Oil and Coolant Circulating Heating System. Model - OCSM



Similar documents
Wilo SP Series Submersible Sump Pumps ECS. ECS ECS ECS Installation and operating instructions

Hydraulic Trouble Shooting

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

IMPORTANT SAFETY NOTICE

Electric Water Heater

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE

CARING FOR YOUR WATER HEATER

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Dealer Sales & Service Guide

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

BERMAD Fire Protection

PC1131 Electric Air Compressor

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

1/3 HP Submersible Sump Pump with Vertical Float Switch

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

ENGINE COOLING SYSTEM

Heat Pump Water Heater IOM Manual

Rexroth Hydraulic Pump A10VO Series User Manual

Float and Thermostatic Traps Series H, C and X

Ceiling Mount Air Handler Manual

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

STAINLESS STEEL TANK TABLE OF CONTENTS TROUBLESHOOTING... 1 TESTING WATER TEMPERATURE... 3 TANK & JACKET ASSEMBLY... 4.

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

SunMaxx Solar Filling Station Operating Instructions

OPL BASIC. Dosing System for Professional Laundry machines. Contents

BOWIE PUMPS OPERATION - MAINTENANCE

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Thermo Top - Troubleshooting Tree

PC1130 Electric Air Compressor

Diesel Engine Driven Generators Page 1 of 6

SF15K SF05KSS, SF10KSS

Miami Heat Pump HP Series Installation Guide

Technical Guide 08/15/14

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

Instruction Manual. Ultrasonic Cleaning Tank. Advanced Ceramics Technology (M) Sdn. Bhd A Crest Group Inc. Company

Chapter 7 Hydraulic System Troubleshooting

, User s Manual

Instruction manual of pumps WQ, WQF, SN, Furiatka, Furia, KRAKEN, BIG, IP, IPE, SWQ, CTR

SWIMMING POOL HEAT PUMP

INSPECTION AND TESTING OF EMERGENCY GENERATORS

Installation Instructions for Alarm Module Kit A043F059

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page Phase Simplex Page 8-13

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

INSTALLATION & OPERATING INSTRUCTIONS

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual

Hydraulic Troubleshooting PRESENTED BY

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

DC400 Dispensing Cutoff System

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Operators manual Basic water heater

LOBOY 16 AIR CONDITIONERS

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19

SELECTION, APPLICATION AND MAINTENANCE

Installation, Operation, Repair and Parts Manual

Super Cascade Filtration Systems (CE)

Trouble Shooting. Pump

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

D I G I T A L C L A M

Aquamax Australia Pty Ltd ABN

Operating Manual. Los Angeles Abrasion Machine HM-70A & HM-70AF

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

IMPORTANT SAFETY RULES TO FOLLOW

Medical Air Systems: Scroll

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

INSTALLATION INSTRUCTIONS GEO-BOOSTER TM

Cooling Systems. Table of Contents

Occupational Health Program Safety Training Series. Lockout/Tagout Safety Awareness Training

INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER

Owner s Manual. Models: 2S5P & 3S5P OPERATION AND MAINTENANCE OF SELF-PRIMING CENTRIFUGAL TRASH PUMPS PEDESTAL DRIVE

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Tankless Electric (RTE) Troubleshooting

GPD 506/P5 Start-up Procedure and Checklist

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR THE HUBBELL MODEL TX / HX TANKLESS WATER HEATER

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

Cooling system components, removing and installing

CEILING CASSETTE FAN COIL UNIT

Fire Pump Plan Review March 2010

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Fuel Injection Pump, Rotary ( )

Transcription:

Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2

Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine propulsion, diesel-powered generator sets, locomotives, gas compression, or any engine applications. The system is pre-wired, preplumbed, and assembled on a steel plate. Each heating system has an identification plate which includes the part number and date code. Warranty information can be found at www.hotstart.com or by contacting our customer service department. Have your model and date code ready when contacting the warranty department. NOTE: When ordering replacement parts, be sure to reference your heating system s Model and Date Code found on the identification plate and the label above. Typical label actual label may vary slightly from model to model, but the general layout is the same. i

HOTSTART, Inc. 5723 E. Alki Ave. Phone: (509) 534-6171 Spokane, Washington Fax: (509) 534-4216 99212 USA Customer Support: Spokane (509) 536-8660 Texas (281) 600-3700 Germany +49-2241-12737-0 Japan +81-3-6902-0551 www.hotstart.com Important Safety Information WARNING CAUTION Hazardous Voltage: Before wiring, servicing or cleaning the system, turn off the power and install a lockout on the heater circuits at the service panel. Failure to do so could allow others to turn on power unexpectedly, resulting in fatal electrical shock. All wiring shall be done by qualified personnel in accordance with national, state and local codes. Failure to properly ground the system may result in electric shock. Operation of the system during engine operation may cause damage to the heater. Please read carefully: The safety of any system incorporating this heater is the responsibility of the assembler. The safe and proper use of this heater is dependent upon the installer following sound engineering practices. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. All applicable electrical safety standards defined by local jurisdictions must be followed. (reference EU directive 2006/95/EC in EU countries) The heater must be connected to a suitable ground (protective earthing conductor). The power supply must be protected by a suitable overcurrent limiting device. The means of disconnection from the power supply is required. HOTSTART recommends a power switch or circuit breaker be located near the heater for the safety and ease of use. Installers and operators of this equipment must be thoroughly familiar with the instructions in this manual before commencing work. Use proper lifting equipment and rigging to move this equipment. Create a plan before attempting to move. Proper lifting locations are identified with labels on each system, please use these locations when lifting and mounting the system. Hot surfaces: avoid contact with the system while it is in service some surfaces may stay hot even if the system is not energized. Rotating equipment: system can start automatically and without warning avoid contact unless a lockout at the service panel has been installed. NOTICE EU Countries Only: Equipment rated for the conditions listed in EN 61010-1 1.4.1 Ingress protection rating IP44. (Special conditions for specific applications may apply) ii

Table of Contents 1 Installation... 3 1.1 Oil/Coolant Plumbing Diagram... 3 1.2 Mounting... 4 1.3 Suction Line Requirements... 4 1.4 Discharge Line... 4 1.5 Main Power Supply... 4 1.6 Customer Interface Connections... 5 2 Heating System Start-Up... 6 3 Overview of Operations... 7 3.1 Coolant Overview... 7 3.2 Oil Overview... 7 4 Maintenance, Repair, and Troubleshooting... 8 4.1 Periodic Maintenance... 8 4.2 System Maintenance... 8 4.2.1 Plumbing Connections... 8 4.2.2 Magnetic Contactors... 8 4.2.3 Pump Seal... 9 4.2.4 Heating Element Replacement... 9 4.3 Troubleshooting... 10 iii

1 Installation 1.1 Oil/Coolant Plumbing Diagram COOLANT DISCHARGE LINE Plumb to the highest possible entrance of the water jacket at the opposite end of the engine. Outlet hose ID should be the same size or larger than the heater outlet size. OIL DISCHARGE LINE Plumb to opposite end of the oil sump. ENGINE USER SUPPLIED FULL FLOW BALL VALVES CHECK VALVE OIL HEATING TANK OIL PUMP COOLANT HEATING TANK COOLANT PUMP HEATING SYSTEM COOLANT SUCTION LINE Plumb to the lowest possible water jacket port, preferably the main engine drains. Suction line ID should be the same size or larger than the pump inlet size. Avoid elbows whenever possible. Do not reduce the inlet line. Pump seal damage will occur. OIL SUCTION LINE Suction port must be immersed at all times. Keep suction port off bottom of oil pan. Suction line ID should be the same size or larger than the pump inlet size. Avoid elbows whenever possible. Do not reduce the inlet line. Pump seal damage will occur. 3

1.2 Mounting System should be as close to the suction port as possible. It is recommended to mount at or below the oil/coolant level to insure a flooded suction. The system should not be mounted directly to the engine, as vibration can cause failures. Isolate when vibration is present. Heating system should be mounted with the base plate in the vertical position such that the outlet of the heating chamber is pointing up. Clearance is required for heating element removal. CAUTION Lifting hazard: Proper rigging and safety equipment must be used to move this equipment. 1.3 Suction Line Requirements Suction plumbing should be at least the size of the port entering the pump. If the connection to the equipment is smaller than this port size, immediately increase it size to reduce pressure losses in plumbing. A check valve should be used at the oil suction port on the equipment if it is mounted above the level of the oil in order to maintain prime in the pump. NOTICE Seal leaks will occur if suction plumbing is not adequately sized for the pump. 1.4 Discharge Line Size the discharge line per the outlet of the heating system. The heated oil must be returned to the opposite end of the oil sump to ensure even heating. The heated coolant must be returned to the highest point possible in the engine water jacket. NOTICE CAUTION Do not reduce the inlet line. Pump seal damage will occur. Position the heating tank so that it is completely full of oil/coolant while in operation. Fill the suction line with oil/coolant. Pump is not self-priming. Liquid must be present in the pump before start-up. Trapped air inside the pump will cause pump and seal damage. After completing oil/coolant line installation, top-off the oil/coolant levels to compensate for the oil/coolant used to fill the lines and heating tank. The system should be configured with user supplied full port ball valves in the oil/coolant lines, allowing maintenance on the heating system without draining the engine oil/coolant. Pressure and steam hazard: This product generates heat during operation. Operation of heating system with closed isolation valves could result in high pressure and serious injury. It is the responsibility of the installer and operator to ensure that no unsafe condition can result from the generation of pressure. In EU countries, PED (97/23/EC) compliant pressure relief may be required (125psi maximum) 1.5 Main Power Supply Connect the specified power from the customer supplied circuit breaker to the terminal blocks located in the main control box. For three phase applications, the terminal blocks are labeled L1, L2, and L3. For single phase applications, use the terminal blocks labeled L1 and L3 or L and N. The circuit breaker must be near the heating system and easily accessible. The main power ground wire must be connected to the ground lug or ground block on the electrical panel located inside the electrical box. 4

The main power supply operates the heating elements and the circulating pumps. A transformer is used to operate the control circuit. The transformer and control circuits are overload protected with fuses and/or a circuit breaker. WARNING Hazardous Voltage: Before wiring, servicing or cleaning the system, turn off the power and install a lockout on the heater circuits at the service panel. Failure to do so could allow others to turn on power unexpectedly, resulting in fatal electrical shock. All wiring shall be done by qualified personnel in accordance with national, state and local codes. Failure to properly ground the system may result in electric shock. Operation of the system during engine operation may cause damage to the heater. 1.6 Customer Interface Connections Reference electrical schematic and control box drawing for proper wiring locations. Shown below are typical customer interface locations. The Fault signal indicates a fault. The 24 VDC connections are for remote control of the heater is ON. Typical wiring on 24VDC remote control relay is N/C, to switch the remote control relay to N/O move the wire from K1:12 to K1:14. Typical Customer Interface: see included drawings and wiring diagram for specific system locations. 5

2 Heating System Start-Up NOTICE Step 1 Check and tighten all electrical and plumbing connections. Step 2 Ensure isolation valves are open before energizing the system. Step 3 Check for proper rotation of the motor by pressing the prime button while watching the motor shaft or fan. Single phase systems are pre-wired to rotate in the correct direction. On a three phase system, if the pump is not rotating in the correct direction, switch any two electrical leads at the main power terminal block. DO NOT RUN MOTOR/PUMP ASSEMBLY DRY FOR MORE THAN A FEW SECONDS. Running a pump that is not completely filled with liquid will cause damage to the pump seal. Step 4 Bleed all trapped air from the heating system by opening a plug or pipe fitting at or near the pump. Press and hold the prime button to evacuate any remaining air in the lines. Step 5 Energize the heating system by switching the control switch to the ON position. WARNING Hazardous Voltage: Before wiring, servicing or cleaning the system, turn off the power and install a lockout on the heater circuits at the service panel. Failure to do so could allow others to turn on power unexpectedly, resulting in fatal electrical shock. Step 6 Verify that when the engine starts, that the heater ceases operation. This verifies the 24V DC remote operation of the system. 6

3 Overview of Operations 3.1 Coolant Overview The heating system is designed to automatically start following engine shut-down if the switch is on. There is a 24 VDC relay in the system that receives a signal from the engine or equipment control to start and stop the heater. Upon heater start-up, the pump motor runs continuously and the heating element cycles on and off to maintain the set temperature of the heater. The heater acts as an after-cooler as it circulates coolant after an engine shutdown. When the engine has cooled to the set temperature minus the hysteresis, the heating element turns on and raises the temperature to the set temperature, and continues the cycle. If there is a failure in the system that causes a high temperature to occur, the high temperature controller shuts down the entire heating system, including the pump motor. To restart the system, the power switch or the 24 VDC start/stop signal has to be cycled off and back on. 3.2 Oil Overview When the system is energized, a positive displacement rotary gear pump takes oil from the engine sump and forces it through the heat exchanger and into the return line back to the sump. A failure in the oil motor that causes the motor protective switch to trip only stops oil heating. The coolant heater will continue to heat the engine. In this circumstance, the user must press the motor protective switch start button to reset the fault. 7

4 Maintenance, Repair, and Troubleshooting 4.1 Periodic Maintenance Yearly: Drain, clean, and flush heating system Check for cracked and/or weakened hoses and replace if necessary Tighten and check electrical wiring and connections for wear and excessive heat Check mounting bolts and tighten if necessary Remove element and clean element and tank Every 3 years or 25,000 hours of operation: Replace control thermostat Replace heating element contactor CAUTION High Temperature: The thermostat and contactor used in this system are critical components to prevent excessive temperatures that could lead to an unsafe condition. Regular inspection and replacement of these components is required to ensure continued safe operation. This is the responsibility of the maintenance personnel. 4.2 System Maintenance Instructions for the following maintenance procedures are provided to ensure trouble-free operation of your heating system. Replacement parts must meet or exceed original part requirements in order to maintain the compliance level of the original heater. Plumbing Connections Magnetic Contactors Pump Seal Heating Tanks/Elements After maintenance is performed, refer to the start-up section of this manual. WARNING Hazardous Voltage: Before wiring, servicing or cleaning the system, turn off the power and install a lockout on the heater circuits at the service panel. Failure to do so could allow others to turn on power unexpectedly, resulting in fatal electrical shock. 4.2.1 Plumbing Connections Periodically check plumbing connections for leaks and, if necessary, tighten connections. A loose connection on the suction side will cause a loss of flow and cavitation in the pump. It can also pull air into the heating tank and cause an element failure. 4.2.2 Magnetic Contactors Magnetic contactors are used as voltage switching controls for motors and heating elements in HOTSTART Heating Systems. The contactors use 120 or 240 V coils. To test for failure, check for continuity across the coil connections; an open or direct-short reading indicates a failed contactor coil. The contactor contacts should be inspected periodically for welding, arc erosion, and mechanical wear. If any of these conditions exist, replace the contactor. 8

4.2.3 Pump Seal Leakage can occur at any time throughout the life of the seal. Always replace the seal at the first sign of leakage. If the heating system is installed on an engine that is used for a critical application, replace the seal annually. Instructions to replace the seal are included with the new seal. 4.2.4 Heating Element Replacement To replace the heating element or perform routine maintenance, observe the following procedure. The wattage and phase of the heating element are listed on the identification label. WARNING Hazardous Voltage: Before wiring, servicing or cleaning the system, turn off the power and install a lockout on the heater circuits at the service panel. Failure to do so could allow others to turn on power unexpectedly, resulting in fatal electrical shock. Step 1 Turn the heating system OFF, close isolation valves, and lock out at the service panel. Step 2 Drain the fluid from the heating tank. Step 3 Remove the cap from the heating element service entrance enclosure. Step 4 Note the termination points for the wires before removing. Step 5 Remove wires from their terminations. Step 5 Remove the electrical wires from the heating element. Step 6 Remove the 4 screws securing the element in place and remove the assembly. Step 7 Replace the heating element or perform the necessary cleaning procedure. Ensure the o-ring is in place before reassembly. 9

4.3 Troubleshooting Faults indicated by the system only occur from an overheating condition or a tripped motor protective switch. Symptom Possible Causes Solution Indicated System Fault Low Temperature Pump not primed properly Isolation valves may be closed Hose kinked or crushed Leak in suction line Pump motor turning backwards Control thermostat failed closed Motor/pump failure Motor contactor failure Motor protective switch tripped Motor/pump failure Control thermostat failed open Heater has been turned off, fluid is cold Heating element failed System fuses failed or Breaker Tripped Element contactor failed Motor contactor failed Bleed all trapped air from lines, restart system Open valves, restart system Remove obstruction, restart system Repair leak, restart system Reverse any two leads on power in (3 phase systems), restart system Check and replace if needed, restart system Check and replace if needed, restart system Check contacts and coil replace if needed, restart system Check and reset, if problem happens again check motor, restart system Check and replace if needed Check and replace if needed Allow time for heater to heat fluid Check elements for continuity and replace if needed Check all element fuses for continuity and replace as necessary or reset breaker Check contacts and coil replace if needed Check contacts and coil replace if needed 10