Contents. Introduction



Similar documents
Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3

PART 11: START-UP PROCEDURES FOR THE INSTALLER

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

RVR Hybrid System Installer Instructions RVR Hybrid System Controller Installation Instructions

1 For All Non-Programmable Digital Thermostat

A Class Air Source Heat Pump User Guide

Controller Automation, Model II+

evohome Wireless Radiator Zoning Kit Installation & User Guide

Condensing Boiler Efficiency

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March Emerson Electric Co. All rights reserved.

Homeowner Quick Start Guide. Version 2

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

Split Controller. User Manual SM-SS-F 2009/01/04

Air-conditioning controller. User's Manual NRT 107 F031, F R R2 Sauter Components

Domestic heat pumps. DHP-A Opti DHP-C Opti DHP-C Opti W/W DHP-H DHP-H Opti DHP-H Opti Pro/Opti Pro + DHP-L DHP-L Opti DHP-L Opti Pro/Opti Pro +

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2014/07) en

F454. Web Server. User Manual 05/12-01 PC

RZAHUC program version 1.1 Regulation for Reznor Air Handling Units

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS

30RB/30RQ. Operation and maintenance instructions

GE Concord 4 Quick User Guide

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

ROTEX Gas-Hybrid-Heat Pump

Elite 8D/Lite Version 8 Zone Controller. Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand

Operating instructions

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TraceNet Command TM Application Suite User Guide

Luna 3 Comfort Troubleshooting Guide June 2008

Instruction manual for Firstline FCS12000CH

INSTALLATION OPERATING & MAINTENANCE MANUAL

Fundamentals of Hydronic Design

F453. TiF453. User guide 10/11-01 PC

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

ELECTRIC CENTRAL HEATING FLOW BOILER

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

CGC s Hybrid System Loop Control

NX Series Inverters. HVAC Pocket Programming Guide

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Heating and Cooling Basics Thermostat Control

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions

HEAT HEAT COOL HEAT PUMP COOL

USER S MANUAL. SMDC-16 Digital Control Communicator and SMPC-32 Personal Control

Y-200 Multi-Stage Sequencer

1 General information

PC PROGRAM INSTRUCTIONS

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

HEAT INTERFACE UNITS (Modular)

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

User manual. Solid (FR 98,),

FA701 Series. User s Guide. K6249-2V2 5/09 Rev. A

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

For installation guide see reverse of book

CM927 - User Guide. Description. Features. 7 day Wireless Programmable Room Thermostat with LoT Technology WHAT IS A PROGRAMMABLE ROOM THERMOSTAT?

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

CoolTeg Plus Chilled Water (CW) version: AC-TCW

User's Instructions. Alpha HE CB25/33 and HE SY25

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

HVAC Processes. Lecture 7

Model SETR-50 and SETR-51 Trim Tab Control

Features of your Air to water heat pump

UM-X Field display for continous level sensors

LiteKeeper 4 & 8 Programming Guide and User Manual

QUICK INSTALLATION GUIDE

Operating instructions

User manual. 086U6297 Rev. 9 EN

BoilerMate SP. benchmark. user instructions A - C L A S S

CONTROL STRATEGIES FOR HVAC SYSTEMS

MAKING MODERN LIVING POSSIBLE. Wiring Diagram DHP-R.

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

Service Manual Models: 502, 752, 1002, 1302,

PANASONIC TROUBLE SHOOTING GUIDE

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

Heating, cooling and irrigation system for a house. Control with two controllers TS-55T + 2 depending on the seasons. option 1 Functional scheme

Users Instructions BQ3030 THESE INSTRUCTIONS TO BE RETAINED BY USER

Electric Flow Boiler

ENERGY RETROFIT PROGRAM

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Overheating limit control

Technical Information

Single Zone LCD Thermostat Operating Instructions

Using the STC firmware

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

INSTALLATION AND OPERATION MANUAL

BA Touch. Operating Instructions. Operation and Display Unit for systemp Temperature Controllers and Hot Runner Control Cabinets

Wireless 7 Day Programmable Room Thermostat

Instruction Manual for Operating Panel 301 and 302

Automation System TROVIS 5100 Ventilation Controller TROVIS 5177

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

Chapter 2 System Basics

User Guide. Temperature and Humidity Datalogger. Model 42280

Transcription:

TION Contents Introduction...1 Basics...2 Main Menu Structure...3 Time Schedule Menu...4 Settings Menu...5 Reports Menu...6 Date / Time Adjustment Menu...7 Introduction TION is an advanced control device for outside air compensated temperature control in central heating systems. TION enables substantial energy savings by enabling control of both the boiler itself and a threeway mixing valve. A number of advanced features are also provided to protect the heating system and to increase comfort levels. www.ontrol.com.tr

Basics General LEDs Display Main View TION has a userfriendly display and menu structure, thanks to clear language prompts. Several languages are available. Green LED: Indicates that the device is powered. If this is not on, please check the power connection and associated circuit breaker or fuse. Red (P) LED: Hardware fault indication. This should normally on with the green (power) LED. Blue (S) LED: Indicates that the controller is functional. This should be blinking in normal operation. Red R ve T LEDs: These modbus communication indicators are present only on devices with the optional modbus comms board. They blink to indicate data transfer to a modbus master. All TION series controllers have a 16 character, twoline, backlighted liquid crystal display. When the system is energized, the display will briefly show the selected heating program, then the main view. The main view provides an indication of current system status. Time and date are displayed on the first line. If no keys are pressed for a while, the display reverts to this main view. Pressing the x key repeatedly will also always return to this main view. The possible status indicators in the main view are: Disabled: All pumps are off and valves are in the off position with the freezeprotection logic still functional. Automatic: Normal operation. All outputs are controlled according to the time schedules and temperature control settings. Hot Water: Zone heating is off, but domestic hot water production and control is operational (summer operation). Sync: (Synchronization) After a power interruption, the controller will drive all valves to fully closed position for a short period to reset position tracking.. Soft Start: At the start of the heating period, the controller will limit the system temperature to a maximum of 50 degrees for the defined period, to prevent noise due to expansion of pipes. System Exercise: In summer operation, the pumps and valves are briefly energized to prevent corrosion due to long periods of inaction. This occurs at noon time, once a week. Sterilization: In systems with domestic hot water heating, the sterilization program raises the hot water temperature to 75 degrees once a week to prevent certain viruses. Test: This shows the controller is in manual test mode, which forces all systems to be running for a period of 20 minutes. To exit this mode, the panel can be reenergized. Alarm Detected: Indicates a faulty temperature sensor. Freeze: Indicates that the system is in freezeprotection mode. This occurs when any one of the pipe sensors detect a temperature below 8 degrees, when all the pumps are started. If the temperature falls further to less then 4 degrees, the burner is also fired automatically. High Temperature: This indication occurs when the boiler output temperature is more then 5 degrees above the configured maximum. In this case, the burner is switched off and all pumps are switched on to reduce the temperature. Main View Examples 16:23THURSDAY AUTOMATIC 10:23THURSDAY SOFT START 16:23THURSDAY V1 SYNC. 10:23THURSDAY ALARM DETECTED 2 www.ontrol.com.tr

Keys Only four keys are sufficient to configure and use the system. These are explained below. x Use the UP / DOWN keys to Navigate between menus Change values and setpoints Use the key to Enter the menus from the main view display Select items in menus Save a value change to memory Use the BACK key to Return to the previous menu Exit a value change without saving it From the main view, press the key to access the user menus. UP/DOWN keys can then be used to navigate between menu choices. When the desired choice is in the top line, press the key to select that choice. The BACK key can be used at any time to return to an upper menu. If the selected choice is a parameter value that can be modified, it will start to blink when the key is pressed. The value can then be changed by the UP/DOWN keys. Holding down one of the keys will cause the value to change more rapidly. Press to save the changed value, or the BACK key to exit without saving. WARNING: In the main view, pressing the BACK and UP keys simultaneously will enter the system configuration menus. Changing parameter values in these menus must be avoided except by expert technical service personnel. The configuration options are explained in detail in the Engineering Guide. Main Menu Structure Main menu structure is shown below. Each option is explained in detail in the following pages. 16:23THUSDAY AUTOMATIC 1TIME SCHEDULE 2SETTINGS 3REPORTS 4TIME/DATE ADJ. 1HEATING SCH1 2HOT WATER SCH 1P1 07:3018:00 2P2 07:3014:00 3P3 00:0023:59 4P4 07:3018:00 5P5 07:3018:00 6P6 07:3018:00 7P7 07:3018:00 8P8 07:3018:00 2SETTING 1HEATING SET 2HOT WATER SET 3GENERAL SETT. 1COMFORT SET 1 VALUE : 20.0 C 2ECONOMY SET 1 VALUE : 0.0 C 3REPORTS 1INPUT REPORTS 2OUTPUT REPORTS 3SETPOINT REPS. 4OUT TEMP. REC. 4TIME/DATE ADJ. 16:25 25/03/2010MON www.ontrol.com.tr 3

Time Schedule Menu The Time Schedule menu allows setting of start and stop times for the heating program and the domestic hot water program. A '' or ' ' sign at the end of each line indicates whether each schedule is active or inactive at that instant. Each schedule allows setting of eight different time periods. These are indicated on individual lines P1...P8 on the display, together with configured start and stop times. For each time period, you can set the start time, stop time and days of the week. Monday to Sunday are indicated as numbers 1..7. A plus () sign under these numbers indicates that the program will be used for that day of the week, a minus () sign indicates that it will not be active. To disable a time period completely, simply make all days of the week inactive. The heating system will use the comfort temperature setpoint during the active periods, and the economy temperature setpoint during the inactive periods. 1TIME SCHEDULE 1HEATING SCH.1 1P1 07:3018:00 4HOT WATER SCH 2P2 07:3014:00 3P3 00:0023:59 4P4 07:3018:00 5P5 07:3018:00 6P6 07:3018:00 7P7 07:3018:00 8P8 07:3018:00 1START TIME 07:30 2STOP TIME 18:00 3DAYS :1234567 4 www.ontrol.com.tr

Settings Menu The settings menu allows viewing and changing of setpoints and operating mode. To change any setting first select it by pressing when the parameter is displayed. The value will begin to flash. Use the UP/DOWN keys to select the desired value. Then click to save the new value, or BACK key to return to the old value without saving. 1Heating Settings Comfort Setpoint The desired room temperature during comfort hours. Economy Setpoint 2Hot Water Settings 3General Settings The desired room temperature outside of comfort hours. If this is set to 0 degrees, the heating will be completely switched off outside of comfort hours. Desired domestic hot water temperature. This is active during the periods set in the associated time schedule. If this is set to 0 degrees, domestic hot water heating is completely switched off. 1Panel Running Mode Disabled All functions are disabled except freezeprotection. Automatic Heating operates according to comfort setpoint during the periods set in the heating time schedule. Outside these periods, heating operates according to economy setpoint. If the economy setpoint is zero, heating will be switched off during the offhours. Domestic hot water production is also active, operating during periods set in the hot water time schedule. Hot Water Only domestic hot water production is enabled, main heating program is off. 2Winter/Summer Changeover This setting determines under which outdoor temperature, the heating will be enabled. The system will switch to summer mode if the outdoor average temperature for the last 24 hours is above this setpoint. 2Test mode enable Selecting YES here will enable the Test Mode. For 20 minutes all pumps and burners will be switched on and the valves driven to open position. This is for testing during installation or device only. To exit this mode, either select NO in this menu item, or simply deenergize and reenergize the controller. www.ontrol.com.tr 5

Reports Menu The Reports menu allows monitoring of process values. It only provides information, there are no modifiable parameters under this menu. 1Input Reports 2Output Reports All temperature measurements in the system can be monitored under this menu. Depending on system configuration, some of the below items may not be visible. If???? is displayed instead of a value, there is a problem with the sensor. In this case, the cabling, connections or the sensor itself needs to be checked. 1Outside Air Temperature The currently measured outdoor temperature 2Supply Temperature 1 Water temperature in the first heating circuit, that is controlled by the threeway valve. This line doesn't appear in systems with no threeway control valve. 3Boiler Temperature Water temperature at the boiler outlet. The burners are switched according to this temperature. This line doesn't appear in systems with no boiler. 4Boiler Return Temperature Water temperature returning from the heating circuit. The bypass pump is switched according to this temperature. This line doesn't appear in systems with no bypass pump. 5Hot Water Temperature Domestic hot water temperature in the hot water tank. The DHW heating pump is switched according to this temperature. This line doesn't appear in systems with domestic hot water heating. 6Room Temperature The room temperature sensor is not commonly used in multiapartment dwellings. 7Supply Temperature 2 Water temperature in the second heating circuit, that is controlled by the second threeway valve. This line doesn't appear in systems with no second heating zone or second threeway control valve. 8Supply Temperature 3 Water temperature in the third heating circuit, that is controlled by the third threeway valve. This line doesn't appear in systems with no third heating zone or third threeway control valve. Current system outputs to pumps, burners and control valves can be monitored under this menu. Depending on system configuration, some of the below items may not be visible. 1Heating Valve 1 Threeway valve position, in percent. 4Burner Stage 1 Burner output. In case of a twostage burner, this line is for the first stage. 5Burner Stage 2 In case of a twostage burner, this line displays the current output to the second stage. 6Hot Water Pump The output to the domestic hot water heating pump. 7Circulation Pump The output to the main heating circulation pumps. 8Bypass Pump The output to the bypass pump, typically installed between the supply and return lines of the boiler. 6 www.ontrol.com.tr

3Setpoint Reports This menu is used to monitor a number of values calculated by the controller. 1Calculated Season 4Outside Temperature Records Result of the automatic summerwinter changeover calculation. Determines the operating mode of the system. 2Average Outside Temperature 24hour average of the outdoor temperature. Used for automatic summerwinter changeover logic. 3Zone 1 Effective Setpoint Desired temperature to be maintained at the heating circuit supply line, by positioning the threeway valve. This calculation is based on the outdoor temperature and comfort or economy setpoint, depending on the time schedule. 4Effective Boiler Setpoint Desired temperature to be maintained at the boiler supply. 5Effective Room Addon When a room temperature sensor is deployed, this parameter determines how much the supply temperature will be shifted, depending on deviation from the comfort or economy setpoint. 6Effective DHW Setpoint Setpoint currently active for domestic hot water heating pump control. 7Zone 2 Effective Setpoint Desired temperature to be maintained at the second heating zone circuit supply line, by positioning the second threeway valve. 8Zone 3 Effective Setpoint Desired temperature to be maintained at the third heating zone circuit supply line, by positioning the third threeway valve. Average hourly outdoor temperatures for each hour of the last 24 hours. These will be reset if the controller loses power. Date / Time Adjustment Menu 4DATE/TIME ADJ. 10:23 30/07/2009MON Select this menu and press the key again to start the date/time adjustment. Initially the hour value will be flashing and adjustable by the UP/DOWN keys. Press the key to move to the next value and adjust similarly. www.ontrol.com.tr 7