Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 1



Similar documents
Guide to OSHA Standard Storage and Handling of Liquefied Petroleum Gases 1

Guarding Floor and Wall Openings and Holes OSHA Standard

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

Texas Department of Insurance. Fire Safety. Provided by. Workers Health & Safety. Pub. No. HS01-028D (7-08)

EMERGENCY ACTION AND FIRE PREVENTION PLAN

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

WINDEX ORIGINAL GLASS CLEANER WITH AMMONIA-D

SAFETY AND HEALTH PROGRAM

WINDEX MULTI-SURFACE CLEANER - VINEGAR

Office of Advocacy. Occupational Safety and Health Administration's (OSHA) Draft Proposed Safety and Health Program Rule 29 CFR 1900.

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Hazard Analysis Critical Control Points (HACCP) Principle 2: Determine Critical Control Points (CCPs) 1

All You Ever Wanted to Know About Fire Extinguishers...

Model Safety Program

Code Compliance Guideline: Swimming Pool Chemicals

Preparing for the Florida Department of Agriculture and Consumer Services Agricultural and Related Pest Control Applicator Exams 1

SCBA Frequently Asked Questions

OSHA Training Guidelines (An Unofficial Summary)

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

CONFINED SPACE POLICY

DOW CORNING CORPORATION Material Safety Data Sheet

DOW CORNING CORPORATION Material Safety Data Sheet

Safety Meeting Topic: Chemical Spills and Emergency Action Plans for General Industry

BERMAD Fire Protection

SECTION 105 PERMITS. Gas:

Code of Corporate Social Responsibility

SECTION 1 - PRODUCT IDENTIFICATION

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Spill Kits and Incidental Spill Response

MURPHY OIL SOAP LIQUID - ORIGINAL

CLEANING AND SANITIZING

MATERIAL SAFETY DATA SHEET Product Code: 10033

An inventory of hazardous materials used in your workplace will prove useful.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

Elgin Fire Department

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Division of Public Health Administrative Manual

Formal Interpretation NFPA 10. Portable Fire Extinguishers Edition

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

OCFRD TENT STANDARD This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

Enviro Safety Products Resource Center. OSHA Checklist for General Industry

TARLETON STATE UNIVERSITY HAZARD COMMUNICATION PROGRAM

BERMAD Fire Protection

Automatic fire-extinguishing systems for commercial cooking

1.0 Purpose Definitions Hot Work Operations. 5

Overview of the OSHA Confined Spaces in Construction Final Rule

SURVIVE INSIDE: Employee Safety in Confined Spaces

ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011

ACCELL GROUP N.V. CODE OF CONDUCT FOR SUPPLIERS

OSHA Compliance Checklist ASC

Sample Checklist for Permit Required Confined Spaces Program

EMERGENCY PLANS FACT SHEET

FIRE SAFETY HANDBOOK

Inspection, Testing and Maintenance

Important Ontario Fire Code Information for Building Owners in the City of Windsor

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS

WINDEX COMMERCIAL LINE GLASS CLEANER WITH AMMONIA- D

Implementation Date: May 5, Table of Contents. Section Description Page. 1.0 Description Initial Response 2

Occupational Medicine

CONFINED SPACE ENTRY WORK STANDARD

FIRE AND LIFE SAFETY TRAINING

RESPIRATORY PROTECTION PROGRAM

FDNY C14 Certificate of Fitness Quiz

Fire Alarms- Use of buildings when they are out of service

What is a Tracking Chart?

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS

Environment of Care Fire Safety Management Plan 2014

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

VERIFY HARD COPY AGAINST WEB SITE IMMEDIATELY PRIOR TO USE

Safety Data Sheet. Product #: Aspira Scientific 521 Cottonwood Dr. Milpitas, CA

The following definitions apply with regard to requirements specified in this document:

Housing As We Grow Older: Independent Choices 1

OVERVIEW SCOPE DEFINITIONS

ASME B31.3 Process Piping. Scope of B31.3 Course

Working with Nonprofit Organizations in Community Settings: The Strategic Plan

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

Roche Supplier. Code of Conduct

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training. For: University of Dayton Hazmat Employees

HERNANDO COUNTY FIRE ALARM GUIDELINES

EMERGENCY ACTION PLAN. for

FIRE SAFETY PRECAUTIONS

FIRE SAFETY FOR OFFICE WORKERS

General Fire Code Requirements Within Commercial Tenant Spaces

MATERIAL SAFETY DATA SHEET Complies with ANSI Z400.1 Format SECTION 1: PRODUCT IDENTIFICATION

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH

Personal Marketing: A Strategy for Marketing Programs to Diverse Audiences 1

HAZARDOUS MATERIALS MANAGEMENT ISSUE 2

On-Site Risk Management Audit Checklist for Program Level 3 Process

Trenching and Excavation Safety

Transcription:

ABE276 Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida Agriculture Florida agriculture, including forestry and seafood, made an annual economic impact of $53 billion in 1998. More than 81,000 people work on the 40,000 farms in the state, and more than 50,000 are employed in other activities related to agriculture. The state's agricultural enterprises range from large citrus, vegetable and cattle operations to small family-operated farms. From 1989 to 1998, there were approximately 240 deaths related to agriculture in Florida, according to data compiled by the Deep South Center for Agricultural Health and Safety. In addition, agriculture has one of the highest injury and death rates among U.S. industries. Safety in Florida agriculture is challenging because: the state's agricultural enterprises are diverse, safety knowledge among workers varies, manual labor is used extensively, the climate creates year-round heat stress. Therefore, it is vital to assist the public in learning about OSHA documents related to agriculture. More related information is available at the following Web sites: Florida AgSafe: <http://agen.ufl.edu/~clehtola/agsaferef.htm> OSHA Regulations: <http://www.osha.gov/comp - links.html> Overview This document, a condensation of Sections 1910.160, 1910.161, 1910.162, and 1910.163 of the Occupational Safety and Health Act (29 CFR), is not intended to be totally inclusive but rather to highlight the information and requirements in the complete 1. This document is ABE276, one of a series of the Agricultural and Biological Engineering Department, Florida Cooperative Extension Service, Institute of Food and Agricultural Sciences, University of Florida. Original publication date September 2000. Reviewed February 2008. Visit the EDIS Web Site at http://edis.ifas.ufl.edu. 2. Carol J. Lehtola, assistant professor and Extension Agricultural Safety Specialist; Charles M. Brown, coordinator information/publication services; William J. Becker, professor emeritus; Agricultural and Biological Engineering Department, Institute of Food and Agricultural Sciences, University of Florida, Gainesville. The Institute of Food and Agricultural Sciences (IFAS) is an Equal Opportunity Institution authorized to provide research, educational information and other services only to individuals and institutions that function with non-discrimination with respect to race, creed, color, religion, age, disability, sex, sexual orientation, marital status, national origin, political opinions or affiliations. U.S. Department of Agriculture, Cooperative Extension Service, University of Florida, IFAS, Florida A. & M. University Cooperative Extension Program, and Boards of County Commissioners Cooperating. Larry Arrington, Dean

Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 2 OSHA standard that owners and managers of agricultural businesses should understand. Refer to the OSHA Web site given above for the complete standard and for court interpretations of the standard. Contents of OSHA Standards 1910.160-1910.163 Fixed Extinguishing Systems, General -- OSHA Standard 1910.160 Section 1910.160(a) -- Scope and Section 1910.160(b) -- General Section 1910.160(c) -- Total Flooding Systems with Potential Health and Safety Hazards to Employees Fixed Extinguishing Systems, Dry Chemical -- OSHA Standard 1910.161 Section 1910.161(a) -- Scope and. Section 1910.161(b) -- Specific Fixed Extinguishing Systems, Gaseous Agent -- OSHA Standard1910.162 Section 1910.162(a) -- Scope and Section 1910.162(b) -- Specific Fixed Extinguishing Systems, Water Spray and Foam -- OSHA Standard 1910.163 Section 1910.163(a) -- Scope and Section 1910.163(b) -- Specific NOTE: Some sections of OSHA standards are labeled "Reserved." This label implies either that information has been deleted from the previous version of the standard or that additions to the standard are anticipated. Because standards often reference other standards, it is important that paragraph numbers remain consistent. Fixed extinguishing systems, general -- OSHA Standard 1910.160 Section 1910.160(a) -- Scope and 1910.160(a)(1) -- This section applies to all fixed extinguishing systems installed to meet a particular OSHA standard except for automatic sprinkler systems which are covered by 1910.159. 1910.160(a)(2) -- This section also applies to fixed systems not installed to meet a particular OSHA standard, but which, by means of their operation, may expose employees to possible injury, death, or adverse health consequences caused by the extinguishing agent. Such systems are only subject to the requirements of paragraphs (b)(4) through (b)(7) and (c) of this section. 1910.160(a)(3) -- Systems otherwise covered in paragraph (a)(2) of this section which are installed in areas with no employee exposure are exempted from the requirements of this section. Section 1910.160(b) -- General 1910.160(b)(1) -- Fixed extinguishing system components and agents shall be designed and approved for use on the specific fire hazards they are expected to control or extinguish. 1910.160(b)(2) -- If for any reason a fixed extinguishing system becomes inoperable, the employer shall notify employees and take the necessary temporary precautions to assure their safety until the system is restored to operating order. Any defects or impairments shall be properly corrected by trained personnel. 1910.160(b)(3) -- The employer shall provide a distinctive alarm or signaling system which complies with 1910.165 and is capable of being perceived above ambient noise or light levels, on all extinguishing systems in those portions of the workplace covered by the extinguishing system to indicate when the extinguishing system is

Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 3 discharging. Discharge alarms are not required on systems where discharge is immediately recognizable. 1910.160(b)(4) -- The employer shall provide effective safeguards to warn employees against entry into discharge areas where the atmosphere remains hazardous to employee safety or health. 1910.160(b)(5) -- The employer shall post hazard warning or caution signs at the entrance to, and inside of, areas protected by fixed extinguishing systems which use agents in concentrations known to be hazardous to employee safety and health. 1910.160(b)(6) -- The employer shall assure that fixed systems are inspected annually by a person knowledgeable in the design and function of the system to assure that the system is maintained in good operating condition. 1910.160(b)(7) -- The employer shall assure that the weight and pressure of refillable containers is checked at least semi-annually. If the container shows a loss in net content or weight of more than 5 percent, or a loss in pressure of more than 10 percent, it shall be subjected to maintenance. 1910.160(b)(8) -- The employer shall assure that factory charged nonrefillable containers which have no means of pressure indication are weighed at least semi-annually. If a container shows a loss in net weight or more than 5 percent it shall be replaced. 1910.160(b)(9) -- The employer shall assure that inspection and maintenance dates are recorded on the container, on a tag attached to the container, or in a central location. A record of the last semi-annual check shall be maintained until the container is checked again or for the life of the container, whichever is less. 1910.160(b)(10) -- The employer shall train employees designated to inspect, maintain, operate, or repair fixed extinguishing systems and annually review their training to keep them up-to-date in the functions they are to perform. 1910.160(b)(11) -- The employer shall not use chlorobromomethane or carbon tetrachloride as an extinguishing agent where employees may be exposed. 1910.160(b)(12) -- The employer shall assure that systems installed in the presence of corrosive atmospheres are constructed of non-corrosive material or otherwise protected against corrosion. 1910.160(b)(13) -- Automatic detection equipment shall be approved, installed and maintained in accordance with 1910.164. 1910.160(b)(14) -- The employer shall assure that all systems designed for and installed in areas with climatic extremes shall operate effectively at the expected extreme temperatures. 1910.160(b)(15) -- The employer shall assure that at least one manual station is provided for discharge activation of each fixed extinguishing system. 1910.160(b)(16) -- The employer shall assure that manual operating devices are identified as to the hazard against which they will provide protection. 1910.160(b)(17) -- The employer shall provide and assure the use of the personal protective equipment needed for immediate rescue of employees trapped in hazardous atmospheres created by an agent discharge. Section 1910.160(c) -- Total Flooding Systems with Potential Health and Safety Hazards to Employees 1910.160(c)(1) -- The employer shall provide an emergency action plan in accordance with 1910.38 for each area within a workplace that is protected by a total flooding system which provides agent concentrations exceeding the maximum safe levels set forth in paragraphs (b)(5) and (b)(6) of 1910.162. 1910.160(c)(2) -- Systems installed in areas where employees cannot enter during or after the system's operation are exempt from the requirements of paragraph (c) of this section. 1910.160(c)(3) -- On all total flooding systems the employer shall provide a pre-discharge employee alarm which complies with 1910.165, and is capable of being perceived above ambient light or noise levels before the system discharges, which will give

Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 4 employees time to safely exit from the discharge area prior to system discharge. 1910.160(c)(4) -- The employer shall provide automatic actuation of total flooding systems by means of an approved fire detection device installed and interconnected with a pre-discharge employee alarm system to give employees time to safely exit from the discharge area prior to system discharge. Fixed Extinguishing Systems, Dry Chemical -- OSHA Standard 1910.161 Section 1910.161(a) -- Scope and systems, using dry chemical as the extinguishing agent, installed to meet a particular OSHA standard. These systems shall also comply with 1910.160. Section 1910.161(b) -- Specific 1910.160(b)(1) -- The employer shall assure that dry chemical agents are compatible with any foams or wetting agents with which they are used. 1910.160(b)(2) -- The employer may not mix together dry chemical extinguishing agents of different compositions. The employer shall assure that dry chemical systems are refilled with the chemical stated on the approval nameplate or an equivalent compatible material. 1910.160(b)(3) -- When dry chemical discharge may obscure vision, the employer shall provide a pre-discharge employee alarm which complies with 1910.165 and which will give employees time to safely exit from the discharge area prior to system discharge. 1910.160(b)(4) -- The employer shall sample the dry chemical supply of all but stored pressure systems at least annually to assure that the dry chemical supply is free of moisture which may cause the supply to cake or form lumps. 1910.160(b)(5) -- The employer shall assure that the rate of application of dry chemicals is such that the designed concentration of the system will be reached within 30 seconds of initial discharge. Fixed Extinguishing Systems, Gaseous Agent -- OSHA Standard1910.162 Section 1910.162(a) -- Scope and 1910.160(a)(1) -- Scope systems, using a gas as the extinguishing agent, installed to meet a particular OSHA standard. These systems shall also comply with 1910.160. In some cases, the gas may be in a liquid state during storage. 1910.160(a)(2) -- The requirements of paragraphs (b)(2) and (b)(4) through (b)(6) shall apply only to total flooding systems. Section 1910.162(b) -- Specific 1910.160(b)(1) -- Agents used for initial supply and replenishment shall be of the type approved for the system's application. Carbon dioxide obtained by dry ice conversion to liquid is not acceptable unless it is processed to remove excess water and oil. 1910.160(b)(2) -- Except during overhaul, the employer shall assure that the designed concentration of gaseous agents is maintained until the fire has been extinguished or is under control. 1910.160(b)(3) -- The employer shall assure that employees are not exposed to toxic levels of gaseous agent or its decomposition products. 1910.160(b)(4) -- The employer shall assure that the designed extinguishing concentration is reached within 30 seconds of initial discharge except for

Fire Extinguishing Systems -- OSHA Standards 1910.160-1910.163 5 Halon systems which must achieve design concentration within 10 seconds. 1910.160(b)(5) -- The employer shall provide a distinctive pre-discharge employee alarm capable of being perceived above ambient light or noise levels when agent design concentrations exceed the maximum safe level for employee exposure. A pre-discharge employee alarm for alerting employees before system discharge shall be provided on Halon 1211 and carbon dioxide systems with a design concentration of 4 percent or greater and for Halon 1301 systems with a design concentration of 10 percent or greater. The pre-discharge employee alarm shall provide employees time to safely exit the discharge area prior to system discharge. Section 1910.163(b) -- Specific 1910.160(b)(1) -- The employer shall assure that foam and water spray systems are designed to be effective in at least controlling fire in the protected area or on protected equipment. 1910.160(b)(2) -- The employer shall assure that drainage of water spray systems is directed away from areas where employees are working and that no emergency egress is permitted through the drainage path. 1910.160(b)(6)(i) -- Where egress from an area cannot be accomplished within one minute, the employer shall not use Halon 1301 in concentrations greater than 7 percent. 1910.160(b)(6)(ii) -- Where egress takes greater than 30 seconds but less than one minute, the employer shall not use Halon 1301 in a concentration greater than 10 percent. 1910.160(b)(6)(iii) -- Halon 1301 concentrations greater than 10 percent are only permitted in areas not normally occupied by employees provided that any employee in the area can escape within 30 seconds. The employer shall assure that no unprotected employees enter the area during agent discharge. Fixed Extinguishing Systems, Water Spray and Foam -- OSHA Standard 1910.163 Section 1910.163(a) -- Scope and systems, using water or foam solution as the extinguishing agent, installed to meet a particular OSHA standard. These systems shall also comply with 1910.160. This section does not apply to automatic sprinkler systems which are covered under 1910.159.