AIR HANDLER INSTALLATION INSTRUCTIONS



Similar documents
How To Install An Evaporator Coil

Installer s Guide 18-AH39D1-13

Installation Instructions

Your safety and the safety of others are very important.

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

Installation Instructions

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

TECHNICAL MANUAL GDS8 & GHS8

Acumen Enterprises, Inc.

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

E2 Series Electric Furnaces

AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency

INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

Cooling/Heat Pump Convertible Air Handlers

INSTALLATION INSTRUCTIONS

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin / March 2013

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents

Packaged Terminal Air Conditioner Wall Sleeve Installation

Evaporator Coil Installation Instructions

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

CEILING CASSETTE FAN COIL UNIT

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

LPM-06 CONVERSION KIT

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Installation Instructions

PACKAGED TERMINAL AIR CONDITIONER (PTAC) / PACKAGED TERMINAL HEAT PUMP (PTHP) AND ACCESSORY INSTALLATION INSTRUCTIONS

Portable Air Conditioner

Glossary of Heating, Ventilation and Air Conditioning Terms

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

Evaporator Coil. Installation Instructions GENERAL

INSTALLATION INSTRUCTIONS

XL PREMIUM OIL COOLER KIT

REMOTE AUXILIARY AIR CONDITIONING SYSTEM AND AIR DISTRIBUTION

Ceiling Mount Air Handler Manual

Cased/Uncased Coils For Gas And Oil Furnaces

Your safety and the safety of others are very important.

INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

Cooling Capacity CFM in. w.c. (125 Pa)

Float and Thermostatic Traps Series H, C and X

ARMSTRONG AIR HEAT PUMPS

Cooktop Low-Profile Ventilation Hoods

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT CHEVROLET/GMC VANS FOR

Test Code: 8297 / Version 1

Air Conditioning Sign-Off Sheet

USER S INFORMATION MANUAL

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Oil and Coolant Circulating Heating System. Model - OCSM

INSTALLATION INSTRUCTIONS FOR INTERNATIONAL 9000 SERIES ROOF TOP AIR CONDITIONERS

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

Installation Instructions For Slider Casement Air Conditioners

5800 Temperature Sensor Cable Assembly

Cooling system components, removing and installing

HP UPS R1500 Generation 3

Reverse Cycle Inverter Split System Air Conditioner

The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs:

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

, User s Manual

SL280UHV SERIES GAS FURNACE WARNING

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

Installation Guide. 5 Series 15 W. Undercounter/Freestanding Nugget Ice Machine

CARING FOR YOUR WATER HEATER

AVPTC**14** AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS

SECTION AIR CONDITIONING UNIT

Cooling system components, removing and installing

specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST CHEVROLET PICKUP

F9MXE. Product Specifications

Air Conditioner B B

G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

Split System Cooling Product Data

Installation Instructions

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

Select Radiators Installation Guide

INSTALLATION MANUAL ELECTRIC RANGE. Please read these instructions thoroughly before installing and operating the range.

HEAT WAVE DUCT KIT KIT #

TYPE. MODEL B3200 Roof-Top Air Conditioner used with Mechanical Air Distribution Box INSTALLATION & OPERATING INSTRUCTIONS Air Conditioner

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

ASX7-4-IOM-7 J

AIR CONDITIONER & HEAT PUMP DIGITAL CONTROL FOR DUCTED SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

Element D Services Heating, Ventilating, and Air Conditioning

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

Evaluate, Clean, and Tune Guidance

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

Local Dealer:

High School Graduation years 2013, 2014, Unit/Standard Number

Power Cube Open Source Ecology Page 1. Power Cube. Version 4

SECTION MORTUARY REFRIGERATORS

Model. Roof-Top Air Conditioner CARAVAN MODEL B3200 TYPE INSTALLATION & OPERATING INSTRUCTIONS B3200

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

Transcription:

AI HANDLE INSTALLATIN INSTUTINS AI HANDLE SAFETY... INSTALLATIN EQUIEMENTS...3 Tools and Parts...3 System equirements...3 Location equirements...3 Electrical equirements... Ductwork equirements... INSTALLATIN INSTUTINS... Inspect Shipment... Installation onfigurations... Install ondensate Drain...7 Install Ductwork...8 Table of ontents Verify rifice Size...8 onnect efrigerant Lines...8 Make Electrical onnections...9 Wiring Diagram...2 omplete Installation...22 SEQUENE F PEATIN...23 ooling ooling nly or Heat Pump...23 Heating Electric Heat nly...23 Heating Heat Pump...23 AI HANDLE MAINTENANE...2 ASSISTANE SEVIE...2 AI HANDLE SAFETY ecognize this symbol as a safety precaution. ecognize Safety Symbols, Words and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of serious personal injury or death, property damage and/or product damage. WANING Hazards or unsafe practices could result in property damage, product damage, severe personal injury or death. Goodman AUTIN Hazards or unsafe practices may result in property damage, product damage, personal injury or death. AUTIN Goodman 9 Hazards or unsafe practices may result in property or product damage. WANING Installation and repair of this unit should be performed NLY by individuals meeting (at a minimum) the requirements Goodman of Entry 7 Level Technician, at a minimum, as specified by the Air-onditioning, Heating and efrigeration Institute (AHI). Attempting to install or repair this unit without such background may result in product damage, personal injury or death. WANING HIGH VLTAGE! Goodman 6 Failure to do so may cause property damage, personal injury or death. Whirlpool Model WAHMV WPI-287G

WANING Goodman 33 This product is factory-shipped for use with 208/20//60 electrical power supply. D NT reconfigure this air handler to operate with any other power supply. WANING To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken electrical ground. The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service Goodman panel. 3 ther methods of grounding are permitted if performed in accordance with the National Electric ode (NE) /American National Standards Institute (ANSI) /National Fire Protection Association (NFPA) 70 and local/state codes. In anada, electrical grounding is to be in accordance with the anadian Electric ode (SA) 22.. AUTIN When installing or servicing this equipment, safety Goodman 3 clothing, including hand and eye protection, is strongly recommended. If installing in an area that has special safety requirements (hard hats, etc.), observe these requirements. WANING Do not connect Goodman to or use any device 36that is not designcertified for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices. WANING Goodman 37 To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this unit. DANGE ABN MNXIDE PISNING HAZAD Special Warning for Installation of Furnace or Air Handling Units in Enclosed Goodman Areas such as Garages, 38 Utility ooms or Parking Areas. arbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide () poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation. This ventilation is necessary to avoid the danger of poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. arbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode. can cause serious illness including permanent brain damage or death. IMPTANT: The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by jurisdiction. A certified technician must perform the installation and service of this product. Should questions arise, contact your local EPA office. This product is designed and manufactured to permit installation in accordance with national codes. It is the installer s responsibility to install this unit in accordance with national codes and/or prevailing local codes and regulations. 2

These instructions are intended as a general guide only for use by qualified persons and do not supersede any national or local codes in any way. ompliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation. ead this entire instruction manual, as well as the instructions supplied in separate equipment, before starting the installation. All models are designed for indoor installation only. The installation of the air handler, field wiring, warm air ducts, etc., must conform to the requirements of the National Electrical ode, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (including plumbing or wastewater codes). Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual. Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-onditioning Systems (latest edition). The air handler is provided with flanges for the connection of the plenum and ducts. Air filters (not provided) must be listed as lass 2 furnace air filters. The air handler can be used with -0A from the factory. The air handler is shipped from the factory completely assembled. Some models are configured for upflow air discharge only, and some models are configured for upflow or horizontal left-hand air discharge. The air handler cabinet conforms to 2 percent or less air leakage. Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the installation. Select the final installation position which best suits the site conditions. onsider required clearances, space, routing requirements for refrigerant line, condensate disposal, filters, ductwork, wiring, and accessibility for service. efer to the air handler rating plate on the air handler for specific information. Tools and Parts Gather the required tools and parts before starting installation. ead and follow the instructions provided with any tools listed here. Tools Needed ¹ ₄" nut driver Level Screwdriver Adjustable wrench INSTALLATIN EQUIEMENTS Tape measure Hammer Sealant Parts Needed heck local codes, check existing electrical supply, and read Ductwork equirements and Electrical equirements before purchasing parts. System equirements The air handler is designed to match, and must be used with outdoor units as rated. The indoor units are manufactured with an interchangeable refrigerant metering orifice to provide optimum refrigerant control and system performance with a variety of different capacities of outdoor units. In some cases, the rating of the outdoor unit may require that the air handler coil assembly orifice be changed to obtain rated performance. Location equirements NTE: When used on cooling applications, excessive sweating may occur when the air handler is installed in a very humid space. UL Listed/SA approved wire connectors eplacement orifice (if needed). See Verify rifice Size. The correct orifice size may be contained in the replacement orifice package located inside the control box of the outdoor unit. If this package does not contain the correct orifice for your air handler, you must purchase the correct orifice size. If the air handler is installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet. Electrical wires should be sealed on the inside where they exit the conduit opening. Sealant is required to avoid air leakage and condensate from forming inside the air handler, control box, and on the electrical controls. The air handler must be installed in such a way as to allow free access to the coil/filter compartment and blower/control compartment. The air handler must be installed in a level position to ensure proper condensate drainage. Installation learances Non-Duct eturn loset Installation The air handler can be installed in a closet with a false bottom to form a return air plenum or be installed with a return air plenum under the air handler. Louvers or return air grilles are field supplied. Local codes may limit the application of systems without a duct return to singlestory buildings. 3

For an air handler installed in a closet with a louvered return opening, the minimum open area for the louvers will be as shown below. 8" and 2" (.7 cm and 6 cm) models 30" and 36" (76.2 cm and 9. cm) models 2", 8" and 60" (06.7 cm, 2.9 cm and 2. cm) models If the free area is not known, assume a 2% free area for wood louvers or a 7% free area for metal louvers or grilles. Using the louver dimensions and the 2% or 7% assumption, determine if the louver open area meets the minimum open area listed in the previous chart. If the return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow for the free flow of return air. When the air handler is not installed in front of the opening, there must be adequate clearance around the air handler to allow for the free flow of return air. The unit clearance from a combustible surface may be 0". Allow a minimum of 2" (6 cm) in front of the unit for service clearance. Do not install the air handler in a location that violates the instructions provided with the condenser. If the unit is located in an area with high ambient temperature and/or high humidity, the air handler may have condensation on the casing. n these installations, a wrap of 2" (. cm) fiberglass insulation with a vapor barrier is recommended. onsult all appropriate regulatory codes prior to determining final clearances. When installing this unit in an area that may become wet, elevate the unit with a sturdy, non-porous material. In installations that may lead to physical damage (for example, in a garage) it is recommended that a barrier be installed to avoid such damage. Electrical equirements 320 sq. in. (2,06 cm 2 ) 360 sq. in. (2,323 cm 2 ) 0 sq. in. (2,903 cm 2 ) WANING To avoid the Goodman risk of injury, electrical 3shock or death, the furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of the National Electric ode (NE). Use copper conductors only. All field wiring must be done in accordance with National Electrical ode, applicable requirements of UL and local codes where applicable. Electrical wiring, disconnect means and overcurrent protection are to be supplied by the installer. efer to the air handler rating plate for maximum overcurrent protection, minimum circuit ampacity, as well as operating voltage. The power supply must be sized and protected according to the specifications supplied on the product. This air handler is factory-configured for 20-volt, single phase, 60 cycles. For 208-volt applications, see 208-Volt onversion in the Make Electrical onnections section. For optional electric heater applications, see Accessories. efer to the instructions provided with the accessory for proper installation. Ductwork equirements Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-onditioning Systems (latest edition). The air handler is provided with flanges for the connection of the plenum and ducts. The air handler is equipped with flanges that can form a filter rack for the installation of the air filter, or the filter may be installed as part of the return air duct system. Air filters must be listed as lass 2 furnace air filters. AUTIN Do not operate this product without all the ductwork attached. Goodman 39 Supply and return ductwork must be adequately sized to meet the system s air requirements and static pressure capabilities. To ensure correct system performance, the ductwork is to be sized to accommodate 37 to 2 FM per ton of cooling with the static pressure not to exceed 0." W.. Ductwork should be insulated with a minimum of " (2. cm) thick insulation with a vapor barrier in conditioned areas or 2" (. cm) minimum in unconditioned areas. Supply plenum should be the same size as the flanged opening provided around the blower outlet and should extend ideally at least 36" (9. cm) from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower.

INSTALLATIN INSTUTINS Inspect Shipment These air handlers are completely factory assembled, and all components are performance tested. Each air handler consists of a blower assembly, refrigerant coil, and controls, in an insulated galvanized steel factory finished enclosure. Knockouts are provided for electrical wiring entrance. heck the air handler rating plate to confirm specifications are as ordered. Upon receipt of air handler, thoroughly inspect it for possible shipping damage. losely examine the air handler inside the carton if the carton is damaged. If damage is found, it should be noted on the carrier s freight bill. Damage claims should be filed with the carrier immediately. laims of shortages should be filed with the seller within days. NTE: If any damages are discovered and reported to the carrier, do not install the air handler because your claim may be denied. eturn Air Filters Each installation must include a return air filter. This filtering may be performed at the air handler or externally such as a return air filter grille. Air handlers mounted in the downflow orientation, including B series, require external filtering. A washable filter is available as an accessory. To ensure optimum performance, frequent filter cleaning is advised. WAHMV Filter Number Quantity equired 830 FIL 36-2 Horizontal Installations Horizontal installations can be left-hand or right-hand air supply. Adequate support must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove, service and access panels if installing in the horizontal position. For the correct horizontal coil installation, see Installation onfiguration ptions later in this section. IMPTANT: This coil is provided with a secondary drain that should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. See Install ondensate Drain. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the air handler as specified by most local building codes. Suspended abinet Installation NTE: Air handlers cannot be installed horizontally lying on or suspended from either the front or back of the air handler. It must be positioned with one side parallel to the floor when in the horizontal position. The suspending means must be field fabricated, and should consist of 2 cradles made by attaching 2 rods to a length of angle iron or suitable gauge steel. Installation onfiguration ptions Upflow As shipped from the factory. eturn in bottom. Shading indicates proper line connections. 337 260 FIL 8-6 Installation onfigurations For ease in installation, it is best to make any necessary coil configuration changes before setting the air handler in place. See Installation onfiguration ptions. Upflow air discharge contains only drain pan. Upflow or horizontal airflow contains 2 drain pans. Vertical Installations Upflow The air handler must be supported on the bottom only and set on a field-supplied supporting frame with an air return opening. Securely attach the air handler to the supporting frame. A B A. Horizontal drain connections (left or right hand) A B. Upflow drain connection. Bottom/filter frame

Installation onfiguration ptions Horizontal ight Left to right airflow As shipped from the factory Invert Air Handler A B Drains D E A B F A. Drain connections B. oil access cover. Blower access cover A. Access panel B. eturn air side of unit. ear channel bracket D. Zee coil support bracket E. oil retaining bracket F. Tie bracket Installation onfiguration ptions Horizontal Left ight to left airflow equires drain pan location change. 8. Install the zee coil supports and the wrapper stiffeners. 9. Install the tie bracket. 0. Install the rear channel bracket.. To avoid possible condensate blow off, the insulation retainers are to be laid into the evaporator coil pan as shown in the Evaporator oil Pan illustration. Evaporator oil Pan Drains A B A. Blower access cover B. oil access cover. Drain connections Downflow onversion onversion to downflow must be performed in an area that allows access to all sides prior to placing the air handler in its final location. To keep the evaporator coil pan from sweating, the DPI accessory insulation kit is to be used when performing this conversion. NTE: The DPI kit is not supplied with this product and is to be purchased separately. See the following chart for the correct DPI kit. WAHMV Model Insulation Kit To complete the conversion, slide the evaporator coil into the chassis and attach the 3 access panels. Evaporator oil A. 3" (7.6 cm) flat insulation retainer (both sides) A B A 830 DPI36-2/20 3036/337/260 DPI8-6/20. Before inverting the air handler, remove all access panels, the coil rear channel bracket, and the filter close-off panel. 2. emove the evaporator coil and the horizontal drain pan. 3. Discard the horizontal drain pan.. Install the plastic plug (provided) into the vacated access panel.. emove the 2 zee coil support brackets and insulation retaining brackets. 6. emove the tie bracket. 7. Install the DPI Insulation Kit onto the bottom of the drain pan. D E F A. Wrapper B. Insulation jacket. Zee coil support D. Wrapper stiffener E. Drain pan insulation kit F. Blower assembly 6

NTE: When the air handler is converted to the downflow position, the coil may protrude above the cabinet on some models. Horizontal onversion The only field modification required for conversion to Horizontal ight-hand is the removal of the plastic knockouts in the horizontal panel drain connections. To keep the horizontal drain pan from sweating in high humidity applications, it is recommended that a DPIH insulation accessory kit be used. NTE: The DPIH insulation kit is not supplied with this product and should be purchased separately. See the following chart for the correct DPIH kit. WAHMV Model Insulation Kit 0. Install the J bracket removed in Step 2 to support the upflow pan to the tie channel.. Attach all panels and the metering device. WAHMV Motor rientation If the unit is in the upflow position, there is no need to rotate the motor. If the unit is in the downflow position, loosen the motor mount and rotate the motor as shown in the following illustration. heck that the motor is oriented with the female connections facing down on the casing. If the motor is not oriented with the connections down, water will collect in the motor and may cause premature failure. A B N/A DPIH8-32 830 DPIH36-2 3036/337/260 DPIH8-6 The following describes converting to Horizontal Left-Hand. onversion to downflow must be performed in an area that allows access to all sides prior to placing the air handler in its final location. D Horizontal Left-Hand onversion A. Front view B. Side view. Female connections D. Use mounting bolts for optional ground. Achieving 2% Low Leakage ate A. DPIH kit B. Secondary drain. Primary drain. emove the 3 air handler access panels. 2. emove the J shaped bracket that retains the evaporator coil. 3. emove the flowrator from the lower left side access panel and slide out the evaporator coil and horizontal drain pan.. emove the gasket from the horizontal pan drain connections.. emove the oval shaped plastic plug from the left side access panel. 6. emove the oval shaped rubber gasket seal from the lower right side access panel. 7. The drain connections for the horizontal pan are sealed with a thin coating of plastic. Knock out this plastic seal with a screwdriver and hammer. NTE: The upper drain will become the secondary drain which is mandatory in many municipalities. 8. Install the plastic plug removed in Step to the right side lower access panel and the oval shaped rubber gasket to the lower left access panel. 9. einstall the evaporator coil with the horizontal panel on the left side. NTE: Push the assembly completely to the rear to ensure the engagement of the upflow pan with the rear channel bracket. A B Ensure that the Neoprene gasket with PSA remains intact on all surfaces that the access panels are secured to. These surfaces are the entire length of the wrapper and areas between the upper tie plate, upper and lower access panels. heck that the upper access panel breaker insert gasket is intact and that the flowrator gasket is installed on the lower access panel. An additional drain hole cover is required. Install ondensate Drain AUTIN If secondary drain is not installed, the secondary access must be plugged. Goodman 2 The air handler is provided with ³ ₄" (.9 cm) NPT condensate drain connections. A field-fabricated secondary drain pan, with a drainpipe to the outside of the building, is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan. In some localities, local codes may require a secondary drain pan for any horizontal installation. Make sure the air handler is level so that the drain pan will empty completely.. emove the appropriate drain knockouts. See Installation onfigurations. You may need to remove the indoor coil assembly from the cabinet. 2. emove any web from inside any threaded drain pan hole to which a drain line is to be connected. Gently remove the web so as not to damage the coil. 7

3. onnect the primary drain line connection to the primary drain pan connection. The primary drain connection is flush with the bottom of the inside of the pan. The secondary connection is raised above the bottom of the inside of the pan. NTE: When making drain fitting connections to the drain pan, hand tighten. Using a sealant is recommended. vertightening the fittings can split connections on the drain pan.. Secondary drain connections, if used, should be connected to a separate drainage system. un the secondary drain line to a place where the occupant would notice water coming from the secondary drain.. Install a 3" (7.6 cm) trap in both the primary and secondary drain lines as close to the unit as practical. Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan. NTE: Horizontal runs must also have an anti-siphon air vent (standpipe) installed ahead of the horizontal run. See Typical ondensate Drain onnection in this section. An extremely long horizontal run may require an oversized drain line to eliminate the trapping of air. Typical ondensate Drain onnection (Secondary Drain Not Shown) Install Ductwork IMPTANT: Install the ductwork in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-onditioning Sytems (latest edition) and any local codes. onnect the supply air duct to the flange on top of the unit. If an isolation connector is used, it must be nonflammable. A return air duct system is recommended. If the unit is installed in a confined space or closet, the entire duct cross sectional area must meet the minimum return air free area. Verify rifice Size. onsult the outdoor unit literature to determine whether the indoor unit has the correct orifice installed. 2. If a change of the orifice is required, loosen the brass hex nut and separate the orifice extension stub from the brass hex fitting. A B D G F E A D B E A. Distributor fitting B. Piston orifice. ing seal (supplied) D. rifice extension stub E. 0.82" brass hex nut F. Brass hex fitting G. Mounting flange A. Air handler B. Drain connection. Drain line D. 2" (. cm) minimum E. Anti-siphon air vent I F. 3" (7.6 cm) minimum G. Drain trap H. Auxiliary drain pan I. 2" (30. cm) maximum NTE: Do not operate the air handler without a drain trap. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will block positive drainage without a proper trap. 6. oute the drain line to the outside or to an appropriate drain. Drain lines must be installed so they do not block service access to the front of the air handler. A 2" (6 cm) clearance is required for filter, coil, or blower removal and service access. NTE: heck local codes before connecting the drain line to an existing drainage system. 7. Insulate the drain lines where sweating could cause water damage. Test ondensate Drain Pan and Drain Line After Installation:. Pour several quarts of water into the drain pan, enough to fill the drain trap and line. 2. heck that the drain pan is draining completely, no leaks are found in the drain line fittings, and water is draining from the end of the primary drain line. 3. orrect any leaks found. H F G 3. emove the orifice with an orifice extractor tool.. Insert the proper orifice into the fitting, seal end first. Make sure the orifice is free to move in the fitting.. eplace the brass hex nut. NTE: vertightening the brass hex nut will crush the gasket and may result in a system leak or stuck piston. 6. Dispose of/recycle all packaging and unused parts. onnect efrigerant Lines efrigerant lines must be connected by a licensed, EPA certified refrigerant technician in accordance with established procedures. IMPTANT: onnecting refrigerant lines must be clean, dehydrated, refrigerant-grade copper lines. Air handler coils should be installed only with specified line sizes for approved system combinations. Handle the refrigerant lines gently during the installation process. Sharp bends or possible kinking in the lines will cause a restriction. Do not remove the caps from the lines or system connection points until connections are ready to be completed. WANING Goodman This product is factory-shipped under pressure. Follow these instructions to prevent injury. 8

AUTIN To protect the unit when Goodman welding close to 3the painted surfaces, the use of a quenching cloth is strongly advised to prevent scorching or marring of the equipment finish. Solder with a minimum of % silver is recommended. Tubing Preparation All cut ends are to be round, burr free and clean. Failure to follow this practice increases the chances for refrigerant leaks. The suction line is spun closed and requires pipe cutters to remove the closed end. Post Brazing Quench all welded joints with water or a wet rag. Piping Size For the correct tubing size, follow the specification for the condenser/heat pump. Special Instructions This coil comes equipped with a check style flowrator for refrigerant management. For most installations with matching applications, no change to the flowrator piston is required. However, in mix-matched applications, a flowrator piston change may be required. See the piston kit chart or consult your local distributor for details regarding mix-matched piston sizing. If the mix-match application requires a different piston size, change the piston in the flowrator on the indoor coil before installing the coil and follow the procedure shown below. IMPTANT: Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed. NTE: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit. Heat trap or wet rags should be used to avoid damage to heat sensitive components such as service valves and TXV valves.. Loosen the ¹³ ₁₆" nut one turn only to allow high pressure tracer gas to escape. No gas indicates a possible leak. 2. After the gas has escaped, remove the nut and discard the black or brass cap. 3. emove the check piston to verify it is correct and then replace the piston. See the piston kit chart in the instructions.. Use a tube cutter to remove the spin closure on the suction line.. emove the tailpiece clamped to the exterior and slide the ¹³ ₁₆" nut into place. 6. Braze the tailpiece to the line set liquid tube. 7. Insert the suction line into the connection. 8. Slide the insulation and the rubber grommet at least 8" (.7 cm) away from the braze joint. 9. Braze suction line. 0. After the tailpiece has cooled, confirm position of the white Teflon seal and hand tighten the ¹³ ₁₆" nut. AUTIN Goodman 8 Excessive torque can cause orifices to stick. Use the proper torque settings when tightening orifices.. Torque the ¹³ ₁₆" nut to 7 to 2 ft-lbs. or tighten one-sixth turn. 2. eplace the suction line, grommet and insulation. A B D A. Tailpiece B. ¹³ ₁₆" nut. Plastic or brass cap 20-Volt Installations E D. White Teflon seal E. Piston Make Electrical onnections WANING HIGH VLTAGE! Goodman 6 Failure to do so may cause property damage, personal injury or death. WANING Goodman 22 F G F. ubber grommet G. Suction line with spin closure To avoid the risk of fire or equipment damage, use copper conductors. WANING To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken electrical ground. Goodman The electrical 3 ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. ther methods of grounding are permitted if performed in accordance with the National Electric ode (NE) /American National Standards Institute (ANSI) /National Fire Protection Association (NFPA) 70 and local/state codes. In anada, electrical grounding is to be in accordance with the anadian Electric ode (SA) 22.. 9

. Disconnect all power supplies. 2. emove the blower access panel. 3. oute the field supply wires to the air handler electrical connection box.. Using UL Listed/SA approved wire connectors, connect the field supply wires to the air handler (black to black and yellow to yellow). 208-Volt onversion WANING HIGH VLTAGE! Goodman 6 Failure to do so may cause property damage, personal injury or death.. Disconnect all power supplies. 2. emove the air handler access panel. 3. Move the 2 connected black transformer leads from the 20-volt terminal on the transformer to the 208-volt terminal on the transformer. See Wiring Diagram Electric Heat and Blower in the Make Electrical onnections section.. onnect the ground wire to the ground terminal marked GND. 6. eplace the blower access panel. Electric Heat efer to this manual in combination with the instructions provided with the heat kit for the correct installation procedure. The air handlers listed in this manual do not have factory installed electric heat. Electric heat is available as an accessory. If you are installing this option, the only heat kits that can be used are the HK series. NTE: The EHK, EB, EDB and EDK kits are not approved for use with these air handlers. The heating mode temperature rise is dependent upon the system airflow, the supply voltage, and the heat kit size (kw) selected. Use the Temperature ise tables to determine the temperature rise ºF (º). Temperature ise Table ºF 230//60 Supply Voltage Heat Kit Nominal kw ºF (º) FM 3 (-6.) (-) 6 (-.) 8 (-3.3) 0 (-2.2) (-9.) 20 (-6.7) 2 (-6.) 600 8 (-7.8) 28 (-2.2) 3 (.7) () 800 3 (-0.6) 2 (-6.) 26 (-3.3) 3 (-0.6) 2 (.6),000 (-.7) 7 (-8.3) 2 (-6.) 2 (-3.9) 3 (.) 0 (0),200 9 (-2.8) (-0) 8 (-7.8) 2 (-6.) 28 (-2.2) 2 (.6) 6 (3.3) 62 (6.7),00 8 (-3.3) 2 (-.) (-9.) 8 (-7.8) 2 (-.) 36 (2.2) 8 (8.9) 3 (.7),600 7 (-3.9) 0 (-2.2) 3 (-0.6) (-9.) 2 (-6.) 3 (-0.6) 2 (.6) 6 (7.8),800 6 (-.) 9 (-2.8) 2 (-.) (-0) 9 (-7.2) 28 (-2.2) 37 (2.8) () 2,000 (-) 8 (-3.3) (-.7) 2 (-.) 7 (-8.3) 2 (-3.9) 3 (.) 37 (2.8) 0

Temperature ise Table ºF 220//60 Supply Voltage Heat Kit Nominal kw ºF (º) FM 3 (-6.) (-) 6 (-.) 8 (-3.3) 0 (-2.2) (-9.) 20 (-6.7) 2 (-6.) 600 7 (-8.3) 27 (-2.8) 3 (.) 39 (3.9) 800 3 (-0.6) 20 (-6.7) 2 (-3.9) 30 (-.) 0 (.),000 0 (-2.2) 6 (-8.9) 20 (-6.7) 2 (-.) 32 (0) 8 (8.9),200 8 (-3.3) 3 (-0.6) 7 (-8.3) 20 (-6.7) 27 (-2.8) 0 (.) 3 (.7) 9 (),00 7 (-3.9) (-.7) (-0) 7 (-8.3) 23 (-) 3 (.) 6 (7.8) (0.6),600 6 (-.) 0 (-2.2) 3 (-0.6) (-9.) 20 (-6.7) 30 (-.) 0 (.) (6.7),800 6 (-.) 9 (-2.8) (-.7) 3 (-0.6) 8 (-7.8) 27 (-2.8) 36 (2.2) 39 (3.9) 2,000 (-) 8 (-3.3) 0 (-2.2) 2 (-.) 6 (-8.9) 2 (-.) 32 (0) 3 (.7) Temperature ise Table ºF 208//60 Supply Voltage Heat Kit Nominal kw ºF (º) FM 3 (-6.) (-) 6 (-.) 8 (-3.3) 0 (-2.2) (-9.) 20 (-6.7) 2 (-6.) 600 6 (-8.9) 2 (-3.9) 32 (0) 37 (2.8) 800 2 (-.) 9 (-7.2) 2 (-.) 30 (-.) 38 (3.3),000 0 (-2.2) (-9.) 9 (-7.2) 22 (-.6) 30 (-.) 6 (7.8),200 8 (-3.3) 3 (-0.6) 6 (-8.9) 9 (-7.2) 2 (-3.9) 38 (3.3) (0.6) 6 (3.3),00 7 (-3.9) (-.7) (-0) 6 (-8.9) 22 (-.6) 33 (0.6) 3 (6.) 8 (8.9),600 6 (-.) 9 (-2.8) 2 (-.) (-0) 9 (-7.2) 28 (-2.2) 38 (3.3) 2 (.6),800 (-) 8 (-3.3) (-.7) 2 (-.) 7 (-8.3) 2 (-3.9) 3 (.) 37 (2.8) 2,000 (-) 8 (-3.3) 0 (-2.2) (-.7) (-9.) 23 (-) 30 (-.) 3 (.) NTE: For installations not indicated in the Temperature ise tables, the following formula is to be used: T = (kw x 32) x (Voltage orrection) / (.08 x FM) Where: T = kw = Temperature ise Heater Kit Actual kw 32 = Btu per kw NTE: The Temperature ise Tables can also be used to determine the air handler airflow delivery. When using these tables for this purpose, set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert 2 thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the room air temperature. Use HK specification sheets to determine the HK available for a given air handler. Voltage orrection = 96 (230 Supply Volts) = 92 (220 Supply Volts) = 87 (208 Supply Volts).08 = onstant FM = Measured Airflow

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. ooling nly 2-Stage Heat Thermostat oom Thermostat For Heat Pump Use nly ondensing Unit W G Y (ptional) To omfort Alert Module (If Used) THEMSTATS IDISTAT E\WW\ T T T2 G Y/Y2 UTD YN M ED W T T2 DIP switch (FM) W HEATE 2 VA DIP SWITH N FF. Y/Y2 enables high speed fan cooling. 2. E/W enables low speed fan heating. W/ enables high speed fan heating. 3. T PJ must be cut for this. DIP Switch must be in the N position.. ut PJ6 jumper if using humidistat. STAT opens on ooling nly 2-Stage Heat st oom Thermostat, 2 nd utdoor Thermostat For Heat Pump Use nly utdoor Thermostat oom Thermostat W G Y ondensing Unit (ptional) To omfort Alert Module (If Used) E\W W/ THEMSTATS T T T2 G Y/Y2 IDISTAT UTD HEATPUMP YN M ED T T2 W W HEATE SWITH 2 VA DIP switch (FM) DIP N FF. Y/Y2 enables high speed fan cooling. 2. E/W enables low speed fan heating. E/W with outdoor thermostat closed enables high speed fan heating. 3. T PJ must be cut for this. DIP Switch must be in the N position.. ut PJ6 jumper if using humidistat. STAT opens on 2

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. ooling nly 2-Stage Heat utdoor Thermostat Enabled For Heat Pump Use nly utdoor Thermostat oom Thermostat W G Y ondensing Unit (ptional) To omfort Alert Module (If Used) THEMSTATS E\W W/ T T T2 G Y/Y2 IDISTAT See Note UTD NDENSE HEAT PUMP YN M ED T T2 W W HEATE SWITH 2 VA DIP switch (FM) DIP N FF st Stage auxiliary heat enabled by room thermostat. 2 nd Stage auxiliary heat enabled by room thermostat and closed T2.. Y/Y2 enables high speed fan cooling. 2. E/W enables low speed fan heating. W/ with outdoor thermostat closed enables high speed fan heating. 3. T PJ must be cut for this. T2 PJ2 must be cut for this. DIP Switch must be in the N position. 6. ut PJ6 jumper if using humidistat. STAT opens on Heat Pump with -Stage Emergency Heat and Stage Auxiliary Heat Heat Pump Y oom Thermostat E G Y HEATPUMP YN M ED (ptional) THEMSTATS E\W W/ T T T2 UTD HEATPUMP G IDISTAT Y/Y2 emove Production Wire - YN M ED W HEATE 2 VA T T2 W SWITH DIP switch (FM) DIP N FF. Y enables high speed fan cooling. 2. E and enable high speed fan heating. 3. If T2 PJ2 is cut, E and enable low speed fan heating.. DIP Switch must be in the N position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. 3

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. Heat Pump with 2-Stage Emergency Heat and -Stage Auxiliary Heat Heat Pump Y oom Thermostat E G Y HEATPUMP YN M ED (ptional) THEMSTATS E\W W/ T T T2 UTD HEATPUMP G IDISTAT Y/Y2 emove Production Wire - YN M ED W HEATE 2 VA T T2 W SWITH DIP switch (FM) DIP N FF. Y enables high speed fan cooling. 2. E enables low speed fan heating. enables low speed fan heating. and T2 closed enable high speed fan heating. 3. T2 PJ2 must be cut for this. DIP Switch must be in the N position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. Heat Pump with 2-Stage Emergency Heat, 2-Stage Auxiliary Heat and utdoor Thermostat Heat Pump utdoor Thermostat oom Thermostat (ptional) E\W W/ G Y/Y2 emove Production Wire - SWITH DIP switch (FM) DIP N FF st Stage auxiliary heat enabled by room thermostat. 2 nd Stage auxiliary heat enabled by room thermostat and outdoor thermostat.. Y enables high speed fan cooling. 2. E enables low speed fan heating. enables high speed fan heating. 3. T PJ must be cut for this. DIP Switch must be in the N position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -.

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. Heat Pump with 2-Stage Emergency Heat, 2-Stage Auxiliary Heat and 2 utdoor Thermostats Heat Pump Y E oom Thermostat G Y YN M HEATPUMP ED T T T2 UTD (ptional) THEMSTATS IDISTAT E\W W/ T T UTD HEATPUMP YN M ED T2 W HEATE 2 VA G Y/Y2 emove Production Wire - T T2 W SWITH DIP switch (FM) DIP N FF No auxiliary heat in heat pump mode until the outdoor thermostat closes.. Y enables high speed fan cooling. 2. E enables low speed fan heating. and T closed enable low speed fan heating. and T2 closed enable high speed fan heating. 3. T PJ and T2 PJ2 must be cut for this. DIP Switch must be in the N position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. Heat Pump with 2-Stage Emergency Heat, -Stage Auxiliary Heat and utdoor Thermostat Heat Pump utdoor Thermostat oom Thermostat G (ptional) E\W W/ emove Production Wire - W W DIP switch (FM) N No auxiliary heat in heat pump mode until the outdoor thermostat closes.. Y enables high speed fan cooling. 2. E enables low speed fan heating. and T2 closed enable high speed fan heating. 3. T PJ and T2 PJ2 must be cut for this. DIP Switch must be in the N position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -.

J I WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. Heat Pump with -Stage Emergency Heat and -Stage Auxiliary Heat Heat Pump oom Thermostat Y2 Y2 NDENSE HEAT PU M P YM M ED (ptional) TH E M S TAT S I D I STAT E\ W W/ W 2 T T T 2 G Y/ Y2 H UM U TD HEAT PUM P NDENSE YN M ED W 2 V A HEATE W T PJ T 2 PJ 2 HU M PJ 6 PN. B368270 ev. A DIP switch (FM). DIP SW IT H 2 6 7 8 3 N F F J2 J3 emove Production Wire -. Y enables high speed fan cooling. 2. E enables low speed fan heating. 3. If T2 PJ2 jumper is cut, E and enable low speed fan heating.. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. Heat Pump with -Stage Emergency Heat and -Stage Auxiliary Heat Heat Pump oom Thermostat Y2 E G Y2 HEAT PUM P NDENSE YN M E D (ptional) T H E M STATS HU M ID ISTAT E\ W W/ T T T 2 G Y/Y2 H UM UTD NDENSE HEAT PU MP YN M E D emove Production Wire - J 2 0 DIP switch (FM) T T2 W 9 PN. B368270 EV. A W HEATE PJ PJ 2 PJ 6 3 DIP SWITH 2 3 6 7 8 N 2 V A F F DS 2 6 7 8 3 J2 J 3 2. Y enables high speed fan cooling. 2. E and enable low speed fan heating. 3. If T2 PJ2 jumper is cut, E and enable low speed fan heating.. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. 6

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. Heat Pump with 2-Stage Emergency Heat and -Stage Auxiliary Heat Y2 Heat Pump E oom Thermostat G Y2 HEAT PUM P NDENSE YN M ED (ptional) J U TD H EAT PU M P NDENSE YN M E D 2 0 E\ W W/ W 2 DIP switch (FM) T W HEATE W W 2 T PJ T 2 PJ 2 HU M PJ 6 9 PN. B368270 EV. A T H E M ST AT S T T 2 G Y/Y2 3 DI P SW IT H 2 3 6 7 8 N 2 V A FF DS 2 I D IST AT H UM 6 7 8 3 J2 J3 2 emove Production Wire -. Y enables high speed fan cooling. 2. E enables low speed fan heating. enables high speed fan heating. 3. T PJ must be cut for this. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. Heat Pump with 2-Stage Emergency Heat, 2-Stage Auxiliary Heat and utdoor Thermostat Heat Pump utdoor Thermostat oom Thermostat Y2 E G Y2 NDENSE H EAT PUMP YN M W 2 ED (ptional) J NDENSE HEAT PUMP YN M E D 2 0 E\ W W/ T T2 DIP switch (FM) W T U TD 9 TH E M STATS T T 2 G Y/Y2 W HEATE PJ PJ 2 PJ 6 3 SW IT H DI P PN. B368270 EV. A 2 3 6 7 8 N 2 V A FF DS 2 HU M IDI ST AT 6 7 8 3 J2 J3 2 emove Production Wire - st Stage auxiliary heat enabled by room thermostat. 2 nd Stage auxiliary heat enabled by room thermostat and outdoor thermostat.. Y enables high speed fan cooling. 2. E enables low speed fan heating. enables low speed fan heating. and T2 closed enable high speed fan heating. 3. T2 PJ2 must be cut for this. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. 7

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. Heat Pump with 2-Stage Emergency Heat, 2-Stage Auxiliary Heat and 2 utdoor Thermostats utdoor Thermostat Heat Pump oom Thermostat E Y2 G Y2 HEAT PU MP NDENSE YN M E D T T T2 (ptional) U TD J U TD HEAT PU MP NDENSE YN M ED 2 0 E\W W/ DIP switch (FM) T W HEATE W W 2 T PJ T 2 PJ 2 HU M PJ 6 9 TH EM STATS T T 2 G Y/ Y2 PN. B368270 EV. A 3 DIP SWITH 2 3 6 7 8 N 2 V A FF DS 2 HU MI DI STAT 6 7 8 3 H UM J2 J3 2 emove Production Wire - No auxiliary heat in heat pump mode until the outdoor thermostat closes.. Y enables high speed fan cooling. 2. E enables low speed fan heating. and T closed enable low speed fan heating. and T2 closed enable high speed fan heating. 3. T PJ and T2 PJ2 must be cut for this. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. Heat Pump with 2-Stage Emergency Heat, -Stage Auxiliary Heat and utdoor Thermostat Heat Pump utdoor Thermostat oom Thermostat Y2 E G Y2 NDENSE HEAT PUMP YN M E D (ptional) J U T D NDENSE H EAT PUM P YN M E D 2 0 E\ W W/ DIP switch (FM) T W HEATE W W 2 T PJ T 2 PJ 2 HU M PJ 6 9 PN. B368270 EV. A T H E M ST AT S T T 2 G Y/Y2 3 DIP SWIT H 2 3 6 7 8 N 2 V A FF DS 2 HU M IDI ST AT 6 7 8 3 H UM J2 J3 2 emove Production Wire - No auxiliary heat in heat pump mode until the outdoor thermostat closes.. Y enables high speed fan cooling. 2. E enables low speed fan heating. and T2 closed enable high speed fan heating. 3. T PJ and T2 PJ2 must be cut for this. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 6. emove orange Jumper Wire -. 8

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. 2-Stage ooling onventional 2-Stage Thermostat 2-Speed ooling nly with -Stage Electric Heat For Heat Pump Use nly W oom Thermostat 2-Speed ondensing Unit (ptional) To omfort Alert Module (If Used) THEMSTATS E W W/ T T T 2 G Y /Y2 IDISTAT UT D NDENSE Y N M HEAT PUMP ED W HE ATE 2 V A T T 2 W SWITH DIP switch (FM) DIP N FF. enables low speed fan cooling. Y/Y2 enables high speed fan cooling. 2. E/W enables high speed fan heating. 3. If T PJ jumper is cut, E/W enables low speed fan heating.. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 2-Speed ooling nly with 2-Stage Heat Thermostat 2-Speed ondensing Unit Y2 To omfort Alert Module (If Used) For Heat Pump Use nly W oom Thermostat (ptional) \ SWITH DIP switch (FM) DIP N FF. enables low speed fan cooling. Y/Y2 enables high speed fan cooling. 2. E/W enables high speed fan heating. 3. If T PJ jumper is cut, E/W enables low speed fan heating.. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 9

WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. 2-Speed ooling nly with 2-Stage Heat Thermostat 2-Speed ondensing Unit Y2 To omfort Alert Module (If Used) For Heat Pump Use nly oom Thermostat W (ptional) \ SWITH DIP switch (FM) DIP N FF. enables low speed fan cooling. Y/Y2 enables high speed fan cooling. 2. E/W enables high speed fan heating. 3. If T PJ jumper is cut, E/W enables low speed fan heating.. DIP Switch must be in the FF position.. ut PJ6 jumper if using humidistat. STAT opens on 2-Speed ooling nly with 2-Stage Heat utdoor Thermostat Enabled For Heat Pump Use nly utdoor Thermostat oom Thermostat W G Y2 2-Speed ondensing Unit Y2 To omfort Alert Module (If Used) THEMSTATS IDISTAT (ptional) E\W W/ T T T2 G Y/Y2 See Note UTD NDENSE HEATPUMP YN M ED T T2 W W HEATE SWITH 2 VA DIP switch (FM) DIP N FF. enables low speed fan cooling. Y/Y2 enables high speed fan cooling. 2. E/W enables low speed fan heating. W/ with outdoor thermostat closed enable high speed fan heating. 3. T PJ must be cut for this. T2 PJ2 must be cut for this. DIP Switch must be in the FF position. 6. ut PJ6 jumper if using humidistat. STAT opens on 20

Wiring Diagram WANING HIGH VLTAGE! Goodman 6 Long - top of each page Failure to do so may cause property damage, personal injury or death. FL HT TL M M2 P W PL 2 3 6 7 8 9 FL HT TL FL HT 2 TL M M3 M2 M P W PL 2 3 6 7 8 9 Y FL FL HT TL HT 2 TL FL HT 3 TL M M2 M3 M Y Y P M M2 2 W B PL 2 3 6 7 8 9 FL FL FL Y FL HT TL HT 2 TL HT 3 TL HT TL M M2 M3 M P Y M M6 YL D BL M7 M8 2 PL B 2 3 W 6 7 8 9 L L2 L L2 Element ows 2 Element ows L L2 L L2 3 Element ows Element ows L L2 L L2 After installing optional heat kit, mark an "X" in the box provided above. Mark according to the number of heater element rows installed. No mark indicates no heat kit installed. *See Note 7 Low Voltage Field onnection Box For Heat Pumps nly To To ondenser Thermostat YN W Y/Y2 G Y W P Y B B G PL 2 PL2 2 3 3 See Note 8 6 7 8 9 6 7 8 9 Equipment Ground Use opper Wire. PL 2 PL2 2 T EM 2 3 208/20 Volts To Low Voltage Terminal Board PL PL2 J T2 VSTB W B DS J2J3 YN M ED W W T PJ PJ2 PJ6 W/ utdoor Y/Y2 ondenser Heat Pump Heater 2 VA Thermostats E/ W T T T2 G Y W B B P G Y B W B W 20 208 2 T 3 M Equipment Ground Use opper Wire. PL2 2V G PJ6 Equipment Ground Use opper Wire. T 2 PJ2 T T 2 Volt W See Note 2 olor ode W White G Green Black P Purple ed B Brown Y Yellow range Blue PK Pink PJ 6 W E W PL2 omponent ode IN00 Diode Y Y2 See Note YN Wiring ode Factory Wiring High Voltage Low Voltage Field Wiring High Voltage Low Voltage See Note Note Diode on VSTB G *See Note 7 PL2 EM EM PL PJ2, PJ, PJ 6 VSTB FL Evaporator Motor Plug Program Jumper Variable Speed Terminal Board Fuse Link TL HT T Thermal Limit Heat Element elay Transformer opper Power Supply (See ating Plate) ontrols shown with utilities in N position and thermostat in FF position.. For heat pump applications, remove the orange jumper wire between and. 2. For 2-stage electric heat applications, cut PJ. Use only on and 20 kw models. 3. For outdoor thermostat operation of 2 nd -stage heat, cut PJ2 and add T8-60 to T and T2.. For single-stage cooling applications, connect the thermostat to Y/Y2 only, tape or remove connection, connect condensing unit to YN and.. When humidstat is provided, cut PJ6. Thermostat opens on 6. ed wires to be on transformer Terminal 3 for 20 volts and on Terminal 2 for 208 volts. 7. See composite wiring diagrams in installation instructions low voltage connections and details on compatible thermostats and their connections. 8. Discard original PL plug connector when installing optional heat kit. 2

omplete Installation Achieving 2% Low Leakage ate Ensure that the Neoprene gasket with PSA remains intact on all surfaces where the access panels are secured. These surfaces are the entire length of the wrapper and areas between the upper tie plate, the upper and lower access panels. heck that the upper access panel breaker insert gasket is intact. heck that the flowrator gasket is installed on the lower access panel. An additional drain hole cover is required. NTE: efer to the outdoor unit installation instructions for system start-up instructions and refrigerant charging instructions. Pre-Start heck Is the air handler properly located, level, secure, and serviceable? Has an auxiliary pan been provided under the air handler with a separate drain for the air handlers installed above a finished ceiling or in any installation where condensate overflow could cause damage? Have all the webs been removed from the drain connections that are being used? Have all of the unused drain pan plugs been properly plugged? Has the condensate line been properly sized, run, trapped, pitched, and tested? Is the ductwork correctly sized, run, taped, and insulated? Have all cabinet openings and wiring been sealed? Is the indoor coil orifice sized correct? Have all unused orifice replacement parts and packaging been disposed of/recycled? Is the filter clean, in place, and of adequate size? Is the wiring neat, correct, and in accordance with the wiring diagram? Is the air handler properly grounded and fused? Is the thermostat correctly wired and in a good location? Are all access panels in place and secure? heck Blower peration. Set the thermostat to FAN N. 2. The indoor blower should come on. heck Electric Heater (If Used). Set the thermostat to call for auxiliary heat (approximately F [-º] above ambient temperature). The indoor blower and auxiliary heat should come on together. Allow a minimum of 3 minutes for all sequencers to cycle on. 2. Set the thermostat so it does not call for heat. Allow up to minutes for all sequencers to cycle off. heck Airflow ooling Blower Speed For proper cooling operation, the airflow through the indoor coil should be between 30 and 0 FM per ton of cooling capacity (or 30 to 0 FM per 2,000 Btu/h) based on the rating of the outdoor unit. The cooling blower speed is factory-configured to provide the correct airflow for an outdoor unit that matches the maximum cooling capacity rating of the air handler. If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler, the cooling blower speed may need to be changed. efer to the Blower Performance hart. IMPTANT: The cooling blower speed must be set to provide a minimum of 30 FM airflow per ton (,200 Btu/h) of outdoor cooling capacity. WAHMV Motor WANING HIGH VLTAGE! Disconnect Goodman ALL power 6 before servicing. Failure to do so may cause property damage, personal injury or death. This section references the operation characteristics of the WAHMV model motor only. The EM control board is factory-set with DIP Switch in the N position and all other DIP switches in the FF position. For most applications, this setting is to be changed according to the electric heat size and the outdoor unit selection. The WAHMV product uses a General Electric EM TM motor. This motor provides many features not available on the traditional PS motor. These features include: Improved Efficiency onstant FM Soft Start and Stop Improved Humidity ontrol Motor Speed Adjustment Each EM TM blower motor has been preprogrammed for operation at distinct airflow levels when operating in cooling, heat pump heating, backup heating (electric heating) and backup plus heat pump heating. Each mode has levels to deliver different airflow FM [L/s]. The adjustment is performed by changing the DIP switch(es) either to an FF or N position. 22

DIP Switch Functions The WAHMV air handler motor has an electronic control that contains an 8-position DIP switch. The function of these DIP switches are shown in the following chart. DIP Switch Number 2 3 N/A Function Electric Heat Indoor Thermostat 6 7 8 ooling and Heat Pump FM FM Trim Adjust FM Delivery The following tables show the FM output for DIP switch combinations, 2,, 6, 7 and 8. Switch Switch Emergency Heat Pump Model 2 7 8 (Electric) Heat with Backup Heat WAHMV830 ff ff ff ff,00,20 n ff ff ff 890 93 ff n ff ff 700 770 DIP Switch onfigurations for ooling and Heat Pump Switch Switch Nominal ooling 6 7 8 Tonnage FM WAHMV830 ff ff ff ff 2.,00 WAHMV337 WAHMV260 n ff ff ff 2 800 ff n ff ff. 600 ff ff ff ff,800 n ff ff ff,80 ff n ff ff 3.,80 n n ff ff 3,200 n n ff n 2.,020 Thermostat Fan nly Mode During Fan nly Mode operation, the FM output is 30% of the cooling setting. FM Trim Adjust Minor adjustments can be made through the DIP switch combination of 7 and 8. The following table shows the switch position for this feature. FM Switch 7 Switch 8 0% n ff -% ff n WAHMV337 WAHMV260 ff ff ff ff 2,00 2,0 n ff ff ff,70,83 ff n ff ff,600,680 n n ff ff,200,260 n n ff n,020,070 Humidity ontrol When using a humidistat (normally closed), cut jumper PJ6 on the control board. The humidistat will only affect cooling airflow by adjusting the airflow to 8%. 2-Stage Heating When using staged electric heat, cut jumper PJ on the control board. SEQUENE F PEATIN ooling ooling nly or Heat Pump When the thermostat calls for cooling, the circuit between and G is completed, and the blower relay is energized. The normally open contacts close, causing the indoor blower motor to operate. The circuit between and Y is also completed; this circuit closes the contactor in the outdoor unit starting the compressor and outdoor fan motor. ircuit and energizes the reversing valve, switching it to the cooling position. (The reversing valve remains energized as long as selector switch is in the L position.) Heating Electric Heat nly When the thermostat calls for heat, the circuit between and W is completed, and the heat sequencer relay is energized. A time delay follows before the heating elements and the indoor blower motor come on. Units with a second heat sequencer relay can be connected with the first sequencer to W on the thermostat subbase or connected to a second stage on the subbase. Heating Heat Pump When the thermostat calls for heat, the circuits between and Y and and G are completed. ircuit -Y energizes the contactor starting the outdoor fan motor and the compressor. ircuit and G energizes the blower relay starting the indoor blower motor. If the room temperature should continue to fall, the circuit between and W is completed by the 2 nd stage heat room thermostat. ircuit -W energizes a heat sequencer relay. The completed circuit will energize supplemental electric heat (if available). Units with a second heat sequencer relay can be connected with the first sequencer to W on the thermostat or connected to a second heating stage W 2 on the thermostat subbase. 23

AI HANDLE MAINTENANE WANING HIGH VLTAGE! Goodman 6 Failure to do so may cause property damage, personal injury or death. IMPTANT: Do not operate system without a filter. A filter is required to keep excessive dirt and dust from the coil, blower, and internal parts. See Installation onfigurations for the location of the filter in the unit cabinet and the service panel giving access to the unit filter. The filter is placed in the supply air return duct by the installer. Inspect air filters at least once a month and replace or clean as required. Dirty filters are the most common cause of inadequate heating or cooling performance. eplace disposable filters. leanable filters can be cleaned by soaking in mild detergent and rinsing with cold water. Install new/clean filters with the arrows on the side pointing in the direction of airflow. Do not replace a cleanable (high velocity) filter with a disposable (low velocity) filter unless the return air system is properly sized for it. If water should start coming from the secondary drain line, a problem exists which should be investigated and corrected. ontact a qualified person. ASSISTANE SEVIE If you need further assistance, you can write to the below address with any questions or concerns: Tradewinds Distributing ompany, LL 60 Breakers Drive Jacksonville, FL 3228 Please include a daytime phone number in your correspondence. r call toll free: -866-9-77. WPI-287G 20. All rights reserved. egistered Trademark/TM Trademark of Whirlpool, U.S.A., Manufactured under license by Tradewinds Distributing ompany, LL, Jacksonville, Florida. Warranty provided by manufacturer. 6/ Printed in U.S.A.