Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.



Similar documents
Portable Air Conditioner

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Use and Care Manual. Model CPA12KH AIR CONDITIONER

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM EXPLOSION VIEW 12 6.

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

14. Troubleshooting Guide

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM EXPLOSION VIEW 16 6

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

USER S MANUAL HSC-24A

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

PORTABLE AIR CONDITIONER

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

Failure code manual. content

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

, User s Manual

How To Use A Power Supply Unit (Upu)

WINDOW ROOM AIR CONDITIONER

ALL IN ONE. Heat Pump Water Heater

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t.

Technical service manual 2009

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

User s Manual AURORA 1.2K/2.2K

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE & MAINTENANCE MANUAL

Important Safeguards

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

PORTABLE AIR CONDITIONER

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Split Air Conditioner

Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC

Oil and Coolant Circulating Heating System. Model - OCSM

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

OWNER S GUIDE OPERATION & INSTALLATION

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Heat Pump Water Heater IOM Manual

INSTALLATION MANUAL. Address card EKAC10B

REMOTE CONTROL MANUAL

AIR CONDITIONER INSTALLATION MANUAL

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

Operating Instructions Air Conditioner

WALL MOUNTED SPLIT TYPE AIR CONDITIONER

Split Type Room Air Conditioner. KSWM units

WHYNTER ECO-FRIENDLY 14,000 BTU PORTABLE AIR CONDITIONER WITH HEATER

SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL

Trouble Shooting. Pump

OWNER S MANUAL SPLIT SYSTEM AIR CONDITIONER. G Series Cooling

NewAir AC-14100E / AC-14100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

FOXAIR 60/50 ALL MODELS

Thermo Top - Troubleshooting Tree

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

SWIMMING POOL HEAT PUMP

Dehumidifier Users manual. For Models: DH45S DH65S

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

English. Symbols used to mark instructions...3. Congratulations...5 Getting the best results...5. Warnings...6 Operating Procedure...

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Technical Service Manual. Version One

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

Calor de Hogar. Av Tecnológico 735, PB. San Salvador Tizatlalli. Metepec, 52172, Edo de México. Teléfono (722) (55)

Quest 105, Dry155, and 205 Dual

Roof Top Unit. Description Model Type Use With Air Distribution Box. Heat Pump B Integral Mechanical

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

READ AND SAVE THESE INSTRUCTIONS. INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC, NEC AND LOCAL ELECTRICAL CODES.

Operating & Maintenance Manual for Islandaire Packaged Terminal Thru-Wall Air Conditioners & Heat Pumps

Heat Surge Model X5C Fire Place Insert Service Manual Applies to all units w/ circuit board

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

PORTABLE AIR CONDITIONER (LOCAL)

Vertical Display and Storage B SKOPE Gen2: Three Door Chiller

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex

Wilo SP Series Submersible Sump Pumps ECS. ECS ECS ECS Installation and operating instructions

Technical Information

Room Air Conditioner Service and Parts Manual

SERVICE & MAINTENANCE MANUAL

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

PANASONIC TROUBLE SHOOTING GUIDE

ACW200C / ACW200CH. Innovative AutoDrain Technology. Owner s Manual Portable Air Conditioner with Heat

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

Wall Mounted Mini Split Heat Pump Air Conditioner

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

SILENT10 PORTABLE AIR CONDITIONER USER MANUAL

Get Me Cool Now Portable Air Conditioner User s Manual

TABLE OF CONTENTS UNIT FEATURES OPERATING INSTRUCTIONS. 230V 20 Amp. 120V 15 Amp Figure 1. LCDI Power Cord Figure 2

Transcription:

Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6 MPK1-14ER-QB6 0

CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2 INSULATION RESISTANCE TEST...2 1.3 FEATURES...2 1.4 CONTROL LOCATIONS...2 2. TROUBLE SHOOTING GUIDE 2.1 REFRIGERATION CYCLE DIAGRAM...4 2.2 ELECTRIC FUNCTION...4 2.3 TROUBLE SHOOTING GUIDE...6 3. WIRING DIAGRAM 3.1 WIRING DIAGRAM FOR COOLING ONLY MODELS...9 3.2 WIRING DIAGRAM FOR COOLING AND HEATING MODELS...9 3.3 ELECTRICAL CONTROL SCHEME...10 3.4 MAIN CONTROL BOARD SCHEME...11 3.5 DISPLAY BOARD SCHEME...12 4. HOW TO DISASSEMBLE THE UNIT.13 5. SPECIFICATIONS...21 1

1. PREFACE This SERVICE MANUAL provides various servicing information, including the mechanical and electrical parts, etc. This room air conditioner was manufactured and assembled under a strict quality control system. The refrigerant was charged at the factory. Be sure to read the safety precautions prior to servicing the unit. 1.1 SAFETY PRECAUTIONS 1. When servicing the unit, set the POWER SWITCH to OFF and unplug the power cord. 2. Inspect the service cord for damage or wear. If a short circuit is found, replace all parts which have been overheated or damaged by the short circuit. 3. After servicing the unit, make an insulation resistance test to protect the customer from being exposed to shock hazards. 1.2 INSULATION RESISTANCE TEST 1. Unplug the power cord and connect a jumper lead between the two (2) live pins. 2. The grounding conductor (yellow/green) is to be open. 3. Measure the resistance value with an ohm meter between the jumped lead and each exposed metallic part on the equipment at all the positions (except OFF) of the ROTARY SWITCH or POWER SWITCH. 4. The value should be over 1MΩ. 1.3 FEATURES Only one exhaust pipe, which makes the A/C Water full alarm easier to use. Anti-icing function at cooling mode. Remote-controlled or gentle-touch keys for easy and comfortable use. Restart relay protection for the compressor. Compressors of famous brands are adopted for Temperature sensor err self-diagnose. reliability and low noise. 24 hours on/off mode time setting. The heating system uses PTC electrical heater Both temperature mode display and will not be affected by ambient temperature, Separate motor for indoor and outdoor system. which saves energy. Multiple uses: dehumidifying and cloth drying. Suitable for local cooling and heating. Low temperature Drying operation. Condenser shower and large volume tank design. There are four casters on the bottom for easy Long time to pour the tank. movement. Directly drainage available. 1.4 CONTROL LOCATIONS For cooling only with electric heater models: MODE FULL TIMER ON TIMER OFF TEMP. ADJU ST FAN SPEED MODE FULL PO WER TIM ER ON TI MER OFF TEMP. ADJU ST FAN SPEED POW E R For cooling only models: 2

MODE Mode setting button. Push this button to select the operation mode: Cool, Dry, Fan only and Heat High fan speed lamp. Med fan speed lamp. Low fan speed lamp. o F o C Remote receiver. Timer ON button. Push this button to set the Timer On time. Timer OFF button. Push this button to set the Timer Off time. Timer ON/OFF lamp. Fahrenheit temperature display. When Fahrenheit temperature display mode is selected. Celsius temperature display. When Celsius temperature display mode is selected. Temperature setting up. Push this button to set temperature setting up. Temperature setting down. Push this button to set temperature setting down. Cooling operation lamp. Drying operation lamp. Fan only operation lamp. POW E R Fan speed setting button. Push this button to select fan speed: High, Med and Low. Power button. Push this button to start the unit. FULL Water full alarm lamp Power lamp Remote controller: LCD display. Mode button: Select the operation mode, AUTO, COOL, DRY, HEAT (cooling only with electric heater models only) and FAN. Fan speed button: Select the Fan speed, AUTO, LOW, MED, HIGH. ON/OFF button: Press this button to operation the unit, again to stop. Temperature setting up button: Press this button to increase temperature setting or adjust the TIMER in a clockwise direction. Temperature setting down button: Press this button to decrease temperature setting or adjust the TIMER in a counter-clockwise direction. Timer on button: Push this button to set the ON timer. Timer off button: Push this button to set the OFF timer. Lock button: Press this button to lock all button except this button. Reset button: Press this button to reset all settings to factory settings. Electric heating operation lamp. 3

2 TROUBLESHOOTING GUIDE 2.1 REFRIGERATION CYCLE DIAGRAM 2.2 ELECTRICAL FUNCTION 2.2.1 Electric Control working environment 2.2.1.1 Input voltage: 187~264V for 50Hz models and 97~127V for 60Hz models; 2.2.1.2 Input power frequency: 50Hz or 60Hz; 2.2.1.3 Ambient temperature: -7 C~+43 C for cooling only with electric heater models and 10 C~+43 C for cooling only models; 2.2.1.4 Indoor fan normal working amp is less than 1A; 2.2.1.5 Outdoor fan. Normal working amp is less than 1.5A; 2.2.1.6 Compressor: single-phase power supply. Its normal working amp is less than 10A; 2.2.2 Proper symbols and their meanings: TA: Indoor ambient temperature TC: Indoor evaporator temperature TS: Setting temperature through the remote controller 2.2.3 Systematic functions Remote receiving (Optional) LED displaying and alarm On or off Timer Protection for the compressor Water full alarm Anti-icing function at cooling mode. Temperature sensor err self-diagnose. Both temperature mode display 2.2.4 Protection 2.2.4.1 The compressor functions protection with a delay of three minutes. 2.2.4.2 Sensor protection at open or short circuit. 2.2.4.3 Evaporator anti-icing protection at cooling mode. 2.2.4.4 Water full alarm There are two water position switches used in the unit. One detects the water depth in the chassis and the other detects the water in the tank. 2.2.4.4.1 Water full alarm will be on when the unit is standing by or operating. 2.2.4.4.2 When the water adds up to the first position on the chassis, the pump will be activated. If the water drops down through the position, the pump will be on and stop after 2 minutes. 2.2.4.4.3 When the water adds up to the position on the tank, the compressor, outdoor fan motor, electric heater and pump will stop operation. And the LED will display P1 while the water full lamp flashes at 2Hz. 2.2.4.4.4 When the water adds up to the second position on the chassis and the switch has been 4

on for 10 seconds, the whole unit will stop operation. The LED will display P2 and the water full lamp will flash at 5Hz. After you have clear the problem, you should unplug the unit and plug again. Then the unit will be ready to operate. 2.2.4.4.5 When the unit is standing by, if the unit displays P1, the pump will not operate. After the problem is cleared, the unit will be ready to operate. But if you push the power button, the unit will shut the P1 display and shut down. 2.2.5 Fan-only Mode Function Requirement 2.2.5.1 The compressor and outdoor fan are OFF at Fan-only mode. 2.2.5.2 The speed of indoor fan can be optionally chosen as High/Mid/Low. 2.2.6 Cooling Mode Function Requirement 2.2.6.1 The speed of indoor fan can be optionally selected as High/Mid/Low. 2.2.6.2 The compressor operate as: TS+1 TS O C ro om temperature (TA) Comp ressor ON Compressor OFF Temp down Temp up 2.2.7 Drying mode 2.2.7.1 When the unit starts to operate in Drying mode, the compressor will start while the room temperature is over 13 o C. After the compressor started, the compressor will operate as: 15 o C 13 o C O C ro om temperature (TA) Compressor and outdoor fan ON Compressor and outdoor fan OFF Temp down Temp up 2.2.7.2 The indoor fan will operate with high speed. The outdoor fan will operate with compressor. 2.2.8 Heating mode 2.2.8.1 The speed of indoor fan can be optionally chosen as High/Mid/Low. 2.2.8.2 Electric heater operate as : O C ro om temperature (TA) Electric heater OFF TS+1 TS Temp up El ectric heater ON Temp down 2.2.9 Temperature display 2.2.9.1 The setting temperature will be displayed in Cooling and Heating mode. The room temperature will be displayed in Drying and Fan only mode. 2.2.9.2 The setting temperature range is from 17 o C to 30 o C or 62 o F to 88 o F. The display temperature range is from 10 o C to 35 o C or 48 o F to 98 o F. If the room temperature is lower than 10 o C or 48 o F, the display will be 10 o C or 48 o F. 2.2.10 Timer Function 2.2.10.1 The maximum length of Timer is 24 hours and the minimum is 0.5 hours. 2.2.10.2 TIMER ON function: first turn OFF the unit, the unit will be automatically ON at the set time. 2.2.10.3 TIMER OFF function: first turn ON the unit, the unit will be automatically OFF at the set time. 2.2.10.4 TIMER ON/OFF function (ON TIMER is earlier than OFF TIMER): first turn OFF the unit, it will be automatically ON at set time, and later be OFF at the set time. 2.2.10.5 TIMER OFF/ON function (OFF TIMER is earlier than ON TIMER): first turn ON the unit, it will be automatically OFF at set time, and later be ON at the set time. 2.2.10.6 Timer function execution is applicable upon one operation only. 2.2.10.7 Timer precision is less than 15 minutes. 2.2.11 Auto restart function In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when power returns. 2.3 TROUBLESHOOTING GUIDE In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused from an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application, and the other is called the Structure Damage. 5

ROOM AIRCONDITIONER VOLTAGE LIMITS: NAMEPLATE RATING MINIMUM MAXIMUM 220~240V 196V 253V PROBLEM POSSIBLE CAUSE REMEDY Check the power supplier if the power supplier is supplied to the Power failure No power display unit. Check the power cord and correct if damaged. on panel or any one Check resistance between the two input/output lines on Transformer (Discharge of the buttons transformer. Replace the transformer if either of the input/output is transformer before testing) failure. open or the transformer is damaged. Display board or main PCB Check the voltage on display board. Replace the display board if it Remote control failure is +5V else replace the main PCB. failure. Check the voltage of battery. Replace batteries if the voltage is Battery failure lower than 2.3V. Check voltage. Call an electrician if not within limits. Test capacitor. Replace if not within +/-10% of manufacture's rating. Fan motor runs Cycles on overload. Check bearings. Replace the motor if the blower wheel cannot intermittently rotate freely. Pay attention to any change from high speed to low speed. Replace the motor if the speed does not change. The amount of the refrigerant is too much, making the compressor Compressor stops Refrigerant load too big. Recycle and recharge the refrigerant after checking instantly after for the reason. startup. The compressor is blocked inside. Replace after checking for the Compressor reason. No power Check voltage at electrical outlet. Correct if none. Water alarm Check and correct if water alarm happens. Power supply cord Check voltage at the power cord terminal on Main PCB. Replace the power cord if none. Check resistance between the two input/output lines on Transformer (Discharge transformer. Replace the transformer if either of the input/output is transformer before testing) open or the transformer is damaged. Wire disconnected or Connect wire. Refer to wiring diagram for terminal identification. Fan motor will not connection loose Repair or replace loose terminal. run. Main PCB failure Select fan speed and Check the voltage on main PCB. Replace the main PCB if no voltage in anyone. Test capacitor. Capacitor (Discharge Replace if not within +/-10% of manufacture's rating. Replace if capacitor before testing) shorted, open or damaged. Fan blower hitting scroll. Realign assembly. Will not rotate Check fan motor bearings. Replace the motor if motor shaft do not rotate. 6

Fan blower Loose screws Fan motor noise. Worn bearings Voltage Wiring Compressor will not Main PCB failure run while fan motor Capacitor (Discharge runs. capacitor before testing) Room temp sensor Compressor Excessive noise. Copper tubing Water tank full Water depth sensor if failure Water pump failure Water full alarm Water depth is over load in chassis Water depth sensing structure Cooling or heating Air filter feels not good Air discharge pipe Unit undersized Condenser and Evaporator Water shower failure Fan motor Air flow Less refrigerant Capillary tube Replace the fan blower if cracked, out of balance, or partially missing. Tighten them. Replace the motor if knocking sounds continue when running or loose, or the motor hums or noise appears to be internal while running. Check voltage. Call Supply Authority if not within limits. Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct. Check voltage of main PCB. Replace the main PCB if open. Check the capacitor. Replace if not within +/-10% of manufacturers rating. Replace if shorted, open, or damaged. Check the temperature setting if not at the coolest (in cooling mode) or the warmest (in heating mode). Set it if not. Check the compressor for open circuit or ground. If open or grounded, replace the compressor. Remove the cabinet and carefully rearrange tubing not to contact cabinet, compressor, shroud and barrier. Check and pour if the water tank is full. Check and replace if failure. Check and replace if the pump if failure. Check and drainage the water in the chassis by open the drainage hose on the chassis. Check and replace or realign if the structure is failure. Clean or replace if restricted. Realign and assemble if the installation of the air discharging pipe failure. Replace if damaged. Determine if the unit is properly sized for the area to be cooled or heated. Clean or replace if restricted. Check the structure of water showering system and clean if blocked. Check the fan capacitor and replace if not within +/-10% of manufactures rating. Clean or remove if any barrier is found to block the inlet/outlet wind flow of the unit. Check the tubes for reasons of leakage. Recycle the refrigerant, correct the leakage points and recharge. Regulate the flow if capillary tube and make the evaporating temperature appropriate if the evaporator is frosted. Replace if blocked. Repair joint if leaking. 7

Compressor Heat sources No power Wiring Temperature setting Mode setting No cooling or Compressor heating. Electric heater failure Over heat fuse failure Main PCB Power supply The unit starts and Main PCB stops frequently. Room temperature The inlet and outlet valve of the compressor is damaged, making the low pressure connected with the high pressure. The refrigerating system can not produce high pressure and low pressure. Replace the compressor after checking for the reason. Reduce if too many. Check the voltage. Call an electrician if no within the limit. Check the terminals. Repair and correct if loose. Check and adjust the temperature setting. Check and adjust the mode setting. Check and replace if the compressor, the over-load protector or wiring is broken. Check and replace if the heater is damaged. Check and replace if the fuse is damaged. Check the voltage of main PCB. Replace the main PCB when the unit failure in heating mode. The input power supply voltage is too low. Call an electrician if not within limits. Check and replace the main PCB if the compressor relay on PCB is shorted or damaged. When the room temperature is too high, the compressor will protect. 3 WIRING DIAGRAM 3.1 FOR COOLING ONLY MODEL: MPK1-09CR-QB8 8

3. 2 FOR COOLING AND HEATING MODELS: MPK1-12ER-QB6 MPK1-14ER-QB6 9

3.3 ELECTRICAL CONTROL SCHEME: 10

3.4 MAIN CONTROL BOARD SCHEME: 11

3.5 DISPLAY BOARD SCHEME: 12

4 HOW TO DISASSEMBLE THE UNIT 4.1 Prepare the unit. Unplug the power cord and disconnect the Air pipe from rear of the unit. Move the unit to a replace where water can be poured. Remove the rubber plug from back of the unit and drainage the water in from the unit. Remove the water tank from the unit and pour the water in the tank. Remember to disassemble the inlet grille. 4.2 Remove the screws which fixed the rear panel. 13

Take care to the indoor temperature sensor attached on the rear board. And be care to the power cord which got through the rear panel. 4.3 To disassemble the display board assembly, just push the clasp and release the assembly. Screws on front bottom of the unit. Screw locates on top of tank box. Now it is easy to replace the display board. Take care to release the connector which connected to the display board. Screw locates on bottom of chassis. 4.4 To disassemble the front panel. Remove the screws fixing the front panel. Screws fix the front panel from side of the unit. Be care to release the connectors which connect to 14

the display board. 4.5 To replace the Main Control board. Remove the screws fixing the enclosure cover. Take care of the wiring diagram on the cover. The wiring diagram is important for reference when wiring. Pay attention to the wires in the enclosure. 1 2 3 4 5 6 7 8 9 10 1: Terminate to display board 2: Terminate to condenser fan motor 3: Out-put of transformer 4: Terminate to evaporator fan motor 5: Terminate to compressor 6: Terminates (N) to condenser fan motor, electric heater, pump, power cord, compressor capacitor 7: Terminate to electric heater 8: Terminate (L) to power cord 9: Terminate (L) to pump 10: Terminate to input of transformer Take care to the grounding wires if need to disconnect. 15

4.7 To replace the evaporator fan motor or electric heater To disassemble the air-out frame. Remove the screws fixing the air-out frame. Lift the frame up then pull the frame forward. Remove the fan motor, fan scroll and blower wheel from the unit. Take care to the wires for electric heater. Slide the electric heater bracket up and remove the parts from the unit. Remove the screws fixing the fan shell box. Now, it is easy to replace the electric heater and/or heat protector attached with the heater. 16

4.8 To replace the condenser fan motor Remove the screws fixing the evaporator 4.9 To repair the refrigerant system or replace the compressor Disconnect the water pipe below. Remove the screws fixing the condenser fan motor bracket. Remove the screws fixing the condenser fan scroll. Then remove the bracket with condenser fan motor and blower wheel from the unit. 17

4.10 To repair the water disposal system or replace the water depth switch or the pump. Remove the screws fixing the supporting board. Remove the water pipe from the cover. Remove the screw fixing the pump clamp. Then, remove the condenser fan scroll. Now, remove the pump and replace. Now, it is easy to repair the refrigerant system. 18

Remove the screw fixing the water switch which controls the water in tank. Then remove the screws fixing the switches and replace. Pay attention to the holes. Don t install into wrong holes. Press the clamp fixing the water switches which control the water in the chassis. Press downward here 19