Guidelines for Selecting and Maintaining Glycol Based Heat Transfer Fluids



Similar documents
Dispelling the Myths of Heat Transfer Fluids. Kevin Connor The Dow Chemical Company

CONVERTING A CLOSED-LOOP WATER SYSTEM TO A GLYCOL SYSTEM

2014 Service Technician Training Program Closed Loop Systems

NORKOOL Industrial Coolants

ALS TRIBOLOGY Engine Coolant Reference Guide

DOWFROST GEO 20: Propylene Glycol-Based Heat Transfer Fluid for Geothermal Heat Pump Systems

NALCO WT-1000 Closed System Corrosion Inhibitor

Metal Rescue Rust Remover Technical Data

Delo XLI Corrosion Inhibitor

Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources

Abrasive Solids Corrosion inhibitors and hard water components that have come out of the coolant solutions and may lead to premature water pump

This chapter is devided into two sections:

: Resin Fibre Discs - Aluminum Oxide, Zirconia Alumina

THE USE OF OZONE IN COOLING TOWERS

Iron and manganese are two similar elements

Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower

EVERYTHING YOU WANTED TO KNOW ABOUT GLYCOL A Brewery Glycol System Guide. Updated

Safety Data Sheet Avesta Neutralization Agent 502

Domestic Chemical Water Treatment Manufacturers Association

DOW CORNING CORPORATION Material Safety Data Sheet

FREE-FLOW Biological Drain Maintenance Systems NCH Corporation

SAFETY DATA SHEET ZANFEL VERSION 1.5.0

DOW CORNING CORPORATION Material Safety Data Sheet

DOW CORNING CORPORATION Material Safety Data Sheet

3.1. Substance Not applicable 3.2. Mixture Name Product identifier % Classification (GHS-US)

Safety Data Sheet. EPSON INK CARTRIDGE T220XL220 Ink for Epson Printers. Proprietary organic materials none. Glycerols none

Material Safety Data Sheet BZK Antiseptic Towelettes / Wipes

WATER-SOLUBLE METALWORKING FLUIDS

SAFETY DATA SHEET TIDYFOAM E2 HAND CLEANER SANITIZER

IMO Approved Tank Cleaning Chemicals

BRAZED PLATE INSTALLATION MANUAL

INTAC PARTS & SERVICES ( H)

DOW CORNING CORPORATION Material Safety Data Sheet

SOFTSOAP LIQUID HAND SOAP LAVENDER & CHAMOMILE

Bio Tread - Hard-Surface Cleaner Safety Data Sheet

Material Safety Data Sheet

Water Treatment & Purification Chemicals

BORYGO EKO car radiator fluid

SAFETY DATA SHEET INSTANT HAND SANITIZER GEL / SANTI-GEL

Technical Information. High-performance Ultra Low Viscous Secondary Refrigerants for Applications down to -50 C TYFOXIT F15-F50.

Material Safety Data Sheet

1. Chemical Product and Company Identification. 2. Hazardous Ingredients

1. PRODUCT AND COMPANY IDENTIFICATION

WATER TABLE WINNERS!

: Fairy Professional Original Washing Up Liquid 5L

Material Safety Data Sheet

Anhydrous Fire Resistant Hydraulic Fluids using Polyalkylene Glycols

Zenith Solar thermal 4.5m pump station Installation manual

: Water and Glycol Leak Detection Solution

Recommended Use: Consumer use : General Household Cleaning

The Use of Magnesium Hydroxide Slurry as a Safe and Cost Effective Solution for H 2

Material Safety Data Sheet Fluid: 5 to 100,000 cp

Material Safety Data Sheet

MURPHY OIL SOAP LIQUID - ORIGINAL

Material Safety Data Sheet

SAFETY DATA SHEET HARMAN Toner Selenium

Best Practice in Boiler Water Treatment

AJAX CLEANER POWDER-OXYGEN BLEACH

SAFETY DATA SHEET. 955 Connecticut Ave, Suite 5202 Bridgeport, CT Tel: Date Prepared: July 22, 2015

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9

Shell Morlina S4 B. Advanced Bearing & Circulating Oils. Interim Technical Data Sheet. Previous Name: Shell Omala RL

EXPERIMENT #9 CORROSION OF METALS

Cooling System Maintenance Products COOLANT

Safety Data Sheet. (REACH Regulation (EC) No. 1907/2006 No. 453/2010)

Corrosion Inhibitors in Antifreeze Coolants

SAFETY DATA SHEET West Skyhawk Drive West Jordan, UT U.S.A. Phone

Automotive Base Oil Presentation

Advantages and Disadvantages of Low VOC Vegetable Based Metalworking Fluids

Material Safety Data Sheet

Material Safety Data Sheet Ampicillin, sodium salt MSDS

PRODUCT SAFETY DATA SHEET Product name: SOFT LEAD PRODUCTS

Material Safety Data Sheet

MATERIAL SAFETY DATA SHEET

Material Safety Data Sheet

: Sharpie King Size Permanent Markers Lacey Road, 10th Floor Downers Grove, IL USA or

Material Safety Data Sheet

Material Safety Data Sheet Fluid: 50 cp

TRICHLOROACETIC ACID SOLUTION Department of Pharmacy Duke University Medical Center Box 3089 Durham, NC

Big Valu Pink Fabric Softener. US: Canada:

SECTION 2: HAZARDS IDENTIFICATION Classification of the Substance or Mixture Classification (GHS-US) Not classified

MATERIAL SAFETY DATA SHEET Description: SAF DRAIN Revision Number: 00

Product Sheet HEAT TRANSFER FLUIDS. Leak Indicator- Clariant CERTIFIED LEAK-INDICATOR-FLUID FOR DOUBLE-WALLED TANKS

MATERIAL SAFETY DATA SHEET

Introducing an All New Line of Cleaning Chemicals

US Safety Data Sheet GEAR OIL SAE 10W/30 GEAR OIL SAE 10W/30

Unit A: Studying Materials Scientifically

Hazardous Substances and New Organisms Act 1996

NON-HAZARDOUS CHEMICAL TREATMENTS FOR HEATING AND COOLING SYSTEMS

Material Safety Data Sheet

Current version : 2.0.1, issued: Replaced version: 2.0.0, issued: Region: GB

COMPOSITION / INFORMATION ON INGREDIENTS

Material Safety Data Sheet Gabapentin MSDS

GROUND WATER CONTAMINATION INFORMATION

Welding. Module

CATHODIC PROTECTION SYSTEM DESIGN

Ergolid EKO antifreeze fluid

Material Safety Data Sheet

Heat Pipe Selection Revision 12/04/2001

MATERIAL SAFETY DATA SHEET

PRETREATMENT TECHNICAL DATA SHEET WATER EMULSIFIABLE RUST PREVENTATIVE PRODUCT DESCRIPTION

Transcription:

Guidelines for Selecting and Maintaining Based Heat Transfer Fluids David Berry Engineering Manager, Chem-Aqua Canada Allan Browning Technical Marketing Manager, Chem-Aqua, Inc. Based Heat Transfer Fluids -water mixtures are commonly used to provide freeze protection in HVAC closed loop heating and cooling systems. is also regularly used to allow low temperature operation in thermal energy storage systems, where ice is made at night and used the following day to cool the building. A properly designed, commissioned, and maintained glycol system can provide 20 or more years of reliable service. However, improperly commissioned and maintained glycol systems can experience severe problems in as little as one to two years. Given the high initial cost of filling a glycol loop, and the even higher cost of the resulting problems if a glycol loop goes bad, it is important to understand how to properly select and maintain a glycol system. Ethylene vs. Propylene Typically either ethylene glycol or propylene glycol are used in HVAC closed loops, with the type of glycol and its concentration determining the freeze point and other physical properties (see Table One). In HVAC applications, ethylene glycol is more widely used because of its lower cost, lower viscosity, and better heat transfer properties. However, due to its moderate toxicity, it is subject to reporting requirements in the event of a spill or discharge (> 5,000 pounds). Propylene glycol is much less toxic than ethylene glycol. Because it is not generally subject to reporting requirements, it is also considered more environmentally responsible. Propylene glycol is typically used in food processing facilities or other applications where there is potential for contamination of potable water or foodstuffs. Using it in a system designed for ethylene glycol can adversely affect performance. For example, the higher viscosity of propylene glycol (about 2x ethylene glycol), especially at lower temperatures, directly translates into higher pumping costs. Its poorer heat transfer properties can also reduce cooling capacity. Automotive antifreezes are unsuitable for HVAC and industrial applications because the high levels of silicate inhibitors can cause heat exchanger fouling and pump seal failures. Preparing a System for Addition Existing Systems Existing systems should be cleaned and flushed thoroughly to remove any rust, scale, and sediment before charging the system with the chosen glycol. For large systems or systems where corrosion is already evident, consult a professional industrial cleaning organization as this procedure may be involved and should be done by an experienced company. If chemical cleaning is used, it is important that all traces of the cleaning agent be removed and the system be thoroughly flushed with water.

Property Ethylene Propylene Comments White Paper Depression More Effective Less Effective More antifreeze is needed of propylene glycol to achieve the same freeze point. Viscosity Lower Higher Propylene glycol increases major head loss in the systems. Pumps head increased. Flammability Low Low Chemical Oxygen Demand Biodegradability Low Degrades in 10-30 days Higher More than 20-30 days to degrade Carcinogenic No No A carcinogen is any substance or agent that promotes cancer. Toxicity High level of acute toxicity when taken orally Lower level of acute toxicity Ethylene glycol should never be used in any drinking water or food processing system. Skin Irritant Low Low Propylene glycol is used in small amounts in cosmetics. Table One - Comparison Between Ethylene and Propylene New Systems New systems are typically coated with oil, grease, or a protective film during fabrication, storage, or construction. Dirt, solder flux, and welding and pipe scale can also cause problems. Therefore, thorough cleaning of new systems is recommended. A solution of one to two percent trisodium phosphate can be used with water for flushing the system. Other commercially available cleaning products may also work. System volume can be calculated during this stage by metering in the initial fill of the system or by chemical analysis of cleaning chemicals after known quantities are introduced into the system. When selecting a glycol concentration based on the desired freeze protection, ensure that the freeze point is at least 5ºF below your lowest anticipated operating/exposure temperature (Table Two). Page 2

% Volume Ethylene % Volume 0 +32 34-3 1 +31 35-4 2 +30 36-6 3 +30 37-8 4 +29 38-9 5 +28 39-11 6 +27 40-13 7 +27 41-15 8 +26 42-17 9 +25 43-19 10 +24 44-21 11 +24 45-24 12 +23 46-26 13 +23 47-28 14 +23 48-31 15 +22 49-34 16 +22 50-36 17 +21 51-39 18 +20 52-42 19 +19 53-45 20 +18 54-48 21 +17 55-52 22 +16 56-55 23 +15 57-59 24 +14 58-62 25 +9 59-66 26 +8 60-70 27 +7 61 < -70 28 +6 62 < -70 29 +4 63 < -70 30 +3 64 < -70 31 +2 65 < -70 32 0 66-99 < -70 33-1 100 +8 Page 3

% Volume Propylene % Volume 0 +32 34 +4 1 +32 35 +2 2 +31 36 +1 3 +31 37-1 4 +30 38-3 5 +30 39-4 6 +30 40-6 7 +29 41-8 8 +28 42-10 9 +28 43-12 10 +27 44-14 11 +27 45-16 12 +26 46-18 13 +25 47-20 14 +24 48-22 15 +24 49-25 16 +23 50-27 17 +22 51-29 18 +21 52-32 19 +20 53-34 20 +19 54-36 21 +19 55-39 22 +18 56-41 23 +17 57-47 24 +16 58-50 25 +15 59-53 26 +14 60-56 27 +13 61-58 28 +12 62-60 29 +11 63 < -60 30 +9 64 < -60 31 +8 65 < -60 32 +7 66-99 < -60 33 +5 100-74 Page 4

Water Quality High quality water should be used for glycol-water solutions. In general, the water quality should follow these guidelines, especially with higher temperatures: < 50 ppm calcium hardness < 50 ppm magnesium hardness < 25 ppm chloride < 25 ppm sulfate If the hardness or other parameters are significantly higher than recommended guidelines, softened or de-ionized water should be considered. Precautions Automatic water-only makeup addition is generally not recommended for glycol systems, especially if used in low temperature applications (< 40oF). Any makeup addition may require that additional glycol and inhibitors be added to maintain the desired level of protection. Inhibited vs. Uninhibited systems will not be adequately protected using conventional closed system treatment programs. They require high levels of specific inhibitors and buffers for protection against corrosion and glycol degradation. These inhibitors can come premixed with the glycol or added as supplemental treatments. sold with the inhibitors and buffers included in the formulation is known as inhibited glycol. Inhibited glycols typically contain four to six percent inhibitors with the remainder being either ethylene or propylene glycol. When using inhibited glycol products, a minimum of 25% glycol must be used to ensure the proper inhibitor levels are achieved. If this 25% concentration is not required for freeze protection, three options exist: 1. Add a higher concentration of the inhibited glycol than needed, which can be expensive. 2. Add compatible supplemental inhibitors and buffers to raise the levels into the desired range. 3. Purchase uninhibited glycol and use supplemental products to provide the necessary level of inhibitors and buffers. Depending on the cost difference between inhibited and uninhibited glycol, option three can be a cost-effective approach, especially in larger systems. However, it is important that your water treatment supplier understands the unique treatment requirements associated with glycol systems and recommends appropriate products. Corrosion and Degradation degradation occurs via three modes: thermal (heat), aeration (oxygenation), and/or microbiological. As a general rule of thumb, the higher the operating temperature and the greater the aeration of the system, the greater the rate of glycol breakdown will be. The products of degradation are various organic acids and water. With respect to microbiological degradation, the system fluid is prone to biological activity if kept below 25% glycol. Untreated glycol solutions are extremely corrosive and will eventually degrade to form organic acids that depress the ph and further contribute to corrosion. Systems containing glycol can have serious, long-term problems unless the proper treatment measures are taken to minimize corrosion and degradation. Page 5

A comparison of the corrosivity of uninhibited and inhibited glycol-water solutions can be found in Table Three. Note that an uninhibited ethylene glycol solution is four-and-a-half times more corrosive towards carbon steel than plain water. If the glycol is allowed to degrade, the corrosion and associated problems will be even more severe. White Paper Metal Type Water Corrosion Rate (MPY) Ethylene Propylene Inhibited Ethylene Inhibited Propylene Mild Steel 9.69 44.50 9.80 0.04 0.04 Cast Iron 21.20 55.70 16.20 0.13 0.05 Copper 0.08 0.16 0.16 0.12 0.04 Brass 0.23 0.46 0.20 0.12 0.08 Aluminum 13.20 19.80 1.80 0.44 +0.36 (weight gain) Table Three - Corrosion Rate of Inhibited and Uninhibited -Water Mixtures Study and test results by Dow Chemical* *ASTM Test D1384-190oF for two weeks, 30% by volume glycol, air bubbling used. An additional concern is glycol contamination. This occurs when a small amount of glycol is introduced into a system, for example the incomplete flushing of winterized coils. When glycol enters a system, bacteria use the glycol as a food source and generate acidic waste products that will rapidly reduce the ph of the loop well below the minimum of eight necessary to impede corrosion. Once the ph is reduced, it begins to solubilize old iron corrosion products, causing the water to turn black and develop a characteristic septic odor. The system is then subjected to under deposit corrosion and acidic conditions, which result in the life of the system being severely reduced. Testing and Monitoring -water solutions should be tested regularly to determine the percentage glycol, ph, reserve alkalinity, inhibitor levels, and degree of contamination. A specially calibrated refractometer is the most reliable and practical means of determining the percentage glycol in the field. Periodic laboratory analysis of the glycol solution is recommended. degradation is a serious problem that can be difficult to address once started. Symptoms of glycol degradation include: ph depression, presence of a sharp aldehyde or septic odor, severe steel corrosion often accompanied by high copper and iron levels, and microbiological problems. Depending on its severity, salvaging the degraded glycol may not be practical. Refractometer Closed loops that contain a high-quality, properly-inhibited glycol solution will provide years of low operating maintenance, provided periodic testing and monitoring are performed. Page 6

Chem-Aqua, Inc. P.O. Box 152170 Irving, Texas 75015 1-800-527-9921 Fax 972-438-0634 www.chemaqua.com Irving, TX Monmouth, NJ Jacksonville, FL Indianapolis, IN Macon, GA Las Vegas, NV Sunnyvale, CA Brampton, ON Page 7 (1M104)