and tested components. The Minimax systems detect a fire at an early stage and extinguish it automatically, minimising downtimes and damage to the equipment. In order to determine the Minimax protection system that best suits your wind turbine, our specialised engineers will advise you on all aspects of the technology and design with you a tailor-made solution that meets your needs. On the above basis, Minimax offers a range of different fire protection solutions that are suitable for new wind turbines as well as for retrofitting in existing units. FIRE DETECTION SYSTEMS Fire gas detectors, smoke or heat detectors installed at the relevant critical locations automatically detect a fire at a very early stage. Also, a number of manual call points are located in the wind turbine. As soon as a detector is triggered, the control panel immediately shuts down the wind turbine and initiates a sequence of pre-programmed procedures. Visual and acoustic alarms indicate the level of risk; at the same time, the alarm signal is forwarded to a continuously manned post. If the fire hazard is not eliminated by shutting down the unit, and if further detectors are triggered, the installed extinguishing system is activated. All messages and data from the fire detection control panel can be easily integrated into the condition monitoring system of the wind turbine. In addition to that the Minimax fire detection and control panel may be equipped to allow remote diagnostics and remote control of the panel.

ARGOTEC AND THE FIRE RUNS OUT OF AIR GAS EXTINGUISHING SYSTEMS Automatic fire detectors Manual release for the nitrogen extinguishing system Downstream pipework with extinguishing nozzles Upstream pipe Argotec extinguishing systems with nitrogen from Minimax are the ideal solution for wind turbines. The figure to the left shows the main components of the fire protection system and their ideal location in the turbine: - Nitrogen gas cylinder bank at the base of the tower - Downstream Pipes with extinguishing nozzles in the nacelle and the electrical devices - Fire detectors and the control panel to detect the fire at an early stage, to control the automatic extinguishing process and alert the fire brigade Nitrogen cylinder bank Fire detection control panel Given that offshore wind parks require huge investments and are difficult to reach in the event of an emergency, automatic fire extinguishing systems are a must, as insurance cover is otherwise not obtainable.

BRANCH SOLUTION As the gas cylinders are stored at the base of the tower, its static properties are not affected by additional weight. The nitrogen is stored in pressurised containers and can thus be quickly distributed through the upstream pipe, reaching even the highest nacelle within seconds. The nitrogen reduces the oxygen in the air, necessary for each combustion process, and extinguishes the fire quickly and without leaving any residue behind. The gas is non-conductive and reaches even the most remote locations in the nacelle, entering every groove and gap and penetrating housings and switch cabinets. Fast and effective. Reliable. In the event of a fire, the extinguishing process is automatically started and controlled. The downstream pipes and installed extinguishing nozzles ensure a fast and homogenous distribution of the nitrogen in the protection zone so that the concentration necessary to extinguish a fire is reached quickly. The fire is smothered before any serious damage is done. When the fire is fully extinguished, the wind turbine can be restarted without delay, as the nitrogen gas does not leave any residue behind. Simply ventilate the room to let the gas escape. Advantages of the Argotec extinguishing technology with nitrogen Fast extinction without leaving residue behind Only short interruption of operations No damage to electrical and electronic components Nitrogen gas harmless to humans and the environment Extinguishes fires even at extremely low ambient temperatures Compact unit requiring minimum space thanks to 300 bar technology Low-cost extinguishing agent that is widely available Tested and approved quality

MINIFOG AND FIRES DISAPPEAR IN THE FOG MINIFOG SYSTEMS Minifog fine water spray systems were developed to allow for protection concepts that combine excellent fire fighting capabilities with a minimum discharge of water. The Minifog nozzles are installed in such a way that crucial components such as main bearings, gear systems, brakes and generators are effectively protected. To ensure reliability even under extreme conditions, an antifreeze solution is used that allows for proper extinguishing at down to minus 30 degrees Celsius. To enhance the efficiency of the extinguishing agent it includes a film forming foam and is sprayed through specially designed nozzles. By atomising the water, its surface is multiplied, increasing the heat binding capability of the agent and intensifying the cooling effect. As the agent evaporates, it effectively reduces the heat from the fire, while the vapour has a suffocation effect, displacing the oxygen at the seat of the fire. As the amount of water released by the Minifog system is minimal, there is normally no need to provide extra retaining containers for the extinguishing agent. The water supply system was developed as a compact unit with minimum weight to allow easy installation in the nacelle. The Minifog system may be installed during nacelle production, thus allowing for a minimised erection time for the wind turbine. Advantages of the Minifog fine water spray technology Highly effective Only small amounts of water required No risk to persons Homogeneous cooling of protected equipment Smoke-cleaning effect Approved technology with low costs Minimisation of expensive downtimes The water supply unit of the Minifog system is of a compact design requiring only minimum space The flexible FMZ 5000 fire detection control panel monitors and controls the attached automatic extinguishing systems Nitrogen gas cylinders of the Argotec compact extinguishing system are pressurised to 300 bar, so that the weight and space requirements are minimised Since 1989, Minimax fire protection systems have been installed in a variety of different wind turbine types. Minimax offers fire protection solutions for all types of units, from simple wind machines to modern turbines with capacities of several megawatts. Systems are developed and extensively tested in our fire research centre to ensure reliability under realistic conditions.

BRANCH SOLUTION While a Minifog fine water spray system protects the mechanical components in the nacelle, the electrical and electronic control cabinets of the wind turbine are safeguarded by an Argotec system.

FOR ALL Insurance companies Proven reduction of risks and damage by automatic fire protection systems Accurate assessment, thanks to the use of approved and certified products and technologies (VdS, German Lloyd, etc.) Operators and investors In the event of a fire, downtimes are minimised Optimised availability, as the risk of fire and serious damage is minimised Only the installation of an automatic fire protection system can prevent total loss by fire Stronger position for negotiations with insurance companies and banks Protection of the investment Upgrading of existing units Manufacturers Competitive edge, thanks to improved availability Enhanced image, as fire protection also means protecting the environment Fire brigade Effective fire protection for persons and property, prevention of damage to the environment and elimination of operational risks Active support of the fire brigade as weaknesses in the safety concept are effectively eliminated Minimax fire fighting solutions Effective prevention of damage by fire and all resulting economic consequences Enhancement of the image of wind turbines as safe and environmentally friendly systems Use of ecologically sustainable technologies Title: Windpark Dubener Platte, Copyright: Das Grüne Emissionshaus Minimax GmbH & Co. KG Industriestrasse 10/12 23840 Bad Oldesloe Germany Phone: +49 4531 803-0 Fax: +49 4531 803-248 E-mail: info@minimax.de www.minimax.de Nr. S 89201 AL07e_01/ 08.03/ 04.07/HA Printed in Germany Please see Minimax product sheets for detailed information.