Professional standards of practice for residential building inspection
|
|
|
- Jasmine Malone
- 10 years ago
- Views:
Transcription
1 Professional standards of practice for residential building inspection A PUBLICATION OF THE ORDRE DES ARCHITECTES DU QUÉBEC ORDRE DES ÉVALUATEURS AGRÉÉS DU QUÉBEC ORDRE DES TECHNOLOGUES PROFESSIONNELS DU QUÉBEC Acknowledgements This publication is the result of joint discussions among several experts associated with the professional construction orders. Its purpose is to inform the public of the nature and scope of a building inspection mandate as well as on the rules governing professionals providing such services to the public. The following people are thanked for the generosity and openness with which they shared their vast experience. Mr. Richard Gervais, T.P. Ordre des technologues professionnels du Québec Mr. Bernard Marois, É.A. Ordre des évaluateurs agréés du Québec Mr. Claude Tanguay, architect Ordre des architectes du Québec This publication was made possible by an agreement of the Offices of the three professional orders, represented by Denis Beauchamp (OTPQ), Jean-Pierre Dumont (OAQ) and Céline Viau (OEAQ). We also appreciate the contribution of Mr. René Vincent, Eng., Me. Mario Dussault and Mr. André Rainville, Eng. of the Ordre des ingénieurs du Québec. Finally, it is with a great deal of gratitude that we would like to underline the editing and coordination work provided by Ms. Patricia Landry, Agr., thanks to whom this project was completed. Publication 2008 Chapter 1 Standards of practice Section I Preamble: 1. These standards are a result of a consensus of the three professional orders involved in building inspections, i.e., the Ordre des architectes du Québec, the Ordre des évaluateurs agréés du Québec, and the Ordre des technologues professionnels du Québec. 2. The orders are professional associations created by virtue of the Professional Code of Québec. Their mandate is to ensure the protection of the public by controlling the exercise of the profession by their members. 3. Within this legal context, these standards constitute the minimum required by the three orders to supervise the professional act of building inspection. In particular, inspectors, members of one of these orders, are required to respect these standards and to obtain professional liability insurance for this action, in addition to be subject to the professional inspection mechanism of their order. They shall respect their code of ethics and collaborate with the syndic s inquiry if a client complaints about their professional services. 4. The professional practice standards are designed to: 4.1 provide a reference document to members of the orders acting as building inspectors to guide their professional practice, by establishing obligatory standards to be respected both during the inspection and in writing the report. 1
2 4.2 define certain terms related to building inspection in order to ensure as uniform comprehension and interpretation as possible; 4.3 inform the public about obligations related to the terms and scope of services rendered by building inspectors. 5. The standards of practice were established recognizing that inspection of a residential building does not correspond to an assessment or a verification of conformance to the codes and standards governing the construction sector. Section II Scope 6. The current standards of practice apply to pre-purchase inspections of residential buildings containing no more than six dwellings. Section III Requirement for an agreement 7. For each inspection, the inspector shall create a written service agreement that confirms the application of these standards of practice. Prior to beginning the inspection, the inspector shall provide the client with a copy of the agreement as well as these standards of practice. Section IV Interpretation 8. Unless the context requires otherwise, the definitions in Appendix I of these standards form an integral part thereof. Chapter 2 Definition of the building inspection Section I Definition of the building inspection 9. Unless provisions establish otherwise, the building inspection consists of a careful visual examination of the main building to determine the physical condition of its systems and their components, as noted on the date of the inspection, and to report thereon. Any additional service shall be the subject of a particular mandate. 10. The inspection is not technically exhaustive. It focuses on the installed systems and their components that are easily accessible without risk to the safety of persons present or to property being inspected. Chapter 3 Features of the building inspection Section I Carrying out the inspection 11. During the inspection, the inspector shall take note of any sign of water infiltration in the building or significant condensation on any building components. 2
3 Section II Structural components 12. The inspector shall examine the structural systems and components, including: 1 the foundations; 2 the floors; 3 the walls; 4 the columns; 5 the ceilings; 6 the roofs. 13. The inspector shall probe structural components that appear to have deteriorated, unless such an action would have the effect of damaging a finished surface. 14. The inspector shall enter crawl spaces, attics and roof spaces in which clearance is salubrious, safe and of reasonable dimensions, and for which access does not require the use of tools. Section III The exterior 15. The inspector shall examine: 1 exterior wall facings, flashings; 2 installed windows and doors; 3 electric garage door control devices; 4 protrusions (terraces, balconies, entrance steps, etc.); 5 eaves, including, fascias and soffits; 6 vegetation, ground slopes, water runoff, garage entrances, entrance walkways, retaining walls, with regard to their effect on the condition of the building. 16. The inspector is not required to examine: 1 removable storm windows, storm doors, screens, shutters, awnings and other similar seasonal accessories not permanently installed; 2 fences; 3 security glazing; 4 garage door remote devices; 5 geological and geotechnical conditions. 17. The inspector shall inform the client of the risks inherent to electric garage door control devices. Section IV Roofing The roof 18. The inspector shall examine: 1 roof coverings; 2 water drainage systems; 3 flashings; 4 skylights, chimney exteriors and structural roof penetrations. 19. The inspector is not required to render an opinion on the status of accessories (solar panels, antennas, etc.). Attic space 20. The inspector shall examine: 1 structural elements; 2 roof support layers (decking); 3
4 Section V Plumbing 3 insulation of unfinished attics; 4 the presence of a vapour barrier; 5 attic space ventilation elements; 6 type of insulation; 7 clearance of combustible materials around the chimney. 21. The inspector shall open the faucets of plumbing fixtures. He/she is not required to open any other type of faucet or valve. 22. The inspector shall examine the visible interior water distribution system, including: 1 water supply and distribution piping materials; 2 fixtures and faucets; 3 functional flow of water; 4 leaks; 5 cross connections. 23. The inspector shall examine the visible internal drainage system, including: 1 U-bends and J-bends; discharge pipes and vents; pipe supports; 2 cleanouts and backflow valve; 3 leakage; 4 efficiency of evacuation. 24. The inspector shall examine the hot water production system, including: 1 water heating equipment; 2 automatic safety devices. 25. The inspector shall examine retention pit evacuation systems and components. 26. The inspector shall obtain information from the seller regarding water supply and wastewater discharge connections to a public or private system. 27. The inspector is not required to examine: 1 water treatment systems; 2 automatic water extinguisher systems; 3 lawn sprinkler systems; 4 water quality; 5 garbage disposal systems; 6 foundation drainage systems; 7 spas, swimming pools, saunas, whirlpool bathtubs and other similar equipment. Section VI Electricity 28. The inspector shall examine: 1 the electric service entrance; 2 grounding equipment, the general protection device, the main panel, distribution panels and their location; 3 the ampere rating and rated voltage of the installation; 4 functioning of a representative number of installed light fixtures, switches and electric outlets within the building and on the exterior; 5 polarity and the grounding of all outlets located: - near interior plumbing fixtures; - in the garage or carport; - on exterior walls of inspected buildings; 6 the operation of ground fault circuit interrupters. 4
5 29. The inspector shall report the presence of any aluminum cable in branch circuits. 30. The inspector is not required to open electrical panels. 31. The inspector is not required to verify or turn on overcurrent protective devices except for ground fault circuit interrupters. 32. The inspector is not required to examine: 1 low voltage systems; 2 security systems. 3 telephone, security, cable television wiring and other auxiliary networks not part of the main electricity distribution system. Section VII Heating 33. The inspector shall examine permanently installed heating systems, including: 1 the primary heat production system and its power source; 2 the heat distribution system; 3 the usual start-up mechanisms; 4 automatic safety devices; 5 the presence of heat sources in every inhabitable room. 34. The inspector shall turn on the systems using the usual start-up mechanisms. 35. The inspector is not required to turn on heating systems if, taking into account climatic conditions or other circumstances, damage to the equipment could result. Nor is he/she required to operate automatic safety devices. 36. The inspector is not required to examine: 1 the interior of a heat production device, in particular a combustion chamber; 2 conformity to applicable standards of the solid fuel burning heating systems, chimneys and accessories; 3 humidifiers; 4 electronic air filters; 5 the consistency or sufficiency of heat supply in each room. 37. The inspector is not required to open the access panels of any device whatsoever. Section VIII Ventilation and air conditioning 38. The inspector shall examine the central air conditioning system, including its energy source and the type of cooling installation. 39. The inspector shall examine the air evacuation and ventilation systems. 40. The inspector shall turn on the systems using the usual start-up mechanisms. 41. The inspector is not required to turn on cooling systems if, taking into account climatic conditions or other circumstances, damage to the equipment could result. 42. The inspector is not required to examine air conditioning devices not part of a central system. 43. The inspector is not required to verify if the cold air supply for each room is consistent or sufficient. 5
6 Section IX Interior 44. The inspector shall examine: 1 walls, floors and ceilings; 2 steps, staircases, balconies and railings; 3 cabinets and counter-tops; 4 windows and doors, including those separating living spaces from a garage; 5 the gas-tightness of walls, doors and ceilings separating living spaces from a garage; 6 water retention pits. 45. The inspector shall open a representative number of permanent windows and interior doors. 46. The inspector is not required to examine the condition of: 1 the paint, wallpaper and other wall finishings, ceilings and Interior floors; 2 carpeting; 3 curtains, blinds and other window accessories; 4 household appliances; 5 recreational facilities. Chapter 4 The building inspection report Section I The building inspection report 47. After analyzing the results of the visual building inspection, the inspector shall provide the client with a written report. This report, in a narrative format, shall comply with these standards of practice, be dated and signed by the professional who carried out the inspection. In addition, it shall conform to the requirements of the professional order of which the inspector is a member. 48. The inspection report: 1 reports everything that was observed and examined by the inspector; 2 indicates the date, time, weather conditions and the names of persons present at the inspection; 3 indicates the name of the person requesting the inspection and the purpose for which it was conducted; 4 describes the building systems and components listed in these standards as well as their respective condition, if observable; 5 indicates the method and equipment used to carry out the visual examination of some of them, where appropriate (binoculars, ladder, etc.); 6 provides, in application of these standards, the reasons for which certain systems and their components were not inspected, as applicable; 7 mentions, if applicable, the impossibility of turning on certain devices; 8 reports observations of any signs of water penetration in the building or significant condensation on building components; 9 contains a summary of the inspector s findings regarding the elements that require immediate or major repair or represent a dangerous situation; 10 contains a number of photographs to illustrate the inspector s principal findings; 11 mentions information obtained from the seller regarding water supply and wastewater discharge connections to a public or private system. 49. The inspection report may contain other information, comment or additional descriptions beyond those required by article 48. Chapter 5 General exclusions and limitations 6
7 Section I General exclusions and limitations 50. During the building inspection, the inspector is not required to: 1 operate any component or system apparently non-functional or lacking the usual start-up mechanism; 2 turn on devices or systems powered by fossil fuel or other systems which could present a hazard; 3 move objects, furniture, or equipment which obstructs access or impair visibility; Nor is he/she required to clear snow or any other exterior obstacle that obstructs or impairs visibility; 4 record the presence of hazardous substances, including toxins, carcinogens, soil, water or air contaminants, problematic soil components, nor provide an opinion about noise; 5 open access panels for plumbing, heating, ventilation and air conditioning systems. 51. The visual inspection does not include: 1 start-up of any fire alarm or security alarm system; 2 start-up of any electronic or home automation systems; 3 verification of household appliances; 4 inspection of recreational facilities; 5 verification of any underground elements, including buried tanks, septic tanks, septic fields, wells, underground pipes and foundation drains; 6 evaluation of the service life of a component or system, nor the calculation or assessment of their efficiency and their usefulness; 7 evaluation of the methods, materials and costs related to corrections to be made to systems and their components; 8 assessment of the building market value; 9 assessment of the compatibility of the building with any specific purpose other than the one for which it was used on the inspection date; 10 offering one or more guarantees of any sort on equipment and systems; 11 the recommendation in favour or against purchasing the property. Appendix 1 Definitions Component An easily observable part of a system, such as a wall or a floor, but not the individual parts (nails, plates or screws) that, when assembled, form the component. Crawl space Low-ceilinged space within the perimeter of the main building and located directly under the lowest floor of the structure. Examine To observe carefully. Exhaustive Treating a subject in depth. Functional flow The amount of water sufficient to use plumbing fixtures normally. Home automation system Relates to electronic management of a dwelling. Narrative report A detailed report on the investor s observations (in contrast to the Quick reference list) Representative number 7
8 One component in each room for multiple identical components. One component on each exterior side of the building in the case of multiple identical exterior components. System Set of components assembled to carry out one or several functions. Usual start-up mechanism The part commonly used to turn on or turn off the element or system (unit, wall or remote switch) Table of contents Page Acknowledgements 1 Chapter 1 Standards of practice 1 Section I Preamble 2 Section II Scope 2 Section III Requirement for an agreement 2 Section IV Interpretation 2 Chapter 2 Definition of the building inspection 2 Section I Definition of the building inspection 2 Chapter 3 Features of the building inspection 2 Section I Carrying out the inspection 3 Section II Structural components 3 Section III Exterior 3 Section IV Roofing 4 Section V Plumbing 4 Section VI Electricity 5 Section VII Heating 5 Section VIII Ventilation and air conditioning 6 Section IX Interior 6 Chapter 4 The building inspection report 6 Section I Building inspection report 6 Chapter 5 General exclusions and limitations 7 Section I General exclusions and limitations 7 Appendix Definitions 8
STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE:
STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: 61-30.801 Standards of Practice, General. (1) Home inspections performed to these Standards of Practice are intended to provide the client with information
South Carolina Home Inspector Standards of Practice
South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,
Inspection Report TPCC. Property Address: 22 Touisset Road Warren RI 02885. Lane's Perfection Inspections
Inspection Report TPCC Property Address: 22 Touisset Road Warren RI 02885 Lane's Perfection Inspections Lane Ukura Ma.# 578 7 St.Louis Avenue Bristol, R.I. 02809 401-255-0726 Table of Contents Cover Page...1
Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections
Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections This is a summary of your rights and responsibilities when having a home inspection done by an Oregon certified
ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS
ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS 1. INTRODUCTION 1.1 This ASHI Standard of Professional Practice for Home Inspections (Standard) defines the scope of home inspections performed
SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS
SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS.1101 DEFINITIONS The following definitions apply to this Section: (1) Automatic safety controls means devices designed and installed
COMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
Inspection Report. Mr. Sample Sample. Property Address: 1234 USA Drive Indianapolis IN 12345. 1234 USA Drive. Morris Home Inspection Group, LLC
Inspection Report Mr. Sample Sample Property Address: 1234 USA Drive Indianapolis IN 12345 1234 USA Drive Morris Home Inspection Group, LLC Cedric Morris HI01200039 Fishers, IN 46037 317-550-6281 Table
Inspection Report. Mr. Happy 2 flat owner. Property Address: Focal Point Home Inspection Ltd.
Page 1 of 35 Inspection Report Mr. Happy Property Address: Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 35 Table of Contents Cover Page Table of Contents
License Requirements for Persons Engaging in the Business of Inspection Practice:
SC Standards of Practice SOUTH CAROLINA RESIDENTIAL BUILDERS COMMISSION HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998 PURPOSE: The purpose of a residential
Self-Home Inspection Checklist
To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional
HOME INSPECTION REPORT
Edgewood Home Inspections, Inc. 407 W. Smith Valley Rd. #1032 Greenwood, IN 46142 (317) 833-6048 HOME INSPECTION REPORT Indianapolis IN 46000 Inspector's Name: License Number: Scott Kissel HI00800073 TABLE
Home Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 [email protected] Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
I NI NP R Inspected Items
6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and
HOMEOWNER S PERMIT GUIDE
HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448
PROPERTY INSPECTION REPORT
Whisper Computer Solutions, Inc. P.O. Box 690502 San Antonio, TX 78269-0502 Phone: (210)681-6325 Fax: (210)681-6325 Email: [email protected] PROPERTY INSPECTION REPORT Prepared For: Concerning:,
Inspection Report Atlanta Strip Mall Commercial Building Property Address:
Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of
Inspecton Report. Property Address:
Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 [email protected] www.nationalhomeservices.com Property Address: 873
Inspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
Inspection Report. Mr. JOHN SMITH. Property Address: 12345 S. Main St Denver Co 12349. A Happy House Home Inspection, LLC
Inspection Report Mr. JOHN SMITH Property Address: 12345 S. Main St Denver Co 12349 A Happy House Home Inspection, LLC Hans Coleman Centennial, Co 80015 720-988-4830 Table of Contents Cover Page...1 Table
Building Permits: When are they required?
Building Permits: When are they required? Generally, you need to obtain a building permit from the City whenever you construct, enlarge, alter, repair, move, remove, improve, convert, or demolish a building
BY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS
CITY OF MONTRÉAL BY-LAW 03-096 BY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS As the municipal administration seeks to ensure that all Montrealers benefit from acceptable housing conditions;
Total Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
Standards of Professional Practice
Standards of Professional Practice Adapted with permission from Standards of Practice, Effective June 1, 1992, Copyright 1993 American Society of Home Inspectors, Inc. Adopted by AZ ASHI Effective January
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
A Residential Owner s Guide to PERMITS. Elgin CITY OF PLANNING & NEIGHBORHOOD SERVICES
A Residential Owner s Guide to PERMITS CITY OF Elgin PLANNING & NEIGHBORHOOD SERVICES CITY OF Elgin A Residential Owner s Guide Welcome! This booklet has been prepared to provide residential property owners
ELIGIBLE REPAIR PROJECT PARAMETERS
THE DISTRICT MUNICIPALITY OF MUSKOKA ONTARIO RENOVATES PROGRAM FOR HOMEOWNERS ELIGIBLE REPAIR PROJECT PARAMETERS 1. To have your project considered and payment processed, all projects requiring a Building
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668
Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:
Inspection Report. Mr. John Doe. Property Address: 123 Somewhere Jacksonville FL 32224. Tabor Hill & Associates LLC
Inspection Report Mr. John Property Address: 123 Somewhere Jacksonville FL 32224 Tabor Hill & Associates LLC James Cox HI4634 P.O. Box 65699 Orange Park FL 32065 Table of Contents Cover Page...1 Table
When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:
When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory
Structure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
Housing Quality Standards Inspection Checklist
Housing Quality Standards Inspection Checklist To prevent delays, the R.T.A. must be complete and upon submission the unit must be in move in condition or an inspection will not be conducted. A Fair Housing
INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 [email protected] INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction
The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE
The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE BUILDING SERVICES DEPARTMENT 789 Broadway Street, Box 3000 Wyoming, ON N0N 1T0 Telephone: 519 845-0801 Toll-free: 1-866-324-6912 Fax: 519
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
How To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
Home Maintenance Checklist
Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your
HOME INSPECTION CHECKLIST
CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways
BUILDING ANALYSIS REPORT. John Doe 1234 Smith Road Atlanta, Georgia 30396
BUILDING ANALYSIS REPORT July 25, 2014 John Doe 1234 Smith Road Atlanta, Georgia 30396 Agent: Ausker and Barbara Morris AT Morris Realty Group, Inc. 3162 Johnson Ferry Road, Suite 260-25 Marietta, Georgia
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792
Inspection Report. Sample Report. Property Address: 1234 Anywhere street Phoenix AZ. Veteran Inspection Professionals
Inspection Report Property Address: 1234 Anywhere street Phoenix AZ Veteran Inspection Professionals Mark Mandery 040901 4725 W. Aire Libre Ave Glendale AZ, 85306 480-694-2111 Table of Contents Cover Page...1
PROPERTY INSPECTION REPORT
(850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304
New Jersey Property Inspections LLC NJ State Home Inspector License # 24GI00105100 27 Neshanic Drive, Ringoes NJ 08551 908-642-2112/908-788-0055
New Jersey Property Inspections LLC NJ State Home Inspector License # 24GI00105100 27 Neshanic Drive, Ringoes NJ 08551 908-642-2112/908-788-0055 PRE-INPECTION AGREEMENT READ THIS DOCUMENT CAREFULLY. IT
The City of Basehor, Kansas
The City of Basehor, Kansas Residential and Miscellaneous Permits This list provides general information regarding permit requirements for various residential construction and maintenance activities. The
Vari Inspection Services
Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
Minimum Housing and Health Standards
APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).
U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!
U.S. Department of Housing and Urban Development Office of Public and Indian Housing A Good Place to Live! Introduction Having a good place to live is important. Through your Public Housing Agency (or
Georgia Home Inspection Services
Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in
2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW
CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,
www.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
A comfortable house is a great source of happiness. - Sydney Smith. Home Maintenance Guide
A comfortable house is a great source of happiness. - Sydney Smith Home Maintenance Guide HOME GUIDE By conducting regular maintenance checks, you can prevent small inexpensive repairs from becoming more
CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
STATE OF SOUTH CAROLINA RESIDENTIAL PROPERTY CONDITION DISCLOSURE STATEMENT
STATE OF SOUTH CAROLINA RESIDENTIAL PROPERTY CONDITION DISCLOSURE STATEMENT The South Carolina Code of Laws (Title 27, Chapter 50, Article 1) requires that an owner of residential real property (single
Building Inspection Report
Building Inspection Report 14100 W. Cleveland Avenue, Phoenix, AZ 55555 Inspection Date: 03/18/2002 Prepared For: Mark Newcomer Prepared By: ABC Home Inspections 212 Wisconsin Avenue Scottsdale, AZ 55555
CHRIS CURLES and ASSOCIATES INSPECTION SERVICES
CHRIS CURLES and ASSOCIATES INSPECTION SERVICES Inc. Chris Curles, President www.homeinspectionsatlanta.com [email protected] Office: 770-493-0227 Professional Member Of: GAHI # 93006 ASHI # 211725
Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations
A Seller s Guide to the Home Inspection By
A Seller s Guide to the Home Inspection By 13277 N. Illinois Street, Suite 120 Carmel, IN 46032 Indianapolis/Carmel - (317) 848-1744 Toll Free - (800) 878-1744 Lafayette (765) 420-7200 Fax (317) 573-2089
Kansas Home Inspection. Registration Board
Page 1 of 16 Kansas Home Inspection Registration Board State of Kansas Home Inspection Standards of Practice Approved September 17, 2009 Page 2 of 16 Table of Contents Section 1 Definitions..4-6 2 Purpose
EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST
DATE TIME EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST INSPECTOR: LICENSE # ADDRESS: PROPERTY OWNER: SINGLE: DOUBLE: MULTI-UNIT # OF UNITS POINT OF INSPECTION Sanitation IPMC 302.1
Home Inspection Report
Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information
159 Morningside Avenue, Toronto
159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
EXIT INVENTORY/SURVEY
EXIT INVENTORY/SURVEY As soon as all your personal belongings have been removed and the property thoroughly cleaned, the inventory of goods and final survey of the premises will be done by the designated
CITY OF TUKWILA Mayor s Office/Human Services Division Minor Housing Repair Assistance Program 2014 Policies
CITY OF TUKWILA Mayor s Office/Human Services Division Minor Housing Repair Assistance Program 2014 Policies The Housing Repair Assistance Program provides and promotes the repair and maintenance of housing
Code Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division
Code Enforcement Inspection Manual City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division LIVING ROOM 304.15 EXTERIOR DOOR(S) Check door(s) and trim for condition,
Inspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants
Page 1 of 53 Inspection Report Jacksonville Property Address: Jacksonville FL 32204 South East Building Consultants Ray Thoroman Inspecting Jacksonville FL and entire South East Page 2 of 53 Table of Contents
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
Does Wall Township require an inspection by the building department on resale of a home?
Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,
Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
GUARDIAN HOME SERVICES LLC P.O. BOX 678 ALPINE, NEW JERSEY 07620 (201) 568-2209 (201) 568-8117 FAX www.guardianhome.net
GUARDIAN HOME SERVICES LLC P.O. BOX 678 ALPINE, NEW JERSEY 07620 (201) 568-2209 (201) 568-8117 FAX www.guardianhome.net REPORT NUMBER: 2011/11/01/001 PROPERTY LOCATION: 123 Main Street, Cresskill, New
Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents
Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions
Property Inspection Report
Property Inspection Report 1234 Bear St., Denver, CO 80223 Prepared For: John Smith Inspection Date: 12/11/2015 Prepared By: Bill Heine, Certified Professional Inspector ResInspect, LLC 303-359-7573 Email:
Building Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
Virginia Maintenance Code Requirements
Virginia Maintenance Code Requirements THE VIRGINIA MAINTENANCE CODE The City of Roanoke has adopted and enforces the Virginia Maintenance Code (VMC) on all existing structures located in the city. This
Inspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748
Inspection Report provided by: Delaware Property Inspection Inspector: Richard Hiddemen (302)355-1748 ASHI # 243377 DPR #H4-0000018 DDA #06-444 Delaware 1992105842 Wilmington #03857 New Castle #2010-845
Schedule B to By-law 33-2009
Amended by By-law 8-2016 Note: This consolidation is prepared for convenience only. For accurate reference the original by-laws should be reviewed. Floor Area Calculation Floor area shall: Schedule B to
Inspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066
Page 1 of 58 Inspection Report Prepared For: Atlanta Commercial Customer Property Address: Building 5 Marietta, GA 30066 Superior Home Inspections Ray Thoroman 8070 Ivy Shaw Dr. Gainesville,GA 30506 678-410-3005
IECC Compliance Guide for Homes in Virginia
IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the