T0118 T2118 T3118. Instruction Manual

Similar documents
Instruction Manual. T3111 T3111L T3111P T3111Ex

GREISINGER electronic GmbH

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Duct Humidity Transmitter

2/ These vacuum switches are used in measuring ranges between -1 and 0 bar.

1. SAFETY INFORMATION

Drayton Digistat +2RF/+3RF

USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL CAUTION CONNECTION DIAGRAM

Modular I/O System Analog and Digital Interface Modules

Contents. Document information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

User Guide. Temperature and Humidity Datalogger. Model 42280

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

4-Channel Thermometer / Datalogger

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Online Infrared Flue Gas Analyzer Gasboard 3000

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

USER GUIDE COMET SYSTEM

USB-500 Series Stand-Alone, Low-Cost Data Loggers

User's Guide. Integrating Sound Level Datalogger. Model Introduction

Name Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage

QFP910. Water detector. Building Technologies. CE1N2732en Synco living

User Guide. Heavy Duty Dissolved Oxygen Meter. Model

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

INSTALLING A/C ADAPTER

HERZ-Thermal Actuators

Model: DC-A2IO Advanced HVAC Controller

PD 100A. Printing data system

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MOUNTING AND OPERATING INSTRUCTIONS

Model: Manual DC: WIRELESS COLOR FORECAST STATION

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Pressure transmitter For general industrial applications Model A-10

TC-9102 Series Surface Mount Temperature Controllers

Hygro-Thermometer + InfraRed Thermometer Model RH101

Subminiature Load Cell Model 8417

Dual Laser InfraRed (IR) Thermometer

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

Hand-held thermometer Model CTH7000

SOUND LEVEL METER 94405

Installation Guide. DEVIreg 530. Electronic Thermostat.

psi fth mbar * /0.1 cmh inhg bar

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

How To Read A Pipe From A Sensor

Temp. & humidity Transmitter Instructions

Manual Ranging MultiMeter

How To Use An Ams 5812 Pressure Sensor With A Usb Starter Kit

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

USB-500 Series Low-Cost Data Loggers and Accessories

User Guide. 4 wire Earth Resistance Tester Model GRT300

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

USB-500/600 Series Low-Cost Data Loggers and Accessories

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

Installation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.

Adjustment functions for both span and shift have been incorporated

Rosemount 333 HART Tri-Loop

Druck DPI 104. GE Industrial Sensing. Digital pressure indicator User manual - K394

Temperature Humidity Meter

DC Electronic Loads 8500 series

Analog signal converters CC-E I/I Current / current isolators

USER MANUAL V5.0 ST100

User's Manual. Heavy Duty Dissolved Oxygen Meter Model

Operating instructions Diffuse reflection sensor with background suppression O1D101 O1D / / 2012

CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.

1000 Series Data Loggers PRODUCT MANUAL

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual

USB TC-08. Temperature Logger. User's Guide. usbtc08.en r7 Copyright Pico Technology Limited. All rights reserved.

Electronic Pressure Switch EDS 300

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

HMI display Installation Guide

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

User's Guide. Digital Psychrometer. Model RH390. F C WBT Dew Point MAX MIN

FTDI VCP DRIVER (free) (WIN/MAC/LINUX)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

8 Channel Status Input Panel model SIP-8

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

SINEAX U553 Transducer for AC Voltage

IN-OUT Thermometer with Cable Free Sensor and Clock

Name Description P/N. Programmer Programmer with calibration function SDD-AAPNP. Parameter Min. Typ. Max. Notes. (Vo+ - Vo-) - Voltage

OZW30. Central Unit SYNERGYR

User's Guide Integrating Sound Level Datalogger Model

3-step setting. 2-Color Display High-Precision Digital Pressure Switch. Series ZSE30A(F)/ISE30A. Added vacuum range.

Video surveillance camera Installation Guide

User Manual. Humidity-Temperature Chart Recorder. Model RH520

Electronic Control Devices The European Product Catalogue 2007

Manual & Technical Documentation V1.1

Transcription:

Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity values T3118 with current output 4 to 20 ma Instruction Manual

Instruction Manual Device type Temperature Humidity Computed value Pressure Output name T0118 - - - I1 T2118 - - - I1 T3118 - I1, I2 Devices are designed for indoor applications. By device type (see previous table) they can measure ambient temperature at C or F, relative humidity of air without aggressive ingredients or atmospheric pressure at hpa, PSI, inhg, mbar, oz/in 2, mmhg, inh 2 O or kpa. Unit choice is provided by User s software see later. It is possible to choice one of the following computed value (for T3118 device only): dew point temperature, absolute humidity, specific humidity, mixing ratio or specific enthalpy. Device T2118 supports pressure correction for altitude setting (offset). All device setting is performed by means of the PC connected via the optional SP003 communication cable (not included in delivery) and User s software Tsensor. Program Tsensor for device setting is available to download free at www.cometsystem.cz. It supports make the adjustment of the device too. This procedure is described at file Calibration manual.pdf which is installed commonly with the software. Program enables to set own device output range, unit selection and make an adjustment process. For T3118 device allows to assign required measured value to one of the two device outputs, it means assign temperature, relative humidity or computed value to output I1 or I2 and set its range. It is also possible to assign both outputs to the same value (with the same range), if two evaluation devices are necessary to connect. Device is connected to circuitry by means of one or two galvanic isolated loops. Each loop has two-wire connection and each loop requires power from evaluation device. It is always necessary to connect current loop I1 for proper device function (from loop I1 part of the device is powered). If current loop I1 is opened or disconnected, then loop I2 and LCD will not work. Measured and computed values are optionally shown on dual line LCD display. If there are two values displayed at one LCD line, they are periodically switched between both readings with period of 4 seconds. Display can be switched OFF totally too. Temperature, relative humidity eventually pressure sensors are non-removable device parts. Please read instruction manual before the first device connection. Device setting from the manufacturer If special setting was not required in the order device is set from the manufacturer to the following parameters: T0118: output I1: temperature, range from 4 to 20 ma corresponds with -10 to +50 C T2118: output I1: atmospheric pressure, range from 4 to 20 ma corresponds with 800 to 1100 hpa correction for altitude 0 hpa (absolute pressure) T3118:output I1: relative humidity, range from 4 to 20 ma corresponds with 0 to 100 % RH output I2: temperature, range from 4 to 20 ma corresponds with -10 to +50 C LCD display: switched ON Change of this manufacturer device setting is possible with the PC connected via the optional SP003 communication cable and User s software Tsensor as described at the end of this document. 2 IE-SNC-Tx118-02

Dimensions T0118, T2118 T3118 IE-SNC-Tx118-02 3

Device installation Devices are designed for indoor applications. It is recommended to mount them on universal wiring box (common installation box KU68) with using two enclosed mounting screws. For correct function there is necessary to find proper device place. It shouldn t be placed at places where it can be affected by sunshine, near radiators, heating elements and other heat sources, air handlers, windows, doors, into racks and shelves and similar places. For buildings with less thermal insulation there is not suitable to place them on external walls of building. If there are communication conductors placed into conduit, there is strongly recommended make it caulk, to restrict air flow around device. It is recommended to use shielded copper cable (e.g. SYKFY), maximal length 1200m. The cable must be located at indoor rooms (device is not protected for outdoor use). The cable should not be led in parallel along power cabling. Safety distance is up to 0.5 m otherwise undesirable induction of interference signals can appear. Electrical system (wiring) may do only worker with required qualification by rules in operation. Setting of pressure correction for altitude For device T2118 only! If there is necessary to read value of atmospheric pressure corrected with respect to altitude, it is possible to set corresponding pressure offset for this altitude. It is possible to do it with Users software. This value is then automatically added to measured pressure value. The resultant value of pressure with added correction for altitude must be between 300 hpa and 1350 hpa (from 4.351 PSI to 19.580 PSI). Outside this range device sends value of Error 2! Device mounting Firstly mount back part of device onto wiring box with two holding screws. Connect cables to terminals with respecting the signal polarity (see figure). Terminals are self-clamping and can be opened by a suitable screwdriver. For the opening, insert the screwdriver to upper terminal hole and lever by him. Then insert front part of device firstly at bottom into hinge and then press both parts together see figure1 Figure1: Device mounting 4 IE-SNC-Tx118-02

IE-SNC-Tx118-02 5

Device demounting If there is necessary demount the device, insert flat bladed screwdriver max. 3.5 mm wide from top side into middle device s air hole. There is fastening member placed, insert screwdriver beyond the fastening member about 2 cm deep number at the picture. Then slightly move screwdriver in arrow direction as shown at the picture. It unlock fastening member and the device is partially opened. Remove the screwdriver and take front part of device at top, see number at the picture. Pull front part with pendulum motion, remove front cover, numbers and at the picture. If there is necessary remove back part of device, please disconnect cables and unscrew two holding screws. Figure2: Device demounting Typical application wiring, connection of terminals Calculation of minimum power voltage Uss for proper operation: Uss min> Uo min + Imax * Rz, where: Uo min= 9 V Imax... approximately 20 ma Rz... sensing resistor (shunt) For device T3118: Both current loops (I1 and I2) are connected analogically, current loop I1 must be always connected. 6 IE-SNC-Tx118-02

Info mode If you would like to check output range settings, it is possible to verify without a use of the computer. It is necessary to connect the power. Button is placed behind small hole on the left side of the device (front view). For button pressing use thin instrument, for example paper clip. Short button press shows low range and type of measured value for first output (output I1, at LCD indicated by symbol 1 ). Type of measured value is indicated with appropriated value unit. (here C = temperature). Upper line shows current value which is assigned to value of measured value (lower display line). Here 4 ma corresponds with temperature of -10 C. Next button press shows values for upper scale limit. (the same channel, the same value) by the same rules as at previous case. Here 20 ma corresponds with temperature of 50 C. For T3118 device there is analogously shown I2 output setting. Next press of button exits info mode and actual measured values are displayed. Note: For atmospheric pressure device T2118 there is at the lower LCD line shown current value assigned to atmospheric pressure value shown at upper LCD line. Note: No measurement and communication is possible during info mode. If device stays in info mode for longer than 15 s, device automatically returns to measuring cycle. Readings on LCD display C, F Reading next to this symbol is measured temperature or error state of value. %RH Reading next to this symbol is measured relative humidity or error state of value. hpa, PSI, inhg, Reading next to this symbol is measured pressure or error state of value. If selected pressure unit is mbar or oz/in 2 or mmhg or inh 2 O or kpa, there is shown only value (number) without corresponding pressure unit! C / F DP Reading next to this symbol is calculated dew point temperature or error state of value. g/m 3 Reading next to this symbol is calculated absolute humidity or error state of value. g/kg Reading next to this symbol is calculated specific humidity or mixing ratio (depends on device setting) or error state of value. If specific enthalpy is selected, there is shown only value (number) without corresponding unit! IE-SNC-Tx118-02 7

Technical parameters of the device: Accuracy data shown are for value displayed on LCD display. For value on analog output is valid too, if selected output range is set inside measuring range. Analog outputs: T0118, T2118: one output channel I1, range from 4 to 20 ma T3118: two galvanic isolated outputs I1 and I2, range 4 to 20 ma Current output in case of error: approximately <3.8 ma or >24 ma Power: 9 to 30 V DC, maximum ripple 0.5 % Measuring parameters: Ambient temperature T0118, T3118: Measuring range: -10 to +50 C Display resolution: 0.1 C Accuracy: ± 0.5 C Response time: air flow approximately 0.3 m/s t90 < 12 min No air flow t90 < 25 min Atmospheric pressure T2118 only: - accuracy of value shown on LCD display: Unit hpa, mbar PSI mmhg inhg inh 2 O oz/in 2 kpa Range 600 8.70 450.0 17.72 240.9 139.2 60.00 1100 15.95 825.1 32.48 441.6 255.3 110.00 accuracy T=23 C ±1.3 ±0.02 ±1.0 ±0.04 ±0.5 ±0.3 ±0.13 0 T 40 C ±1.5 ±0.02 ±1.1 ±0.04 ±0.6 ±0.3 ±0.15 Else ±2.0 ±0.03 ±1.5 ±0.06 ±0.8 ±0.5 ±0.20 Output accuracy: ±(accuracy of value shown on LCD display + 0.06% FS)hPa Response time 1 : t90 <44 s Relative humidity - T3118 only (reading is temperature compensated at entire temperature range): Measuring range: 5 to 95 % RH (see Device installation) Display resolution: 0.1 % RH Accuracy: ± 2.5 %RH for range from 5 to 60 %RH, ± 3 %RH for range from 60 to 95 %RH, at 23 C Response time: t90 < 30 s (air flow approximately 1 m/s, relative humidity step 65 %RH, constant temperature) 1 There is possible to change response time. For more details see file Description of calibration and adjustment procedure.pdf, which is installed together with Users software. 8 IE-SNC-Tx118-02

The value computed from ambient temperature and relative humidity - T3118 only: You can choice one of the next value. Display resolution: 0.1 C Dew point temperature Accuracy: ±1.6 C at ambient temperature T < 25 C and RH > 30 % Range: -60 to +80 C Absolute humidity Accuracy: ±3g/m 3 at ambient temperature T < 40 C and RH < 95 % Range: 0 to 400 g/m 3 Specific humidity 2 Accuracy: ±2g/kg at ambient temperature T < 35 C and RH < 95 % Range: 0 to 550 g/kg Mixing ratio 2 Accuracy: ±2.2g/kg at ambient temperature T < 35 C and RH < 95 % Range: 0 to 995 g/kg Specific enthalpy 2 Accuracy: ± 3.5kJ/kg at ambient temperature T < 25 C and RH < 95 % Range: 0 to 995 kj/kg Recommended calibration interval: T0118 2 years T2118, T3118 1 year Measuring interval and LCD display refresh: 0.5 s, T2118 2 s Communication with computer: via USB port by means of USB communication cable SP003 Protection: IP20 Operating conditions: Operating temperature range: -10 to +50 C Operating humidity range: 0 to 100 %RH (without condensation) Outer characteristics in accordance with EN33-2000-3 normal environment with the specifications: AE1, AN1, BE1 Electromagnetic compatibility: complies EN 61326-1 Storing conditions: temperature -30 to +80 C, humidity 0 to 100 %RH without condensation Not allowed manipulations: It is not allowed to operate the device under other than specified conditions in technical parameters. Devices are not designed for locations with chemically aggressive environment. Temperature and humidity sensors must not be exposed to direct contact to water or other liquids. Do not use the device in an explosive environment. Dimensions: 106 x 88 x 33 (h x l x d) Weight: approximately 150 g Material of the case: ABS 2 This value depends on the atmospheric pressure. For computing there is used constant value stored inside the device memory. Default value preset by manufacturer is 1013hPa and can be changed by user s software. IE-SNC-Tx118-02 9

Procedure of modification of device adjustment: device adjustment is performed by means of the optional SP003 communication cable, connected to USB port of the PC. It is necessary to have installed configuration program Tsensor on the PC, It is free to download at www.cometsystem.cz. During installation please take care about installation of driver for USB communication cable Demount the device (see chapter Device demounting ) Connect SP003 communication cable to the device and PC. Installed USB driver detect connected cable and create virtual COM port inside the PC. Display must light up, or at least must light up all symbols for one second (if LCD was switched OFF by program before). Run installed Tsensor program and select corresponding communication COM port (as described above) Now make new device setting throw Tsensor program When new setting is saved and finished, disconnect the cable from the device and mount the device. Error States of the device Device continuously checks its state during operation. In case error is found LCD displays corresponding error code: Error 0 First line displays Err0. Check sum error of stored setting inside device s memory. Output value is < 3.8 ma. This error appears if incorrect writing procedure to device s memory occurred or if damage of calibration data appeared. At this state device does not measure and calculate values. It is a serious error, contact distributor of the device to fix. Error 1 Measured or calculated value except in pressure is over upper limit of allowed full scale range. There is a reading Err1 on LCD display. Output value is about 24.5 ma This state appears in case of: Measured temperature is higher than approximately 600 C (i.e. high non-measurable resistance of temperature sensor, probably opened circuit). Relative humidity is higher than 100%, i.e. damaged humidity sensor, or humidity calculation of humidity is not possible (due to error during temperature measurement) Computed value calculation of the value is not possible (error during measurement of temperature or relative humidity or value is over range) Error 2 There is a reading Err2 on LCD display. Measured or calculated value is below lower limit of allowed full scale range or atmospheric pressure error occurred. Output value is about 3.8 ma. This state appears in case of: Measured temperature is lower than approximately -210 C (i.e. low resistance of temperature sensor, probably short circuit). 10 IE-SNC-Tx118-02

Relative humidity is lower than 0%, i.e. damaged sensor for measurement of relative humidity, or calculation of humidity is not possible (due to error during temperature measurement) Computed value calculation of computed value is not possible (error during measurement of temperature or relative humidity) Measured pressure value with added correction for altitude is outside of range from 300 hpa to 1350 hpa (from 4.351 PSI to 19.580 PSI) or the pressure sensor is damaged. Please check setting of pressure correction for altitude with User s software. Error 3 There is a reading Err3 on LCD display upper line. Error of internal A/D converter appeared (converter does not respond, probably damage of A/D converter). This error does NOT affect pressure measurement. Rest values are NOT measured. Output value is about 3.8 ma. It is a serious error, contact distributor of the device. Error 4 There is a reading Err4 on LCD display. It is internal device error during pressure sensor initialization. Under this condition device does NOT measure atmospheric pressure Output value is about 3.8 ma. Pressure sensor is probably damaged. It is a serious error, contact distributor of the device. End of operation Device itself (after its life) is necessary to liquidate ecologically! Technical support and service Technical support and service is provided by distributor. For contact see warranty certificate IE-SNC-Tx118-02 11