Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements

Similar documents
The Grid Interconnection of Renewable Energy at Distribution Level with the Features of High Power-Quality Improvement

v v v Keywords-- Power Quality, Shunt active filter, Indirect current control, ANN control

Parametric variation analysis of CUK converter for constant voltage applications

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: [633] [Choudhary, 3(12): December, 2014] ISSN:

New Control Strategy To Improve Power Quality Using A Hybrid Power Filter

How To Improve Power Quality

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

A new approach for three-phase loads compensation based on the instantaneous reactive power theory

POWER QUALITY IMPROVEMENT OF GRID INTERCONNECTION WITH RENEWABLE ENERGY SOURCES AT DISTRIBUTION LEVEL

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique

FOUR LEGGED ACTIVE POWER FILTER COMPENSATION FOR A UTILITY DISTRIBUTION SYSTEM

Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Control of a Three Phase Induction Motor using Single Phase Supply

Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique

Control of a 3-phase 4-leg active power filter under non-ideal mains voltage condition

New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar

Analysis of AC-DC Converter Based on Power Factor and THD

SIMULATION OF CLOSED LOOP CONTROLLED BRIDGELESS PFC BOOST CONVERTER

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.

MODELING AND SIMULATION OF A THREE-PHASE INVERTER WITH RECTIFIER-TYPE NONLINEAR LOADS

Mathematical Modelling of PMSM Vector Control System Based on SVPWM with PI Controller Using MATLAB

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

MULTI-LEVEL INVERTER WITH DC LINK SWITCHES FOR RENEWABLE ENERGY SOURCES

Product Data Bulletin

International Journal of Power Control Signal and Computation (IJPCSC) Vol. 2 No. 2 ISSN : X

POWER QUALITY ISSUES IN A STAND-ALONE MICROGRID BASED ON RENEWABLE ENERGY

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

How To Improve Power Quality

High Intensify Interleaved Converter for Renewable Energy Resources

Variable Voltage Variable Frequency Speed Control of Induction Motor Using FPGA-Xilinx

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

MODELLING AND SIMULATION OF SVPWM INVERTER FED PERMANENT MAGNET BRUSHLESS DC MOTOR DRIVE

Line Reactors and AC Drives

An Efficient AC/DC Converter with Power Factor Correction

The design and performance of Static Var Compensators for particle accelerators

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

A Novel Control Strategy of Three-phase, Four-wire UPQC for Power Quality Improvement

Low Frequency AC Transmission System

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

Keywords: Electric circuits, passive circuits, active circuits, voltage source inverter, reactive power theory, active filters.

Keywords: Self-Excited Induction Generator (SEIG), Single Phase Synchronous D-Q Frame Theory, Static Synchronous Compensator (STATCOM).

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

A Novel Three-Phase Active Power Filter

Dynamic Simulation of Induction Motor Drive using Neuro Controller

A bidirectional DC-DC converter for renewable energy systems

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

Simulation on Micro Wind Power Generator with Battery Energy Storage for Critical Load

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

How To Simulate A Multilevel Inverter

TORQUE RIPPLES MINIMIZATION ON DTC CONTROLLED INDUCTION MOTOR WITH ADAPTIVE BANDWIDTH APPROACH

Introduction. Harmonics and IEEE 519 Page 1 of 19

LOW-VOLTAGE three-phase four-wire electrical distribution

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Genetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads

Novel Loaded-Resonant Converter & Application of DC-to-DC Energy Conversions systems

Enhancement of load balancing for dynamic loads using D-STATCOM

Power System Harmonics

MATHEMATICAL MODELING OF BLDC MOTOR WITH CLOSED LOOP SPEED CONTROL USING PID CONTROLLER UNDER VARIOUS LOADING CONDITIONS

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

Design And Implementation Of Seven Level Inverter With Solar Energy Genration System

K.Vijaya Bhaskar,Asst. Professor Dept. of Electrical & Electronics Engineering

Advance Electronic Load Controller for Micro Hydro Power Plant

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters

DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,

Considering the effects of UPS operation with leading power factor loads

Modeling of electric railway vehicle for harmonic analysis of traction power-supply system using spline interpolation in frequency domain

Network Theory Question Bank

STATOR FLUX OPTIMIZATION ON DIRECT TORQUE CONTROL WITH FUZZY LOGIC

Survey of Harmonics Measurements in Electrical Distribution Systems

Three phase circuits

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Lecture - 4 Diode Rectifier Circuits

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Online Tuning of Artificial Neural Networks for Induction Motor Control

Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )

Application Guide. Power Factor Correction (PFC) Basics

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Analysis of PV cell fed High Voltage Gain Seven and Nine level inverter with Reduced Switches

MODELING AND SIMULATION FOR VOLTAGE SAGS/SWELLS MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)

Transcription:

International Journal of Electrical and Computer Engineering (IJECE) Vol.1, No.1, September 2011, pp. 31~ 42 ISSN: 2088-8708 31 Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements 1 Y.Kusuma Latha, 2 Ch.Saibabu, 3 Y.P.Obulesh 1.3 Department of EEE, Lakireddy Balireddy College of Engineering (Autonomous), Mylavaram-521230, A.P, India 2 Department of Electrical Engg, University College of Engineering (Autonomous), JNTUk, Kakinada, A.P, India e-mail: kusumalathay@gmail.com, chs_eee@yahoo.co.in, ypobulesh@gmail.com Abstract The active power filter has been proved to be an effective method to mitigate harmonic currents generated by nonlinear loads as well as to compensate reactive power. The methods of harmonic current detection play a crucial part in the performance of active power filter (APF). This paper presents a new control strategy in which two shunt active power filter configurations are developed in order to define new simple control algorithm which requires minimum number of current measurements. The effectiveness of the proposed control strategies are demonstrated through results. The proposed systems are implemented with MATLAB/SIMULINK. The simulation results are presented for two control strategies and comparison is made among them. Keywords: Harmonics, Active power filter, current sensors, power qualityinprovement 1. Introduction The increasing use of solid-state power-conversion equipment (rectifiers,inverters, cycloconverters) and other power electronic-type devices (voltage controllers, motor-speed controllers) on distribution systems is causing utilities to become much more concerned about voltage and current harmonic levels[1,2]. The nonlinear characteristic of the power semiconductors results in serious harmonics and reactive power pollution in power system[3.4]. The effective methods for harmonic suppression and reactive power compensation are more and more needed. The Passive Power Filter (PPF) is a traditional way for harmonic suppression, which is composed of power capacitor, power inductance and resistance. PPF has been regarded as the main approach in the field based on its simple architecture, little maintenance and well-developed design. But there are several disadvantages existing in PPF:1) filtering characteristic depends on the impedance of the power supply;2) the impedance characteristic is deteriorated with the frequency reduce to below the lowest resonance frequency;3) PPF can not filter the noncharacteristic harmonics entirely; 4) it s possible to result in current resonance. Active power filters are used to eliminate harmonic currents as well as to compensate for reactive power [5,6]. Principally, the active power filter operates by detecting harmonic current to calculate the amount of the compensating current needed for feeding back to the power system in the opposite direction of the harmonic current[7,8]. In the conventional p-q theory based control approach for the shunt APF, the compensation current references are generated based on the measurement of load currents and the current feedback from the shunt APF output is also required and therefore, minimum four current sensors are desired in a balanced system[9,10]. In this paper, in order to simplify the control scheme for the three phase sunt active power filter, two types of configurations for are developed based on single current measurement. One control scheme based on measurement of load current only, and other control scheme based on measurement of source current only. 2. Proposed control startegies Basic principle of shunt active power filter is showed in Fig.1. Shunt active power filter is mainly composed of harmonic current detecting circuit and compensation current generationcircuit and is parallel connected with thenon-linear load. Its working procedure is as following: firstly the current of the load i L (t) is detected, and its harmonic component is then calculated by the harmonic current detecting circuit. The inverter is controlled to output the compensation current whose polarities are inversed with the harmonic currents. According to the formula for power line current calculation i s (t) = i L (t)+i c (t) = i L (t)-i Lh (t), the fundamental frequency component of power line current is left only. If the reactive power compensation is demanded additionally, the only procedure to add is to compute the reactive power component together with the calculation of harmonic component. Consequently, the unity power factor can be realized. In the conventional p-q theory based control approach for the shunt APF, the compensation current references are generated based on the measurement of load currents and the current feedback from the shunt APF output is also required and therefore, minimum four current sensors are desired in a balanced system. In order to simplify the control scheme, two types of control techniques are developed for shunt active power Received July 20 th, 2011; Revised August 3 rd, 2011; Accepted Sept 12 th, 2011

32 ISSN: 2088-8708 filter based on single current measurement. One control scheme needs only measurement of load current, and other control scheme needs only measurement of source current. Fig. 1 Shuntactive power filter 2.1 Active Power Filter with Load Current Detection Active power filter with load current detection only requires load current, source voltage and capacitor voltage. The control system acts in order to perform an indirect regulation of source currents, which must be sinusoidal and in phase with the corresponding line to neutral voltages. Here indirect regulation of the source current is achieved by introducing a closed loop control of the filter flux, defined as the time integral of the filter voltage [6]. The block diagram of shunt active power filter with load current measurement is shown in Fig 2. Fig.2 A.P.F with load current detection The voltage equation for the shunt active power filter is given as V = V + L (1) IJECE Vol. 1, No. 1, September 2011 : 31 42

IJECE ISSN: 2088-8708 33 The integration of equation (1) leads to the following flux equation. φ = φ Li (2) Where φ is the reference filter flux and φ is the actual source flux. The r eference filter current is given by i = I I (3) Where I L is the measured load current and I S * is the reference source current. I S * is obtained by the equations i t = I sin (wt) i t = I sin (wt 120 ) (4) i t = I sin (wt + 120 ) and I L is directly measured by current sensors. For balanced load condition two current sensors are used for measuring load current. Equation (2) is used for calculating reference flux,φ. The actual value of φ is obtained by integrating the output filter voltage, which can be determined on the basis of the dc voltage V c and the inverter switch states S A, S B, S C. v = V (S + S e π + S e π ) (5) In this way, the non idealities of voltage source inverter (switching voltage drop and dead times) are neglected leading to steady state errors but avoiding the use of additional wide bandwidth voltage transducers to sense the voltage source inverter output voltage. The difference between reference filter flux and actual filter flux is given to the PWM controller. PWM controller generates firing pulses to control voltage source inverter. Current controlled voltage source inverter is used to inject a compensating current in to the system to relieve the supply from harmonic and reactive currents and enhance power quality indices. The shunt active power filter with load and filter current measurement is requires to measure load currents and the current feedback from the shunt active power filter therefore minimum four current sensors are desired in a balanced system. For unbalanced system six current sensors are required. Furthermore, power full microprocessors are necessary for the online evaluation of the harmonic content of the load currents. The shunt active power filter with load current detection only not requires to measure compensation current and source current and the reference source current is generated based on regulation of capacitor voltage by using PI controller. So shunt active power filter with load current detection is low cost and easy to implement. 2.2 Active Power Filter with Source Current Detection Active power filter with source current detection only measures source current, source voltage and capacitor voltage. The basic compensation principle of a shunt APF is shown in Figure 3. It is controlled to draw/supply a compensating current Ic from/to the system, so that it cancels current harmonics on AC side, and makes the source current in phase with the source voltage. The different waveforms are shown in Fig 3. Curve A is the non-linear load current waveform and curve B is the desired mains current.curve C shows the compensating current injected by the active filter containing all harmonics, to make mains current sinusoidal. The voltage equation for the shunt active power filter is given as V = V + L (6) The source current for the shunt active power filter is given as I = + (7) Being the rate of change of the filter current usually higher than that of the load current, equation (6) can be written as V = V L (8) For small variations, the time derivatives can be replaced by finite differences and equation (8) can be written as Control strategy for three phase shunt active power filter (Y.Kusuma latha)

34 ISSN: 2088-8708 V = V i (9) Fig 3. A.P.F with source current detection IJECE Vol. 1, No. 1, September 2011 : 31 42 Fig 4. Simulink model of shunt APF with load current detection

IJECE ISSN: 2088-8708 35 Where i S represents the instantaneous source current error and it obtained by the equation (10) i = I I (10) Where I is the measured source current and I is the reference source current. I is obtained by the equation (10) and I is directly measured by current sensors. For balanced load condition two current sensors are used for measuring source current. The difference between reference source current and actual source current is given to the hysteresis controller. Hysteresis controller generates firing pulses to control inverter. Current controlled voltage source converter (VSC) is used to inject a compensating current in to the system to relieve the supply from harmonic and reactive currents and enhance power quality indices. In shunt active power filter with load and filter current measurement the compensation current references are generated based on the measurement of load currents and the current feedback from the shunt APF output is also required and therefore, minimum four current sensors are desired in a balanced system. The shunt active power filter with source current detection only not requires to measure compensation current and load current and the reference source current is generated based on regulation of capacitor voltage by using PI controller. So shunt active power filter with source current detection is low cost and easy to implement. Implementation of shunt APF with load current detection is done with Matlab/Simulink and it it is shown in Fig.4 Fig 5 Three phase load current waveforms Control strategy for three phase shunt active power filter (Y.Kusuma latha)

36 ISSN: 2088-8708 3. Results and Analysis 3.1 Shunt APF with Load current detection The system shown in Fig 2 is simulated in Matlab/Simulink and the Simulink diagram is shown in Fig.4. The load current containing harmonics is shown in Fig 5. IJECE Vol. 1, No. 1, September 2011 : 31 42 Fig 6. Compensating currents waveforms

IJECE ISSN: 2088-8708 37 This harmonics are eliminated by injecting compensation currents at PCC. The compensation currents are shown in Fig 6. The compensation currents supply harmonic currents and reactive power demand of the load. Total Harmonic Distortion of the Source current is reduced to 4.89%. Harmonic spectrum for source current after compensation is shown in Fig 7. From Fig 8, it is noticed that the source current is in phase with source voltage and power factor is close to unity. The source current is close to fundamental sinusoid, showing that harmonic current is eliminated from the source current. From Fig 9, it is very clear that the D.C side capacitor voltage is remains constant at its value. Fig 7 Source current Harmonic Spectrum Fig 8 Source voltage and source current wave form Control strategy for three phase shunt active power filter (Y.Kusuma latha)

38 ISSN: 2088-8708 Fig 9 capacitor voltage 3.2 Shunt APF with Source Current Detection The system shown in Fig 3 is simulated and results are presented. The load current containing harmonics are eliminated by injecting compensation currents at PCC. The compensation currents are shown in Fig 10. The compensation currents supply harmonic currents and reactive power demand of the load. Harmonic spectrum for source current after compensation is shown in Fig 11. The source current Total Harmonic Distortion is reduced to 3.20%. The source current waveform is close to fundamental sinusoid, showing that harmonic current is eliminated from the source current and also the power factor is close to unity. The source current is in phase with source voltage and is shown Fig 12. The voltage across the D.C side capacitor is also shown in Fig 13. Table 1. Comparison of %THD in source current and required current sensors TYPE %THD for 10A %THD for 20A Without Active Power Filter Load current detection Source current detection Number of current sensors for balanced load Number of current sensors for unbalanced load 28.22 29.8 --------- -------- 4.89 6.9 2 3 3.20 5.7 2 3 4. Conclusion Control methods of shunt active power filter with minimum measurement requirements are discussed in this chapter. One control scheme is based on measurement of load current only and other control scheme is based on source current only. These Active power filters are used to eliminate harmonic currents as well as to compensate reactive power of the load. The technique is used in this work is easy to implement, and requires less number of current sensors and transformations. Shunt active power filter with source current detection and shunt APF with load current measurement are investigated and the corresponding results are compared with each other and it is observed that the shunt active power filter with source current measurement exhibits superior performance. The steady state and dynamic responses of the shunt active power filter with source current measurement is better than the APF with load current measurement IJECE Vol. 1, No. 1, September 2011 : 31 42

IJECE ISSN: 2088-8708 39 Fig 10 compensating currents waveforms Control strategy for three phase shunt active power filter (Y.Kusuma latha)

40 ISSN: 2088-8708 Fig 11 Source current Harmonic Spectrum Fig 12 Source voltage and source current wave form IJECE Vol. 1, No. 1, September 2011 : 31 42

IJECE ISSN: 2088-8708 41 Fig 13 Capacitor voltage waveform References [1] F.-Z. Peng, G. W. Ott, and D. J. Adams, Harmonic and reactive power compensation based on the generalized instantaneous reactive power theory for three-phase four-wire systems, IEEE Trans. Power Electron., vol. 13, no. 6, pp. 1174 1181, Nov. 1998. [2] H. Akagi, S. Ogasawara, and H. Kim, The theory of instantaneous power in three-phase four-wire systems: a comprehensive approach, in Proc. IEEE IAS Annu. Meeting, 1999, pp. 431 439. [3] Domenico Casadei, Gabriele Grandi,Ugo Reggiani and Claudio Rossi, Control Methods for Active Power Filters with Minimum Measurement Requirements, IEEE APEC, Vol. 2, pp.1153-1158, 1999. [4] B. Singh, K. Al-Haddad, and A. Chandra, Harmonic elimination, reactive power compensation and load balancing in three-phase, four wire electric distribution systems supplying nonlinear loads, J. Electric Power Syst. Res.,vol,44, pp. 93 00, 1998. [5] Chandra.A, Singh.B, Singh B.N, Al-Haddad.K, "An improved control algorithm of shunt active filter for voltage regulation, harmonic elimination, power-factor correction, and balancing of nonlinear loads," IEEE Trans. Power Electronics,Vol.15, pp. 495-507, May 2000. [6] M. J. Newman, D. N. Zmood, and D. G. Holmes, Stationary frame harmonic reference generation for active filters, IEEE Trans. Ind.Applicat., vol. 38, no. 6, pp. 1591 1599, Nov./Dec. 2002. [7] H. Karimi, M. Karimi-Ghartemani, R. Iravani and A. Bakhshai, An adaptive filter for synchronous extraction of harmonics and distortions, IEEE Trans. Power Delivery, vol. 18, no. 4, pp. 1350-1353, Oct. 2003. [8] L. H. Tey, P. L. So, and Y. C. Chu, Improvement of power quality using adaptive shunt filter, IEEE Trans. Power Del., vol. 20, no. 2,pp. 1558-1568, April 2005. [9] Lucian Asiminoaei, Frede Blaabjerg, Steffan Hansen, Evaluation of Harmonic Detection Methods for Active Power Filter Applications, IEEE Applied Power Electronics Conference and Exposition, Vol. 1, pp.635 641, 2005. [10] Abdelmadjid Chaoui, Jean Paul Gaubert, Fateh Krim,G rard Champenois PI Controlled Three-phase Shunt Active Power Filter for Power Quality Improvement EPE proc.electric power components and systems,volume 35,issue 12 December 2007 Bibliography of authors Y.Kusuma latha received the B.E (Electrical and Electronics Engineering) degree from Nagarjuna University, Guntur.A.P, India, M.Tech degree from Jawaharlal Nehru Technological University, Anantapur, India in 2000 and 2004. Currently she is working for her Ph.D. She is working as an Associate Professor in the Dept. of Electrical and Electronic Engineering, at Lakireddy Balireddy College of Engineering (Autonomous),Mylavaram. Her areas of interest are Power Quality, Harmonic mitigation techniques, Active power filters and DSP Controllers Control strategy for three phase shunt active power filter (Y.Kusuma latha)

42 ISSN: 2088-8708 Ch. Sai Babu received the B.E from Andhra University (Electrical & Electronics Engineering), M.Tech in Electrical Machines and Industrial Drives from REC, Warangal and PhD in Reliability Studies of HVDC Converters from JNTU, Hyderabad. Currently he is working as a Professor in Dept. of EEE in JNTUCEK, Kakinada. He has published several papers in National and International Journals and Conferences. His area of interest is Power Electronics and Drives, Power System Reliability, HVDC Converter Reliability, Optimization of Electrical Systems and Real Time Energy Management. Y. P. Obulesh received his B.E degree in Electrical Engineering from Andhra University, Visakhapatnam, India, M.Tech degree from Indian Institute of Technology, Kharagpur, India, in 1996 and 1998.He received his PhD degree from Jawaharlal Nehru Technological University, Hyderabad, in 2006. He got publications in several National and International Journals and Conferences. His areas of interest are simulation and design of power electronics systems, Active filters, Power quality, fuzzy logic and neural network application to power electronics and drives IJECE Vol. 1, No. 1, September 2011 : 31 42