The Remote Control of Power Supplies Experience of Exploitation*



Similar documents
Mixing Sodium and Lead Battery Technologies in Telecom Applications

FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store.

Big Data Collection and Utilization for Operational Support of Smarter Social Infrastructure

Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks

MPR-Systems. Mini Power Racks 1200 W W

TECHNICAL DESCRIPTION OF THE DISTRIBUTION SUBSTATION REMOTE MONITORING SYSTEM

Our comprehensive range of services

EFFECTIVE ROOT CAUSE ANALYSIS AND CORRECTIVE ACTION PROCESS

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

FPGA Implementation of IP Packet Segmentation and Reassembly in Internet Router*

POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery

DECISION. Single Registry of Legal Entities Transaction Accounts in. Bosnia and Herzegovina. Article 1

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

Exam : EX Title : ITIL Foundation Certificate in IT Service Management. Ver :

Process approach to quality management in education

Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery

14. Troubleshooting Guide

Power Management of Cell Sites

WHAT ARE THE BENEFITS OF OUTSOURCING NETWORK SECURITY?

TracKing. A complete web-enabled temperature management system.

Movicon in energy efficiency management: the ISO standard

OPERATIONAL SERVICE LEVEL AGREEMENT BETWEEN THE CLIENT AND FOR THE PROVISION OF PRO-ACTIVE MONITORING & SUPPORT SERVICES

BELEX15 Methodology. Ver 2.3. Belgrade Stock Exchange, Avgust Page 1

APPENDIX 7. ICT Disaster Recovery Plan

Fuel Management System. Fuel Tank Monitoring TB-9001

BLAST MONITORING Solutions

How To Monitor Safety Management System Performance

UPS Monitoring Software. User manual Borri Power Guardian

Dynamic: Dynamic risk management is carried out by all personnel at an operational incident.

TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING

ITIL A guide to event management

UPS Monitoring Software User Manual. Emily2

OUTSOURCING MAINTENANCE PROCESSES IN ELECTRICITY UTILITIES. Philip Wester. NUON InfraCore, The Netherlands

Regulations on Information Systems Security. I. General Provisions

NetVision. NetVision: Smart Energy Smart Grids and Smart Meters - Towards Smarter Energy Management. Solution Datasheet

GENERAL TERMS OF USE OF INTESA SANPAOLO ELECTRONIC BANKING FOR RETAIL CLIENTS

Inverter / Charger Installation General Operations and AC and DC Connections

Polish Financial Supervision Authority. Guidelines

Nuclear Safety Council Instruction number IS-19, of October 22 nd 2008, on the requirements of the nuclear facilities management system

SD Series. SD Series Rectifiers. EPC Energy & Power Conversion

UPS Monitoring. Tutorial A guide from: Your partners in UPS Monitoring Systems

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Predictive Maintenance in a Mission Critical Environment

ARTIFICIAL NEURAL NETWORK FOR OVERHEAD TRANSMISSION LINE MONITORING

Release: 1. CPPSEC4015A Maintain networked security system

Part A OVERVIEW Introduction Applicability Legal Provision...2. Part B SOUND DATA MANAGEMENT AND MIS PRACTICES...

INTERNATIONAL STANDARD ON AUDITING 401 AUDITING IN A COMPUTER INFORMATION SYSTEMS ENVIRONMENT CONTENTS

Engineering & Support Services

SAFETY MANAGEMENT SYSTEM FOR MAJOR HAZARD FACILITIES - BOOKLET 3: Part 7.17

1 What does the 'Service V model' represent? a) A strategy for the successful completion of all service management projects

AAPT Business NBNPhone

Data Analytics and Reporting in Toll Management and Supervision System Case study Bosnia and Herzegovina

New Automatic Radiation Monitoring Network in Slovenia

ITIL A guide to Event Management

POWER QUALITY MEASUREMENT ANALYSIS OF THE ELECTROSTATIC PRECIPITATOR

QUANTITATIVE MODEL FOR INFORMATION SECURITY RISK MANAGEMENT

Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery

SELECTION OF THE MANNER OF MEASURING SIGNIFICANT CHARACTERISTICS OF THE INSURANCE COMPANIES SERVICE QUALITY

Towards a Field-Data-Driven Productivity Analysis and Planning System for Industrial Service

Sensitivity Analysis of Safety Measures for Railway Tunnel Fire Accident

COMPLIANCE REVIEW OF 2006/07 ASSET MANAGEMENT PLAN. Top Energy Limited

APPENDIX 7. ICT Disaster Recovery Plan

Incident Response Plan for PCI-DSS Compliance

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Back-UPS Pro 1300/1500 Installation and Operation

PATTERN MATCHING OF LIVE DATA TO IMPLEMENT PROACTIVE NETWORK MANAGEMENT

Adlib Hosting - Service Level Agreement

FaultAnalysisandElectricalProtectionofDistributionTransformers

Information Security Team

A Guide to Carrying Out a SWOT Analysis Introduction

University of Sunderland Business Assurance Information Security Policy

SWITCHING STRATEGIES: MOVING TO CONDITION- BASED MAINTENANCE. By David Stevens, Technical Manager & Trainer, AVT Reliability

Community Infrastructure (CI) Recovery. Krishna S. Vatsa Regional Disaster Reduction Advisor BCPR, UNDP

Pump Controller Type ABS PC 441 Monitoring and/or Control of Pumps and Pumping Stations

Enterprise Remote Monitoring

Online Transformer Insulation Monitoring System BushingGard Product Focus. Maximizing Transformer Uptime and Reliability

Proactive Monitoring of Friction Management Systems Reduces Costs and Downtime

wireless alarm system reliable protection for small-size buildings

Using reporting and data mining techniques to improve knowledge of subscribers; applications to customer profiling and fraud management

Which ITIL process or function deals with issues and questions about the use of services, raised by end users?

Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant

HYBRID POWER SYSTEMS for TELECOM applications

Module 4, Lesson 12 Fire Alarm Systems

Cyber Security Incident Handling Policy. Information Technology Services Center (ITSC) of The Hong Kong University of Science and Technology

GE Consumer & Industrial Power Protection. Digital Energy LP Series UPS. Uninterruptible Power Supply 3-30 kva. GE imagination at work

3.4.4 Description of risk management plan Unofficial Translation Only the Thai version of the text is legally binding.

EUROPASS DIPLOMA SUPPLEMENT

False Alarm/Unwanted Fire Signals Reduction Guidance

General Terms of Public Procurement in Supply Contracts JYSE 2014 SUPPLIES

GENERAL TERMS AND CONDITIONS for Registration of National Internet Domain Names

Transcription:

SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 9, No. 1, February 2012, 95-105 UDK: 621.311.68-52 DOI: 10.2298/SJEE1201095P The Remote Control of Power Supplies Experience of Exploitation* Dragana Petrović 1, Miroslav Lazić 1 Abstract: The remote control of power supplies has been developed according to Telecom Serbia s technical requirements. It has been exploited for five years. From this system specially developed for the needs of a telecom company, it has evolved into a universal system. After five years of usage of SDNU, analysis and systematization of the detected problems were carried out. The data were collected from about 200 external devices. The analysed objects were of the first priority, located in larger cities, but also objects in inaccessible locations far from the city. The identified problems were grouped into four categories. According to classification of the problem, recommendations about SDNU users work organisation were made in order to exploit the results effectively. This paper presents the characteristic forms of signals for every category of the detected problems. Keywords: Remote control, Power supply, Exploitation. 1 Introduction SDNU system enables remote monitoring and control of the devices that are placed in remote objects. System is specially developed for the needs of Telecom Serbia. It is usually used in objects which are of great importance for the user, or objects that are placed in remote areas. Heart of this system is the device for data acquisition DNU24 which is mounted in the peripheral objects. With its probes that are connected to characteristic measuring points, buy the request of the user, it measures the currents velocity, voltage or temperature. Measured quantities are sent to the computer in the monitoring center. Graphical display on the computer gives clear and unambiguous information about the status of the device which is being monitored. Collected data is memorised and the user can get the report of the work for monitored device at any time. In this way, we can very simply do the analysis of the work of monitored device, or work of the system of devices in monitored object. It was 1 IRITEL a.d., Batajnički put 23, 11080 Belgrade, Serbia; E-mails: titelac@iritel.com; mlazic@iritel.com *Award for the best paper presented in Section Electronics, at Conference ETRAN 2011, June 6 9, Banja Vrućica Teslić, Bosnia and Herzegovina. 95

D. Petrović, M. Lazić observed that there are objects where single devices work very good, but that with their connection in the system creates a problem that is not easily recognized. With correct usage of SDNU and with analysis of the results by the side of professional staff, mistakes can be quickly noticed and removed before they create a breakdown in the work and greater consequences to the devices In the five year exploitation period, product-development team of the remote monitoring and control system SDNU has faced different problems connected to the work of devices which are being monitored, installation in monitored objects and disorders created by the weather conditions. 2 Reports of Remote Control Reports on the work unit, obtained from SDNU, contain important data, which indicate the operation of the unit, problems that occur (incidents), a skilled analysts from these reports can reveal the cause of the incident. Remote monitoring devices not only allow the supervise company to determine what is right on the device and that adjustments or repairs are needed. These reports also allow to device manufacturers to determine defects in the devices which were monitored and improve their production process. Report of the remote control can be used for different purposes. The most common application is to gain insight into device operation and incidents that occur. However, these reports can be used for different analysis, such as analysis of the incidents which locations are most likely to occur, the analysis of the most common causes of accidents, etc. All reports received from SDNU must be analyzed and this analysis document. In the addition is given the suggestion of the main phases that each documented report of remote monitoring must go through. Bacis phases [4] can include the following. 1. Identification of the report - Report has been identified at the moment when it arrives in the computer system and when the person that follows the remote monitoring notices that there is an incident that occured on the device. Incident can also be reported by SMS. Each report about the incident (as well as the foregoing daily reports about the work of the device) has its own unique mark, which consist from the date and time when incident occured, as well as the mark of the device and location where it is placed. 2. Storage and usage of the report - Reports that arrive must be taken into consideration as soon as they are identified, in order to undertake the necessary measures, so that we do not have failiure in the work of the device. However, these reports have to be storaged on the computer, so that we are able to do additional analysis of the report. Also, we need to 96

The Remote Control of Power Supplies Experience of Exploitation define who will be responsible for following the reports, gathering them, storing them and later analyzing them. Employee which is responsible for the that (usually they are employees of the monitoring center) have to be appropriatly trained. Ability to recognise priority in obtained reports is very important. Not every report of the remote monitoring will indicate on the incident which causes the system to stop working. Sometimes, incidents are less significant. That is why we need to define which reports indicate on urgent actions (repairs, significant adjustments, replacement of parts..), because, for example, they indicate that device has stopped working and that system will not be able to function. Urgency of action in relation to results of the report needs to be based on detailed analysis of the risk. Risk analysis should take into consideration all of the damages that can occur with malfunction of the device, with possibility of the damages appearing again. 3. Approach to the reports Approach to the reports should be granted only to employees in the monitoring center, which are appropriately trained for conducting this activity. 4. Rejection of the reports Not all of the reports from monitoring center should be stored forever. It is enough to keep the reports from previous three years. However, we need to make report analysis for each year and to store them as documents for acquisition the new knowledges in the company. From each analysis we are able to see the deficiencies in the work of the device and to determine places for improvement. 3 Categorization of the Problem of Power Electronics Devices for continuous power feed between primary sorces of energy and users-consumer devices. Besides the fact that we need to provide the continuos work of consumer device, devices for continuous power are awarded the protective function so we can say that they represent heart of every system. The are different factors that affect the work of equipment which is powered from the electrical network, and the quality of the electrical energy is one of them. Influence of the voltage changes in the electrical network is directly transferred to consumer devices, and there is mutual influence of the devices that are connected to the same power line. Correct work of the devices of Power electronics is one of the conditions for undisturbed work of the equipment which is powered from electrical network. Analysis conducted over the period of years have confirmed that many of the failures in telecomunication systems are cause by the shotdowh of the devices that are used for power supply. 97

D. Petrović, M. Lazić The analysis of reports which are drawn from the existing system SDNU mounted in Serbia and Republika Srpska at about 200 peripheral structures, was found that the problems of the power devices can be classified into four groups: 1. External Factors The problems caused by external influences such as incorrect incoming voltage from the power company, atmospheric discharges, intervention by unauthorized persons, etc. are often the cause for malfunctioning. Rectifier plant must be adapted to conditions by, wherever possible, to protect consumer devices from external factors. Protective role of rectifier systems can be classified in the first and second group of problems. 2. The Quality Of The Delivered Equipment The delivered power electronic equipment is often not in accordance with the specifications under which it is declared as stated in 1. For example, rectifier systems must meet the required standards. One of the important features of these regulations is to charge the battery at IVV (voltage-current-voltage) characteristics. Only in this way it is possible to achieve the life of the battery capacity prescribed by the manufacturer. However, the practice is often the case. 3. Installation Errors Errors occurred while connecting installations are common in buildings mounted decades ago, but are also present in the new facilities. It is very difficult to detect errors of this type. Error can be manifested in different ways and therefore difficult to locate. SDNU facilitates detection of such errors, but you need a good working knowledge of monitored devices and SDNU. 4. The Human Factor Non-intentional errors that occur caused by human factors are uncommon and cannot make the catastrophic consequences, but they are enough to lead to incorrect operation. Employees responsible for the equipment monitoring, resolve problems in different ways to avoid downtime and catastrophic outcomes. Often, unintentionally, other problems are caused. 4 Identified Issues After Five Years of Exploitation During five years of exploitation many irregularities have been observed. They were recorded and analyzed in detail by experts of power electronics. Some of them are mentioned here to illustrate the possibilities SDNU. 98

The Remote Control of Power Supplies Experience of Exploitation An example of the impact of external factors Figs. 1 and 2 show the captured signal forms of the input line voltage, which clearly shows the power supply problems. Fig. 1 shows the waveforms of all three phases of the input voltage signal. It was observed that the disappearance of one phase (Fig. 1b) causes an increase of voltage values of other two phases (Figs. 1a and 1c). Increase in input voltage causes disruption in the work of consumer products and even their failures. (a) (b) (c) Fig. 1 Forms voltage mains voltage: (a) first phase; (b) second phase; (b) third phase. 99

D. Petrović, M. Lazić Waveform shown in Fig. 2 shows the measurement of a input phase voltage during the day. Measurements were recorded in fifteen minutes intervals. It is clear that during the 24 hours interval, supply voltage was disrupted for four times. The first disappearance lasted for 7h, the second and third fifteen minutes and the last 45 min. Common variations in supply voltage can affect backupbattery life by reducing its capacity. Fig. 2 (a) Forms voltage one phase mains voltage. An example of the impact of quality of delivered equipment Figs. 3, 4 and 5 show the voltage and current waveforms at the output of rectifier plants and demonstrates the way they work. Comparing Fig. 3 and Fig. 4 easily can be noticed that plant rectifiers charge batteries in different manners. Fig. 3 shows rectifier which charges the battery without the regime of constant current and without charging voltage V boost. The battery is charging with 10 A and with voltage V float. Fig. 4 shows the charging waveforms of batteries that are charged in compliance with standards. Battery is charged with constant current to a preset voltage charging (V boost ). The battery voltage rises exponentially to voltage V boost. After reaching that voltage, charger goes into constant voltage mode, where the charge current decreases and the voltage is held constant. When battery current reaches a predefined value, the voltage applied to the battery gets the value of V float. Fig. 5 shows the voltage and current waveforms of rectifying plant that does not charging the battery properly. The battery has defined boost and float voltage, but there is no constant current charging. It can be seen in Fig. 5a that there it is not applied an exponential charging curve. Peak current (Fig. 5b) that fully charges the battery to V boost damages the battery. Battery charging, shown in Figs. 3 and 5, very quickly lead to battery damage. Rectifier plants that charge the battery in the manner shown in Figs. 3 and 5 after several times damage the battery (battery lose its capacity). 100

The Remote Control of Power Supplies Experience of Exploitation (a) (b) Fig. 3 Forms of signals at the output of power supplies: (a) voltage; (b) current. (a) (b) Fig. 4 Forms of signals at the output of power supplies: (a) voltage; (b) current. 101

D. Petrović, M. Lazić (a) (b) Fig. 5 Forms of signals at the output of power supplies: (a) voltage; (b) current. An example of influence of installation errors An example of influence of installation errors is given in Fig. 6. Waveforms on the left represent supply voltage, and waveforms on the right output voltage of the generator. Fig. 6 clearly shows that the backup unit properly overtakes the role of power supply when grid failure occurs. However, the output voltage of backup unit exceeds value of 300V, which can affect the consumer devices. Analysis revealed that the neutral conductor is not properly connected. An example of influence of the human factor An example of the impact of human factors: workers responsible for maintenance of power electronics devices always striving to increase the use of batteries. Very often they make the situation worse. Fig. 7 shows the battery voltages. It can be easily seen that one battery is charging another battery. This means that one battery is malfunctioning. We thus conclude that the workers wanted to strengthen the system by adding an extra set of batteries. This caused that the set of high capacity batteries charge the weak set of batteries. In this manner, a counter effect occurred and instead of increasing overall capacity by adding a set of battery, battery capacity is reduced because the defective battery consumed energy. 102

The Remote Control of Power Supplies Experience of Exploitation Fig. 6 Forms of signals main voltage end diesel generators. 103

D. Petrović, M. Lazić Fig. 6 (continuation) Forms of signals main voltage end diesel generators. (a) (b) Fig. 7 Forms of signals: (a) first battery bank; (b) second battery bank. 104

The Remote Control of Power Supplies Experience of Exploitation 5 Conclusion Proper use of reports generated by the system for remote monitoring and management SDNU, as discussed in chapter two, can help prevent the operation of monitored systems. No matter which devices are being monitored, errors in setting up and installation of equipment can occur. On the other hand, weather conditions cannot be predicted and therefore, there is possibility of equipment failure. To take full advantage of SDNU, the user should make a proper organization of employees. In other words, failure information should be sent to the operator who can react accordingly. SDNU device provides detailed information for each measured size and the occurrence of an alarm is transmitted immediately when it happens. The experts who analyze the results sent by SDNU can very easy recognize the problem and eliminate it before damage occurs. SDNU offers the user the freedom in the choice of measured values, alarm thresholds and where the measured information will be sent. Therefore, the best results are achieved if SDNU device is properly used. 6 Acknowledgement This paper is partially supported by the project TR32016 which is carried out with the financial support of the Ministry of Science and Education of the Republic of Serbia, to which the authors are very grateful. 7 References [1] M. Lazić, D. Titelac: One Solution for Remote Control of Power Supplies in Telecommunication Systems, Infoteh, Jahorina, Bosnia and Hercegovina, 22 24 March 2006. Vol. 5, Ref. E-IV-1, p. 440 443. (In Serbian). [2] M. Stanković, D. Stajić: Device for Data Collection DNU 24 Basic Functions, Infoteh, Jahorina, Bosnia and Hercegovina, 26 28 March 2008, Vol. 7, Ref. B-III-3, p. 240 243. (In Serbian). [3] B. Jovanović, M. Lazić, B. Kosanović: Measurement, Analysis and Improvement in Organization of Remote Control, Infoteh, Jahorina, Bosnia and Hercegovina, 21 23 March 2011, Vol. 10, Ref. D-18, p. 358 361. (In Serbian). [4] SRPS ISO 9001:2008 Sistemi menadžmenta kvalitetom Zahtevi, Institut za standardizaciju Srbije, t. 4.2.4. 105