HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS



Similar documents
Applications in Mobile Air-Conditioning and Applications in Heat Pumps

DESIGN AND APPLICATION OF AMMONIA HEAT PUMP SYSTEMS FOR HEATING AND COOLING OF NON-RESIDENTIAL BUILDINGS

AIR REVERSING R744 AIR CONDITIONING SYSTEM

Natural geothermal energy.

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

LG Electronics AE Company, Commercial Air Conditioning

UNIT 2 REFRIGERATION CYCLE

High Pressure Ammonia Systems New Opportunities

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

Low GWP Replacements for R404A in Commercial Refrigeration Applications

The Development of Heat Pump Water Heaters Using CO 2 Refrigerant

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

Renewable Heat Pumps. A guide for the technically minded

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Design and simulation of a heat pump for simultaneous heating and cooling using HFC or CO 2 as a working fluid

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

How To Calculate The Performance Of A Refrigerator And Heat Pump

Hybrid heat pumps. saving energy and reducing carbon emissions

How does solar air conditioning work?

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

New Trends in the Field of Automobile Air Conditioning

Heat Recovery In Retail Refrigeration

Session 2: Hot Water Supply

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Daikin Altherma hybrid heat pump. The natural combination

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

DAikin Altherma low temperature heat pump. end user leaflet

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

How To Know If A Refrigeration System Is Efficient

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

IMMERSION MANAGEMENT SERVICE KG

Thermal Coupling Of Cooling and Heating Systems

New technical solutions for energy efficient buildings

Field test of a novel combined solar thermal and heat pump system with an ice store

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

Optimal operation of an Ammonia refrigeration cycle

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Daikin Altherma. hybrid heat pump. The natural combination

GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES

RESEARCH HIGHLIGHT. The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption

Commercial CO 2 Refrigeration Systems

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Delivering exceptional performance and Ecovalue. Ecocent

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Hot Water. Heat pump water heaters. Residential and Commercial R410a

How Ground/Water Source Heat Pumps Work

Increasing the evaporation temperature with the help of an internal heat exchanger

Commercial Hot Water. Make a difference...

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

Energy consumption and heat recovery of refrigeration system in modern Arena

The natural ombination

Research on the Air Conditioning Water Heater System

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

ECOCIAT. Domestic hot water heat recovery unit

Mohan Chandrasekharan #1

Combined Air-conditioning and Tap Water Heating Plant, Using CO2 as Refrigerant for Indonesian Climate Condition. By Willy Adriansyah

REFRIGERATION (& HEAT PUMPS)

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

Selecting a New Water Heater

AMMONIA AND CARBON DIOXIDE HEAT PUMPS FOR HEAT RECOVERY IN INDUSTRY

DE-TOP User s Manual. Version 2.0 Beta

Chapter 3.4: HVAC & Refrigeration System

Simulation study of a heat pump for simultaneous heating and cooling coupled to buildings

Heat Pumps for Domestic Hot Water Preparation in Connection with Low Temperature District Heating

Energy Procedia Energy 00 Procedia (2011) (2012) 56 65

How To Improve Energy Efficiency Through Raising Inlet Temperatures

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

Silicagel-water adsorption cooling prototype system for mobile air conditioning

The natural ombination

Analytical Study of Vapour Compression Refrigeration System Using Diffuser and Subcooling

ROTEX gas hybrid heat pump. A strong team.

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE

Solar and heat recovery hybrid system

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Vitocaldens 222-F Compact Gas-Hybrid appliance

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS

Crowne Plaza Copenhagen Towers The world s greenest hotel

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

Rainwater Harvesting

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

ROTEX Gas-Hybrid-Heat Pump

HEAT PUMP FOR DISTRICT COOLING AND HEATING AT OSLO AIRPORT, GARDERMOEN

SONNENKLIMA package solution description

Small-Scale Solar Heating and Cooling Systems

GEOTHERMAL HEATING AND COOLING INTRODUCTION

PERFORMANCE EVALUATION OF NGCC AND COAL-FIRED STEAM POWER PLANTS WITH INTEGRATED CCS AND ORC SYSTEMS

Transcription:

1 HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS Jørn Stene SINTEF Energy Research, 7465 Trondheim, Norway Jorn.Stene@sintef.no In hotels, hospitals, nursing homes, sport centres, block of flats and apartments buildings the annual energy demand for heating of domestic hot water (DHW) typically range from 25 to 60% of the total annual heating demand of the building. Due to the considerable DHW heat load, a centralized DHW system that covers the entire demand can be a very profitable installation. Possible heating systems include electric immersion heaters, solar collectors in combination with electric immersion heaters for supplementary heating, gas-fired boilers, pellet-fired boilers and heat pump water heaters (HPWH) utilizing e.g. ambient air, exhaust ventilation air, groundwater, boreholes in crystalline rock or grey water as heat source. This papers shows that HPWH systems using carbon dioxide (CO 2, R744) as working fluid will typically achieve 20% higher COP than the most energy-efficient HPWH systems on the market using HFC or propane as working fluid. In terms of energy efficiency and utilization of renewable heat it even outperforms state-of-the-art solar heating systems. Air-to-water and water-to-water CO 2 HPWHs in the capacity range from about 5 to 60 kw have now become commercially available in Japan and Europe from a number of Japanese manufacturers. 1 Evaluation of Different Heat Pump Water Heater Systems 1.1 Heat Exchanger Configuration and System Design The COP for a heat pump unit is heavily depending on the condensation temperature/pressure, and the COP typically increases by 3-4% per K reduction in the condensation temperature. In order to enable production of domestic hot water (DHW) in the required temperature range (60-80ºC) and still achieve a relatively high COP for a heat pump, state-of-the-art heat pump water heater (HPWH) systems are normally equipped with a desuperheater and possibly a subcooler. A desuperheater is a heat exchanger that cools down the hot exhaust gas from the compressor for reheating of DHW, while a subcooler is a heat exchanger that cools down the working fluid after the condenser (condensate) for preheating of DHW. Many HPWH systems are also using a combination of a desuperheater and a suction gas heat exchanger. The latter heat exchanger transfers heat from the condensate to the suction gas at the compressor inlet, and increases the exhaust gas temperature and the superheating enthalpy for the HPWH. Figure 1 on the following page shows, as an example, a schematic diagram of a HPWH system equipped with a subcooler (SC), condenser and desuperheater (DSH), while Figure 2 shows the cooling curve of the working fluid and the heating curve of the water in a Temperature-Enthalpy diagram when the city water (CW) is being heated from 5/15 to 70ºC. Heat pump systems using carbon dioxide (CO 2, R744) as working fluid represent a new and promising technology, e.g. for HPWH systems. CO 2 is a non-flammable and non-toxic fluid that does not contribute to global warming as the HFC working fluids, i.e. GWP=0. Due to the unique thermophysical properties of CO 2, high energy efficiency can be achieved if the heat pump system is correctly designed and operated in order to utilize the properties of the fluid.

2 Figure 1 Heat pump water heater equipped with three separate heat exchangers in series. Figure 2 Heat pump water heater with heat rejection in a subcooler (A), condenser (B) and desuperheater (C) for heating of city water from 5 to 70ºC. Due to the low critical temperature of CO 2 (31.1ºC), a CO 2 HPWH will be operating in a socalled transcritical heat pump cycle were heat is rejected by cooling of CO 2 vapour at supercritical pressure in a counter-flow gas cooler. Figure 3 on the following page shows an example of temperature profiles for CO 2 and water in a CO 2 gas cooler for DHW heating. 1.2 COP Comparison for Different HPWH Systems Four different HPWH designs have been analyzed in order to identify the system with the highest COP at varying evaporation temperature (-10 to +10ºC), varying inlet city water temperature (5 to 30ºC) and varying outlet water temperature (60 to 85ºC). The HPWH systems were as follows (Hjerkinn, 2007): System 1 Heat pump with condenser and desuperheater System 2 Heat pump with subcooler, condenser and desuperheater System 3 Heat pump with suction gas heat exchanger, condenser and desuperheater System 4 CO 2 (R744) heat pump with a single counter-flow gas cooler unit

3 Figure 3 Example of temperature profiles in a CO 2 gas cooler for DHW heating. HPWH systems no. 1, 2 and 3 were simulated with both R134a and R290 (propane), since these working fluids have a sufficiently high condensation temperature (60-70ºC) when using standard components with 25 bar pressure rating. In order to attain equal boundary conditions for the four different heat pump units, the various heat exchanger combinations were simulated with equal UA-values, which limited the size and heat transfer efficiency for the heat exchangers. The UA-value ranged from 1,800 to 2,400 W/K, and the higher the UA-value the lower the condensation temperature. Figure 4 shows the calculated COP for the different HPWH systems as a function of the evaporation temperature, t 0 (Hjerkinn, 2007). In the calculations it was assumed a total UAvalue of 2,100 W/K for both the condenser/heat exchanger combinations and the CO 2 gas cooler, 5 K superheated vapour from the evaporator, 5ºC inlet city water temperature and 70ºC DHW temperature. The overall isentropic efficiencies for the compressors were calculated on the basis on typical efficiency curves from laboratory measurements. Figure 4 Calculated COP as a function of the evaporation temperature t 0 (Hjerkinn, 2007).

4 For the state-of-the-art HPWH systems with R134a or R290 as working fluid, System 2 (subcooler, condenser and desuperheater) and System 3 (suction gas heat exchanger, condenser and desuperheater) achieved more or less the same COP at varying operating conditions. System 1 (condenser and desuperheater) achieved roughly 15% lower COP than System 2 and 3. The main reason for the lower COP was that System 1 operated at a higher condensation temperature due to poorer temperature fit between the water and the working fluid. The most energy efficient HPWH was System 4, the CO 2 system, which in average achieved about 20% higher COP than System 2 and 3. This was mainly due to higher compressor efficiency and the excellent temperature fit in the gas cooler between the CO 2 and the water, which minimized the average CO 2 temperature during heat rejection. In addition to the high energy efficiency for the CO 2 HPWH, CO 2 has the advantage of being a non-flammable, nontoxic and environmentally friendly fluid with zero GWP factor when used as a working fluid. 2 Case Study Design and Evaluation of a CO 2 HPWH Bergen Housing Cooperative is about to construct a number of apartment buildings of passive house standard at Damsgårdssundet in Bergen, Norway with about 300 flats. An indepth analysis has been carried out for one of the buildings with 40 flats in order to develop a high-efficiency centralized CO 2 HPWH system (Hjerkinn, 2007). 2.1 Design of the HPHW and the Storage Tanks The energy demand for DHW heating in the apartment building was estimated to be approx. 170,000 kwh/year, i.e. about 4,250 kwh/year for each flat. This also included DHW to washing machines and dish-washing machines (600 kwh/year). The CO 2 HPWH was designed for a heating capacity of 26 kw at 12ºC inlet city water temperature, 70ºC DHW temperature and 3 K temperature difference between the outlet CO 2 and the inlet city water in the gas cooler. The isentropic and volumetric efficiency of the compressor was 0.70 and 0.75, respectively. The HPWH heating capacity was calculated assuming 18 hours operating period per 24 hours for the heat pump unit and the application of four 1,000 litres DHW storage tanks to cover large momentary DHW demands (Hjerkinn, 2007). Figure 5 shows the estimated 24 hour DHW consumption diagram for the apartment building, with the maximum DHW demand between 16-19 o clock in the evening (approx. 3 hours maximum). 26 kw Figure 5 24 hours DHW consumption diagram for the apartment building (Hjerkinn, 2007).

5 2.2 Component and System Design The 26 kw CO 2 HPWH system was simulated in CSIM (Skaugen, 2002), which is an advanced computer programme developed at NTNU-SINTEF for optimization of CO 2 heat pump systems. CSIM calculates, among other things, real evaporator, gas cooler, suction gas heat exchanger and compressor performance based on laboratory measurements. The CO 2 HPWH was equipped with a 60 bar plate heat exchanger as evaporator (SWEP), a reciprocating compressor with 150 bar pressure rating (Bitzer), a 140 bar counter-flow plate heat exchanger as gas cooler (SWEP), a counter-flow tube-in-tube suction gas heat exchanger, an automatic expansion valve (back-pressure valve) and a low-pressure receiver (LPR). The expansion valve and the LPR were used for optimization of the pressure in the gas cooler at varying operating conditions in order to maximize the COP. The inlet water temperature in the gas cooler has a considerable impact on the COP of a CO 2 HPWH, and the lower the temperature the higher the COP. A low inlet water temperature leads to a low CO 2 outlet temperature from the gas cooler and with that a large enthalpy difference during heat rejection. Figure 6 shows simulated relative COP values for a CO 2 HPWH unit at varying inlet water temperature and 60 and 80ºC DHW temperature. Example by increasing the inlet city water temperature from 5ºC to 15ºC at 60ºC DHW temperature, the COP is reduced by approximately 10% (Stene, 2004). From Figure 6 it can be concluded that the DHW storage system for a CO 2 HPWH should use relatively small diameter storage tanks connected in series in order to minimize conductive heat transfer between the DHW and the city water in the tanks (exergy loss). Efficient diffusers at the tank inlets should also be installed in order to minimize the water velocity and consequent mixing of water at different temperature levels (exergy loss). 1.00 0.95 Relative COP [-] 0.90 0.85 0.80 0.75 0.70 DHW 80 C DHW 60 C Figure 6 0.65 5 10 15 20 25 30 Inlet Water Temperature [ C] Simulated relative COPs for a CO 2 HPWH as a function of the inlet water temp. to the gas cooler at 60 and 80ºC set-point temperature for the DHW (Stene, 2004). Figure 7 on the following page shows a schematic diagram of the CO 2 HPWH system including four 1,000 litre single-shell storage tanks connected in series and an inverter controlled pump, Pump 1 (Hjerkinn, 2007).

6 Figure 7 Schematic diagram of the 4000 litre DHW storage tank system connected to the single counter-flow CO 2 gas cooler unit (Hjerkinn, 2007). 2.3 Control Strategy The DHW system is designed as a closed unvented (pressurized) system, where DHW tank 4 is connected to the city water supply and DHW tank 1 is connected to the tapping sites. During the tapping periods, cold city water will enter the bottom of DHW tank 4 whereas the same amount of hot water will flow from the top of DHW tank 1 to the tapping sites. The CO 2 HPWH will normally run during the tapping periods. An inverter controlled pump (Pump 1) circulates the cold city water to the single CO 2 gas cooler unit, where the water is being heated to the set-point temperature (T1) before it enters DHW tank 1. When the tapping period has ceased, the CO 2 heat pump will be running as long as the water temperature (T2) at the bottom of DHW tank 4 is lower than the set-point temperature (e.g. 70ºC). The gas cooler pressure for the CO 2 heat pump unit is optimized in order to maximize the COP for the heat pump at varying operating condition. 2.4 Simulation Results COP and Profitability When using groundwater at 7ºC as the heat source, the calculated seasonal performance factor (SPF) for the CO 2 HPWH was approximately 3.8 (Hjerkinn, 2008). This corresponds to an annual energy saving of about 70-75% compared to a conventional DHW system with electric immersion heaters, and is 20-35 percentage points higher that that of Scandinavian DHW systems based on solar collectors and electric immersion heaters for supplementary heating. Figure 8 shows the energy saving (i.e. the utilization of renewable heat green bars) for the CO 2 HPWH compared to electric immersion heaters and a solar heating system. The maximum (permissible) investment cost for the CO 2 HPWH system was as high as 125,000 (4,800 /kw) when using the following boundary conditions: 170,000 kwh/year annual heating demand, 3.5 average heat pump COP (conservative value), 6% real interest rate, 15 years economic lifetime, 0.1 /kwh (0.80 NOK/kWh) electricity price and electric immersion heaters as reference DHW system.

7 Figure 8 Primary energy demand and utilization of renewable heat for different hot water heating systems (electric immersion heater, heat pump, solar heater). 3 Conclusion Due to the high energy efficiency and the favourable environmental properties of carbon dioxide (CO 2 ) as a working fluid, CO 2 heat pump water heater (HPWH) systems are regarded a promising technology for centralized DHW heating in e.g. hotels, hospitals, nursing homes, sport centres, block of flats and apartments buildings. In terms of energy efficiency and utilization of renewable heat the CO 2 system even outperforms state-of-the-art solar heating systems. Air-to-water and water-to-water CO 2 HPWH systems in the capacity range from about 5 to 60 kw are now available in Japan and Europe from a number of Japanese manufacturers (ref. www.r744.com). 4 References Hjerkinn, T., 2007: Analysis of Heat Pump Water Heater Systems for Low-Energy Block of Flats (in Norwegian with English summary). Master thesis at the Norwegian University of Science and Technology (NTNU), Dept. of Energy and Process Engineering. EPT-M- 2007-24. Skaugen,G., 2002. Investigation of Transcritical CO 2 Vapour Compression Systems by Simulation and Laboratory Experiments. Doctoral Thesis at the Norwegian University of Science and Technology (NTNU), Dept. of Energy and Process Engineering, 2002-141. ISBN 82-471-5536-2. Stene, J., 2004: Residential CO 2 Heat Pump System for Combined Space Heating and Hot Water Heating. Doctoral Thesis at the Norwegian University of Technology and Science, Dept. of Energy and Process Engineering, 2004:53. ISBN 82-471-6316-0.