Drying of brick walls after impregnation



Similar documents
Frost Damage of Masonry Walls A hygrothermal Analysis by Computer Simulations

Long-Term Hygrothermal Performance of Green Roofs

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan

Martin Krus, Klaus Sedlbauer, Herbert Sinnesbichler

Moisture Content in Insulated Basement Walls

WUFI-ORNL/IBP A North American Hygrothermal Model

Influence of rain water leakage on the hygrothermal performance of exterior insulation systems

Mold Preventing I nterior System

Technical Data Sheet Art. No Kiesol. applications. Shelf-life. rate depending on application. Characteristic data of the product

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

FIXIT.CH. Aerogel Insulating Plaster System. Handling Guidelines. Easy to use. Mineral based W/mK BAUSTOFFE MIT SYSTEM

Hygrothermal Simulations and Analysis of Solar- Driven Inward Water Vapor

Moisture risk in prefabricated wooden wall elements (TES-elements) with a vapour retarder of OSB/3

Development of conservation compatible new materials for envelope retrofitting of historic buildings

Basements are Changing. Basements Part of the Enclosure. Basements. Energy Efficient, Durable, Healthy. Below grade enclosure

Improving the flood resistance of your home. Advice sheet 4: Flood-resilient walls.

Post-insulation of cellar ceiling and cellar walls

Sustainable construction criteria to evaluate the thermal indoor climate - further development of the BNB assessment tool and practical implementation

WATERPROOFING OF WET ROOMS

orizontal BarrierS PATENTED SYSTEM

ROOFS, SNOW AND ICE DAMS

Basement Insulation: Best Practices for Efficient, Durable, & Healthy Homes

HEALTHY LIVING WITH WOOD FIBRE INSULATING MATERIALS

Moisture-Safe Unvented Wood Roof Systems

EPSRC Research Project EP/G00028X/1. Environmental Assessment of Domestic Laundering. Final Modelling Report

NANSULATE NANOTECHNOLOGY BASED SOLUTIONS TO REDUCE HEAT LOSS THROUGH WINDOWS

3 Masonry and Manufactured Stone (Interior and Exterior)

Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction

European technical approval

Baumit Renders for Porotherm Masonry. Application Guidelines. n Light and easy application n Tried and tested

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls

Salt Weathering of Masonry Walls The Venice Experience. By M. Collepardi, S. Collepardi and R. Troli

WUFI 2D. Calculation Example Step by Step. D. Zirkelbach Th. Schmidt H.M. Künzel M. Kehrer Ch. Bludau

Molds and mildew are fungi that grow

Module 3.7. Thermal bridging

Crawl space heat and moisture behaviour

Signs of insulation problems In the winter. In the summer. conditioning system

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

PERFORMANCE GUIDELINES

Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi

Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM

Exemplary Retrofitting of an Old School in Stuttgart - EROS -

Garver Feed Mill Condition Evaluation

Water Damage & Repair

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

Infrared Moisture Detection

Sealing & Bonding Sika solutions for Window Installation

Repair of Spalling and Leaking Clay Brick Building Walls

European Technical Approval ETA 13/0526

Chimney systems ICOPAL WULKAN C/CI/C-eko/CI-eko

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

Insulating Basements: Part 3 Basement Wall Systems

Aalborg Universitet. Reduction of moisture problems in old basements Brandt, Erik; Møller, Eva B.; Vesterløkke, Michael

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program

WATERPROOFING SYSTEMS IN BUILDING CONSTRUCTION

National Building Code of Canada 2010

Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving

In accordance with the Department of Labor and Industry s statute , Subd. 11,

ETAG 004 EXTERNAL THERMAL INSULATION COMPOSITE SYSTEMS WITH RENDERING

Understanding BS EN 771-3: Aggregate concrete masonry units

Chapter D9. Irrigation scheduling

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

High performance thermal insulation materials

Models and Methods in Applied Sciences

The Influence of Low-Permeance Vapor Barriers on Roof and Wall Performance

TEXTILE FABRICS AS THERMAL INSULATORS

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

Foundation. Foundation

CONDENSATION. Section Break (Next Page)

BEST PRACTICE GUIDE. Fibrelime Premixed Universal Plaster and Render

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Mineral waterproof coating PCI Dichtschlämme

EXPERT OPINION on the applicability of the construction technology "GRÈMOUND non-tectonic system on grounds of the documentation submitted

CHAPTER 3. The sun and the seasons. Locating the position of the sun

Wall Moisture Problems in Seattle

Energy savings in the residential area are essential in

Introduction. 1. Heat Transfer. In Townsville s climate it is essential to choose building materials that perform well in our local conditions.

AND MEMBRANES ROOFING UNDERLAYS.

How To Test Water Penetration On Concrete Block And Mortar

Water Permeability vs Waterproof

ELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.

Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

DETERMINATION OF WOOD MOISTURE PROPERTIES USING CT- SCANNER IN A CONTROLLED ENVIRONMENT

Building Condition Assessment: West Lexington Street Baltimore, Maryland

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

TECH BULLETIN. Roofing No. Impact of Temperature on Polyiso R-value. Subject: Impact of Temperature on the R-value for Polyisocyanurate Insulation

Tunnels & Arches OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM

Metropolitan Builders Association Masonry & Concrete Standard

Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group

Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades

Garden Bothy, Cumnock

THERMAL STORAGE WITH PCM VS. THERMAL INSULATION IN WARM AND HOT CLIMATES

Transcription:

Drying of brick walls after impregnation H.M. Künzel and K. Kießl Fraunhofer-Institute of Building Physics (Director: Prof. Dr.-Ing. habil. Dr. h.c. Dr. E.h.mult. Karl Gertis) Abstract Elevated moisture due to driving rain impact on unrendered brick walls can lead to frost damage or accelerated decay of the exposed facade. Additionally, in the case of monolithic exterior walls which are often encountered in historic buildings, a high water content reduces the already low thermal resistance of the wall, thus leading to poor hygienic indoor conditions. Since the appearance of the facade should in general remain unaltered for esthetical reasons, the obvious measure to improve the moisture protection and thermal quality of brick masonry is the impregnation with water repellent agents, possibly combined with an interior insulation. In field test, the effect of siloxane impregnation on the moisture behaviour of exposed brick masonry with and without cracks was examined in comparison with untreated as well as with sheltered facades. In all cases the impregnation of exposed wall elements with elevated moisture led to a drying process which resulted in low water contents, similar to the moisture conditions of sheltered facades. The drying of the impregnated wall elements with a thickness of 24 cm takes about one year. Since monolithic brick walls of historic buildings are mostly thicker, complementary heat and moisture transport calculations were carried out for representative walls. Depending on the interior finish (e.g. insulation) of such brick walls, the drying time after impregnation ranges from 2 to 7 years. In order to avoid frost damage or a long dry-out time, an interior insulation is best applied some time after impregnation. Key words: Brick wall, frost damage, impregnation, water repellent agents, water content, heat and moisture transport. Drying of brick walls after impregnation 1

1. Introduction Single layer brick walls of old buildings often lack sufficient protection against driving rain and may thus exhibit elevated moisture contents, especially on the weather side. This further reduces the mostly low thermal resistance of these walls, which may in some cases even fall below the minimum heat insulation required for hygienic reasons. Additionally, an elevated moisture content entails the danger of frost damage close to the facade. Installing an interior heat insulation, e.g. to increase thermal comfort, aggravates this danger since the drying process of the wall is slowed down and its mean temperature reduced. Prerequisite for a better thermal quality and a better protection against moisture of these walls is therefore an increased rain protection. In the case of unrendered masonry, which should retain its appearance for esthetical reasons, the only way to improve rain protection is repointing the facade and treating it with water repellent agents. In this paper the performance of siloxane impregnation is examined in a field test and the consequences of such a treatment for the hygrothermal behaviour of single layer brick walls with and without interior insulation is analysed by experimentally verified heat and moisture transfer calculations. The drying time of representative walls after impregnation is assessed by assuming an effective long term rain protection by the water repellent treatment. 2. Experimental and numerical investigations 2.1 Combination of field tests and calculations It has been shown in [1] that a combination of field tests and heat and moisture transport calculations can enhance the interpretation and transferability of experimental results concerning the hygrothermal behaviour of building components. If the measured and calculated results for a certain construction element correspond well, it can be assumed that the dominant factors for the hygrothermal behaviour of the considered construction are correctly implemented in the calculation model. This means that further conclusions can be drawn by a numerical study without additional costly and time consuming field tests. Drying of brick walls after impregnation 2

2.2 Experimental set-up In a test hall which is conditioned during wintertime of 20 C and 50 % R.H., masonry elements with a surface of 60x60 cm 2 and a thickness of 24 cm have been exposed with one side facing to the wet and to the east, respectively [2]. The western facade of the hall faces a plain without any obstructions. The amount of driving rain hitting the facade varies between about 400 to 500 l/m 2 a year. The eastern facade is sheltered by a overhanging roof, so that hardly any rain water hits it. The masonry in the wall elements is made of solid brick (format: 24x11.5x5 cm 3 ) and lime-cement mortar. The mortar gaps have a thickness of about 15 mm. At some elements, artificial cracks were introduced with a thin wire while the mortar was still soft, which led to cracks of up to 1 mm in thickness between the mortar and the brick. After exposing the wall elements to the natural climate in Holzkirchen (Bavaria), the water content was monitored by weighing the elements about once a month. Due to unusually dry weather at the beginning of the observation period, the elements facing west were sprayed by a lawn sprinkler in the end of May 1993 in order to obtain a representative water content. Five days later, half of the wall elements were treated with siloxane in organic solvent while the other half of the elements remained untreated. The impregnation was applied twice with the aid of a paint brush by wetting the surface thoroughly. The total amount of solution taken up by the masonry was about 0.3 kg/m 2. After the treatment, the moisture behaviour of the wall elements was registered by discontinuous weighing for a period of more than two years. Towards the end of the observation period, the rain protection of one element was blemished by drilling holes (diameter 3 cm) in the facade and filling them with untreated lime-cement mortar, thereby producing an unimpregnated area of less than 2 % of the facade element. 2.3 Heat and moisture transfer calculations The calculations are done with the PC-program WUFI, a one-dimensional version of the calculation model described in [3]. Although this model has been validated by comparison with experimental results several times, a verification of the calculations for this case is necessary because the material parameters of the masonry have to be approximated from standard material properties as listed in table 1. The resulting liquid diffusivities for water absorption and liquid redistribution, res. drying, are shown in Fig. 1. The retention curve is approximated from the sorption moisture at 80 % R.H. and the capillary saturation according to [3]. As boundary conditions for the comparison, the Drying of brick walls after impregnation 3

Table 1: Hygrothermal parameters of brick masonry and the interior insulation materials. material brick masonry expanded polystyrene mineral wool insulating plaster density [kg/m 3 ] 1900 15 60 310 thermal conductivity [W/mK] moisture related increase of λ [%/M.-%] vapour diffusion resistance factor [-] sorption moisture at 80 % R.H. [Vol.-%] capillary saturation [Vol.-%] 0.6 0.04 0.04 0.07 15 -- -- 1 10 30 1.3 8 1.8 -- -- 1.3 19 -- -- 20 Fig. 1: Liquid diffusivity of the brick masonry for water absorption during rain periods and the redistribution respectively drying process. Drying of brick walls after impregnation 4

measured meteorological data, i.e. temperature, relative humidity, driving rain and solar radiation of the test period, are used in form of hourly mean values. The initial moisture content assumed for this calculation is the water content after the spray-wetting of the wall elements assuming a uniform distribution. The effect of the water repellent impregnation is simulated by a non water-absorbing surface and an additional surface diffusion resistance of 0.2 m which was measured by a wet-cup test. The thickness of the tested wall elements is not representative for single layer brick walls found in old buildings, which are mostly at least 40 cm thick. The same holds for the precipitation load in Holzkirchen which is classified in driving rain group III according to [4]. Unrendered brick walls cannot bear such a high load and are therefore uncommon in areas classified in group III. Therefore, the driving rain load in the outdoor boundary conditions taken from an average year in Holzkirchen has been reduced to one third of the measured amount. The interior temperatures and relative humidities are approximated by sine waves with mean value of 22 C and 50 % relative humidity and amplitudes of 2 K and 10 % R.H., respectively. The maximum values are reached in July. In contrast to [5], where the moisture distribution in an exposed wall was derived from the measured distribution in a rendered brick wall, the conditions in untreated walls without insulation and with 6 cm of interior insulation using different insulation materials (material parameters are given in table 1) is determined by calculating over several years applying the same meteorological data until no changes from one year to another are observed anymore. From the thus obtained moisture distribution, the drying behaviour of the walls after impregnation is calculated assuming a perfect rain protection, i.e. without water absorption of the exposed surface. 3. Results 3.1 Performance of siloxane impregnation in the field test The course of the change in water content of the exposed wall elements during the observation period is shown in Fig. 2. Prior to the siloxane impregnation, which was applied in the beginning of June 1993 shortly after the spray wetting of the west facing elements, the moisture change of the west facing elements are very similar. After the impregnation however, the untreated masonry elements are becoming increasingly wet until they reach a dynamic equilibrium, whereas the siloxane impregnated masonry Drying of brick walls after impregnation 5

elements dry out continuously. As expected, the drying process is faster in summer than in winter. There appears to be no influence of the cracks on the moisture behaviour of the masonry since the changes in water content with and without cracks between the bricks and the mortar are almost equal for the treated and the untreated wall elements. The effect of the untreated mortar areas in the impregnated facade without cracks introduced in autumn 1995 (hollow circles in Fig. 2 above) seems, however, quite important. The increase in water content compared to the unaltered impregnated masonry element (full circles in Fig. 2) has to be carefully observed in future. The eastward facing sheltered wall elements show no difference in the moisture behaviour for the treated and untreated masonry. The slight increase in material moisture during winter time due to vapour diffusion from the inside and a higher relative humidity on the outside is equal in both cases. That means that the siloxane impregnation has only a minor effect on the vapour diffusion and sorption behaviour of the masonry. 3.2 Comparison of calculation and experiment The calculated and measured courses of the mean water content of an impregnated and an untreated west facing wall element after the artificial wetting are compared in Fig. 3. The agreement between the calculated results and the measurements is quite good which means that the approximated material parameters are sufficiently accurate in order to obtain realistic calculation results. It also shows that rain water penetration of the impregnated facade is very low because the measured water content hardly deviates from the calculated course where zero water absorption is assumed. 3.3 Calculated moisture behaviour of a representative wall The annual mean moisture profiles (solid lines) and the annual variation range (hatched areas) in the masonry of a 40 cm thick untreated brick wall with and without interior insulation are shown in Fig. 4. In all cases, the exterior surface shows the highest variation in water content but the annual mean water content there is rather low. The variations are decreasing rapidly towards the interior of the wall, whereas the mean water content increases steeply. While the annual mean moisture reaches a peak of about 8 Vol.-% in the masonry without insulation, the maximum with interior insulation lies above 10 Vol.-%. This means that the frost damage risk of a brick facade is considerably increased by applying an interior insulation. Compared with the uninsulated wall, the influence of the type of insulation on the moisture behaviour of the masonry is not significant. This shows that there is no risk-free interior insulation measure, because the reduction in masonry temperature seems to be more important Drying of brick walls after impregnation 6

for the drying process than the vapour permeability of the insulation layer. A low vapour diffusion resistance leads to better drying conditions during summer time which are almost compensated by interstitial condensation during the heating period. Fig. 2: Moisture behaviour of the exposed masonry elements over a period of approximately three years. The roman numbers indicate the quarters of a year. The impregnation of the exterior surface of the elements was done shortly after the spray wetting. Drying of brick walls after impregnation 7

Fig. 3: Comparison of the calculated and the measured variation in water content of 24 cm thick brick masonry under natural conditions. The initial water content (marked with an arrow) was reached by artificial spray wetting of the facade elements. Fig. 4: Annual mean profiles (solid lines) and annual variations (hatched areas) of the water content in the masonry of a west oriented wall without and with different types of interior insulation. Drying of brick walls after impregnation 8

If the moisture content in the masonry shown in Fig. 4 is regarded to be too high, an impregnation of the facade may be considered. However, an immediate change of the moisture conditions after application of the water repellent agent should not be expected. Fig. 5 shows the development of the mean water content in the masonry with and without insulation starting from the calculated moisture profiles analogous to those in Fig. beginning of July after facade impregnation. While the uninsulated masonry reaches the practical moisture content of 1.5 Vol.-% in less than two years, it takes more than five years for the insulated walls to dry out completely. Fig. 5: Drying behaviour of unrendered brick walls without and with different types of interior insulation after impregnation. The initial water content in the walls corresponds to the respective condition at the beginning of July without impregnation. 4. Discussion of the results and conclusion The field test shows that a siloxane impregnation, if properly applied, can repel rain water to such an extent that a complete drying of the masonry is possible. The question remains, however, whether the experience from rather small test elements even with artificial cracks which were impregnated by experts can be translated into the application on a real building. It seems possible that in inappropriate impregnation can Drying of brick walls after impregnation 9

even increase the moisture content and hence the danger of frost damage as stated in [6]. The quality of workmanship and the preparation of the facade, for example by repointing it, appear to be of major importance. If the quality conditions are met, an impregnation can be considered as an effective rain protection. Small cracks up to 1 mm wide do not affect the rain protection if they are thoroughly impregnated and if the wall is of sufficiently low air permeability, e.g. by the application of a plaster on the inside. A similar result for cracks up to 0.5 mm has been obtained by laboratory simulations [7]. The drying time of the masonry even after an effective impregnation should not be underestimated. It is recommendable to install an interior insulation after the impregnation and leaving some time for the excessive moisture in the masonry to dry out. Finally, it should be noted that a high accumulation of salt in the brickwork may impede the drying process or even prevent it altogether [8]. Under these circumstances, impregnation measures may fail to have the desired effect or even worse, salt crystallisation behind the impregnated surface layer may lead to spalling effects at the facade. If the moisture in the wall is not due to ran but to rising damp, an impregnation can result in a further rise of the water front. Literature [1] Künzel, H.M. und Krus, M.: Beurteilung des Feuchteverhaltens von Natursteinfassaden durch Kombination von rechnerischen und experimentellen Untersuchungsmethoden. Bauinstandsetzen 1, 5-19 (1995). [2] Riedl, G. und Kießl, K.: Untersuchungen zum Feuchteverhalten von Ziegelmauerwerk mit unterschiedlichen Imprägnier- und Beschichtungssystemen unter natürlicher Bewitterung. Report of the Fraunhofer-Institut für Bauphysik FtB- 31 (1994). [3] Künzel, H.M.: Simultaneous Heat and Moisture transport in Building Components. IRB-Verlag, Stuttgart (1995). [4] DIN 4108, Teil 3: Wärmeschutz im Hochbau. Klimabedingter Feuchteschutz. August 1981. [5] Künzel, H.M. and Kießl, K.: Hydrophobing historical facade for rain protection and thermal quality purposes. Proceedings of the International Symposium on Moisture Problems in Building Walls. Porto, 11.-13. Sept., pp 1-14 (1995). [6] Franke, L. und Bentrup, H.: Schädigung von Mauerwerksbauten durch Umwelteinflüsse; Beurteilung und Instandsetzung. Bauphysik 13, 187-195 (1991). [7] Franke, L. und Bentrup, H.: Einfluß von Rissen auf die Schlagregensicherheit von hydrophobiertem Mauerwerk und Prüfung der Hydrophobierbarkeit. Bautenschutz + Bausanierung 14, 98-101 and 117-121 (1991). [8] Künzel, H.: Trocknungsblockade durch Mauerversalzung. Bautenschutz + Bausanierung 14, 63-66 (1991). Drying of brick walls after impregnation 10