& MAINTENANCE INSTRUCTIONS INSTALLATION, OPERATION AIR COOLED CONDENSERS FLUID COOLERS HEAT RECLAIM UNITS



Similar documents
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

Steam Coil Installation, Operation and Maintenance

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

REMOTE AIR-COOLED CONDENSERS. Installation and Maintenance Data. Models Bulletin H-IM-73A June 2000 Part Number

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Why and How we Use Capacity Control

Miami Heat Pump HP Series Installation Guide

Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

CEILING CASSETTE FAN COIL UNIT

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Refrigeration System Installation & Operation Manual

Oil and Coolant Circulating Heating System. Model - OCSM

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.

NITROUS TRANSFER PUMP INSTRUCTIONS

GAS SAFETY PRECAUTIONS

COMPRESSOR REPLACEMENT PROCEDURE

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Bottom Loading Water Dispenser

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

CARING FOR YOUR WATER HEATER

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

T-Series Air Conditioner T62 Model

Dehumidifier Users manual. For Models: DH45S DH65S

DESIGN STANDARDS SECTION

Ceiling Mount Air Handler Manual

LOBOY 16 AIR CONDITIONERS

Air vacuum pump with r134a & r12/22

Installation Manual DIAPHRAGM WELL TANK

Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.

Owners Manual 2009 PRICE LIST DRYMAXTM. Compressed Air Treatment Products. Refrigerated Air Dryers

TWIN EAGLES ALL WEATHER ELECTRIC RADIANT HEATER

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400

, User s Manual

Instructions and precautions. Fork Height. Visit our website at:

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

12V Portable Diaphragm Compressor Operating and Maintenance Instructions

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Installation Manual DIAPHRAGM WELL TANK

Table Z. Troubleshooting Chart for Air Conditioners. Cause

AE R6 December Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE R6

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

DBF 4XL Dryer Booster Fans

Refrigeration Installation 101

1 / 4 IN. FFL x 4 FT. 9 IN. 1 / 2 IN. ACME x 4 FT. 9 IN. Gauge Accuracy +/-2% Set includes Quick Disconnect Valves

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

ON-VEHICLE INSPECTION

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Wine Cooler with Thermo-Electric Cooling & Heating Technology

Home Owners Guide HR SERIES HEAT RECOVERY VENTILATOR (HRV) Models HR100V, HR160H & HR220H RESIDENTIAL USE ONLY HR160H & HR220H

Threaded Inline Air Heaters

SAFETY PRECAUTIONS Read all of the instructions before using this appliance. When using this appliance, always exercise basic safely precautions,

OWNER S Manual PRINTED IN CANADA 10/2009

MAC-120HE-01 Air-Cooled Chiller

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS

COMPRESSOR REPLACEMENT PROCEDURE

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

KRAMER ELECTRIC DEFROST EVAPORATORS LPE - LVE - MSE - CSE - HSE - CED - KED INSTALLATION, START-UP AND MAINTENANCE INSTRUCTIONS

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Installation Instructions

SWIMMING POOL HEAT PUMP

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

LUCCI AIRFUSION QUEST II CEILING FAN

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

What you can expect from your Solar Hot Water System

INSTANT HOT WATER RECIRCULATING SYSTEM

Evaluate, Clean, and Tune Guidance

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI

Using Portable Spot Air Conditioners in Industrial Applications

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Panel Mounted Air Conditioners by Dantherm, Inc.

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

FASCINATION 700 HVLP TANNING PRO SYSTEM USER MANUAL

10 tips for getting more reliability from your air-conditioning system [reliability]

Element D Services Plumbing

ECOCIAT. Domestic hot water heat recovery unit

MODEL G300 BRAKE BLEEDER

EXTENDED 10 YEAR LIMITED LIFETIME WARRANTY LIMITED LIFETIME WARRANTY

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Recharge Procedure for Telemark TVP-2000 and TVP-3500

SINGLE STAGE INLINE FIRE PUMP

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

First irst Co. Products

PALLET JACK TON

AIR CONDITIONER & HEAT PUMP DIGITAL CONTROL FOR DUCTED SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

Foodservice Equipment Specialists P.O. Box 880 Saco, ME. / U.S.A * FAX (207)

tire inflator with pressure gauge

Transcription:

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS AIR COOLED CONDENSERS FLU COOLERS HEAT RECLAIM UNITS

CONTENT SAFETY CONSERATIONS...2 INTRODUCTION...2 HANDLING...3 INSTALLATION...3 STEPS #1&#2 INSPECTION/LOCATION:..3 STEP #3 WIRING:...3 STEPS #4&#5 PIPING/LEAK TESTING...3 OPERATION...4 FAN MOTORS/FAN CYCLING...4 MAINTENANCE - CLEANING...4 TABLE 1: FLU COOLERS:...5 TABLE 2: CONDENSER & HEAT RECLAIM...6 to 16 Fig # 1: Standard legs...17 Condenser/Fluid Cooler Dimensions...18& 19 Fig. #2 : Extended Legs...20 Fig #3 : 2 fans...21 Fig # 4: 1 fan...22 Table #3...23 Table #4...24 Table #5...25 Table #6...26 Table #7...27 Replacement part list... 28 & 29 WARRANTIES...30 SAFETY CONSERATIONS Installing, starting up, and servicing equipment can be hazardous due to system pressures, electrical components and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment. When working on the equipment, observe precautions in the literature and on the tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloths and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. WARNING Before installation, always check to be sure main power to systems is OFF. Electrical shock can cause personal injury or death. INTRODUCTION Air Cooled condensers series CCR, CMR, CLR, CLW, CLX, CNR, CNW, CNX, CVR, CVW, CVX, CCD, CQD, CLD, CMD, CH8, CL8, CHD and C are designed for refrigerant condensing of refrigeration and air conditioning systems. They can be manufactured for single or multiple circuits, for single or multiple compressors. Fluid coolers series FCD, FLD, F, FMD, FNV, FVD, FVV and FND are designed to cool glycol, oil or any other fluid that is not corrosive to copper and will not let the leaving air temperature exceed 140 F (60 C). Heat recovery units HCD and HMD are designed to recover heat from refrigeration system in warehouse or shipping area. 2

HANDLING CAUTION : Do not use forklift truck to handle units. Use only chains with hooks and spread bars to lift units. When a unit is shipped on its side, two or three hangers are installed. Use them to unload the unit from truck. A lift truck can be used with the wood base in that position only to lower the unit on the ground. Two others hangers, four, six or eight legs (depending on the unit) and the required hardware are supplied attached to the cabinet. Lifting method 1 : Install all the legs on the same side as hangers. Gently lower the unit on those legs. Install hangers on opposite side. Raise the other side and install other legs. Install chains and spread bars to raise the unit to its final position. Lifting method 2 : Gently lower the unit on a flat surface. Install hangers on opposite side. Install chains and spread bars to raise the unit. Lift the unit and install all the legs. Lift the unit to it s final position. See fig # 1 for more details. If the unit as been ordered with extended legs, see fig. #2 for field assembly. Also refer to table #1, #2 for unit weight. INSTALLATION STEP #1 INSPECTION: If the unit is suspected of having been damaged in transit, immediately notify the carrier and file a claim with that carrier. The refrigeration coil section(s) of the unit should display a pressurised nitrogen gas holding charge. Unit should then be pressurised to 350 psi with dry nitrogen gas and leak-checked prior to rigging; this to insure no coil damage has occurred after the unit left the factory. Bolts & nuts may have become loose in transit, as well as electrical components. Please make sure that everything is tight prior to startup. STEP #2 LOCATION: Condensers and fluid coolers are installed on the roof or ground level. If a unit is installed on the ground it must be fenced to prevent possible damage. Heat recovery units are installed inside at the ceiling level. Check loading capacity of the roof, the ceiling or the floor before installation. The unit is intended to be installed in an atmosphere containing only neutral water vapour, natural precipitation and air. Use in any other atmosphere must be checked for compatibility with metals, materials and coating used in manufacturing of this equipment. Unit positioning as well as firmness and perfect levelness of mounting base supports are important: Good installation practices are well known and are to be followed. Air flow paths on all sides as well as coil inlet and fan discharge areas are not to be restricted. Unit positioning that may result in air recirculation as well as prevailing wind impedance is to be avoided. If a unit is to be placed close to a wall the minimum distance should be 24 inches for single row of fans and 48 inches for double row of fans. If units are to be placed side by side, the minimum distances should be 48 inches for single row of fans and 96 inches for a double row of fans. The chosen location must be convenient and allow safe accessibility for maintenance. STEP #3 WIRING: NOTE: A wiring diagram is provided with the unit, it is located on the inner face of the electrical box access door. All wiring must be done in accordance with national and local codes. Check the nameplate with the current characteristics to be used for wiring unit. Internal wiring connections of the fan motors, optional controls and contactors have been completed at the factory. Once wired, make sure the unit has been grounded. Disconnect switch at the unit must be provided by others. On air cooled condensers with flooding valve, one fan (single width unit) or one pair of fans (double width unit) must operate when compressor is operating to avoid internal damage to the condenser coil. 3

STEP #4 PIPING: CAUTION: The unit has not been designed to carry the weight of any extended piping or valves. The piping must be well supported otherwise tube breaking at the coil will most probably occur. All refrigerant or fluid system components must be installed in accordance with applicable local and national codes and in accordance with good engineering practice required for proper operation. Use top quality refrigeration tubing that is internally free of dirt, humidity or other contaminants. Unsealed tubing should not be used. Long radius elbows are recommended. Dry nitrogen must be swept through the lines while joints are brazed to avoid oxidation and carbon deposits. IMPORTANT: The use of a calibrated pressure gage and regulator must always be used with nitrogen gas cylinders. To minimise hydraulic shock line breakage possibilities, valving and controls must be designed to eliminate any rapid introduction of hot gas into cold piping. Most especially if the piping contains liquid refrigerant or is at a much lower pressure than the hot discharge gas, which can be the case of double-wide condensers that feature one-half operation during winter. Plans should be for utilising either a slow-shifting three-way/four-way valve, or not completely lowering to suction pressure the condenser coil side that deactivates during winter. Most often, a combination of both of these options works well in geographic areas that encounter lower than freezing seasonal outdoor temperatures. Air-cooled condensers must be provided with inverted P trap with a purge connection. A separate sub cooling circuit may be necessary if liquid line must rise to level higher than the unit. Vibration in the discharge or liquid line must be corrected immediately to avoid piping and/or header breakage and refrigerant loss. Generally, horizontal-piping runs should grade slightly downwards in the direction of the flow. Liquid line piping must be arranged so that it is free draining from the condenser to the receiver. It is best to pipe liquid lines so that there is an immediate drop, at least 2 or 3 feet, at the condenser outlet, before headering or running horizontally. STEP #5 LEAK TESTING: Leak testing and evacuation must be done in accordance with local and national codes. Once all refrigerant connections are made, leak test all joints before charging the system with refrigerant. After leak testing, all moisture and non-condensable gas must be evacuated from the system. Attach high vacuum line pump and gage on both high and low pressure sides of the system. A minimum vacuum level of 100 microns is required to effectively remove moisture. Be sure all valves such as compressor, hot gas, receiver, and liquid solenoid valves are open. Break the vacuum in the system with the refrigerant to be used. Always charge the refrigerant into the system through a new 16 cu. in drier (field supplied) in the charging manifold line. OPERATION The notice below depicts the label that is affixed to the control box cover. WARNING Warranty Condition ONE FAN (SINGLE WTH UNIT) OR ONE PAIR OF FANS (DOUBLE WTH UNIT) AND THE COMPRESSOR MUST OPERATE SIMULTANEOUSLY TO AVO DAMAGE TO THE CONDENSER COIL. Not complying to this condition can cause uneven rapid expansion and contraction of the condenser core tubing contributing to condenser tubes failures. Violation of this condition will void the warranty of the misused unit. For a refrigeration system to function properly, the condensing pressure and temperature must be maintained within certain limits. To prevent excessively low head pressure during winter operation, two basic control methods are used, refrigerant side control and air side control. 4

1) A) -side control is accomplished by modulating the amount of active condensing surface available for condensing by flooding the coil with liquid refrigerant. This method requires a receiver and a larger charge of refrigerant. See fig. #3. B) -side control by doing the one-half condenser operation. The condenser is initially resigned with two equal sections, each accommodating 50% of the load during normal operation. During winter an ambient controlled flow divider valve blocks off one section of the condenser and pumps down the inactive section in the suction. This saves the flooding overcharge and sometimes allows the shutdown of the fans on the inactive condenser side. Fig. #4 2) Airside control is accomplished by cycling fans in response to condensing pressure or outdoors-ambient temperature. To reduce stress on the condenser coil, one fan or one pair of fans must operate when a condenser is operating. Speed control on the constant operating fan may be used to reduce motor cycling and stabilise the operating pressure. See table 3 to 6 for more information. For low ambient operation this method must be combined with refrigerant side control. FAN MOTORS: Check the fan blade clearances within the venturies, as well as check for proper rotation. Fan motors operating at higher elevations will draw lower than rated amp as well as draw less effective air volume across the coil surface. This is due to the reduced density of the higher altitude air, which results in higher compressor, and higher discharge pressure along with reduced unit capacity. Please consult factory if you suspect this situation. The fan motors are permanently lubricated for service free operation. The motor may restart on automatic thermal protection. Motors are readily serviced by removing fan guards and fans. If a motor is inoperative or it cycles on thermal protection, check supply voltage at the motor leads. Fan motors may cycle on thermal protection if the coil is blocked. Units equipped with axial fans, CVR, CVW, CVX: The entire fan assembly, motor, blade and ventury need to be replaced if there is a failure of any kind. With the two speed version, 3 contactors are used per motor. Do not attempt to manually close one of these contactors; this may result in motor winding damage. FAN CYCLING: Optional temperature or pressure controls are located in the control box. Air temperature sensors are located in the air flow and pressure controls are directly connected to the circuit in a return bend. Optional line duty controls are connected directly to the fan motors. Controls are double pole single throw, one line remain live on the motors. Units must be completely disconnected before servicing. Optional pilot duty controls are connected to 3 pole motor contactors. If controls or contactors are defective, they must be replaced. CLEANING: MAINTENANCE After one day of operation, check for any vibration that might have developed in the unit. It is recommended that the unit be inspected occasionally for dirt accumulation. Grease and dust should be removed from the fans and fan guards. Periodical cleaning of finned surfaces can be done by washing down dust with warm water spray and a mild detergent. Do not use alkaline or acidic solution as it will attack the coil material. The inner face of the coil may be cleaned by the access panel on the side of the units or by removing the fan guards. Always pressure -clean in reverse of the air flow. 5

Fluid Cooler TABLE 1: FLU COOLERS Fluid Cooler FCD02 1 1 190 FLD015 1 1 654 FCD03 1 1 201 FLD018 1 2 985 FCD04 1 1 210 FLD021 1 2 1005 F010 1 1 515 FLD023 1 2 1063 F011 1 1 525 FLD026 1 2 1091 F013 1 1 592 FLD028 1 2 1117 F014 1 1 602 FLD030 1 2 1159 F016 1 1 641 FLD035 1 3 1460 F017 1 1 654 FLD040 1 3 1490 F020 1 2 985 FLD042 2 2 1625 F023 1 2 1005 FLD043 1 3 1570 F025 1 2 1063 FLD045 1 3 1609 F029 1 2 1091 FLD049 2 2 1792 F031 1 2 1117 FLD050 1 4 1875 F034 1 2 1159 FLD053 2 2 1781 F039 1 3 1460 FLD054 1 4 1915 F044 1 3 1490 FLD056 2 2 1882 F046 2 2 1625 FLD057 1 4 2019 F049 1 3 1570 FLD060 2 2 1934 F051 1 3 1609 FLD061 1 4 2071 F054 2 2 1792 FLD063 2 3 2323 F055 1 4 1875 FLD066 1 5 2403 F058 2 2 1781 FLD070 1 5 2475 F059 1 4 1915 FLD075 1 5 2540 F064 2 2 1882 FLD080 2 3 2508 F065 1 4 2019 FLD085 2 3 2664 F068 2 2 1934 FLD090 2 3 2742 F069 1 4 2071 FLD099 2 4 3029 F070 2 3 2323 FLD106 2 4 3129 F073 1 5 2403 FLD113 2 4 3338 F079 1 5 2475 FLD120 2 4 3442 F085 1 5 2540 FLD124 2 5 4198 F088 2 3 2508 FLD132 2 5 4298 F095 2 3 2664 FLD142 2 5 4560 F101 2 3 2742 FLD150 2 5 4690 F112 2 4 3029 FLD159 2 6 5292 F119 2 4 3129 FLD170 2 6 5642 F129 2 4 3338 FLD180 2 6 5798 F137 2 4 3442 FLD190 2 6 6535 F141 2 5 4198 FMD05 1 1 308 F149 2 5 4298 FMD07 1 1 335 F162 2 5 4560 FMD08 1 1 350 F171 2 5 4690 FMD09 1 2 489 F178 2 6 5292 FMD11 1 2 518 F194 2 6 5642 FMD12 1 2 532 F205 2 6 5798 FMD13 1 2 544 F214 2 6 6535 FMD14 1 2 566 FLD009 1 1 515 FMD18 1 3 727 FLD010 1 1 525 FMD20 1 3 741 FLD012 1 1 592 FMD21 1 3 767 FLD013 1 1 602 FMD23 1 3 789 FLD014 1 1 641 6

TABLE 2: CONDENSER AND HEAT RECLAIM Condenser Summer Winter Condenser Summer Winter CCD02 1 1 1.8 5.8 190 CL8053 2 2 47 153 1882 CCD03 1 1 2.7 8.7 201 CL8054 1 4 46 150 2019 CCD04 1 1 3.5 12 210 CL8055 2 3 34 112 2323 CH8010 1 1 5.8 19 515 CL8059 1 5 43 140 2403 CH8013 1 1 8.8 29 592 CL8068 1 5 57 187 2475 CH8015 1 1 12 38 641 CL8071 2 3 52 169 2508 CH8020 1 2 12 38 985 CL8081 2 3 69 225 2664 CH8026 1 2 17 57 1063 CL8094 2 4 68 224 3029 CH8029 1 2 23 76 1117 CL8108 2 4 91 299 3338 CH8038 1 3 26 85 1460 CL8118 2 5 85 280 4198 CH8040 2 2 23 75 1625 CL8135 2 5 114 373 4560 CH8044 1 3 34 112 1570 CL8141 2 6 164 553 5292 CH8051 2 2 35 115 1792 CL8162 2 6 218 717 5642 CH8052 1 4 34 112 1875 CLD009 1 1 5.8 19 515 CH8058 2 2 47 153 1882 CLD010 1 1 5.8 19 525 CH8059 1 4 46 150 2019 CLD012 1 1 8.8 29 592 CH8060 2 3 34 112 2323 CLD013 1 1 8.8 29 602 CH8065 1 5 43 140 2403 CLD014 1 1 12 38 641 CH8074 1 5 57 187 2475 CLD015 1 1 12 38 654 CH8078 2 3 52 169 2508 CLD018 1 2 12 38 985 CH8088 2 3 69 225 2664 CLD021 1 2 12 38 1005 CH8104 2 4 68 224 3029 CLD023 1 2 17 57 1063 CH8118 2 4 91 299 3338 CLD026 1 2 17 57 1091 CH8130 2 5 85 280 4198 CLD028 1 2 23 76 1117 CH8147 2 5 114 373 4560 CLD030 1 2 23 76 1159 CH8156 2 6 197 664 5292 CLD035 1 3 26 85 1460 CH8177 2 6 262 860 5642 CLD040 1 3 26 85 1490 CHD010 1 1 5.8 19 515 CLD042 2 2 23 75 1625 CHD012 1 1 5.8 19 525 CLD043 1 3 34 112 1570 CHD013 1 1 8.8 29 592 CLD045 1 3 34 112 1609 CHD014 1 1 8.8 29 602 CLD049 2 2 35 115 1792 CHD015 1 1 12 38 641 CLD050 1 4 34 112 1875 CHD016 1 1 12 38 654 CLD053 2 2 35 115 1781 CHD020 1 2 12 38 985 CLD054 1 4 34 112 1915 CHD024 1 2 12 38 1005 CLD056 2 2 47 153 1882 CHD026 1 2 17 57 1063 CLD057 1 4 46 150 2019 CHD029 1 2 17 57 1091 CLD060 2 2 47 153 1934 CHD030 1 2 23 76 1117 CLD061 1 4 46 150 2071 CHD032 1 2 23 76 1159 CLD063 2 3 34 112 2323 CHD040 1 3 26 85 1460 CLD066 1 5 43 140 2403 CHD044 1 3 26 85 1490 CLD070 1 5 57 187 2475 CHD045 1 3 23 75 1625 CLD075 1 5 57 187 2540 CHD048 1 3 34 112 1570 CLD080 2 3 52 169 2508 CHD049 2 2 34 112 1609 CLD085 2 3 69 225 2664 CHD055 2 2 35 115 1792 CLD090 2 3 69 225 2742 7

Condenser Summer Winter Condenser Summer Winter CHD056 1 4 34 112 1875 CLD099 2 4 68 224 3029 CHD059 2 2 35 115 1781 CLD106 2 4 68 224 3129 CHD060 1 4 34 112 1915 CLD113 2 4 91 299 3338 CHD061 2 2 47 153 1882 CLD120 2 4 91 229 3442 CHD062 1 4 46 150 2019 CLD124 2 5 85 280 4198 CHD063 2 2 47 153 1934 CLD132 2 5 85 280 4298 CHD064 1 4 46 150 2071 CLD142 2 5 114 373 4560 CHD073 2 3 34 112 2323 CLD150 2 5 114 373 4690 CHD074 1 5 43 140 2403 CLD159 2 6 164 553 5292 CHD077 1 5 57 187 2475 CLD170 2 6 218 717 5642 CHD079 1 5 57 187 2540 CLD180 2 6 218 717 5798 CHD089 2 3 52 169 2508 CMD05 1 1 3.3 11 308 CHD092 2 3 69 225 2664 CMD07 1 1 4.9 16 335 CHD096 2 3 69 225 2742 CMD08 1 1 6.5 22 350 CHD110 2 4 68 224 3029 CMD09 1 2 6.3 21 489 CHD118 2 4 68 224 3129 CMD11 1 2 9.5 31 518 CHD123 2 4 91 299 3338 CMD12 1 2 9.5 31 532 CHD127 2 4 91 229 3442 CMD13 1 2 13 42 544 CHD138 2 5 85 280 4198 CMD14 1 2 13 42 566 CHD148 2 5 85 280 4298 CMD18 1 3 14 47 727 CHD153 2 5 114 373 4560 CMD20 1 3 14 47 741 CHD159 2 5 114 373 4690 CMD21 1 3 19 62 767 CHD177 2 6 164 553 5292 CMD23 1 3 19 62 789 CHD184 2 6 218 717 5642 CQD008 1 1 5.8 19 525 CHD191 2 6 218 717 5798 CQD009 1 1 5.8 19 535 C010 1 1 5.8 19 515 CQD010 1 1 8.8 29 602 C011 1 1 5.8 19 525 CQD011 1 1 8.8 29 612 C013 1 1 8.8 29 592 CQD012 1 1 12 38 651 C014 1 1 8.8 29 602 CQD013 1 1 12 38 664 C016 1 1 12 38 641 CQD016 1 2 12 38 1085 C017 1 1 12 38 654 CQD019 1 2 12 38 1025 C020 1 2 12 38 985 CQD021 1 2 17 57 1083 C023 1 2 12 38 1005 CQD022 1 2 17 57 1111 C025 1 2 17 57 1063 CQD023 1 2 23 76 1137 C029 1 2 17 57 1091 CQD024 1 2 23 76 1179 C031 1 2 23 76 1117 CQD031 1 3 26 85 1490 C034 1 2 23 76 1159 CQD034 1 3 26 85 1520 C039 1 3 26 85 1460 CQD035 1 3 34 112 1600 C044 1 3 26 85 1490 CQD036 1 3 34 112 1639 C046 2 2 23 75 1625 CQD041 2 2 35 115 1832 C049 1 3 34 112 1570 CQD042 1 4 34 112 1915 C051 1 3 34 112 1609 CQD044 2 2 35 115 1821 C054 2 2 35 115 1792 CQD045 1 4 34 112 1955 C055 1 4 34 112 1875 CQD046 2 2 47 153 1922 C058 2 2 35 115 1781 CQD047 1 4 46 150 2059 C059 1 4 34 112 1915 CQD048 2 2 47 153 1974 C064 2 2 47 153 1882 CQD049 1 4 46 150 2111 C065 1 4 46 150 2019 CQD057 1 5 43 140 2453 C068 2 2 47 153 1934 CQD058 1 5 57 187 2525 8

Condenser Summer Winter Condenser Summer Winter C069 1 4 46 150 2071 CQD061 1 5 57 187 2590 C070 2 3 34 112 2323 CQD069 2 3 52 169 2568 C073 1 5 43 140 2403 CQD070 2 3 69 225 2724 C079 1 5 57 187 2475 CQD072 2 3 69 225 2800 C085 2 5 57 187 2540 CQD083 2 4 68 224 3109 C088 2 3 52 169 2508 CQD091 2 4 68 224 3209 C095 2 3 69 225 2664 CQD093 2 4 91 299 3418 C101 2 3 69 225 2742 CQD096 2 4 91 299 3522 C112 2 4 68 224 3029 CQD104 2 5 85 280 4298 C119 2 4 68 224 3129 CQD114 2 5 85 280 4398 C129 2 4 91 299 3338 CQD116 2 5 114 373 4660 C137 2 4 91 229 3442 CQD121 2 5 114 373 4790 C141 2 5 85 280 4198 CQD137 2 6 164 553 5412 C149 2 5 85 280 4298 CQD140 2 6 218 717 5762 C162 2 5 114 373 4560 CQD145 2 6 218 717 5918 C171 2 5 114 373 4690 HCD02 1 1 0.6 0.6 190 C178 2 6 164 553 5292 HCD03 1 1 0.9 0.9 201 C194 2 6 218 717 5642 HCD04 1 1 1.2 1.2 210 C205 2 6 218 717 5798 HMD05 1 1 1.1 1.1 308 CL8009 1 1 5.8 19 515 HMD07 1 1 1.6 1.6 335 CL8012 1 1 8.8 29 592 HMD08 1 1 2.1 2.1 350 CL8014 1 1 12 38 641 HMD09 1 2 2.1 2.1 489 CL8018 1 2 12 38 985 HMD11 1 2 3.1 3.1 518 CL8024 1 2 17 57 1063 HMD12 1 2 3.1 3.1 532 CL8027 1 2 23 76 1117 HMD13 1 2 4.3 4.3 544 CL8035 1 3 26 85 1460 HMD14 1 2 4.3 4.3 566 CL8036 2 2 23 75 1625 HMD18 1 3 4.6 4.6 727 CL8041 1 3 34 112 1570 HMD20 1 3 4.6 4.6 741 CL8047 2 2 35 115 1792 HMD21 1 3 6.3 6.3 767 CL8048 1 4 34 112 1875 HMD23 1 3 6.3 6.3 789 9

Condenser Summer Winter Condenser Summer Winter CCR02 1 1 2 6 190 CMR16 1 2 13 42 566 CCR03 1 1 3 9 201 CMR18 1 3 10 33 727 CCR04 1 1 4 12 210 CMR22 1 3 15 48 741 CNW011 1 1 6 19 520 CMR25 1 3 20 66 789 CNW014 1 1 9 29 597 CMR30 2 4 19 62 1064 CNW017 1 1 12 38 648 CMR33 2 4 26 84 1132 CNW021 1 2 12 38 612 CMR36 2 6 20 66 1454 CNW028 1 2 23 76 995 CMR45 2 6 29 96 1482 CNW033 1 2 23 76 1138 CMR49 2 6 39 132 1578 CNW042 1 3 26 85 1475 CVR012L 1 1 6 19 565 CNW050 1 3 34 112 1590 CVR014L 1 1 6 19 575 CNW056 1 4 34 112 1796 CVR016L 1 1 9 29 642 CNW057 2 4 35 115 1900 CVR017L 1 1 9 29 652 CNW066 1 4 46 150 1908 CVR018L 1 1 12 38 691 CNW067 2 4 47 153 2045 CVR019L 1 1 12 38 704 CNW077 1 5 68 230 2361 CVR025L 1 2 12 38 1085 CNW089 1 5 90 298 2507 CVR028L 1 2 12 38 1105 CNW085 2 6 52 170 2468 CVR031L 1 2 17 57 1163 CNW092 1 6 82 276 2768 CVR034L 1 2 17 57 1191 CNW100 2 6 68 224 2703 CVR035L 1 2 23 76 1217 CNW107 1 6 109 359 3003 CVR037L 1 2 23 76 1259 CNW113 2 4 68 224 3079 CVR047L 1 3 26 85 1610 CNW133 2 4 92 300 3390 CVR051L 1 3 26 85 1640 CNW154 2 5 136 460 4248 CVR053L 1 3 34 112 1720 CNW179 2 5 180 596 4625 CVR056L 1 3 34 112 1759 CNW185 2 6 164 552 5242 CVR061L 1 4 34 112 2075 CNW215 2 6 218 718 5716 CVR062L 2 4 35 115 1910 CNR012 1 1 6 19 515 CVR067L 1 4 34 112 2115 CNR014 1 1 6 19 525 CVR068L 2 4 35 115 1992 CNR016 1 1 9 29 592 CVR070L 1 4 46 150 2219 CNR017 1 1 9 29 602 CVR071L 2 4 47 153 2082 CNR018 1 1 12 38 641 CVR074L 1 4 46 150 2271 CNR019 1 1 12 38 654 CVR075L 2 4 47 153 2134 CNR024 1 2 12 38 985 CVR083L 2 6 36 114 2623 CNR027 1 2 12 38 1005 CVR084L 1 5 68 230 2653 CNR032 1 2 17 57 1063 CVR089L 1 5 68 230 2653 CNR035 1 2 17 57 1091 CVR092L 1 5 90 298 2725 CNR036 1 2 23 76 1117 CVR096L 1 5 90 298 2790 CNR039 1 2 23 76 1159 CVR094L 2 6 52 170 2730 CNR048 1 3 26 85 1460 CVR099L 1 6 82 276 3000 CNR052 1 3 26 85 1490 CVR101L 2 6 52 170 2808 CNR054 1 3 34 112 1570 CVR105L 1 6 82 276 3108 CNR058 1 3 34 112 1609 CVR106L 2 6 68 224 2964 10

Condenser Summer Winter Condenser Summer Winter CNR063 1 4 34 112 1875 CVR111L 1 6 109 359 3264 CNR064 2 4 35 115 1792 CVR112L 2 6 68 224 3042 CNR069 1 4 34 112 1915 CVR116L 1 6 109 359 3342 CNR070 2 4 35 115 1781 CVR125L 2 4 68 224 3429 CNR072 1 4 46 150 2019 CVR135L 2 4 68 224 3529 CNR073 2 4 47 153 1934 CVR141L 2 4 92 300 3738 CNR077 1 4 46 150 2071 CVR149L 2 4 92 300 3842 CNR078 2 4 47 153 2071 CVR165L 2 5 136 460 4698 CNR082 2 6 36 114 2323 CVR177L 2 5 136 460 4798 CNR085 1 5 68 230 2338 CVR184L 2 5 180 596 5060 CNR092 1 5 68 230 2403 CVR192L 2 5 180 596 5190 CNR096 1 5 90 298 2475 CVR200L 2 6 164 552 5736 CNR101 1 5 90 298 2540 CVR212L 2 6 164 552 5892 CNR095 2 6 52 170 2430 CVR221L 2 6 218 718 6242 CNR102 1 6 82 276 2730 CVR231L 2 6 218 718 6398 CNR104 2 6 52 170 2508 CVR012 1 1 6 19 565 CNR111 1 6 82 276 2808 CVR014 1 1 6 19 575 CNR109 2 6 68 224 2664 CVR016 1 1 9 29 642 CNR116 1 6 109 359 2964 CVR017 1 1 9 29 652 CNR115 2 6 68 224 2742 CVR018 1 1 12 38 691 CNR121 1 6 109 359 3000 CVR019 1 1 12 38 704 CNR127 2 4 68 224 3029 CVR025 1 2 12 38 1085 CNR139 2 4 68 224 3129 CVR028 1 2 12 38 1105 CNR145 2 4 92 300 3338 CVR031 1 2 17 57 1163 CNR154 2 4 92 300 3442 CVR034 1 2 17 57 1191 CNR171 2 5 136 460 4198 CVR035 1 2 23 76 1217 CNR185 2 5 136 460 4298 CVR037 1 2 23 76 1259 CNR193 2 5 180 596 4560 CVR047 1 3 26 85 1610 CNR202 2 5 180 596 4690 CVR051 1 3 26 85 1640 CNR205 2 6 164 552 5136 CVR053 1 3 34 112 1720 CNR222 2 6 164 552 5292 CVR056 1 3 34 112 1759 CNR231 2 6 218 718 5642 CVR061 1 4 34 112 2075 CNR243 2 6 218 718 5798 CVR062 2 4 35 115 1910 CNX015 1 1 7 24 550 CVR067 1 4 34 112 2115 CNX019 1 1 11 35 600 CVR068 2 4 35 115 1992 CNX021 1 1 15 47 650 CVR070 1 4 46 150 2219 CNX030 1 2 14 46 850 CVR071 2 4 47 153 2082 CNX038 1 2 22 69 900 CVR074 1 4 46 150 2271 CNX043 1 2 29 92 950 CVR075 2 4 47 153 2134 CNX057 1 3 32 103 1300 CVR083 2 6 36 114 2623 CNX064 1 3 43 137 1425 CVR084 1 5 68 230 2653 CNX076 1 4 43 136 1725 CVR089 1 5 68 230 2653 CNX086 1 4 57 182 1900 CVR092 1 5 90 298 2725 11

Condenser Summer Winter Condenser Summer Winter CNX096 1 5 53 170 2150 CVR096 1 5 90 298 2790 CNX108 1 5 71 227 2375 CVR094 2 6 52 170 2730 CNX123 1 6 101 323 2575 CVR099 1 6 82 276 3000 CNX135 1 6 134 430 2850 CVR101 2 6 52 170 2808 CNX144 1 7 117 376 3012 CVR105 1 6 82 276 3108 CNX158 1 7 157 501 3362 CVR106 2 6 68 224 2964 CNX164 1 4 134 429 3450 CVR111 1 6 109 359 3264 CNX181 1 4 179 572 3800 CVR112 2 6 68 224 3042 CNX061 2 4 29 92 1000 CVR116 1 6 109 359 3342 CNX077 2 4 43 138 1600 CVR125 2 4 68 224 3429 CNX087 2 4 58 184 2000 CVR135 2 4 68 224 3529 CNX115 2 6 64 205 2600 CVR141 2 4 92 300 3738 CNX129 2 6 86 274 3000 CVR149 2 4 92 300 3842 CNX154 2 4 85 273 3600 CVR165 2 5 136 460 4698 CNX172 2 4 114 363 4000 CVR177 2 5 136 460 4798 CNX192 2 5 106 340 4500 CVR184 2 5 180 596 5060 CNX215 2 5 142 453 5000 CVR192 2 5 180 596 5190 CNX247 2 6 202 645 5400 CVR200 2 6 164 552 5736 CNX271 2 6 269 860 6000 CVR212 2 6 164 552 5892 CNX288 2 7 235 752 6400 CVR221 2 6 218 718 6242 CNX316 2 7 313 1002 7000 CVR231 2 6 218 718 6398 CNX329 2 8 268 858 7400 CVW011 1 1 6 19 570 CNX362 2 8 358 1145 8000 CVW014 1 1 9 29 647 CLW009 1 1 6 19 515 CVW016 1 1 12 38 698 CLW012 1 1 9 29 592 CVW021 1 2 12 38 1012 CLW014 1 1 12 38 641 CVW028 1 2 23 76 1095 CLW019 1 2 12 38 985 CVW033 1 2 23 76 1238 CLW024 1 2 23 76 1063 CVW042 1 3 26 85 1625 CLW028 1 2 23 76 1117 CVW049 1 3 34 112 1740 CLW036 1 3 26 85 1460 CVW055 1 4 34 112 2100 CLW042 1 3 34 112 1570 CVW056 2 4 35 115 1996 CLW048 1 4 34 112 1875 CVW064 1 4 46 150 2245 CLW049 2 4 35 115 1792 CVW065 2 4 47 153 2108 CLW056 1 4 46 150 2019 CVW070 1 5 68 230 2611 CLW057 2 4 47 153 1882 CVW081 1 5 90 298 2757 CLW066 1 5 68 230 2403 CVW084 2 6 52 170 2768 CLW075 1 5 90 298 2475 CVW090 1 6 82 276 3068 CLW073 2 6 52 170 2508 CVW098 2 6 68 224 3003 CLW079 1 6 82 276 2808 CVW104 1 6 109 359 3303 CLW085 2 6 68 224 2664 CVW112 2 4 68 224 3479 CLW090 1 6 109 359 2964 CVW130 2 4 92 300 3790 CLW097 2 4 68 224 3029 CVW140 2 5 136 460 4748 CLW113 2 4 92 300 3338 CVW163 2 5 180 596 5125 12

Condenser Summer Winter Condenser Summer Winter CLW131 2 5 136 460 4198 CVW167 2 6 164 552 5842 CLW151 2 5 180 596 4560 CVW195 2 6 218 718 6316 CLW158 2 6 164 552 5292 CVW011L 1 1 6 19 570 CLW181 2 6 218 718 5642 CVW014L 1 1 9 29 647 CLR010 1 1 6 19 515 CVW016L 1 1 12 38 698 CLR011 1 1 6 19 525 CVW021L 1 2 12 38 1012 CLR013 1 1 9 29 592 CVW028L 1 2 23 76 1095 CLR014 1 1 9 29 602 CVW033L 1 2 23 76 1238 CLR015 1 1 12 38 641 CVW042L 1 3 26 85 1625 CLR016 1 1 12 38 654 CVW049L 1 3 34 112 1740 CLR021 1 2 12 38 985 CVW055L 1 4 34 112 2100 CLR023 1 2 12 38 1005 CVW056L 2 4 35 115 1996 CLR027 1 2 17 57 1063 CVW064L 1 4 46 150 2245 CLR029 1 2 17 57 1091 CVW065L 2 4 47 153 2108 CLR031 1 2 23 76 1117 CVW070L 1 5 68 230 2611 CLR032 1 2 23 76 1159 CVW081L 1 5 90 298 2757 CLR040 1 3 26 85 1460 CVW084L 2 6 52 170 2768 CLR044 1 3 26 85 1490 CVW090L 1 6 82 276 3068 CLR046 1 3 34 112 1570 CVW098L 2 6 68 224 3003 CLR049 1 3 34 112 1609 CVW104L 1 6 109 359 3303 CLR053 1 4 34 112 1875 CVW112L 2 4 68 224 3479 CLR054 2 4 35 115 1792 CVW130L 2 4 92 300 3790 CLR057 1 4 34 112 1915 CVW140L 2 5 136 460 4748 CLR058 2 4 35 115 1781 CVW163L 2 5 180 596 5125 CLR060 1 4 46 150 2019 CVW167L 2 6 164 552 5842 CLR062 2 4 47 153 1882 CVW195L 2 6 218 718 6316 CLR064 1 4 46 150 2071 CVX015 1 1 7 24 600 CLR065 2 4 47 153 1934 CVX019 1 1 11 35 650 CLR069 2 6 36 114 2323 CVX021 1 1 15 47 700 CLR072 1 5 68 230 2338 CVX031 1 2 14 46 950 CLR077 1 5 68 230 2403 CVX038 1 2 22 69 1000 CLR081 1 5 90 298 2475 CVX042 1 2 29 92 1050 CLR084 1 5 90 298 2540 CVX057 1 3 32 103 1450 CLR080 2 6 52 170 2430 CVX063 1 3 43 137 1575 CLR086 1 6 82 276 2730 CVX076 1 4 43 136 1925 CLR087 2 6 52 170 2508 CVX084 1 4 57 182 2100 CLR093 1 6 82 276 2808 CVX096 1 5 53 170 2400 CLR092 2 6 68 224 2664 CVX106 1 5 71 227 2625 CLR096 1 6 109 359 2964 CVX122 1 6 101 323 2875 CLR097 2 6 68 224 2742 CVX131 1 6 134 430 3150 CLR101 1 6 109 359 3042 CVX142 1 7 117 376 3362 CLR107 2 4 68 224 3029 CVX153 1 7 157 501 3712 CLR117 2 4 68 224 3129 CVX163 1 4 134 429 3850 13

Condenser Summer Winter Condenser Summer Winter CLW131 2 5 136 460 4198 CVW167 2 6 164 552 5842 CLW151 2 5 180 596 4560 CVW195 2 6 218 718 6316 CLW158 2 6 164 552 5292 CVW011L 1 1 6 19 570 CLW181 2 6 218 718 5642 CVW014L 1 1 9 29 647 CLR010 1 1 6 19 515 CVW016L 1 1 12 38 698 CLR011 1 1 6 19 525 CVW021L 1 2 12 38 1012 CLR013 1 1 9 29 592 CVW028L 1 2 23 76 1095 CLR014 1 1 9 29 602 CVW033L 1 2 23 76 1238 CLR015 1 1 12 38 641 CVW042L 1 3 26 85 1625 CLR016 1 1 12 38 654 CVW049L 1 3 34 112 1740 CLR021 1 2 12 38 985 CVW055L 1 4 34 112 2100 CLR023 1 2 12 38 1005 CVW056L 2 4 35 115 1996 CLR027 1 2 17 57 1063 CVW064L 1 4 46 150 2245 CLR029 1 2 17 57 1091 CVW065L 2 4 47 153 2108 CLR031 1 2 23 76 1117 CVW070L 1 5 68 230 2611 CLR032 1 2 23 76 1159 CVW081L 1 5 90 298 2757 CLR040 1 3 26 85 1460 CVW084L 2 6 52 170 2768 CLR044 1 3 26 85 1490 CVW090L 1 6 82 276 3068 CLR046 1 3 34 112 1570 CVW098L 2 6 68 224 3003 CLR049 1 3 34 112 1609 CVW104L 1 6 109 359 3303 CLR053 1 4 34 112 1875 CVW112L 2 4 68 224 3479 CLR054 2 4 35 115 1792 CVW130L 2 4 92 300 3790 CLR057 1 4 34 112 1915 CVW140L 2 5 136 460 4748 CLR058 2 4 35 115 1781 CVW163L 2 5 180 596 5125 CLR060 1 4 46 150 2019 CVW167L 2 6 164 552 5842 CLR062 2 4 47 153 1882 CVW195L 2 6 218 718 6316 CLR064 1 4 46 150 2071 CVX015 1 1 7 24 600 CLR065 2 4 47 153 1934 CVX019 1 1 11 35 650 CLR069 2 6 36 114 2323 CVX021 1 1 15 47 700 CLR072 1 5 68 230 2338 CVX031 1 2 14 46 950 CLR077 1 5 68 230 2403 CVX038 1 2 22 69 1000 CLR081 1 5 90 298 2475 CVX042 1 2 29 92 1050 CLR084 1 5 90 298 2540 CVX057 1 3 32 103 1450 CLR080 2 6 52 170 2430 CVX063 1 3 43 137 1575 CLR086 1 6 82 276 2730 CVX076 1 4 43 136 1925 CLR087 2 6 52 170 2508 CVX084 1 4 57 182 2100 CLR093 1 6 82 276 2808 CVX096 1 5 53 170 2400 CLR092 2 6 68 224 2664 CVX106 1 5 71 227 2625 CLR096 1 6 109 359 2964 CVX122 1 6 101 323 2875 CLR097 2 6 68 224 2742 CVX131 1 6 134 430 3150 CLR101 1 6 109 359 3042 CVX142 1 7 117 376 3362 CLR107 2 4 68 224 3029 CVX153 1 7 157 501 3712 CLR117 2 4 68 224 3129 CVX163 1 4 134 429 3850 14

Condenser Summer Winter Condenser Summer Winter CLR122 2 4 92 300 3338 CVX175 1 4 179 572 4200 CLR130 2 4 92 300 3442 CVX062 2 4 29 92 1100 CLR144 2 5 136 460 4198 CVX077 2 4 43 138 1700 CLR155 2 5 136 460 4298 CVX085 2 4 58 184 2100 CLR161 2 5 180 596 4560 CVX115 2 6 64 205 2750 CLR167 2 5 180 596 4690 CVX127 2 6 86 274 3150 CLR173 2 6 164 552 5292 CVX154 2 4 85 273 3800 CLR186 2 6 164 552 5642 CVX170 2 4 114 363 4200 CLR193 2 6 218 718 5798 CVX192 2 5 106 340 4750 CLR202 2 6 218 718 5798 CVX212 2 5 142 453 5250 CLX013 1 1 7 24 550 CVX245 2 6 202 645 5700 CLX016 1 1 11 35 600 CVX262 2 6 269 860 6300 CLX018 1 1 15 47 650 CVX285 2 7 235 752 6750 CLX026 1 2 14 46 850 CVX306 2 7 313 1002 7350 CLX032 1 2 22 69 900 CVX326 2 8 268 858 7800 CLX036 1 2 29 92 950 CVX350 2 8 358 1145 8400 CLX049 1 3 32 103 1300 CVX015L 1 1 7 24 600 CLX054 1 3 43 137 1425 CVX019L 1 1 11 35 650 CLX064 1 4 43 136 1725 CVX021L 1 1 15 47 700 CLX071 1 4 57 182 1900 CVX031L 1 2 14 46 950 CLX081 1 5 53 170 2150 CVX038L 1 2 22 69 1000 CLX089 1 5 71 227 2375 CVX042L 1 2 29 92 1050 CLX103 1 6 101 323 2575 CVX057L 1 3 32 103 1450 CLX111 1 6 134 430 2850 CVX063L 1 3 43 137 1575 CLX120 1 7 117 376 3012 CVX076L 1 4 43 136 1925 CLX129 1 7 157 501 3362 CVX084L 1 4 57 182 2100 CLX138 1 4 134 429 3450 CVX096L 1 5 53 170 2400 CLX148 1 4 179 572 3800 CVX106L 1 5 71 227 2625 CLX053 2 4 29 92 1000 CVX122L 1 6 101 323 2875 CLX065 2 4 43 138 1600 CVX131L 1 6 134 430 3150 CLX072 2 4 58 184 2000 CVX142L 1 7 117 376 3362 CLX097 2 6 64 205 2600 CVX153L 1 7 157 501 3712 CLX107 2 6 86 274 3000 CVX163L 1 4 134 429 3850 CLX130 2 4 85 273 3600 CVX175L 1 4 179 572 4200 CLX143 2 4 114 363 4000 CVX062L 2 4 29 92 1100 CLX162 2 5 106 340 4500 CVX077L 2 4 43 138 1700 CLX178 2 5 142 453 5000 CVX085L 2 4 58 184 2100 CLX207 2 6 202 645 5400 CVX115L 2 6 64 205 2750 CLX222 2 6 269 860 6000 CVX127L 2 6 86 274 3150 CLX241 2 7 235 752 6400 CVX154L 2 4 85 273 3800 CLX259 2 7 313 1002 7000 CVX170L 2 4 114 363 4200 CLX275 2 8 268 858 7400 CVX192L 2 5 106 340 4750 CLX296 2 8 358 1145 8000 CVX212L 2 5 142 453 5250 15

Condenser Summer Winter Condenser Summer Winter CMR06 1 1 3 11 308 CVX245L 2 6 202 645 5700 CMR07 1 1 5 16 335 CVX262L 2 6 269 860 6300 CMR08 1 1 7 22 350 CVX285L 2 7 235 752 6750 CMR12 1 2 6 21 489 CVX306L 2 7 313 1002 7350 CMR15 1 2 10 31 532 CVX326L 2 8 268 858 7800 CVX350L 2 8 358 1145 8400 16

Fig. #1: Standard Legs 17

18

19

Fig. #2 : Extended Legs 20

Fig #3: 2 fans 21

Fig # 4: 1 fan 22

Table #3 Condenser Fan Alignment Ambient Control Temperature Setting ( F) Temperature Control ------ T1 T2 T3 T4 T5 T6 T7 Fan Motor Single Wide Units M1 M2 M3 M4 M5 M6 Number Double Wide Units M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15 M16 Difference FAN (S) 20 Fan On RUNS 60 Fan Off WITH ANY 40 COM- Difference 10 15 PRESSOR Fan On 55 65 Fan Off 45 50 Difference 10 5 5 Fan On 55 60 70 Fan Off 45 55 65 Difference 10 5 5 5 Fan On 55 60 70 75 Fan Off 45 55 65 70 Difference 10 5 5 5 5 Fan On 55 60 65 70 80 Fan Off 45 55 60 75 75 Difference 10 5 5 5 5 5 Fan On 55 60 65 70 75 80 Fan Off 45 55 60 65 70 75 Difference 5 5 5 5 5 5 5 Fan On 50 55 60 65 70 75 80 Fan Off 45 50 55 60 65 70 75 23

Table #4 Condenser Fan Alignment Pressure Control Pressure Settings (PSIG) (R-22) Pressure Control ------ P1 P2 P3 P4 P5 P6 P7 Fan Motor Single Wide Units M1 M2 M3 M4 M5 M6 Number Double Wide Units M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15 M16 Difference FAN (S) 40 Fan On RUNS 200 Fan Off WITH ANY 160 COM- Difference 40 40 PRESSOR Fan On 200 210 Fan Off 160 170 Difference 40 40 40 Fan On 200 205 215 Fan Off 160 165 175 Difference 40 40 40 40 Fan On 200 205 210 220 Fan Off 160 165 170 180 Difference 40 40 40 40 40 Fan On 200 205 210 215 225 Fan Off 160 165 170 175 185 Difference 40 40 40 40 40 40 Fan On 200 205 210 215 220 225 Fan Off 160 165 170 175 180 185 Difference 40 40 40 40 40 40 40 Fan On 200 205 210 215 220 225 230 Fan Off 160 165 170 175 180 185 190 24

Table #5 Condenser Fan Alignment Pressure Control Pressure Settings (PSIG) (R-404A, R-507) Pressure Control ------ P1 P2 P3 P4 P5 P6 P7 Fan Motor Single Wide Units M1 M2 M3 M4 M5 M6 Number Double Wide Units M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15 M16 Difference FAN (S) 40 Fan On RUNS 240 Fan Off WITH ANY 200 COM- Difference 40 40 PRESSOR Fan On 240 250 Fan Off 200 210 Difference 40 40 40 Fan On 240 250 255 Fan Off 200 210 215 Difference 40 40 40 40 Fan On 240 245 255 260 Fan Off 200 205 215 220 Difference 40 40 40 40 40 Fan On 240 245 255 255 265 Fan Off 200 205 215 215 225 Difference 40 40 40 40 40 40 Fan On 240 245 250 255 260 265 Fan Off 200 205 210 215 220 225 Difference 40 40 40 40 40 40 40 Fan On 240 245 250 255 260 265 270 Fan Off 200 205 210 215 220 225 230 25

Table #6 Condenser Fan Alignment Pressure Control Pressure Settings (PSIG) (R-134) Pressure Control ------ P1 P2 P3 P4 P5 P6 P7 Fan Motor Single Wide Units M1 M2 M3 M4 M5 M6 Number Double Wide Units M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15 M16 Difference FAN (S) 30 Fan On RUNS 125 Fan Off WITH ANY 95 COM- Difference 30 30 PRESSOR Fan On 125 135 Fan Off 95 105 Difference 30 30 30 Fan On 125 130 130 Fan Off 95 100 110 Difference 30 30 30 30 Fan On 125 130 135 145 Fan Off 95 100 105 115 Difference 30 30 30 30 30 Fan On 125 130 135 140 150 Fan Off 95 100 105 110 120 Difference 30 30 30 30 30 30 Fan On 125 130 135 140 145 150 Fan Off 95 100 105 110 115 120 Difference 30 30 30 30 30 30 30 Fan On 125 130 135 140 145 150 155 Fan Off 95 100 105 110 115 120 125 26

Table #7 Condenser Fan Alignment Pressure Control Pressure Settings (PSIG) (R-407) Pressure Control ------ P1 P2 P3 P4 P5 P6 P7 Fan Motor Single Wide Units M1 M2 M3 M4 M5 M6 Number Double Wide Units M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15 M16 Difference FAN (S) 40 Fan On RUNS 220 Fan Off WITH ANY 180 COM- Difference 40 40 PRESSOR Fan On 220 230 Fan Off 180 190 Difference 40 40 40 Fan On 220 225 235 Fan Off 180 185 195 Difference 40 40 40 40 Fan On 220 225 230 240 Fan Off 180 185 190 200 Difference 40 40 40 40 40 Fan On 220 225 230 235 245 Fan Off 180 185 190 195 205 Difference 40 40 40 40 40 40 Fan On 220 225 230 235 240 250 Fan Off 180 185 190 195 200 210 Difference 40 40 40 40 40 40 40 Fan On 220 225 230 235 240 245 250 Fan Off 180 185 190 195 200 205 210 27

28

29

WARRANTIES RefPlus warrants the labeled (serial No.), new Refplus equipment and all parts thereof, to be free from defects in workmanship and material at the time of purchase. Apply to original purchaser only (Not transferable). Under this warranty RefPlus shall be limited to repairing or exchanging any parts, without charge FOB factory or nearest authorized parts wholesalers, which may prove defective to the satisfaction of RefPlus within one year from date of start up, not to exceed eighteen (1 8) months from date of shipment from the factory. The warranties to repair or replace above recited, are the only warranties, express, implied, or statutory, made by RefPlus. No express or implied warranties as to merchantability or fitness for a particular purpose or use. RefPlus neither assumes, nor authorizes any person to assume for it, any other obligation or liability in connection with the sale of said equipment or any part thereof. EXCLUSIONS THIS WARRANTY SHALL NOT APPLY TO LOSS OF PRODUCT OR REFRIGERANT DUE TO FAILURE FOR ANY REASON. RefPlus SHALL NOT BE LIABLE: 1 - For any repairs or replacement by buyer without the written consent of RefPlus, or when the equipment is installed or operated in a manner contrary to the instructions covering installation and service which accompanied such equipment. 2- For any damages, delays, or losses, direct or consequential, caused by defects, nor for damages caused by short or reduced supply of materials, fire, flood, strikes, acts of God, or circumstances beyond its control. 3- When the failure or defect of any part or parts is incidental to ordinary wear, accident, abuse or misuse; or when the serial number of the equipment has been removed, defaced, altered, or tampered with. 4- When this equipment is operated on low or improper voltages. 6- When this equipment is moved to different location other than the original installation. 5- For payment of any removal or installation charges of parts or units. Specifications subject to change without notice. 30