ANCHOR BOLTS FOR NUCLEAR POWER PLANT APPLICATIONS



Similar documents
HUS-V Screw anchor. HUS-V Screw anchor. Basic loading data (for a single anchor) Mean ultimate resistance

Hilti HIT-HY 150 MAX with rebar

HSL-3 Heavy duty anchor carbon steel. Anchor Fastening Technology Manual HSL-3. Heavy duty anchor. Version /

INSTRUCTIONS FOR USE

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI

HUS-A 6 / HUS-H 6 / HUS-I 6 / HUS-P 6 Screw anchor in precast prestressed hollow core slabs

Detailing of Reinforcment in Concrete Structures

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,

PPM High-Strength Anchor Bolt

HUS-HR, CR Screw anchor, stainless steel

Design and Construction of Cantilevered Reinforced Concrete Structures

HPM Rebar Anchor Bolt. For bolted connections. Technical Manual. European Technical Approval ETA-02/0006. Version: Peikko Group 01/2015

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

HUS-H Screw Anchor. Technical data. Seismic design data. HUS-H Carbon steel screw anchor. HUS-H diameter 8, 10, 14. Seismic design data

Page 1 of Sven Alexander Last revised SB-Produksjon STATICAL CALCULATIONS FOR BCC 250

Hilti HIT-HY 200 with rebar

ICC-ES Evaluation Report

Olkiluoto 3 Project. AREVA Suppliers Day Warsaw October 4, 2011

HUS-HR Stainless steel Concrete Screw A CE conformity. Corrosion resistance. European Technical Approval

Technical Application Document. Hilti HIT-RE 500-SD

HVU with HAS/HAS-E rod adhesive anchor

Numerical modelling of shear connection between concrete slab and sheeting deck

European Technical Assessment ETA-10/0153 of 10/06/2015

EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS

Connection Solutions

Europeiskt Tekniskt Godkännande European Technical Approval

Fero Angle Support Technology TECHNICAL REPORT. Yasser Korany, Ph.D., P.Eng. Mohammed Nazief

TZ WEDGE ANCHOR FOR CRACKED AND UNCRACKED CONCRETE

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Ultrasonic Technique and Device for Residual Stress Measurement

Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor

Concrete Design Manual

Embedded Parts Introduction - Anchors

FLOORS REINFORCEMENT Shear Stud Connector for steel- concrete composite structures cold applied by pins

Chapter 5 Bridge Deck Slabs. Bridge Engineering 1

Submittal Information

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

NUCLEAR POWER OVERALL GOOD FOR THE SOCIETY Finnish German Energy Day, 7th November 2012

HUS-HR, CR Screw anchor, stainless steel

Olkiluoto 3 Project June 2010

Wisconsin Building Products Evaluation

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: No.: SE-...

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta

Steel Door Frame Installation in Steel Stud Construction

Structural Integrity Analysis

Hardened Concrete. Lecture No. 14

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA MECHANICAL PRINCIPLES OUTCOME 2 ENGINEERING COMPONENTS TUTORIAL 1 STRUCTURAL MEMBERS

Design MEMO 60 Reinforcement design for TSS 102

Operations and Instruction Manual Might Swivel - Part # Concrete and Steel Anchorage Connector ANSI Z ,000 lbs / 44kn

DESIGN OF SLABS. Department of Structures and Materials Engineering Faculty of Civil and Environmental Engineering University Tun Hussein Onn Malaysia

Design MEMO 54a Reinforcement design for RVK 41

Why HARDOX in tipping trailers?

European Technical Approval ETA-09/0169

European Technical Approval ETA-10/0153

A World Class Manufacturer of Induction Bends

Technical handbook Panel Anchoring System

LOAD-CARRYING CAPACITY OF AXIALLY LOADED RODS GLUED-IN PERPENDICULAR TO THE GRAIN

Design Manual to BS8110

European Technical Assessment. ETA-02/0020 of 22 September English translation prepared by DIBt - Original version in German language

Diameter. Swift Lift Round Recess Plug. Note: The diameter of the narrow recess plug is the same as the diameter of the round recess plug.

AREVA, an unparalleled experience in building nuclear reactors

Hilti HIT-V and HAS Threaded Rod and Hilti HIT-Z Anchor Rod

Concrete structures for nuclear facilities

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION

Cover. When to Specify Intermediate Precast Concrete Shear Walls Rev 4. White Paper WP004

Eurocode 4: Design of composite steel and concrete structures

PERFORMANCE OF SLABS REINFORCED BY PEIKKO PSB STUDS

Building New Generation Nuclear Plants Worldwide : AREVA's Experience

European Technical Approval ETA-12/0500

Conceptual Design of Buildings (Course unit code 1C2)

(English language translation, the original version is in French language) Powers Throughbolt PTB-XL-ETA7-PRO 01/02/ /01/2018.

REPAIR AND STRENGTHENING OF HISTORICAL CONCRETE BRIDGE OVER VENTA RIVER IN LATVIA

Structural Failures Cost Lives and Time

NATIONAL INSTITUTE OF BIOLOGICALS

English translation prepared by DIBt Original version in German language

B.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

METHOD OF STATEMENT FOR STATIC LOADING TEST

European Technical Approval ETA-09/0040

SERIES NG 1800 STRUCTURAL STEELWORK

(English language translation, the original version is in Czech language) DEWALT PTB-PRO. DeWalt Black-&-Decker Str Idstein Germany

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued November 1, Legacy report on the 1997 Uniform Building Code

Optimum proportions for the design of suspension bridge

Eurooppalainen tekninen hyväksyntä ETA 08/0173 European Technical Approval. Sormat S KA kiila ankkurit Sormat through bolt S KA

Structural welding is a process by which the parts that are to be connected are heated and

Swiss media visit to Olkiluoto August 15, 2014

English Version. Eurocode 2: Design of concrete structures - Part 4: Design of fastenings for use in concrete

DESIGN PROCEDURE JOINT CONFIGURATION

3M Mobile SkyWalk Series Horizontal Lifeline Product Return Form

STANDARD SPECIFICATIONS SECTION METAL FABRICATIONS

1.2 Advantages and Types of Prestressing

Guide to the Concrete Capacity Design (CCD) Method Embedment Design Examples

(English language translation, the original version is in French language) Injection system Hilti HIT-HY 150 MAX

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Eurooppalainen tekninen hyväksyntä ETA 01/0003. Sormat Oy Harjutie 5 FIN Rusko. Sormat Oy Harjutie 5

Removable Aluminium posts

Transcription:

ANCHOR BOLTS FOR NUCLEAR POWER PLANT APPLICATIONS EXPERIENCE FROM DESIGN AND CONSTRUCTION OF OLKILUOTO UNITS 2015-11-03 Kukkola Timo

2

OL1 AND OL2 CROSS-SECTION 3

OL1 AND OL2 OL1 and OL2 continuous improvement through modernization projects and plant modifications. 2018 renewal of operating licence. 4

OL1 AND OL2 ANCHOR PLATES DESIGN Codes: -Concrete code of Finland 1967 -Steelcode of Finland1958 and St BK-NI 1970 Method: -Källersjö&Trepp -steelplate thickness (Fe37B, allowable stress 137MPa) is designed according to normal steelcode allowable stress methods assuming symmetric and unsymmetric load -anchor bolts are either smooth or reinforcement bars, anchoring lenghts are taken from concrete code -load excentric assumed -load combination (shear, tension) has been taken account, see next page 5

OL1 AND OL2 COMBINATION RULES As an example: -P2 is tensile force, max 2Mp -Rx and Ry are shearforce components, also max 2Mp 6

OL1 AND OL2 MATERIAL Anchor plates -thickness typically 15-50mm and depends on chosen anchors c/c -ultrasonic testing Anchor bolts: -either smooth or weldable reinforcement bars -allowable stress 220MPa Concrete material minimum K25 Every anchorplate has its own number and coated also from side surfaces. 7

OL1 AND OL2 FOUR STANDARD TYPE ANCHOR PLATES Type A: -size 300mm, height n*150mm -anchors c/c 150 length 300mm, welded Type B: -size 300mm, height n*250mm -anchors c/c 250 length 300mm, welded Type C: -size 300mm, height n*300mm -anchors c/c 300 length 300mm, welded Type D: -size 300*300-4 anchors, length 300mm, welded 8

OL1 AND OL2 9

OL1 AND OL2 OTHER ANCHOR PLATES Typically materials and calculation methods are not changing: -Plate size is changing -Anchor length is changing Special anchor plates differs a lot: -examble LOCA giljotine break anti whip strain anchor plates 10

11

OL1 AND OL2 ANCHORPLATES 12

OL1 AND OL2 DETALJER Reinforcement anchorbars ribs have been grinded in welding area 13

OL1 AND OL2 POSTINSTALLED ANCHOR PLATES Later on post installed anchor plates has been used. Some problems has been found if postinstalled anchors has been used for pipe fixing (dynamic forces) or crane fixing. In that kind of locations in-service inspection is needed. It is allowed to use post-installed anchors according to TVO rules. 14

OL3 15

OL3 OL3 construction works completed and installation works on the final stages, I&C engineering proceeding 16

OL3 ANCHOR PLATES 120 000 Embedded anchor plates (AP) with headed stud anchors, total number of approximately over 100 000 in Nuclear Island (AREVA) and 10 000 in Turbine Island (Siemens). Several manufactures of APs: Peikko, Anstar, Barlage Types of embedded anchor bolts: Nelson, KÖCO Basic line has been to limit the use of post installed anchors Post-Installed Anchor Plates (PIAP) -Post-installed anchors: Hilti, Liebig, Fischer 17

OL3 ANCHOR PLATES Traceability: -identification number, manufacturing number, type Surface treatment: -sandblasting, coating, sides and also partly backside according to specification 18

OL3 ANCHOR BOLT, DESIGN CODES NI Design according to European Technical Approvals (Nelson, KÖCO) and ETAG 001, Annex C, 3 rd Amendment August 2010. CEN TS has been applied in certain individual cases. However, ETAG has been valid from the beginning of the project and fulfillment of ETAG, as OL3 valid code, has been generally checked. 19

OL3, ANCHOR DESIGN FLOW Mostly, the design has been performed by using catalogues prepared by civil experts of AREVA and approved by TVO and STUK. The catalogues have been made by using conservative parameters and assumptions. The designers from different disciplines (piping, HVAC, electricity ) have chosen suitable AP (size, load capacity) by using catalogue. Also the utilization ratio have been checked. However, the catalogues are not always applicable and in many cases they are too conservative. Therefore in special cases, a more detailed calculation has been performed by civil engineers (Single Validation). At the end of construction phase, the utilizations are checked by civil engineers, considering the final loads as well as the vicinity influence of afterwards installed PIAPs and openings (this final verification of anchorages work is now ongoing). 20

ANCHOR PLATES 21

ANCHOR PLATES 22

ANCHOR PLATES 23

OL3 ANCHOR BOLTS SPECIAL CASE: SITE TEST Small steel angles L 100 x 75 x 8-150 have been used in OL3 for fastening of door frames. It has been noticed that ETAG is not directly applicable for calculation of capacity of these angles. Following has been made: the capacity was calculated using approach based on engineering judgement, applying ETAG. The method is not fully covered by current valid codes, standards or technical approvals for validation of the calculated capacity, a site test was performed six angles in real structure were tensioned until maximum force of 25 kn (determined by calculation), taking deformation measurements in each 2.5 kn steps deformation measurement results were within the limits and no cracks were observed above-described calculated capacity (< < 25 kn) has been accepted for these certain door frames in OL3, based on the test 24

OLKILUOTO 3 ANCHOR BOLTS SPECIAL CASE: SITE TEST 25

OL3 ANCHOR BOLTS In OL3, a conservative approach has been chosen in the design of embedded anchor plates with headed studs and post-installed anchors plates. The as-built verification considering the final loads as well as the vicinity influence of afterwards installed PIAPs and core drilling openings is ongoing. The capacity exceeding is not foreseen but the work is challenging due to high amount of the plates. It has been also noted that the codes are very conservative in some cases when considering the real structures in OL3. For example, it is difficult to see pry-out as governing failure mechanism in OL3 structures where the slabs and walls are strongly reinforced and the anchor plates are deeply embedded into the concrete and l/d ratio of the headed studs is quite high. One simplified site test has been done by tensioning small angle fastenings located in wall edge next to door opening. No cracks were occurred although the test force was high considering the theoretical capacity and the fact that the main reinforcement of wall edge is located behind the studs. 26

PEIKKO, ANCHOR PLATES SPECIAL PROJECT: special requirements high quality demands factory production control (FPC) specified quality system OL3: - post-installed fasteners were not allowed cast in place headed fastners / studs required - Peikko delivered/supplied >> 100 000 anchor plates + other frames and embedded parts 27

28

29

THANK YOU