Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000



Similar documents
SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES

Material Safety Data Sheet

On-Site Risk Management Audit Checklist for Program Level 3 Process

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Confined Spaces. The National Food and Drink Manufacturing Conference October 2012

G11. Acceptable Solutions and Verification Methods. For New Zealand Building Code Clause G11 Gas as an Energy Source

Thermal Mass Flow Meters

LPG, Flammable Liquids, Toxic and Corrosive Substances

Compressed Gas Cylinder Program

ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion

WORKING IN CONFINED SPACES GUIDELINES

IGEM/UP/16 Communication 1756

INDEX GENERAL

Liquefied Natural Gas (LNG)

WHS GUIDANCE MATERIAL WHS GUIDANCE SECTION MATERIAL 4 WORKING IN CONFINED & ENCLOSED SPACE DEVELOPING WORKPLACE HEALTH & SAFETY GUIDANCE

FLAMMABLE LIQUIDS COMPLIANCE NOTE

COMMERCIAL GAS DRYER FUELLED BY TOWN GAS CODE OF PRACTICE GU13 (MODULE ONE)

DRAFT FOR CONSULTATION

A Code of Practice for Pressure Equipment in the Department of Physics

University of Tennessee Safety Guidelines

MANAGEMENT AND USE OF WORK EQUIPMENT: PRESSURE SYSTEMS

How To Get A Type B Gas Appliance Approved In Western Australia

SECTION A... 3 SECTION B... 7

Certain specific properties of compressed gases make them highly useful in various research activities.

Consultation response: PPC Technical Guidance Note 35 Anaerobic Digestion

Introduction to Waste Treatment Technologies. Contents. Household waste

Advisory Note. Plumbing Regulation PLUMBING AND DRAINAGE SERVICES INSTALLED IN PROXIMITY OF OTHER SERVICES AND UNDERGROUND OBSTRUCTIONS

Hazardous Substance Class Definitions & Labels

This fact sheet provides an overview of options for managing solid

HAZARDOUS MATERIALS MANAGEMENT ISSUE 2

Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use

Site and Storage Conditions for Class 3.1 Flammable Liquids

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities

Factory owners must ensure the boiler is:

Explosion Prevention

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen

Hazards in the Workplace

PBX Series Quick Fit Connector Bimetallic Steam Traps

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS

Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS

Energy Saving Fact Sheet Boilers

THE SAFE USE OF THERMAL OXIDISER (INCINERATION) SYSTEMS FOR POTENTIALLY FLAMMABLE MIXTURES. Gordon Newsholm

Routine and Emergency Boiler Operation

Natural Gas Information Contents

CSA Group Safety Standards for Oil and Gas Pipeline Systems: A Life-Cycle Approach

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

Rule EMISSIONS OF OXIDES OF NITROGEN FROM LARGE WATER HEATERS AND SMALL BOILERS

Gas-Fired, Residential Storage Type Water Heaters

Boiler Preparation, Start-Up and Shutdown

EUROPEAN INDUSTRIAL GASES ASSOCIATION

Examples of pressure systems and equipment are:

Preventing Overheated Boiler Incidents

Installation Guidance: CNG Refueling Stations

G SPECIFICATION: GAS METER AND REGULATOR INSTALLATION REQUIREMENTS. 3 and Gas Yellow Book. REVISIONS: (See ) 1/15/14 5 Years

Summary of Environment and Social Impacts for Activates Associated with Petroleum Refining and the Storage of Petroleum Products

BUSINESS LICENSE (2014) CHARTER TOWNSHIP OF FLINT 1490 S. DYE ROAD, FLINT Ml (810) OR FAX (810)

PIPELINE EMERGENCIES. Chapter 5 Gas Pipeline Operations. Michael Callan

Pressure Vessels (Air Compressors) and LPG Tanks

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

Confined spaces can be deadly. What is a confined space?

SAFETY AND HEALTH PROGRAM

Continuous flow direct water heating for potable hot water

Safe Method: Gas Safety in Catering Establishments

POLICY: CONFINED SPACES

Hackney Biomass Boiler Information Request Form

SL280UHV SERIES GAS FURNACE WARNING

Natural Gas Safety. What You Need to Know

POWER ENGINEERS REGULATION

Instrument Gas to Instrument Air Conversion Protocol October 2009 SPECIFIED GAS EMITTERS REGULATION OCTOBER Version 1.0.

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

Australian Standard Industrial and commercial gas-fired appliances

Guidance notes to the CER s recently enacted Gas Works Regulations. These Guidance Notes should be read in conjunction with:

ARE YOU IN COMPLIANCE WITH THE OSHA COMBUSTIBLE DUST DIRECTIVE? Revised March 18, 2009

FLARE SELECTION AND SIZING (ENGINEERING DESIGN GUIDELINE)

Ethanol Vehicle and Infrastructure Codes and Standards Citations

GAS HEATING IN COMMERCIAL PREMISES

Waste Oil Collection / Storage

WORK IN CONFINED SPACES

CONFINED SPACE PROCEDURE

BUILDING A WORLD OF DIFFERENCE. Safe work in confined spaces

Process Safety Management

PROPASAL FROM FOR PUBLIC LIABILITY INSURANCE (For Industrial Risks and Storage Risks)

Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service

Digester Gas Safety Equipment

Arapahoe County Residential Water Heater Installation and Inspection Guide

* * * EMERGENCY OVERVIEW * * * High pressure gas. Can cause rapid suffocation. Can increase respiration and heart rate.

LANDFILL GAS TO ENERGY- COMBINED ENGINE AND ORC-PROCESS

Contents. 1. Legal Requirement Responsibility of Related Parties What are Confined Spaces Hazards Identification 4

Work Health and Safety Regulations: Classification and labelling for workplace hazardous chemicals

Electrical Equipment in Hazardous Areas: Field Inspections

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

Compressed Gas Cylinder Storage and Handling Guide

A practical guide to restrictive flow orifices

Fuels Safety Program FS DIRECTOR S PUBLIC SAFETY ORDER

DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY

If you have any questions about how to safely undertake a task or project, ask your supervisor before you begin.

Transcription:

Gas Standards and Safety Guidance Note January 2015 (GN106) Version 1.0 GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000 A guide to assist in the design of biogas facilities, where biogas is collected or conditioned. SCOPE This guide is to assist those designing biogas or Bio Methane facilities, where biogas is collected or conditioned. It also covers the installation of any flare or appliance, and control systems when making application to the Director of Gas Safety (Director) for acceptance of the gas installation downstream of the gas supply point. While this document primarily provides guidance for biogas installations downstream from the gas supply point, Appendix A also provides some additional guidance regarding biogas collection and generation matters. Infrastructure both upstream and downstream of the gas supply point will form part of a Gas Safety Management System (GSMS) to be provided to the Director as required in Section 77 of the Gas Act 2000 and Regulations 46(3) (f & g) of the Gas (Safety) Regulations 2014. The documented Gas Safety Management System must provide sufficient evidence that the owner/operator of the biogas infrastructure has systems in place to ensure the biogas installation will be designed, installed, maintained and operated safely. For further safety management system and application for acceptance instructions, refer to Guidelines for the Preparation of a Submission for the Acceptance of Gas Installations (Major) Safety Management Plan, available from the Building Standards and Occupational Licensing Gas Standards and Safety team contact details below. DEFINITIONS For the purposes of this guideline the following definitions apply: Building Standards and Occupational Licensing Department of Justice

Gas as per the Gas Act 2000 means: o natural gas; or o liquefied petroleum gas; or o any other gaseous fuel, being a gaseous fuel that is not declared by the regulations to be excluded from the operation of this Act. Biogas as per the AS/NZS 5601.1 Gas installations, means: A mixture of gases produced by anaerobic microbial decomposition of organic matter and principally comprising methane and carbon dioxide together with lesser amounts of hydrogen sulphide, water vapour or other gases. Gas Supply Point The Director has determined that the gas supply point for a biogas installation is the outlet of an anaerobic digester for digester type installations, or the inlet of the gas conditioning plant for collection type facilities such as landfill sites. SYSTEM DESIGN Each installation will have its special features. These will be unique to the operation of plant and relate to the use of the gases generated and collected. However, there are a number of safety features that are considered minimum requirements to ensure the safe and reliable operation of gas-fired appliances or flares, and the associated gas supply installation and facility. Before the system is designed there must be clear identification of the risks and hazards associated with the operation of the facility. A HAZID and HAZOP must form part of the design process considering, but not limited to, the following areas: 1. Site selection and layout including risks to neighbouring properties. During any conceivable incident the radiant heat should not exceed 4.7 kw/m2 at any boundary. 2. Provision of automatic isolation. 3. Risks associated with odourless gas. 4. The clear identification of all biogas pipework to prevent accidental damage by a third party both underground and aboveground. 5. Separation of biogas pipework from other services. 6. Location of extraction system hardware related to end-use devices such as gas flares and power or steam generation systems. 7. Construction materials used in gas conditioning systems must be compatible with the biogas and associated leachate or condensates including problems associated with stress corrosion cracking. Email: wstinfo@justice.tas.gov.au Visit: justice.tas.gov.au Page 2

8. Any pressure vessel that is part of a gas conditioning system, such as a knockout pot, accumulator or chilled water moisture separator will need to be assessed and installed according to the relevant standards. It must also be registered if required by the Workplace Health and Safety Act. 9. Flame arresters compatible with the gas must be installed at the inlet of appliances and flares where there is a likelihood that an air gas mixture may be present within the system or negative pressures may induce an air gas mixture into the system at the appliance. 10. Gas conditioning system interlocks, not limited to the following, to ensure safe system operating conditions: o The monitoring of the methane content to alarm at concentrations less than 30% and trip at 25%. Gases with less than 20 % are not flammable and will result in flame failure and system unreliability. o Appliance flame supervision lockout on flame failure. o Low gas pressure monitoring to ensure adequate supply for the maintenance of acceptable combustion characteristics. o High gas pressure monitoring to ensure maintenance of acceptable combustion characteristics and the limitation of component exposure to higher than safe working pressures. o Flame arrestors with provision for fusible link or a temperature sensor to initiate a shutdown if there is the presence of flame at the arrester. 11. The electrical installation must be compliant with AS/NZS 3000 Electrical Installations. ACCEPTANCE OF A BIOGAS CONDITIONING FACILITY DOWNSTREAM OF THE GAS SUPPLY POINT BY THE DIRECTOR The design, construction and installation of the complex gas installation requires acceptance by the Director pursuant to section 77 of the Gas Act 2000 and must be designed, manufactured and installed in accordance with Australian standard AS/NZS 5601.1 Gas installations or any other standard acceptable to the Director. A Section 77 application for acceptance provided to the Director in accordance with the Act must include; Detail of the gas collection, compression, pressure reduction infrastructure and control systems Determination by the Director of the bio gas supply point to the gas installation Detail and P&ID of the gas installation and appliances. Any appliance that is not certified to an Australian appliance standard (Type B appliance) will be subject to a separate acceptance and the requirements of AS3814 - Industrial and commercial gas-fired appliances, or any other standard prescribed by the Director. Email: wstinfo@justice.tas.gov.au Visit: justice.tas.gov.au Page 3

Work on downstream biogas installations including appliances must be undertaken by suitably licensed certifying gas fitters. If the biogas system is wholly located on private property and the gas is for use solely by the owner/operator in a gas installation then the biogas collection and conditioning systems will be subject to a Gas Safety Management Plan as part of the gas installation as required by Regulation 46(3) of the Gas (Safety) Regulations 2014. Where the routing of biogas pipework passes through public property or is used to supply gas by reticulation to consumer s please contact the Director in respect to additional requirements for gas distribution and reticulation systems. Requirements will vary between installations. All submissions will be reviewed and conditions on an acceptance may be imposed. The Director may require independent design and/or component certification as part of any acceptance. The Director may also require a test and commission plan prior to commissioning. Details should be discussed with the Office of the Director prior to submission. TYPE B APPLIANCES INCLUDING FLARE SYSTEM The design of type B appliances and flare burner management system is required to comply with AS 3814 - Industrial and commercial gas-fired appliances or any other standard prescribed by the Director. The following list must be considered as a minimum requirement, and information provided in the application for acceptance for any appliance: 1. Demonstration of the suitability of gas appliances, including flares or work engines to operate on biogas from the original equipment manufacturer. 2. The location of the appliance must be such that in the event of unburnt gas being vented it will not cause a hazard. 3. During normal operation the radiant heat will not exceed 1.6kW/m2 at any boundary. 4. Separation distance from flammable goods, hazardous chemicals and other plant shall be required for the Directors assessment. 5. The separation distances from sources of ignition must comply with AS/NZS 60079.10.1 Classification of hazardous areas. 6. In the case of an enclosed appliance the operating temperature shall be considered and limits set to ensure adherence to local environmental protection policy for in-stack emission concentrations and proper destruction of trace toxic chemicals. 7. The extraction system must have some form of pressure control specifically for appliances associated with covered lagoons or sewage treatment system operating under negative Email: wstinfo@justice.tas.gov.au Visit: justice.tas.gov.au Page 4

pressure to ensure that oxygen is not introduced into the gas production or gathering system. OPERATING AND MAINTENANCE Operating and maintenance instructions are to be included in the draft GSMS for assessment by the Director. The plan must include testing, maintenance, servicing, training, isolation, safety and system control frequency for the biogas plant. Where practical the owner/operator of the system should receive the settings of all interlocks and acceptable operating ranges along with frequency of maintenance. If there are no specific recommendations by the manufacturers or suppliers of gas components, equipment and piping the Director recommends that Appendix B of AS1375 be used as a guide for maintenance frequency of the burner and gas systems. A maintenance schedule should include, but not be limited to, the annual testing and inspection of gas water/condensation traps and safety shut off valves and inspection of flame arrestors. APPENDIX A GUIDANCE FOR BIOGAS COLLECTION AND DIGESTER FACILITIES BIOGAS COLLECTION SYSTEMS Management of biogas collection and production systems must be included in the GSMS for the entire plant including gas conditioning and utilisation systems. The GSMS is to include confirmation of the biogas combustion quality, composition and supply adequacy, and where applicable, detail of physical or chemical conditioning processes intended to be used for the conditioning of the biogas to render it suitable for combustion in gas appliances or work engines. This information may require independent certification by an approved chemist or engineer before the Director assesses or accepts the gas installation design downstream of the gas supply point. For further information refer to fact sheet Acceptance Requirements for Composition of Fuel Gas to Be Used in a Biogas or Industrial Off Gas Process Supplying a Gas Installation, available from Building Standards and Occupational Licensing Gas Standards and Safety team contact details below. Materials for the construction of the reticulated landfill biogas extraction system shall comply with AS 4130 or other applicable standard acceptable to the Director. The reticulated biogas extraction systems must be underground unless the site is fenced off and on private property. Email: wstinfo@justice.tas.gov.au Visit: justice.tas.gov.au Page 5

The potential for fire damage should be considered for plastic piping and isolation that is above ground or shallow that may be vulnerable to accidental damage. Particular attention should be paid to piping upstream of any extraction blower where isolation is not possible. All system components, such as blowers, and valves must be compatible with the biogas and other impurities and be safe for use, for example non-sparking. The monitoring of the oxygen content within the systems is recommended to alleviate concerns of conveying gas that is within the flammable range. Alarm and trip at levels exceeding 1% to 5% respectfully is suggested. Alternative alarm and trip levels should be satisfactorily demonstrated by risk assessment. Explosion relief and flame arrestors should be considered especially those not being monitored for oxygen. Management of biogas collection and digester must be included in the Gas Safety Management System for the entire system including gas conditioning and utilisation plant. FURTHER INFORMATION For more information contact the Gas Standards and Safety team at Building Standards and Occupational Licensing Phone: (in Tasmania) 1300 366 322 Phone: (outside Tasmania) (03) 6166 4600 Fax: (03) 6173 0205 Email: wstinfo@justice.tas.gov.au Address: This document has been produced and published by the Building Standards and Occupational Licensing Division of the Department of Justice. Although every care has been taken in the production of the work, no responsibility is accepted for the accuracy, completeness, or relevance to the user's purpose, of the information. Those using it for whatever purpose are advised to verify it with the relevant government department, local government body or other source and to obtain any appropriate professional advice. The Crown, its officers, employees and agents do not accept liability however arising, including liability for negligence, for any loss resulting from the use of or reliance upon the information and/or reliance on its availability at any time. Email: wstinfo@justice.tas.gov.au Visit: justice.tas.gov.au Page 6