NALCO BT-25 Boiler Internal Treatment



Similar documents
NALCO WT-1000 Closed System Corrosion Inhibitor

Best Practice in Boiler Water Treatment

IMPLEMENTATION OF BOILER BEST PRACTICES

BASIC WATER TREATMENT OF STEAM BOILERS

A Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities

Technical Presentation IMPORTANT TOPICS

Association of Water Technologies Technical Manual

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

Sulfites for Oxygen Control

Inferred ph in Steam Plant Water Chemistry Monitoring

WATER TREATMENT THE NEED FOR CONTROL COMMON IMPURITIES FOUND IN WATER. CALCIUM CARBONATE (CaCO3) CALCIUM SULFATE (CaSO4) MAGNESIUM SULFATE (MgSO4)

THE USE OF OZONE IN COOLING TOWERS

WATER TREATMENT GLOBAL PRODUCT SELECTION GUIDE

The National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio

2014 Service Technician Training Program Closed Loop Systems

Boiler Chemistry Management Using Coordinated Approach of Chemicals, Membranes and Online Monitoring

Boiler Blowdown. Boiler Blowdown Benefits. Best Operating Practices for Boiler Blowdown

Dispelling the Myths of Heat Transfer Fluids. Kevin Connor The Dow Chemical Company

Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower

Boiler Blowdown Analysis In An Industrial Boiler

SUGAR MILL BOILER CYCLE CHEMISTRY: AN UPDATE ON BEST PRACTICES DAVID RODMAN. Nalco Australia Pty Ltd, Townsville

Industrial Water Reuse and Wastewater Minimization

DEGASSED CATION CONDUCTIVITY MEASUREMENT

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9

Guidelines for Selecting and Maintaining Glycol Based Heat Transfer Fluids

Best Practices: The Engineering Approach for Industrial Boilers Natalie R. Blake, ONDEO Nalco

CONVERTING A CLOSED-LOOP WATER SYSTEM TO A GLYCOL SYSTEM

High-Pressure Steam Cycle and Boiler Water Treatment

steam centre of excellence Steam Boiler System Optimization

IGEMA BOILER LEVEL & TDS CONTROLS

World Class Water Chemistry By Accident? BRO Chemistry Session 8/5/2014

Hydrogen Exchange Resin. Steam Purity Analysis

Hydrogen Sulfide in Petroleum. Mike Nicholson/Tim O BrienO Baker Petrolite Corporation

Scale and Deposit Formation in Steam Assisted Gravity Drainage (SAGD) Facilities

Iron and Manganese BACTERIA AND IRON AND MANGANESE

THE PHOSPHATE METHOD FOR PRODUCING QUALITY DRINKING WATER!

Some Criteria for Choosing a Steam Boiler for a Microbrewery

Industry Development Manager. Thomas Lu,

Design of Purified Water and Water For Injection Systems. Hugh Hodkinson Engineers Ireland Chemical & Process Division

Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources

The Use of Phosphates For Potable Water Treatment

C. Provide temporary water treatment for chilled, hot and condenser water until facility has final connections.

AdBlue. Technical Leaflet

TABLE OF CONTENT

WISCONSIN WASTEWATER OPERATORS ASSOCIATION

Chapter 2.2: Boilers

Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation

Water Softening for Hardness Removal. Hardness in Water. Methods of Removing Hardness 5/1/15. WTRG18 Water Softening and Hardness

WATER CHEMISTRY AND POOL WATER BALANCE

Conductivity and TDS Meters

The Impact of Thermal Stability on the Performance of Polymeric Dispersants for Boiler Water Systems

RO / NF Cleaning Guidelines

Trace Dissolved Oxygen Sensor

4.0 EXPERIMENT ON DETERMINATION OF CHLORIDES

Common Problems with Online Water Quality Analyzers. Greg Macy Director AquatiPro LLC

NON-HAZARDOUS CHEMICAL TREATMENTS FOR HEATING AND COOLING SYSTEMS

Steam Generation Efficiency Module Blowdown Losses Section

Delo XLI Corrosion Inhibitor

Hardness ions also interfere with many chemical processes such as chemical compounding and aqueous cleaners.

RO Reverse Osmosis equipments

NORKOOL Industrial Coolants

1. Inspection and monitoring... 3

Environmental Water Testing: Surface Water, Groundwater, Hard Water, Wastewater, & Seawater

EASY-TO-USE TEST KITS - BOILER & COOLING WATER

Technical Information. High-performance Ultra Low Viscous Secondary Refrigerants for Applications down to -50 C TYFOXIT F15-F50.

Corrosivity of Water Supplies

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to Nonvolatile TOC content < 1.0 ppm

WATER TABLE WINNERS!

The control of corrosive conditions caused by concentration of low-volatility solutes in boilers and steam generators

Domestic Chemical Water Treatment Manufacturers Association

Pure Water. Isn t Hard to Find

Product Bulletin INTEROX HYDROGEN PEROXIDE

CYCLE CHEMISTRY COMMISSIONING

Subject: Technical Letter 22 April 1977 Removal of Water Supply Contaminants -- Copper and Zinc

D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:

Troubleshooting Your RO

ROSS Technology Removal of Oil, Solids and Scale Formers

Recover Heat from Boiler Blowdown Water

ALS TRIBOLOGY Engine Coolant Reference Guide

Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank

Filtering Samples to On-Line Process Analyzers. Guidelines for Proper Filtration and Delivery of Samples to On-Line Process Analyzers

WASTE WATER TREATMENT SYSTEM (OPERATING MANUALS )

FLASH TANK ECONOMIZER PRODUCT GUIDE

Enhanced Hydrocarbon Recovery Via Proven & Safe Chemical Tank Cleaning

Metal Ion + EDTA Metal EDTA Complex

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

SARKOSYL O, an N-acyl sarcosine, is a corrosion inhibitor for lubricating oils, greases O R C N CH COOH CH 2 3

ACUSOL 810A Detergent Grade Rheology Modifier and Stabilizer

Drinking Water Problems: Corrosion

5.0 EXPERIMENT ON DETERMINATION OF TOTAL HARDNESS

Extran detergents the perfect solution for cleaning your laboratory utensils

Technical Training Guide Turbine Oil Condition Monitoring

Background. 179 million gallons saved for make-up water

Boiler Preparation, Start-Up and Shutdown

Water Treatment & Purification Chemicals

WARNING: IMPROPER SERVICING AND START-UP OF THIS EQUIPMENT MAY CREATE A POTENTIAL HAZARD TO EQUIPMENT AND TO OPERATORS OR PERSONS IN THE BUILDING.

8 Chemicals from water treatment and distribution

Dissolved Oxygen Sensors

Transcription:

PRODUCT NAME NALCO BT-25 Boiler Internal Treatment PRODUCT DESCRIPTION AND APPLICATION NALCO BT-25 is an innovative program that combines the use of polyphosphate and the most advanced synthetic organic polymer with new TRASAR Technology plus state-of-the-art diagnostic, monitoring, feed, and control equipment. NALCO BT-25 is designed for maximum scale inhibition for boilers operating at or below 600 psig (41 barg) with feedwater hardness greater than or equal to 0.02 ppm. The product can be used as a residual phosphate or phosphate-ph control program for boiler systems running on softened, RO, or demineralised water. PHYSICAL & CHEMICAL PROPERTIES These properties are typical. Refer to the Material Safety Data Sheet (MSDS), SECTION 9, for the most current data. Form Liquid Appearance Clear Yellow Odour None Specific Gravity @ 20 C (68 F) 1.0796 g/cm 3 (9.0097 lb/gallon) Relative Density @ 20 C (68 F) 1.0796 Solubility in Water Complete ph (100%) 13.6 Freezing Point -8.3 C (17.1 F) Freeze-Thaw Recovery Incomplete, Protect from Freezing Viscosity @ 20 C (68 F) 1.488 cst REGULATORY APPROVALS Refer to the Material Safety Data Sheet (MSDS), SECTION 15 for the most recent information on approvals. NALCO BT-25 is approved by the National Sanitation Foundation (NSF International) for treating boilers or steam lines (G6/W1) where steam produced may contact edible products. NALCO BT-25 is in full compliance with the applicable Federal laws (FDA) and regulations pertaining to food additives and may be used for applications covered under 21 CFR 173.310, Boiler Water Additives. 08-07-09/JLM ; BT-25 CPP-DPL 1

MATERIALS OF COMPATIBILITY Compatible Not Compatible Metal Stainless steel Aluminium, brass, copper, zinc, light alloys Container materials Polyethylene, polypropylene, PVC Elastomers Nylon, Viton, Buna-N, neoprene, EPDM, butyl rubber, Teflon (PTFE) DOSAGE AND FEEDING The feedwater dosage of NALCO BT-25 will vary depending on average feedwater total acid hardness and the required residual phosphate level. For your specific application, your local Nalco sales engineer will make the appropriate feedrate recommendations. Overfeed of NALCO BT-25 will result in excessive treatment costs and may result in boiler carryover. Underfeed of NALCO BT-25 will result in higher maintenance costs and potential failures. DOSAGE REQUIREMENTS NALCO BT-25 can be used for scale control as a phosphate residual program (Calculation 1) or for corrosion control as a coordinated phosphate-ph program (Calculation 2). For both these applications, the polymer dispersant in NALCO BT-25 will control particulates, sludge, and iron. CALCULATION 1 - PHOSPHATE RESIDUAL NALCO BT-25 dosage will vary depending on the feedwater calcium hardness and the desired boiler water phosphate residual. Calcium Factor = 16 ppm NALCO BT-25 per ppm feedwater calcium hardness (as CaCO3). Phosphate Factor = 25 ppm NALCO BT-25 per ppm phosphate residual (as PO4). Determine Boiler Pressure Feedwater Calcium Hardness Number of cycles Desired Boiler Water Phosphate Residual Calculate the daily NALCO BT-25 dosage by: Step 1: Feedwater calcium hardness x calcium factor = ppm NALCO BT-25 for calcium control Step 2: Desired Boiler Water Phosphate Residual residual x phosphate factor =ppm NALCO BT-25 for phosphate 08-07-09/JLM ; BT-25 CPP-DPL 2

Number of Cycles Step 3: ppm NALCO BT-25 for calcium control (Step 1) + ppm NALCO BT-25 for phosphate residual (Step 2) = total ppm NALCO BT-25 in feedwater EXAMPLE: Boiler Pressure 20 bar Feedwater Calcium Hardness 0.5 ppm Number of Cycles 20 Desired Boiler Water Phosphate Residual 30 ppm 1. ppm NALCO BT-25 for calcium control = 0.5 ppm x 16 = 8 ppm NALCO BT-25 2. ppm NALCO BT-25 for phosphate residual = (30/20)x 25 = 37.5 ppm NALCO BT-25 3. total ppm NALCO BT-25 in feedwater = 8 + 37.5 = 35.5 ppm NALCO BT-25 CALCULATION 2 - COORDINATED PHOSPHATE - ph NALCO BT-25 is a highly alkaline phosphate product with a Na/PO4 ratio of 3.1:1. The dosage requirements can be determined based on required phosphate and ph of the boiler water. (See Figure 1). 08-07-09/JLM ; BT-25 CPP-DPL 3

Phosphate Step 1 Desired Boiler Water Phosphate x 25 = Concentration Ratio ppm NALCO BT-25 to feedwater EXAMPLE: Boiler Pressure 20 bar Number of cycles 50 Boiler Water Phosphate 15-25 ppm Boiler Water ph 10.2 Desired Boiler Water ph 9.8-10.2 (20 ppm /50) x 25 = 10 ppm NALCO BT-25 to feedwater If you are using the product to handle not only feedwater hardness and/or phosphate residual, but also feedwater iron, then the dosage based on above calculations 1 and/or 2 is more than enough to handle the iron. No additional product is required to increase your iron transport through the boiler. Practically speaking, there should only be 15% to 20% Fe transport through the boiler. Increasing your dosage with the goal to increase your Fe transport may cause preboiler & boiler corrosion. The Total Fe & Fe(II) test may be used to verify if active preboiler & boiler corrosion is taking place. 08-07-09/JLM ; BT-25 CPP-DPL 4

To verify that enough NALCO BT-25 is dosed for hardness control, the product dosing may be monitored in the feedwater, either by on-line TRASAR or by grab-sample tests with the hand-held TRASAR unit. To verify that phosphate levels in the boiler are in the correct range, phosphate tests may be run on grab samples from the blow-down. High dosages may cause mechanical carryover. Check for carryover by measuring conductivity and product by TRASAR in condensed steam samples. Maximum TRASAR dosage is 2000 ppm in the boiler water. For TRASAR monitoring and control in the feedwater, the minimum recommended product dosage is 10 ppm. If lower dosages are used TRASAR monitoring and control can be applied on the boiler water. TRASAR #3, Product Factor 100.0, Calibration Solution 460-S0980.75 Concentrations of NALCO BT-25 in excess of 1000 ppm can impart a green colour to the boiler water. The green color will not affect program performance. PRODUCT FEEDING AND PROGRAM COMPATIBILITY NALCO BT-25 should be fed via a closed feed system. A closed feed system is defined as a system in which fluid is moved from a closed storage vessel into a treated media without exposure to the atmosphere, except through normal venting or pressure relief devices. NALCO BT-25 must be fed continuously or fed using tight deadband control(on/off) with TRASAR. Any interruption in feed can result in scale formation or corrosion problems in the boiler and possible tube failure. NALCO BT-25 should be fed neat for product applications exceeding 2.0 LPD (0.5 GPD). Where dilution is used, cooled condensate less than 32 o C (90 o F ) or softened make-up is required as a diluent. Copper and copper alloys are not compatible with neat NALCO BT-25. Prior to proposing NALCO BT-25 ensure that no copper or copper alloys will come in contact with the neat product. NALCO BT-25 should not generally be mixed with other chemicals either neat or in diluted form. Separation or inactivation of the product may result. If NALCO BT-25 is to be mixed with neutralizing amines in a solution (day) tank, use only demineralized quality water or cooled condensate for dilution. The concentration of amine or NALCO BT-25 should not exceed 1% by weight. Ensure complete mixing to ensure homogeneity. The tank should be covered to minimize odors and amine loss. NALCO BT-25 must not be fed prior to a deaerator. If products containing polymers are fed to the storage section of a deaerator, they can reduce the activity of the catalyst in systems using sulfite as oxygen scavenger. The NALCO BT-25 program must be supplemented with the feed of an oxygen scavenger. At the point of injection, the dissolved oxygen in the feedwater should be as low as possible but not more than 100 ppb. Oxygen levels greater than 100 ppb will result in a reduction of polymer dispersant in the boiler and decreased boiler water hardness transport. 08-07-09/JLM ; BT-25 CPP-DPL 5

NALCO BT-25 must be fed downstream of any attemperation water takeoffs. Release of chip scale is possible when changing treatment chemistries in boilers with heavy scale and deposit. Release of chip scale may cause blockage in bent boiler tubes or blowdown lines. Boiler inspections and deposit analyses should be reviewed whenever a change in boiler water chemistry is considered and the need for boiler cleaning should be assessed. Although the appearance of boilers using a polymer dispersant may improve over time, the use of a dispersant is not a substitute for off-line chemical cleaning. Rapid removal of heavy deposits in operational boilers should never be attempted. Feed Point Location It is recommended to feed NALCO BT-25 to the feedwater line. If the product is dosed too close to the dosing point of sulfite, it can reduce the activity of the oxygen scavenger. Moreover NALCO BT-25 must be fed downstream of any attemperation water takeoffs. Feed point location is also determined by TRASAR utilisation. TRASAR Utilization To gain full advantage of the inert tracer, NALCO BT-25 should be fed to the feedwater line before the steam drum and a suitable sample point should be installed downstream of this injection point. This allows for accurate measurement and control of feedwater dosage and the calculation of boiler cycles of concentration. In many applications, installing a product injection quill near the economizer outlet and then locating a sample point about 12 feedwater pipe diameters downstream from the injection quill will yield the best results. This allows for good mixing between the product and feedwater before the sample point but will not result in a long lag between the time a product dosage change is made and the time the dosage change becomes apparent at the sample point. A sample point for the final feedwater is not only desirable for TRASAR applications but is also valuable for monitoring corrosion in the feedwater system and for determining the purity and chemistry of the final boiler feedwater. The arrangement described above is not possible for many boiler designs and there are numerous other factors to be considered when automating boiler chemical feed, so Equipment Solutions should be consulted whenever a boiler automation package is being considered. TESTING AND CONTROL Prior to starting feed of any traced product to a boiler system, a background fluorescence analysis should be performed on those waters that will be monitored by TRASAR (boiler feedwater and blowdown). This will account for any natural fluorescence of the waters. Samples should be submitted to the Leiden analytical lab under test code "TRA" while mentioning the product number 22325. The result provided by the lab is account specific. It is entered as the "TRA VAL" on both the on-line and hand-held fluorometers. This product contains inert TRASAR #3 and can be directly monitored in the 10 to 2000 ppm range by all TRASAR fluorometers. Measurements made outside this range may be inaccurate and could result in poor control and performance. Product Lifecycle Marketing should be consulted for TRASAR measurements outside this range. If TRASAR #3 is measured in a water sample below ph 8, the measured fluorescence value can be low. This should not be a problem for most boiler water samples; but during carryover studies, condensate samples may need ph adjustment. A small amount of dilute caustic can be used to adjust the sample ph to above 8. In dilute solution, TRASAR #3 is susceptible to decomposition by light, particularly sunlight, so if samples are retained for more than 8 hours, they should be kept in amber bottles or protected from exposure to light. Alternatively, samples taken in clear bottles can be wrapped with aluminum foil, or stored in a cardboard box to minimize exposure. 08-07-09/JLM ; BT-25 CPP-DPL 6

Separate analysis of both the inert TRASAR and the phosphate level can be used to study phosphate deposition in a system. Based on TRASAR readings and the known product factor (PF = 100) the product level in the boiler can be determined as ppm of 22325. Levels of total phosphate should be 25 times lower than the level of NALCO BT-25 based on TRASAR. If total phosphate levels are considerably lower than this theoretical value, deposition of phosphates in the system can be expected. Phosphate deposition measurement is an excellent tool for identifying and solving problems in a boiler system. Although the corrosion potential of NALCO BT-25 is low compared to all-polymer treatment, the polymer present in NALCO BT-25 may cause corrosion and iron pickup in the feedwater system if heavily overfed. This can be studied using the Fe(II) colorimetric test with a DR2000/DR2010/DR890 spectrophotometer (methods AP-022 and AP-103). A final feedwater sample point after all chemical addition and after all preboiler equipment such as economizers is desirable for this testing. Fe(II) should be measured without product feed at this sample point and then with product feed to determine the amount of iron pickup caused by the polymer. Fe(II) pickup changes in proportion to product feed and the Fe(II) concentration responds very rapidly to changes in dosage, so testing time is short. For boilers operating at less than 20 bar (300 psig), the Fe(II) value with no polymer feed should be 50 ppb or less and the increase in Fe(II) concentration caused by polymer feed (iron pickup) should be less than 50 ppb. Obtaining this level of pickup may require feeding polymer after all preheaters and economizers. Fe(II) values without polymer feed greater than 100 ppb or iron pick up values greater than 100 ppb are excessive and may indicate an active corrosion problem in the system. TABLE 1 Parameters Range Test Method Nalco Test Kit Product by TRASAR #3 10 ppm to 2000 ppm TRASAR 8000 Part # 100-TR0000.88 Handheld Product by TRASAR #3 10 ppm to 2000 ppm NexGuard probe Part # 081-PR2120.88 Fe(II) AP-022, AP-103 DR2000/2010/890 Phosphate (PO4) 1 to 25 ppm AP-029 DR2000/2010/890 TRASAR #3 Background Fluorescence N/A TRA "22325" N/A ROI CRITICAL SUCCESS FACTORS There are several significant advantages of this new phosphate/ polymer program over other phosphate/polymer programs. They are as follows: Improved performance during hardness upsets. Improved thermal stability of polymer over other acrylic acid-based polymer treatments. Use of new FDA approved tracer, which can be detected by state-of-the-art equipment. An easier detection of phosphate deposition by comparing fluorescence readings with PO4 readings. Use of polyphosphate in stead of orthophosphate used in some older products, thus preventing calcium phosphate scaling in the feedwater line Use of sodium salts instead of potassium salts used in some older products, thus reducing the risk of corrosion. 08-07-09/JLM ; BT-25 CPP-DPL 7

In some applications, there are advantages of this new phosphate/ polymer program over all-polymer programs. They are as follows: At high silica levels and high alkalinity in the boiler water, all-polymer product dosing needs to be increased. Under such conditions all-polymer programs may be less economic. For NALCO BT- 25 the dosing does not need to be increased at higher silica or alkalinity values. NALCO BT-25 provides alkalinity, so that no separate source of alkalinity will be needed for lowalkalinity feedwater (f.ex. RO water) NALCO BT-25 provides phosphate, which is desired or required by some of our customers There are several significant advantages of this new phosphate/ polymer program over traditional phosphate programs. They are as follows: Cleaner boiler, due to polymer dispersant. Better transport of iron and sludge due to polymer dispersant Use of new FDA approved tracer, which can be detected by state-of-the-art equipment. An easier Detection of phosphate deposition by comparing fluorescence readings with PO4 readings. ENVIRONMENTAL AND TOXICITY DATA Refer to the Material Safety Data Sheet (MSDS), SECTIONS 11 and 12, for all aquatic and mammalian information. SAFETY AND HANDLING Refer to the Material Safety Data Sheet (MSDS), SECTIONS 3 and 8, for the most current data. STORAGE NALCO BT-25 should be stored in a location where the product temperature can be kept in a range between 0 C (32 F) and 54 C (130 F). For NALCO BT-25, the recommended in-plant storage limit is 1 year. Refer to the Material Safety Data Sheet (MSDS), SECTION 7, for the most current data. REMARKS If you need assistance or more information on this product, please call your nearest Nalco Representative. For more news about Nalco Company, visit our website at www.nalco.com. For Medical and Transportation Emergencies involving Nalco products, please see the Material Safety Data Sheet for the phone number. ADDITIONAL INFORMATION TRASAR, NALCO and the Logo are registered trademarks of Nalco Company (2-24-2009) Latin America, Europe and Pacific should consult your local EH&S representative. 08-07-09/JLM ; BT-25 CPP-DPL 8