PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by



Similar documents
APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

SIZING OF WATER PIPING SYSTEM

Sizing Plumbing Water System

CHAPTER 2: The Plumbing System

Isometric Plumbing Drawings

What to Expect From the Examination. How to Study the Plumbing Codes

Introduction to Water Pipe Sizing

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

One of the fundamental design elements that every

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Supply Piping Planning Tool Reducing Water Wasted Waiting for Hot

Plumbing Code Sections For Commercial Food Facilities

Home comfort: water heating

Water Pressure Reducing Valves

Codes and Standards Research Report. California s Residential Indoor Water Use. 2 nd Edition (Revised May 8, 2015)

ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since Wet Venting. Incorporating Stack Venting and NPC Harmonization

PLUMBING PERMIT APPLICATION (PLUMBING PERMIT TO BE SECURED 24 HOURS BEFORE WORK STARTS)

Surge Pressure in Plumbing Pipe Materials

Pressure Drop Basics & Valve Sizing

City of Elk River BASEMENT Office Use Only

Element D Services Plumbing

Utility Service Application

PROPOSED Plumbing Fee Ordinance Amendment

WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION

PMA ONLINE TRAINING Venting for Plumbing Systems

Research of Grey Water for Use in Residential Applications Original date of publication: Updated:

Whole House Water Treatment System. Installation, Operation and Maintenance Manual. Multi-Pure Model TO15000

detection kit the water leak water leaks: What you should know A helpful guide for locating indoor and outdoor water leaks Getting Ready

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

WATER SUPPLY AND DISTRIBUTION

CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC

Oregon Plumbing Rule and Law RV

2012 British Columbia Plumbing Code Update

Dominic i Barbato Dpt. Of Building and Safety (818) domenico.barbato@lacity.org

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

SECTION Hot Water Heaters (Hot Water Recirculation Systems and Point-of-Use Water Heaters)

Plumbing Lesson One: Help! Call the Plumber. Student Handouts

DRAFT ONLY ORDINANCE NO.

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

What is Thermal Expansion?

Leak Detector Guide. Your Guide to Home Water Conservation

Georgia State Amendments to the International Plumbing Code

WATER LEAK DETECTION G

This document was scanned from hard copy to portable document format (PDF) and edited to 99.5% accuracy. Some formatting errors not detected during

Energy Efficiency. Energy Efficient Water Heating: Purchasing a new electric water heater. Hot water use has a significant impact on your bill.

Proposed Revision to International Residential Code 2012 (as proposed to the ICC for IRC 2015)

LEAK DETECTION GUIDE

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Codes and Standards Research Report. California s Residential Indoor Water Use

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

A High Bill Usually Means a Leak

2006 Codes. Please verify the following before calling for inspection

2. What building projects are exempted? (permit not required)

Residential Plumbing BCN 1058

PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC

Shaw s Incorporated Winterization Agreement

When Should Examination Preparation Begin?

Calculation of Potential Water Savings in

PLUMBING CODE REGULATION

8 plumbing. plumbing PulteGroup, Inc. All Rights Reserved.

THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: Section 1. Article V of Chapter XII of the Los Angeles Municipal Code is added to read:

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector

Amendments to the 2012 International Plumbing Code

This presentation premiered at WaterSmart Innovations. watersmartinnovations.com

Water Heater Sizing TS Saturday 2:15pm 5:15pm J. Joe Scott CPD, FASPE, LEED

CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004

How To Calculate Fixture Counts For A Building

Residential Water-Use Survey

REQUIREMENTS FOR SINGLE FAMILY DWELLINGS

What you can expect from your Solar Hot Water System

CHAPTER 26 PLUMBING CODE

FIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS

Frequently Asked Questions about water & sewer bills

2010 Residential Water Heater Replacement Check List

FAQ and Device/Usage Chart. What Is a Cross-Connection? What Is Backflow Prevention? What Is Backflow?

R432. Health, Health Systems Improvement, Licensing. R Nursing Facility Construction. R Legal Authority. R Purpose.

WATER & SEWER SERVICES

Roland Garcia Pearland Fire Department

Common Causes of High Water Bills

INDIRECT WATER HEATER. Installation and Operating Instruction Manual

Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents

Pipe Sizes For Water Distribution System Design

ADVICE NOTE WATER LEAKS. How to prevent water leaks in your flat

FOOD ESTABLISHMENT GUIDE FOR DESIGN, INSTALLATION, AND CONSTRUCTION RECOMMENDATIONS

INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville

ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM REQUIREMENTS

How To Fix A Leaky Water Heater

Backflow Bulletin #1

To many people, a home s plumbing system is perceived as being extremely

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs

CHAPTER 9: WATER HEATING

Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text

Metropolitan Domestic Water Improvement District. Backflow Prevention Control Ordinance. Ordinance No

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS

ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007

Transcription:

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS Second Edition Prepared by NAHB Research Center, Inc. 400 Prince Georges Boulevard Upper Marlboro, MD 20774-8731

DISCLAIMER This report was prepared by the NAHB Research Center, Inc., which makes no warranty, express or implied, and assumes no legal liability or responsibility for the accuracy, completeness or usefulness of any information provided by the Research Center by outside parties. This report is not intended as an endorsement or criticism of any particular product or class of products. The Research Center does not warrant or represent that use of the information contained herein would not infringe on privately-owned rights. Reproduction of this report in whole or in part, is prohibited without advance permission in writing from the NAHB Research Center, Inc., 400 Prince Georges Boulevard, Upper Marlboro, MD 20774-8731. First Edition: July 1997 Second Edition: December 1997 Copyright 1997 by NAHB Research Center, Inc. All Rights Reserved. TABLE OF CONTENTS ii g:\dat\common\lab\softener\homebase.doc

BACKGROUND... 1 MODEL PLUMBING CODES IN THE UNITED STATES... 1 PLUMBING CODE REQUIREMENTS FOR WATER SOFTENERS... 2 PLANNING THE INSTALLATION... 3 SIZING PROCEDURES... 4 REFERENCES... 9 SIZING FORM FOR WATER SOFTENERS... 10 iii

BACKGROUND Plumbing codes list minimum performance requirements for potable water supply and distribution systems. Since water softening devices are an integral part of many residential water supply systems, it is imperative for water softeners to be constructed, sized, and installed in accordance with the provisions of nationally recognized performance standards and the model plumbing codes. MODEL PLUMBING CODES IN THE UNITED STATES There are five model plumbing code organizations in the United States. Uniform Plumbing Code (UPC) (adopted mainly in the western U.S.) Standard Plumbing Code (SPC) (adopted mainly in the southern U.S.) BOCA Plumbing Code (BOCA) (adopted mainly in the eastern U.S.) International Plumbing Code (IPC) CABO Plumbing Code (CABO) (written exclusively for residential construction) The International Plumbing Code (IPC) is a new code and a joint effort between the three major model code groups (UPC, SPC, and BOCA). This code was first published in 1995 with the intention of eventually replacing the UPC, SPC, and BOCA codes with one unified code. The CABO plumbing code is derived from the three major model codes and is designed specifically for plumbing of one and two family (residential) dwellings. A local municipality can choose to adopt one of the model codes as published, or can add amendments to deal with factors that are unique to the area. The provisions of the model plumbing codes are generally consistent, but contain somewhat different requirements to address factors that are unique to the area of the country for which each is written. For example, the UPC contains explicit requirements for strapping water heaters due to the risk of earthquakes in the western U.S. 1

PLUMBING CODE REQUIREMENTS FOR WATER SOFTENERS A. The following information shall be incorporated in Manufacturer s design and installation instructions. Design, installation and maintenance instructions shall be in compliance with model plumbing codes. 1. All of the model plumbing codes require water supply systems to be designed to deliver a specified flow rate (gallons of water per minute). Each code lists procedures for calculating design flow rates, which are directly related to the number of plumbing fixtures in the building. 1 Consequently, a water softener must have a listed flow rate that meets or exceeds the design water flow rate of all portions of the plumbing system served by the water softener. 2. The minimum static water pressure at the building entrance must be at least 40 psi. 2 3. The performance of water softeners shall comply with the provisions of WQA S-100 3 (Water Quality Association S-100-95: Household, Commercial, and Portable Exchange Water Softeners; An Equipment Validation Standard). 4. The nominal diameter of water supply piping to the softener must be at least ¾-inch. 4 5. The inlet and outlet diameter of the water softener must match the diameter of the water supply piping at the location where the softener will be installed. 5 6. Plumbing fixtures must have a minimum available flow pressure of 8 psi. 6 7. Sizing provisions contained in Manufacturer s documentation are intended to help designers and installers provide homes with water softeners that are capable of supplying water at pressures and flow rates required by the model plumbing codes. Sizing provisions for all model plumbing codes shall be provided. 8. The following table illustrates the design flow rates required by the model plumbing codes. This example is for a house with two baths, with required design flow rates calculated in accordance with CABO, UPC, SBCCI and IPC code requirements. NOTE: Hosebibs should be connected to the water supply upstream of the water softener, or a manual bypass valve should be provided to isolate the water softener during hosebib usage. 9. Residential fire (sprinkler) suppression systems shall be addressed in Manufacturer s design and sizing criteria. 1 1995 CABO Sect. 3409, 1997 UPC Appendix A, 1997 SPC Appendix F, 1995 IPC Appendix E 2 1997 CABO Sect. 3403.2 3 1997 UPC: Appendix C 4 1997 UPC Sect. 610.8, 1995 IPC Sect. 604.1, 1995 CABO Sect. 3403.4, 1997 SPC Sect. 608.2 5 1997 UPC Sect. 610.2 6 1997 SPC Sect. 607.4, 1995 CABO Sect. 3403.2.1, 1995 IPC Sect. 605.3 2

PLANNING THE INSTALLATION The following information is required to properly size water softeners: Water pressure at the service entrance to the house (can be obtained from local water service provider or by measuring the static pressure at the service entrance). The number of the following plumbing fixtures: Bathroom sinks and utility sinks (lavatories) Bathtubs (with/without overhead shower head) Showers Stalls Water Closets Kitchen Sinks Dishwashers Clothes Washers Hose Bibbs (outdoor faucets) Determine the location where the water softener will be installed in the water supply piping. This location should be located near the service entrance but downstream from the main water supply shutoff valve 7. Furthermore, the softener should be located upstream from water fixtures and appliances with the following exceptions: Fire Sprinklers: If the house is equipped with a fire sprinkler system that draws water from a single connection point near the service entrance, the required water softener size can be reduced by installing the softener downstream from the branch supplying the sprinkler system. If the sprinkler system draws water from individual branches of the water supply system, this reduction is not possible and the sprinklers must be included in the water softener sizing calculations. Outdoor Hose Bibbs: Since water hardness is typically irrelevant for outdoor uses, it may be possible isolate outdoor hose bibbs from the water softener. If the outdoor hose bibbs connect to the water supply piping near the service entrance, the required water softener size can be reduced by installing the softener downstream from the branch supplying the hose bibbs. Determine the local plumbing code adopted by the town where the water softener will be installed (UPC, SPC, BOCA, IPC, or CABO). Note that some localities use their own plumbing code, and the model codes may not apply. 7 1997 SPC 610.1, 1997 UPC 605.5 3

SIZING PROCEDURES Model plumbing codes have similar requirements for sizing water supply piping. These requirements are designed to ensure that water fixtures will have an adequate supply of water under normal household use. 1. Begin by making a list of the type and number of water fixtures that will be installed downstream from the water softener. Determine whether fire sprinklers and outdoor hose bibbs will be supplied by the water softener. The required flowrate of the water softener can be significantly reduced if fire sprinklers and hose bibbs can be isolated from the water softener (not connected to the water softener outlet). 2. Refer to the sizing tables in this document. Each page has two tables that contain sizing requirements for a particular model plumbing code. Choose the page that corresponds to the model plumbing code that will be used to size the water softener. 3. Plumbing codes account for water demand by assigning water supply fixture units (wsfu) to each water appliance. Using the first table on the page, find the wsfu rating for each water fixture in the house (to be located downstream from the water softener). Add these individual wsfu ratings to obtain a total wsfu rating for the entire house. 4. Use the total wsfu rating to find the required minimum flowrate (gallons per minute) from the second table on the page (interpolate the flowrate if necessary). 5. If the home is equipped with fire sprinklers that cannot be isolated from the water softener (ie: water softener cannot be installed downstream from the take-off for the fire sprinklers), the minimum required flowrate of the water softener is 26 gallons per minute. 8 6. Refer to the flowrates calculated in steps 4 and 5 above. The higher value is the minimum required flowrate for the water softener (gallons per minute of water). For homes without fire sprinkler systems, the minimum required flowrate is the value calculated in step 4. 7. The example on the following page demonstrates the proper procedure for sizing a water softener for a particular house. 8 NFPA 13D-1994 Sect. 4-1 (two sprinklers rated at 13 gallons per minute). 4

EXAMPLE: Sizing Requirements for CABO Plumbing Code and UPC Plumbing Code Compare the minimum required flowrate for a water softener sized in accordance with CABO requirements and UPC requirements for a house with the following water fixtures: 2-1/2 bathrooms (2 bath/showers, 3 lavatories, and 3 water closets) (1) Clothes washer (1) Kitchen sink (1) Dishwasher (2) Hose bibbs Use the tables on the top of pages 6 and 7 to find the wsfu value for each individual water fixture. Page 6 lists the sizing criteria for CABO, and page 7 lists sizing criteria for UPC. Make certain to multiply the wsfu value by the number of fixtures to get the total wsfu s for each fixture type. Add the total wsfu s for each fixture type to get total wsfu s for the house. Use the total wsfu s for the house with the tables on the bottom of pages 6 and 7 to find the minimum required flowrate for the water softener. For the house in this example, we have: Water Fixture Type 2-1/2 Baths Bath/shwr. Lavatory Water Closet Number of Fixtures 2 3 3 CABO Sizing Reqs. wsfu s for Total each fixture wsfu s 5.6 - - - 5.6 (CABO lists wsfu s for bathrooms) UPC Sizing Reqs. wsfu s for Total each fixture wsfu s Clothes 1 1.4 1.4 4.0 4.0 Washer Kitchen Sink 1 1.0 1.0 1.5 1.5 Dishwasher 1 1.4 1.4 1.5 1.5 Hose Bibbs 2 2.5 5.0 2.5-1 st bibb 1.0-2 nd 3.5 bibb Total wsfu s for House - 14.4 29.0 Min. Required Flowrate 10.6 19.5 (gpm) 4.0 1.0 2.5 8.0 3.0 7.5 This example shows that water softener flowrate requirements vary between the plumbing codes. Consequently, it is very important to size the water softener in accordance with the model plumbing code recognized in the municipality where the softener is to be installed. Make certain to use the proper table (that corresponds to the plumbing code in your area) when sizing the water softener. 5

Sizing Water Softeners with the 1995 CABO Plumbing Code Determine the total number of water supply fixture units (wsfu rating) for all water fixtures to be supplied by the water softener from the following table: Water Supply Fixture Unit Values for CABO Plumbing Code 9 Type of Fixtures or Group of Fixtures wsfu value (combined hot & cold) Multiple Bath Groups 1-1/2 baths 2 baths 2-1/2 baths 3 baths 3-1/2 baths Additional 1-1/2 bath if part of group 4.4 5.2 5.6 6.3 6.8 0.8 Bathtub (with/without overhead shower) 1.4 Shower Stall 1.4 Lavatory 0.7 Water Closet (tank type) 2.2 Kitchen Sink 1.4 Dishwasher 1.4 Clothes Washer 1.4 Hose Bibb (outdoor faucet) 2.5 After adding together the wsfu values of the individual water fixtures, use the table below to find the minimum required flowrate of the water softener. Required Flowrate of Water Softener based on CABO wsfu Rating 10 Total wsfu value of all water fixtures downstream from water softener Required water softener flow rate (gallons per minute) 9 7.2 10 7.7 12 9.0 14 10.4 16 11.6 18 12.7 20 14.0 25 16.8 30 19.5 9 1995 CABO Table 3409.2 10 1995 CABO Table 3409.3 6

Sizing Water Softeners with the 1997 Uniform Plumbing Code Determine the total number of water supply fixture units (wsfu rating) for all water fixtures to be supplied by the water softener from the following table: Water Supply Fixture Unit Values for Uniform Plumbing Code 11 Type of Fixtures or Group of Fixtures wsfu value (combined hot & cold) Bathtub (with/without shower) 4.0 Lavatory 1.0 Shower 2.0 Water Closet - 1.6 gallons/flush (tank type) 2.5 Water Closet - 3.5 gallons/flush (tank type) 3.0 Kitchen Sink 1.5 Dishwasher 1.5 Clothes Washer 4.0 Hose Bibb (outdoor faucet) 2.5 Hose Bibb - each additional 1.0 After adding together the wsfu values of the individual water fixtures, use the table below to find the minimum required flowrate of the water softener. Required Flowrate of Water Softener based on UPC wsfu Rating 12 Total wsfu value of all water fixtures downstream from water softener Required water softener flow rate (gallons per minute) 7.5 6.0 10 8.0 15 11.5 20 15.0 25 17.5 30 20.0 11 1997 UPC Table 6-4: values based on individual dwelling 12 Values determined from Chart A-3 in Appendix C of 1997 UPC per section A2.1 7

Sizing Water Softeners with the 1997 Standard Plumbing Code and 1995 International Plumbing Code Determine the total number of water supply fixture units (wsfu rating) for all water fixtures to be supplied by the water softener from the following table: Water Supply Fixture Unit Values for Standard Plumbing Code and International Plumbing Code 13 Type of Fixtures or Group of Fixtures wsfu value (combined hot & cold) Bathtub (with/without shower) 1.4 Lavatory 0.7 Shower 1.4 Water closet 2.2 Kitchen sink 1.4 Dishwasher 1.4 Clothes washer 1.4 Hose bibb Designer s discretion* *SPC and IPC states that load should be determined by comparing hose bibbs to fixtures using similar amounts of water at similar rates. After adding together the wsfu values of the individual water fixtures, use the table below to find the minimum required flowrate of the water softener. Required Flowrate of Water Softener based on SPC and IPC wsfu Rating 14 Total wsfu value of all water fixtures downstream from water softener Required water softener flow rate (gallons per minute) 8 12.8 10 14.6 12 16.0 14 17.0 16 18.0 18 18.8 20 19.6 25 21.5 30 23.3 13 1997 SPC Table F101B, 1995 IPC Table E101B (demand for fixtures in private buildings) 14 1997 SPC Table F102, 1995 IPC Table E102 (demand for distribution systems with flush tanks) 8

REFERENCES CABO One and Two Family Dwelling Code - 1995 Edition. Published by the Council of American Building Officials, 5203 Leesburg Pike, Falls Church, VA, 22041. International Plumbing Code - 1995 Edition. Published by the International Code Council, Inc. Current Secretariat: Building Officials and Code Administrators International, Inc., 4051 West Flossmoor Road, Country Club Hills, IL, 60478-5795. NFPA 13D: Standard for the Installation of Sprinkler Systems in One- and Two- Family Dwellings and Manufactured Homes - 1994 Edition. Published by the National Fire Protection Association, Inc. Standard Plumbing Code - 1997 Edition. Published by the Southern Building Code Congress International, Inc., 900 Montclair Road, Birmingham, AL, 35213-1206. Uniform Plumbing Code - 1997 Edition. Published by the International Association of Plumbing Officials, 20001 Walnut Drive South, Walnut, CA, 91789-2825. Water Quality Association S-100-95: Household, Commercial, and Portable Exchange Water Softeners; An Equipment Validation Standard. Published by the Water Quality Association, 4151 Naperville Road, Lisle, IL, 60532. 9

SIZING FORM FOR WATER SOFTENERS Step 1 List each type of water fixture (ie: bath/shower, lavatory, etc.) that will be connected to the outlet of the water softener in left column of the table below. In the next column to the right, list the total number of each type of water fixture that will be connected to the softener (i.e.: three lavatories). In the fourth column, list the wsfu unit for each type of water fixture from the appropriate model code (i.e.: 1.4 for a dishwasher using CABO sizing requirements). Multiply the values in columns 2 and 4 and write the result in the right-hand column of the table below. Repeat this process for each type of water fixture and add the values in the right-hand column to get the total wsfu s for the house. Type of Water Fixture # of fixtures to be connected to water softener Multiply # of fixtures by.. wsfu value for fixture (from plumbing code) Equals Total wsfu s for House (add total wsfu s for each fixture type) Total wsfu s for each water fixture type Step 2 With the total wsfu s for the house calculated in step 1, use the required flowrate table from the appropriate model plumbing code to find the minimum required flowrate of the water softener. 10