Subsurface Sewage Treatment System (SSTS) Self-Install Guide



Similar documents
SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

Indiana State Department of Health Construction Guidelines for Gravity and Flood-Dose Trench Onsite Systems

Checklist for plans to Construct, Alter or Repair An Individual Subsurface Sewage Disposal System

Louisiana Administrative Code Title 51 Part XIII. Sewage Disposal

Specifications for Residential Property Owners Connection to New Public Sewer

ONSITE WASTEWATER TREATMENT SYSTEM Property Transfer Certification Instructions and Inspection Report

9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems

SHORELINE SANITATION

Onsite Wastewater Concepts, Materials, Regulations & The Application Process Part I

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

Homeowners and Home Buyers Guide to Wells and Private Sewage Systems

Properly maintaining your septic system will help reduce the. It s Your Septic System. Homeowner s Guide. Here s How to Take Care of It

Procedures for Correcting a Sludge / Grease Clogged Elevated Sandmound Sewage Disposal System.

Residential Foundations and Basements

Septic System Owner s Manual

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA (7300 Short Road, Serene Lakes)

EFFECTIVE FEBRUARY note: drainage permit required to call for a dampproof inspection

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

Septic System Management Plan for Below Grade Systems

SECTION GRAVITY SANITARY SEWERS

ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM REQUIREMENTS

Gravelless Distribution Products

Understanding and Caring for Your Septic System

Septic Records and Maintenance Guidelines

Designing Septic Systems

HOW A SEPTIC SYSTEM FUNCTIONS

Septic Systems and Their Maintenance

Section 402. STORM SEWERS

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

Chapter 3 CULVERTS. Description. Importance to Maintenance & Water Quality. Culvert Profile

SECTION EARTH MOVING

THURSTON COUNTY SEPTIC TANK PUMPERS' MANUAL

SECTION STORM DRAINAGE TABLE OF CONTENTS

WASTEWATER TREATMENT AND DISPOSAL BY ON-SITE WASTEWATER TREATMENT SYSTEMS

COUNTY OF SUFFOLK STEVEN BELLONE SUFFOLK COUNTY EXECUTIVE STANDARDS. James L. Tomarken, MD, MPH, MBA, MSW Commissioner of Health Services

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

SEPTIC TANKS FOR THE COLLECTION & SETTLEMENT OF DOMESTIC SEWAGE

STANDARD SPECIFICATIONS SECTION PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200

CERTIFIED SEPTIC EVALUATION PREPARED FOR MATT HASHEM 1673 MT. MAJOR HWY, ALTON, NH 03810

Glen Hills Area: Septic System and Public Sewer Q & A Information Sheet Page 1

City of Shelbyville Site Inspection Checklist

Septic System Design Manual

SECTION 5: SANITARY SEWER SYSTEM DESIGN

DESCRIPTION OF STORMWATER STRUCTURAL CONTROLS IN MS4 PERMITS

DO-IT-YOURSELF SEPTIC SYSTEM INSPECTION FIELD GUIDE (Mound System)

SEPTIC SYSTEMS. 1. Building sewer connects the building plumbing to the septic tank.

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

CHAPTER 32 PLUMBING CODE

ON-LOT SEWA G E S Y S T E M S

STANDARD AND SPECIFICATIONS FOR STORM DRAIN INLET PROTECTION

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH Purpose and Application.

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Understanding and Living With Your Septic System

Section SEWER PIPE INSTALLATION AND TESTING

Beacon Hill Sewer District Standard Specifications

Technical Guidance for Inspections of Onsite Wastewater Treatment and Disposal Systems

Permeable Pavement Construction Guide

SANITARY SEWER SPECIFICATIONS

Emerging Technologies in Wastewater Collection Systems

Septic System Information for Residents

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SE-10 STORM DRAIN INLET PROTECTION. Objectives

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

Storm Drain Inlet Protection - IP

Homeowner s Guide to Maintaining a Sewage Treatment System

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

Top 10+ Mistakes of DWV plumbing design

Construction Site Inspection Checklist for OHC By making use of some simple Best Management Practices (BMPs) a construction site operator can

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE

MARICOPA COUNTY ENVIRONMENTAL HEALTH CODE CHAPTER II SEWAGE AND WASTES SECTION 8

Soil depth: meters Type of restrictive layer:

[L] If the top of the tank is level with or above ground level, finding it should not be a problem.

Sewer Pipe Lining An Economic Solution for Pipe Rehabilitation By Tawana Albany Nicholas, Virgin Islands Waste Management Authority

PERC-RITE DRIP DISPERSAL DESIGN GUIDE FOR SEPTIC TANK OR ADVANCED TREATMENT EFFLUENT MAINE

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

BMP 6.4.6: Dry Well / Seepage Pit

Does Part of My Basement Floor Have to Be Removed to Install. Where Does the Water from the Sump Pump Go?...Page 5

FY08 SEWER POINT REPAIRS BID TABULATION

DIVISION 4300 STORM DRAINAGE

Septic Systems Maintenance:

Affordable and Reliable. Wastewater. &Rainwater Solutions for Domestic & Commercial Applications FREE. Delivery. On-site advice.

EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS

CHAPTER 17: STORM SEWER STANDARDS Introduction Administration Standards 17.1

Section 3: Septic Tanks. 3. Septic Tanks

Type of Sewer Systems. Solomon Seyoum


Exhibit A. Rules and Regulations for House Connections and Sewer Extensions

BMP #: Dry Wells / French Drains

BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY

ALL YOU NEED TO KNOW...

R E S I D E N T I A L H O U S I N G

Transcription:

Subsurface Sewage Treatment System (SSTS) Self-Install Guide Hubbard County Environmental Services Updated: February 2010

Introduction The purpose of this guide is to familiarize the homeowner with some of the important items involved when planning and installing an onsite sewage treatment system and more importantly after a permit has been issued, passing inspection. The licensed designer you hire should be aware that you are planning to do your own installation so that s/he can provide you with a more detailed design plan and information about code requirements, both state and local. The designer will also do a to scale or dimension site sketch showing the locations of the proposed system (i.e. tank, lift station [if required] and soil treatment area [drainfield]). These locations should be marked out on your property and must be followed exactly. During construction, any deviation from the approved plan will require a new site evaluation, design, and approval by Hubbard County Environmental Services before work can continue. This could delay your project and cost you extra in terms of time, materials, and re-inspection fees. If you are not sure of something, call your designer. Since most self-installs take longer than a professional job, give yourself plenty of time to complete the task. Be aware of the weather forecast. The drain field must not be exposed to any form of precipitation until it is backfilled. Important before you start Call Gopher State One for utilities location two (2) working days prior to start time at 1-800-252-1166. Call Hubbard County Environmental Services to schedule an inspection. Call either the day before or before 9:30AM on the day you want your inspection. (A call received after 9:30AM may result in no inspection due to scheduling.) Be aware of overhead power lines. 2

The Septic Tank Before you set the tank, be sure that all rocks are removed from the bottom of the hole and the bottom is raked smooth and level. The tank must be level in all directions or you will not pass inspection. If soils are stony, excavation must be bedded with 6 of sand. A word about polyethylene tanks-these have different installation requirements so be sure to get instructions from the tank manufacturer. If you backfill incorrectly, the tank could collapse. Also, these tanks may not come with inlet and outlet baffles, so you will have to construct them. Have your designer provide the required baffle dimensions. The following must be done to pass inspection: Schedule 40 pipe across excavated areas. Six-inch inspection pipes over inlet, outlet, and manhole. Manhole to be at finished grade. A riser will be required if over twelve (12) inches. Manhole must be secured. Seal around inlet, outlet, manhole riser, and around all inspection pipes. Tank level in all directions. Required setbacks from all wells (50 feet), dwellings (10 feet), and property lines (10 feet). Air test required on any building sewer line or lift line within 50 feet of any well head. No part of the system is allowed closer than 20 feet from a well. Lift Station (if required) If you have to lift effluent to the soil treatment area, be sure to get a pump sheet from your designer. This will have information to help you set the pump floats correctly. Be sure to use the correct pipe size and length (the 3

distance from pump to point of discharge). Call your designer if there is a variation in length of lift line and elevation from the calculated specifications on the pump sheet. Using the wrong size pump could cause you trouble. You must also have an alarm system installed. Any electrical wiring must be done to State code. All the requirements for the septic tank (listed above) apply to the lift tank as well with the manhole at finished grade. Soil Treatment Area (drainfield) This area must be protected from heavy equipment to minimize soil compaction. This is the most critical part of your new system and great care should be taken when working in this area. Do not excavate if the soil is wet and do not allow open trenches to be exposed to any form of precipitation or you will not pass inspection. Trench Construction Serial distribution must be used to load individual trenches (e.g. one trench at a time.) Using drop boxes or end caps on chambers. Trenches shall not be less than eighteen (18) inches and no more than thirty-six (36) inches wide if using rock as the distribution medium. If using anything other than rock as the distribution medium, follow manufacturing design guidelines. All trenches must be in original soil. Trench Construction (continued) Total depth shall not exceed forty-eight (48) inches below existing grade. The only exception is if the water table or restricting layer will not allow. Trenches must be level. 4

Must have at least six (6) inches of cover and be crowned to allow for settling. In sandy soils, you must have pressure distribution. Trenches shall not be exposed to precipitation prior to backfilling. A four (4) inch inspection pipe with 3/8 inch or larger perforations spaced vertically no more that six (6) inches apart must be installed at the end of each trench. At least two (2) perforations must be located in the distribution medium. No perforations shall be located above the geotextile cover or wrap. The pipe must extend to the bottom of the trench and be capped flush with or above finished grade. If your design calls for rock-filled trenches, the rock depth of six (6), twelve (12), eighteen (18), or twenty-four (24) inches is a measured depth below the pipe. Then rock is added to completely encase the top and sides of the distribution pipes to a depth of at least two (2) inches. The total thickness of rock-filled trenches must not exceed thirty (30) inches, and drainfield rock must be covered with a durable non-woven geotextile cover. Clean washed rock must be used. Rock must be sized per specifications in Chapter 7080. Drop Boxes The invert (bottom) of the inlet pipe must be one (1) inch higher than the invert of the outlet pipe to the next drop box. The invert of the outlet pipe to the next drop box shall be no greater than two (2) inches higher than the crown (top) of the outlet pipe of the trench in which the box is located. In cases where effluent is delivered by pump to a drop box, the discharge shall be directed against a wall or side of the box on which there is no outlet. A four (4) inch inspection pipe must be installed on each drop box and capped flush or be above finished grade. 5

Drop boxes must be: 1. set level and on a firm base, 2. backfilled, and 3. compacted by hand to minimize settling. Soil Treatment Setbacks Twenty (20) feet from dwellings this includes an attached garage. Ten (10) feet from property lines. Fifty (50) feet from a deep well. One hundred (100) feet from a shallow well. One hundred fifty (150) feet from a lake or river. Note: Above distances also pertain to neighboring wells. Pressure Bed A pressure bed is a rectangular excavation with a level rock base of six (6) or twelve (12) inches. Perforated laterals of one and one-half (1 ½) or two (2) inch pipe are laid level on the rock bed and covered with additional rock. Effluent is then delivered by pump and dispersed over the entire rock bed. Listed below are some important things you need to know: Perforation holes must be drilled straight into the pipe, not at an angle. Perforations must be no smaller than 1/8 and no larger than 1/4. Laterals must be level with the holes downward. Holes must be free of burrs. Holes shall be spaced no more than three (3) feet apart. A method to introduce air into the pipe after dosing must be provided and one (1) hole on end cap. 6

Laterals must be spaced no further than three (3) feet apart, and no further than twenty-four (24) inches from the edge of the rock bed. Laterals must not be installed closer than twelve (12) inches from the edge and end of the rock bed. Total bed depth shall not exceed forty-eight (48) inches from existing grade. Entire rock bed must be covered with a non-woven geotextile fabric. One four (4) inch inspection pipe installed at center end of bed. Same setbacks apply. Pressure distribution pipe clean outs must be provided. Clean outs must be accessible from final grade. Mound System Recommend you hire a professional installer. The Inspection You must schedule an inspection the same day as the installation. The inspector will want to see all components before you backfill so pictures and setback measurements can be taken. You can backfill some trenches partially, but leave the last one open. The inspector must witness any required air tests. If you need a weekend inspection, call in advance as we will need to see if an inspector is available. Weekend inspections are not guaranteed. 7