30 ms High Speed Transfer System (HSTS) Product Description

Similar documents
IEC in ZX Gas-insulated medium voltage switchgear

UFES Active protection for switchgear

VD4. Vacuum circuit-breaker

DS1 Diode-based transient-free capacitor switch

Service Power Technologies. Retrofitting A future-oriented concept in lifecycle management

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Permissible ambient temperature Operation Storage, transport

The Intelligent AX1 Switchgear for Medium Voltage

Safe and secure distribution of medium voltage with AX1

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Power network telecommunication

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Analog signal converters CC-E I/I Current / current isolators

Data Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work.

Arc Terminator Active Arc-Resistant Switchgear

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic overload relay EF65, EF96 and EF146

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

Remote Monitoring and REC 501 Control Unit Product Guide

Three-phase monitoring relay CM-PFE

HVDC 2000 a new generation of high-voltage DC converter stations

Power products and systems. Intelligent solutions for power distribution Zone concept

Increased power protection with parallel UPS configurations

Electronic overload relay EF19 and EF45

ABB PSPS Erich Steinmann; Generator control-2013

MNS is Switchgear System Technical Overview

HYDRO-ELECTRIC POWER PLANTS

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

How To Choose A Transformer

Medium voltage arc flash eliminator units VAM 3ED,

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

Power transformers. Special transformers Railway

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Product brochure. GMS600 monitoring system for generator circuit-breaker State-of-the-art monitoring

water is cooled in a secondary cooling control tasks: use of seawater. Treatment of the seawater formation of algal vegetation.

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

Comparison of GIS and AIS systems for urban supply networks

Safety technique. Emergency stop module BO 5988 safemaster

Isolated-Parallel UPS Configuration

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Managing Relion IEDs Protection and control IED manager PCM600

Cahier technique no. 196

Industrial IT for Substation Automation & Protection

Gas turbine power plants

2012 San Francisco Colloquium

Fundamentals of Power

Current and voltage measuring relays

Relion. Power system protection and automation reference Fast substation busbar protection with IEC and GOOSE

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network.

Chapter 1. Network Structures

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

Paralleling Switchgear

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Designed for uptime. Defining data center availability via a tier classification system

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Design of electrical power system for a 1000MW nuclear power generating station

ABB i-bus KNX Security Solutions with KNX Security Terminal Product Information

Product brochure Multi Functional Switchgear PASS M kv Flexible and compact switchgear solutions for windfarms

Catalog. Arc Guard System TM TVOC-2

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

Voltage Regulator SPAU 341 C. Product Guide

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

White Paper - July ATS021-ATS022 Automatic transfer switching

Switchgear Application Issues for Mission Critical Power Systems, Part One

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template

CONTENTS.

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Power transformers. Phase shifting transformers Reliable and efficient power flow control

Disturbance Recoder SPCR 8C27. Product Guide

04 / Panel Design Configurator The modular planning software for low voltage distribution systems

EBS852 (Contrac) Power Electronic Unit

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

The ABB i-bus KNX Room Master Concept Your first step into the KNX world

Electrical Shore Connections / Cold Ironing

EFC Frequency converters

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

New standardized approach to arc flash protection

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Unified requirements for systems with voltages above 1 kv up to 15 kv

Arc Protection Relay REA 101. Operator s Manual

Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Communication Unit 560CMU05 Data sheet

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

Arc Protection Relay REA 10_. Product Guide

ABB i-bus KNX DALI Gateways Product Information

Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

Transcription:

30 ms High Speed Transfer System (HSTS) Product Description

2 30 ms High Speed Transfer System (HSTS) Product Description

Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system HSTS 5 1.2 Applications 5 2 The 30 ms high speed transfer system (HSTS) 6 2.1 System preconditions 6 2.2 System structure 6 2.2.1 Busbar with 2 feeders (2 circuit-breaker configuration) 6 2.2.2 Busbar with 2 feeders and a busbar coupling (3 circuit-breaker configuration) 6 2.3 System components 7 2.3.1 REF542plus switchbay protection and control unit 7 2.3.2 SUE 3000 high speed transfer device 7 2.3.3 VM1-T circuit-breaker 8 2.4 How the high speed transfer system functions 8 2.5 Operating time of the high speed transfer system 8 3 Technical data 10 Illustrations Page Figure 1: Structure of the HSTS for a busbar with 2 feeders 6 Figure 2: Structure of the HSTS for a busbar with 2 feeders and a coupling breaker 6 Figure 3: Operating time of the HSTS (Detection time for VS module) 8 Figure 4: Operating time of the HSTS (From fault until clearance of fault) 9 Figure 5: Operating time of the HSTS (From fault until connection of standy supply) 9 Figure 6: Operating time of the HSTS (Total transfer time) 9 Product Description 30 ms High Speed Transfer System (HSTS) 3

Reference documents Title Document Number Revision Date Operating Manual High Speed Transfer System SUE 3000 1HDK400072 D Feb. 2008 Operating Manual Switchbay Protection and Control Unit REF542plus 1MRS756367 C Apr. 2008 Protection Manual REF542plus 1MRS755860 B Sep. 2006 REF542plus, Release 2.6 (SP1), Drawing and Connection Diagram 1VCD400049 Sep. 2003 Operating Instructions BA 543/01 Vacuum Circuit-Breaker VM1-T GCEA670543P0102 Mar. 2011 REF542plus Product Data Sheet 1MRS756368 A Jan. 2007 List of abbreviations Abbreviation HSTD HSTS FDI VS DSP Meaning High Speed Transfer Device High Speed Transfer System Fast Direction Indication Voltage Supervision Digital Signal Processor 4 30 ms High Speed Transfer System (HSTS) Product Description

1 General 1.1 Description of the 30 ms high speed transfer system HSTS In order to protect medium-voltage applications and systems against voltage failures, and to assure almost uninterrupted continued operation of the consumers connected to the process involved, the SUE 3000 high speed transfer device is used. In the event of a disturbance in the supply, it will transfer to a standby supply, taking various factors into due account. The SUE 3000 is used predominantly in the auxiliary supply systems of power plants and in industrial facilities. In conjunction with conventional circuit-breakers and protection devices total transfer times in the range of < 100 ms will be achieved (counting from the occurrence of the fault in the main feeder until the circuit-breaker of the standby feeder is closed). For smooth operation of motor-driven consumers, a transfer in this range will usually be sufficient and non-critical. 1.2 Applications The applications for high speed transfer systems HSTS include sensitive production processes in which even a brief voltage dip can cause serious damage to important production lines and may also result in a total loss of production. Expensive downtimes may ensue. Processes of this sensitivity are characterized by computercontrolled manufacturing and a multiplicity of numerical controls. Typical examples here would include: Automotive production Semiconductor production Paper industry Chemical and petrochemical industry Logistics Glass production etc. For extremely stringent requirements in the millisecond range, only thyristor-based, static systems are a viable option. These, however, will typically possess only a limited connected load capability, necessitate high capital investment, and cause substantial running operation costs, e.g. due to continual losses through cooling systems. For this reason, their use is mostly restricted to protecting important mainframe computer systems. Market investigations and customer requirements more and more show that there is an increasing demand for transfer systems that provide transfer times between the two solutions mentioned above. For this purpose, the SUE 3000 has been extended with additional components and performanceenhancing features, to create the High Speed Transfer System (HSTS). This system with optimized medium voltage circuit breaker VM1-T and switchbay protection and control unit REF542plus, achieves transfer times of 30 ms. This result in a transfer time that permits sensitive industrial processes to continue in operation without any interruption. Product Description 30 ms High Speed Transfer System (HSTS) 5

2 The 30 ms High Speed Transfer System (HSTS) 2.1 System preconditions The high speed transfer system HSTS is able to transfer consumer groups to a standby supply within 30 ms. To enable such ultra-fast transfer times, the system s components have been specifically harmonized for optimum interaction: Voltage sensors Extremely fast detectors for detecting the location of the fault Short signal propagation time thanks to static outputs Optical communication link between REF542plus and the SUE 3000 VM1-T circuit-brekaer with extremely short operating times 2.2 System structure The HSTS is available for switchgear layouts with 2 feeders and one common busbar (2 circuit breaker configuration) or 2 feeders with 2 busbar sections and a coupling circuitbreaker (3 circuit-breaker configuration). For further information on these two variants please consult the Operating Manual of the SUE 3000 high speed transfer device. The function and structure of the two variants differ only in the number of circuit-breakers installed. Each of the feeders is monitored by an REF542plus. These are connected in three phases to sensors for voltage supervision and transformers or sensors for current supervision. A fault in a feeder is detected by extremely fast detectors (VS and FDI), integrated in the REF542plus. Via an optical link this will lead to the initiation of the SUE 3000 high speed transfer device. The SUE 3000 is connected to the two feeders and to the busbar(s) via transformers. In contrast to the REF542plus, the current is measured in a single phase, and the voltage is measured using a concatenated voltage (e.g. L1-L2). Figure 1: Structure of the HSTS for a busbar with two feeders In the system, the REF542plus monitors the actual main feeder. It evaluates the phase voltages and currents by means of the detectors VS and FDI, and in the event of a fault will initiate the SUE 3000 high speed transfer device. This, taking due account of various factors, transfers to the other supply in the fastest possible transfer mode. (See the Operating Manual for the SUE 3000). 2.2.2 Busbar with two feeders and a busbar coupling (3 circuit-breaker configuration) The configuration consists of two independent synchronous feeders, each able to supply the entire load of the busbar. The system consists of two busbar sections, connected to each other via a coupling breaker. In normal operation, the circuit-breakers of the two feeders are closed, and the coupling circuit-breaker is opened. In case of a fault, the system transfers between the faulty feeder and the coupling where-upon the intact feeder supplies both busbar sections. Once the fault in the disturbed feeder has been cleared, a transfer back to the recovered main feeder is possible. In order to execute a transfer, the SUE 3000 monitors and controls all the VM1-T circuit-breakers in the system. 2.2.1 Busbar with two feeders (2 circuit-breaker configuration) The configuration consists of two independent synchronous feeders, each able to supply the entire load of the busbar. One supply is the main feeder, while the other is the reserve supply for the busbar. Both feeders are connected to the busbar via circuit-breakers. The circuit-breaker of the main supply is closed, while the other one of the standby supply is opened. In case of a fault, the high speed transfer system transfers between the faulty and the reserve feeder. Once the fault in the disturbed feeder has been cleared, a transfer back to the recovered main feeder is possible. Figure 2: Structure of the HSTS for a busbar with two feeders and a coupling breaker 6 30 ms High Speed Transfer System (HSTS) Product Description

2.3 System components System component 2-breaker configuration 3-breaker configuration Equipped with REF542plus 2 2 Sensor board, Full-Mainboard, FDI/VS detectors SUE 3000 1 1 Full-Mainboard, static I/O boards VM1-T 2 3 Optimized magentic operating mechanism Current transformer / current sensors Voltage sensors / voltage transformer 1 set of transformers / sensors per REF542plus 1 transformer / sensor per supply for SUE 3000 1 set of sensors per REF542plus 2 transformers per supply and 2 transformers for the busbar for SUE 3000 1 set of transformers / sensors per REF542plus 1 transformer / sensor per supply for SUE 3000 1 set of sensors per REF542plus 2 transformers per supply and 2 transformers for the busbar section for SUE 3000 2.3.1 REF542plus switchbay protection and control unit Besides the general control and protection functions, the REF542plus are equipped with special, innovative detectors for detecting the location of the fault. The high speed transfer device will be initiated in 10 ms. These algorithms are used for very fast, undelayed under- and overvoltage detection and for monitoring the power direction. The REF542plus continuously monitors the analog values of the supply network. When voltage and current sensors are used, they show the following advantages compared to conventional transformers: High accuracy Large linear range Compact dimensions Simple integration in a switchgear panel Initiation of the SUE 3000 via an optical communication link: The transmission of the initiation signals between the REF542plus and the SUE 3000 is realized by means of optical signals in the high speed transfer system. The REF542plus must be equipped with a Full Mainboard (Mainboard 6 Full Version, see REF542plus product data sheet). The REF542plus is equipped with the following hardware: Full Mainboard (optical interfaces) Power supply 1-3 binary input/output modules Analog input board with voltage sensors and current sensors or current transformers Communication board (optional) 2.3.2 SUE 3000 high speed transfer device The SUE 3000 is the heart of the high speed transfer system. The task of the SUE 3000 is to provide nearly uninterrupted transfer from a faulty supply to a redundant independent reserve supply. For this purpose, the SUE 3000 continually compares the network conditions of the feeder currently active with those of the reserve feeder. If the networks are synchronous at the moment when a transfer is initiated, a fast transfer can be performed. In the case of non-synchronous networks, transfer will be performed, depending on the setting involved, in the first phase coincidence (in-phase transfer), after the busbar voltage has reached a permissible value (residual-voltage transfer) or after a parameterizable time has elapsed (time-controlled transfer). Initiation of the SUE 3000 via an optical communication link: The transmission of the initiation signals between the REF542plus and the SUE 3000 is realized by means of optical signals in the high speed transfer system. The SUE 3000 must be equipped with a Full Mainboard (Mainboard 6 Full Version, see SUE 3000 operation manual). The SUE 3000 is equipped with the following hardware: Full mainboard (with optical interfaces) Power supply 3 binary input/output modules (static I/O boards) Analog input board Communication board (optional) Product Description 30 ms High Speed Transfer System (HSTS) 7

2.3.3 VM1-T vacuum circuit-breaker The VM1-T is a special version of the field-proven VM1 vacuum circuit-breaker for use in medium-voltage substations. In contrast to circuit-breakers with a spring operating mecha-nism, the VM1-T is equipped with a magnetic operating mechanism, enabling extremely fast operating times. This will be achieved due to the following characteristics: Magnetic operating mechanism Optimization of the magnetic flux Intelligent control of the coil current Storage of the energy required for a switching cycle in integrated energy storage mechanisms (only a small amount of auxiliary energy needed for switching) Extremely fast operating times The VM1-T can be used in all standard air-insulated substations from ABB and from many other manufacturers as well. Further characteristics can be found in the VM1-T vacuum circuit-breaker operating manual BA 543/01. 2.4 How the high speed transfer system functions In the high speed transfer system both of the two independent supplies are monitored by a REF542plus. In order to assure even faster reaction times, the REF542plus not only have available the usual protective functions but also two detectors developed specifically for the high speed transfer system to detect the location of the fault concerned: FDI (Fast Direction Indiction) and VS (Voltage Supervision) The FDI module continuously checks the power direction of a supply, while the VS module continuously checks for over- or undervoltage. Both modules are described in the REF542plus protection manual). FDI and VS evaluate phase voltages and currents continuously. If a fault is detected in one of the two supplies, the relevant REF542plus will initiate the SUE 3000. In order to obtain additional performance, the REF542plus are connected to the SUE 3000 by fiber-optic cables. 2.5 Operation time of the high speed transfer system The system's performance has been verified by comprehensive testing under realistic conditions. The illustrations below provide examples of the reaction time achieved by the highspeed transfer system: Figure 3: Reaction time of the VS protection function. The time elapsing from detecting the voltage dip to issuing the trip command is in this case 3.2 ms. 8 30 ms High Speed Transfer System (HSTS) Product Description

Figure 4: Reaction time of the system from occurance of the fault to opening of the main contact of the circuit-breaker of the fault supply (13 ms) Figure 5: Reaction time of the system from fault to closing the main contact of the circuit-breaker of the reserve supply (21ms) Figure 6: Total transfer time of the HSTS (30 ms) exemplified on a single-phase voltage fault Product Description 30 ms High Speed Transfer System (HSTS) 9

3. Technical data (*) Opening time VM1-T circuit-breaker Closing time VM1-T circuit-breaker Total transfer time (in case of a fast transfer) 10 ms 16 ms 30 ms The times are referenced to the circuit-breaker VM1-T 1212-25 Auxiliary voltage supply Rated frequency Rated voltage Rated current Short-circuit breaking current 110 / 220 V DC 50 / 60 Hz 12 kv 1,250 / 2,000 A 25 ka (*) Other technical data on request 10 30 ms High Speed Transfer System (HSTS) Product Description

Product Description 30 ms High Speed Transfer System (HSTS) 11

Contact ABB AG Calor Emag Medium Voltage Products Oberhausener Strasse 33 40472 Ratingen, Germany Phone: +49(0)21 02/12-0 Fax: +49(0)21 02/12-17 77 Email: powertech@de.abb.com ABB AG Calor Emag Medium Voltage Products Petzower Strasse 8 14542 Werder (havel) OT Glindow, Germany Phone: +49(0)21 02/12-0 Fax: +49(0)21 02/12-17 77 Email: powertech@de.abb.com Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2011 ABB All rights reserved DEABB 1407 11 GB printed in Germany (03.11-100-AMC) www.abb.com/mediumvoltage