1 InfraStruXure Generator InfraStruXure Power Generation System Reference Manual
2
3 About This Manual Audience This manual is intended for end-users of an InfraStruXure Power Generation System generator. It provides important safety warnings and instructions, an overview of generator components, technical specifications, and warranty information. Companion manuals For additional information about the generator and the InfraStruXure Power Generation System, see the following InfraStruXure Power Generation System manuals: ATS with Power Distribution Unpacking Sheet ( ) Electrical Installation Manual ( ) ATS with Power Distribution Operation Manual ( ) Network Management Interface User s Guide (available on the Utility CD) ( ) Refer also to the following Cummins manuals, supplied with your generator, for engine specific information and instructions: Installation Manual Operator s Manual Operation and Maintenance Manual Parts Catalogs Operator s Manual 12 and 24V Battery Charger Installation and Service Manual 12 and 24V Battery Charger How to find updates to this manual You can check for updates to this manual by clicking on the User Manuals link on the Support page of the APC Web site ( In the list of InfraStruXure Power Generation manuals, look for the latest letter revision (A, B, etc.) of the part number on the back cover of this manual. InfraStruXure Generator i
4
5 Contents Safety Save these instructions Safety symbols used in this manual Cross-reference symbols used in this manual Warnings The InfraStruXure Power Generation System is an Optional Standby System Fuel and fumes are flammable Exhaust gases are deadly Moving parts can cause severe personal injury or death Do not operate in flammable and explosive environments Electric shock can cause severe personal injury or death General safety precautions Caution batteries InfraStruXure Generator Components Overview kW InfraStruXure Generator kW InfraStruXure Generator kW InfraStruXure Generator Generator Control Panel Special Features of Diesel Generators Maintenance Overview Maintenance Checkpoints Oil Oil Type Oil capacity Engine oil level Replacing the oil filter Changing the oil InfraStruXure Generator iii
6 Coolant Overview Coolant type Coolant capacity Draining, cleaning, flushing, and refilling the coolant system Fuel Overview Problems with diesel fuel Preventing potential problems with diesel fuel Fuel specifications Fuel tank size Fuel monitoring/runtime calculation Generator runtimes and fuel consumption E-Stop Button Overview Stopping the generator using the E-stop button Resetting the E-stop button to return the generator to automatic operation Clearing a Shutdown Fault Batteries Replacement battery type Keeping the batteries clean Charging the batteries Block Heater Specifications Warranty Life-Support Policy Service iv InfraStruXure Generator
7 Safety Save these instructions This manual contains important instructions that must be followed during installation, operation, and maintenance of the InfraStruXure Generator. Safety symbols used in this manual Electrical Hazard Indicates an electrical hazard, which, if not avoided, could result in injury or death. DANGER Indicates a hazard, which, if not avoided, could result in severe personal injury or substantial damage to product or other property. Caution Indicates a potential hazard, which, if not avoided, could result in personal injury or damage to product or other property. Indicates a heavy load that should not be lifted without assistance. Heavy Indicates important information. Note Cross-reference symbols used in this manual Indicates that more information is available on the same subject in a different section of this manual. See also Indicates that more information is available on the same subject in a different manual. InfraStruXure Generator 1
8 Warnings The components in the InfraStruXure Power Generation System and UPS power distribution system can pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents, be aware of the dangers and act safely. Read and follow all of the safety instructions and warnings in this manual and in all of your component manuals. The InfraStruXure Power Generation System is an Optional Standby System The Generator and Automatic Transfer Switch (ATS) that you purchased from APC is classified as an Optional Standby System it provides backup or standby power to data centers in the event of a sustained power failure. The InfraStruXure Power Generation System is not to be classified as an Emergency System that is essential for safety to human life (e.g., fire pumps, operating room and life-support equipment in hospitals) as legally required by municipal, state, federal, or other governmental codes. The InfraStruXure Power Generation System is not to be classified as a Legally-Required Standby System as it s not supplying power to aid in fire fighting, rescue operations, control of health hazards (e.g., sewage) and similar operations as required by municipal, state, federal, or other governmental codes. Emergency and Legally-Required Systems are not allowed to rely on municipal fuel for operation and municipal water for cooling. Emergency and Legally-Required Systems require dual fuel systems, with one of them being a two-hour, on-site fuel supply. Your InfraStruXure Power Generation System is not to be classified as an Integrated Electrical System as an orderly shutdown is not required to prevent damage to the generator. The generator is not to be paralleled with another generator. Your generator will operate at its rated load without being re-fueled for a minimum of six hours, and should run for a minimum of 12 hours. Fuel and fumes are flammable Fire, explosion, and personal injury or death can result from improper practices. DO NOT fill fuel tanks while engine is running, unless tanks are outside the engine compartment. Fuel contact with hot engine or exhaust is a potential fire hazard. DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near the generator or fuel tank. 2 InfraStruXure Generator
9 Warnings Exhaust gases are deadly Ensure exhaust gases are properly discharged away from enclosed or sheltered areas and areas where individuals are likely to congregate. Ensure that the unit is well ventilated. Engine exhaust and some of its constituents are known to the state of California to cause cancer, birth defects, and other reproductive harm. Moving parts can cause severe personal injury or death Keep your hands, clothing, and jewelry away from moving parts. Before starting work on the generator, disconnect battery charger from its AC source, then disconnect starting batteries, negative ( ) cable first. This will prevent accidental starting. Make sure that fasteners on the generator are secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc. Do not wear loose clothing or jewelry in the vicinity of moving parts, or while working on electrical equipment. Loose clothing and jewelry can become caught in moving parts. If adjustment must be made while the unit is running, use extreme caution around hot manifolds, moving parts, etc. Do not operate in flammable and explosive environments Flammable vapor can cause an engine to over speed and become difficult to stop, resulting in possible fire, explosion, severe personal injury and death. Do not operate a generator where a flammable vapor environment can be created by fuel spill, leak, etc., unless the generator is equipped with an automatic safety device to block the air intake and stop the engine. The owners and operators of the generator are solely responsible for operating the generator safely. InfraStruXure Generator 3
10 Warnings Electric shock can cause severe personal injury or death Remove electric power before removing protective shields or touching electrical equipment. Wear rubber boots when working on electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment. Do not wear jewelry jewelry can short out electrical contacts and cause shock or burns. Use extreme caution when working on electrical components. High voltage can cause injury or death. DO NOT tamper with interlocks. Follow all applicable state and local electrical codes. Have all electrical installations performed by a qualified licensed electrician. Lock out and tag open switches to avoid accidental closure. Hazardous voltages can flow from the generator into the utility line. This creates a potential for electrocution of service personnel or property damage. DO NOT CONNECT GENERATOR DIRECTLY TO ANY BUILDING ELECTRICIAL SYSTEM. CONNECT ONLY TO THE AUTOMATIC TRANSFER SWITCH. General safety precautions Coolants under pressure have a higher boiling point than water. DO NOT open a radiator heat exchanger pressure cap while the engine is running or hot. Allow the generator to cool and bleed the system pressure first. Used engine oils have been identified by some state and federal agencies as causing cancer or reproductive toxicity. When checking or changing engine oil, take care not to ingest oil, breathe the fumes, or contact used oil. Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment (ref. NFPA No. 10). Make sure that rags are not left on or near the engine. Make sure generator is mounted in a manner to prevent combustible materials from accumulating under the unit. Remove all unnecessary grease and oil from the unit. Accumulated grease and oil can cause overheating and engine damage which present a potential fire hazard. Keep the generator and the surrounding area clean and free from obstructions. Remove any debris from the set and keep the floor clean and dry. Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment unsafe. Substances in exhaust gases have been identified by some state and federal agencies as causing cancer or reproductive toxicity. Take care not to breathe, ingest, or come into contact with exhaust gases. 4 InfraStruXure Generator
11 Warnings Do not store any flammable liquids, such as fuel, cleaners, oil, etc., near the generator. A fire or explosion could result. Wear hearing protection when going near an operating generator. To prevent serious burns, avoid contact with hot metal parts such as radiator, turbo charger, and exhaust system. Caution batteries Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. When replacing batteries, use the same number and the following type of batteries: 12V, 225A, 1400 cold cranking amps, sealed lead acid. Do not dispose of batteries in a fire. The battery is capable of exploding. Do not open or mutilate the batteries. Released electrolyte has been known to be harmful to the skin and eyes and to be toxic. A battery presents a risk of high short circuit current. The following precautions are to be observed when working on batteries. Remove watches, rings, or other metal objects. Use tools with insulated handles. Do not lay tools or metal parts on top of batteries. The electrolyte is a diluted sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed: Wear full eye protection and protective clothing. Where electrolyte contacts the skin, wash it off immediately with water. If electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention. Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried. InfraStruXure Generator 5
12 Warnings Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following precautions are to be followed: DO NOT SMOKE near batteries. DO NOT cause flame or spark in battery area. Discharge static electricity from body before touching batteries by first touching a grounded metal surface. 6 InfraStruXure Generator
13 InfraStruXure Generator Components Overview The seven doors of the generator provide access to the different engine components for service and maintenance. This section lists the parts found behind each door for the three different generator models. 80kW InfraStruXure Generator Generator controller, battery charger Door not used for engine access in this model generator Oil drain, oil level sensor, air filter change indicator, block heater, 120VAC outlet box * Oil filter, turbo charger Coolant drain, coolant overflow receptacle, oil fill point, fuel pump Fuel sensor, visual fuel gauge, air filter, oil dipstick Main output circuit breaker * The 120VAC outlet box also has two (2) GFCI receptacles. These receptacles are for customer use and should not have the battery charger or the block heater connected to them. InfraStruXure Generator 7
14 InfraStruXure Generator Components 125kW InfraStruXure Generator Generator controller, battery charger Door not used for engine access in this model generator Oil drain point, oil level sensor, block heater, air filter change indicator, 120VAC outlet box * Turbo charger, oil filter Coolant drain, coolant overflow receptacle, oil fill point, fuel pump Oil dipstick, fuel sensor, visual fuel gauge, air filter Main output circuit breaker * The 120VAC outlet box also has two (2) GFCI receptacles. These receptacles are for customer use and should not have the battery charger or the block heater connected to them. 8 InfraStruXure Generator
15 InfraStruXure Generator Components 200kW InfraStruXure Generator Generator controller, battery charger Door not used for engine access in this model Oil dipstick, 120VAC outlet box * Turbo charger, block heater, oil filter, coolant filter Fuel pump, oil drain point, coolant overflow receptacle Oil fill point, fuel sensor, visual fuel gauge, air filter Main output circuit breaker * The 120VAC outlet box also has two (2) GFCI receptacles. These receptacles are for customer use and should not have the battery charger or the block heater connected to them. InfraStruXure Generator 9
16 Generator Control Panel The generator s control panel connects to the ATS monitoring unit for communication purposes. At the generator controller you can clear alarms, perform an emergency stop of the system, clear a shutdown fault, and manually start the generator. The following illustration shows the InfraStruXure Generator s control panel. The home button brings you back to the main menu screen from any other screen. The menu selection button allows you to step through the various menu items and adjust parameters. The digital display allows you to view menus, faults, and shutdown messages. An asterisk (*) before a listed fault indicates that it is an active fault. The previous main menu button brings you to the previously viewed main menu. The E-stop button allows you to perform an emergency shutdown of the generator set. For more information, refer to E-Stop Button on page 23. The generator s indicator lights provide a visual indication of the generator status and any warnings present. For more information, refer to Indicator lights on page 11. The generator s /Manual/Auto switch should be in the Auto position when the InfraStruXure Power Generation System is running in automatic operation and should be in Manual when the generator must be started manually. The manual run/stop button starts and stops the generator set locally. The /Manual/Auto switch must be in Manual to enable this button. The panel lamp and lamp test button allows you to test all panel LEDs and to turn the control panel lamps ON or OFF. The fault acknowledge/reset button allows you to clear faults once they have been corrected. 10 InfraStruXure Generator
17 Generator Control Panel Indicator lights. The indicator lights on the generator controller provide information about the status of the generator and any current generator faults. Indicator Light Color Description Running Green Indicates that the generator is running. Remote Start Green Indicates that the generator is receiving a start signal remotely, from the ATS. Not in Auto Red Flashes continuously when the /Manual/Auto switch is not in the Auto position. Low Oil Pres. Warning Yellow Indicates that oil pressure is lower than the normal range of operation. High Engine Temp Yellow Indicates the engine temperature is higher than normal range of operation. Low Oil Pres. Shutdown Red Indicates that the engine has shut down due to low oil pressure. Overspeed Shutdown Red Indicates that the engine has shut down because of excessive speed. Fail to Start Red Indicates that the engine has failed to start. How to clear a shutdown fault. See Clearing a Shutdown Fault on page 25 for instructions. How to manually start the generator. See also For detailed directions on how to start the InfraStruXure Power Generation System manually, refer to the ATS with Power Distribution Operation manual ( ). InfraStruXure Generator 11
18 Special Features of Diesel Generators Differences between diesel engines and gas engines Before operating the generator it is important to be aware of the differences between diesel engines and gasoline engines. Some of the most notable differences between the two are: Diesel engines do not have spark plugs. Unlike a gas engine, a diesel engine takes in air, compresses it, and then injects the fuel into the compressed air. The heat of the compressed air spontaneously lights the fuel. Do not let your diesel engine run out of fuel. A diesel engine may not restart when refilled if it runs out of fuel. To avoid this situation, ensure that your generator s fuel never reaches below a half a tank. Diesel engines run more efficiently when they are loaded. Always attempt to run the generator with a 30% load or higher. Diesel engines burn less fuel per watt generated if they are generating near their full potential. Diesel engines do not regulate the intake air, but rather, they regulate the amount of fuel injected to the cylinders. Unlike gasoline engines which run best at a fixed air/fuel ratio, diesel engines run with essentially the same air, but add more fuel when they require more power. 12 InfraStruXure Generator
19 Maintenance Overview You should establish and follow a maintenance schedule that works with your particular application and its environment. APC recommends quarterly service visits for generator maintenance. If the InfraStruXure Power Generation System will be subjected to extreme operating conditions, reduce the service intervals accordingly. The following factors may affect the maintenance schedule: Use of the generator for continuous duty (prime power) Extremes in ambient temperature Exposure to severe weather Exposure to salt water Exposure to dust, sand, or other airborne contaminates Note This manual outlines the basics of generator maintenance. In most cases, the required maintenance will be covered by a service contract purchased with your InfraStruXure generator. For full instructions on how to perform the procedures outlined in this manual, refer to the Cummins Engine Operation and Maintenance Manual included with your generator. InfraStruXure Generator 13
20 Maintenance Checkpoints The following maintenance items should be completed during your scheduled maintenance visit: Check coolant heater Check coolant level Check oil level Check fuel level Check charge air piping Check air cleaner (clean, if required) Check battery charging system Drain water and sediment from fuel tank Drain exhaust condensate trap Change air cleaner element Check radiator hoses for water and cracks Drain fuel filters Check anti-freeze and DCA concentration Check crankcase oil and filter Check drive belt tension Change coolant filter Change fuel filters Clean cooling system Adjust valve lash Check starting batteries 14 InfraStruXure Generator
21 Oil Oil Type Use a high-quality, 15W-40 multi-viscosity lubricating oil. Oil capacity The oil capacity of the generator is as follows: 80kW and 125kW generators 17.3 quarts (16.4 liters) 200kW generators 25.2 quarts (24 liters) Engine oil level Warning Do not check the oil level at the generator while it is running as it may cause oil to be dispersed and could cause severe burns. You can check the generator oil level either at the generator or through the ATS. Checking the oil level at the ATS. For convenience, you can check the oil level through the ATS display interface. To check the oil using this method, select Generator Status and then Engine Parameters from the Generator screen. See also For more information about the Generator screen on the ATS, see Generator under the Display Interface chapter of the ATS with Power Distribution Operation manual. InfraStruXure Generator 15
22 Oil Checking the oil level at the generator. If checking the oil level at the generator, make sure that the oil level is as close to the high mark on the dipstick as possible without exceeding it. Do not operate the generator if the oil level is above the high mark on the dipstick or below the low mark. Refer to InfraStruXure Generator Components on page 7 for the location of the oil dipstick for your specific generator model. High mark (H) Low mark (L) Caution Do not operate the generator if the oil level is too low or too high. Operating the generator with too much oil can cause foaming or aeration. Operating the generator with too little oil may cause loss of oil pressure. Replacing the oil filter Your InfraStruXure Power Generation System s generator has a six cylinder engine. Refer to the following table for the type of replacement filter that you will need for your particular application: Type of application 80kW or 125kW generator 200kW generator Type of filter Fleetguard LF3349 or equivalent Fleetguard LF3000 or equivalent To replace the generator s oil filter: 1. Fill the filter with clean lubricating oil. 2. Apply a light film of oil to the gasket sealing surface of the filter. Note The LF3000 oil filter has two gaskets. Lubricate both of the gaskets. 3. Install the filter on the generator according to the manufacturer s instructions. Changing the oil Note Handling and disposing of used oil is subject to federal, state, and local regulations. Use authorized waste disposal facilities. If in doubt, contact your local EPA authorities for guidance as to proper handling of used oil. See also For detailed instructions on changing your generator s oil, refer to the Cummins Engine Operation and Maintenance manual included with your generator. 16 InfraStruXure Generator
23 Coolant Overview The diesel engine of the generator requires a balanced coolant mixture of water, antifreeze, and coolant additives. You can check the coolant level of your generator through the ATS display interface. To check the coolant level using this method, select Generator Status and then Engine Parameters from the Generator screen. See also For more information about the Generator screen on the ATS, see Generator under the Display Interface chapter of the ATS with Power Distribution Operation manual. Coolant type Use a low silicate antifreeze that meets ASTM4985 test criteria. It is recommended that you use an antifreeze with a 50-percent concentration level of ethylene glycol or propylene glycol in most climates. The following table provides specifications for the antifreeze protection that you need according to the climate that your generator is operating in: Ethylene Glycol Propylene Glycol 40% = 9 F ( 23 C) 40% = 6 F ( 21 C) 50% = 35 F ( 37 C) 50% = 27 F ( 33 C) 60% = 65 F ( 54 C) 60% = 56 F ( 49 C) 68% = 96 F ( 71 F) 68% = 81 F ( 63 C) Coolant capacity The coolant capacity for the generator is as follows: 80kW = 6.5 gallons (24.6 liters) 125kW = 8.2 gallons (31.0 liters) 200kW = 6.8 gallons (25.7 liters) InfraStruXure Generator 17
24 Coolant Draining, cleaning, flushing, and refilling the coolant system Caution Note Do not add cold coolant to a hot engine. To prevent damage, allow the engine to cool to below 120 F (50 C) before adding coolant. Handling and disposing of used antifreeze is subject to federal, state, and local regulations. Use authorized waste disposal facilities. If in doubt, contact your local EPA authorities for guidance as to proper handling of used antifreeze. See also For instructions on how to perform maintenance on the generator s cooling system, including changing or refilling the generator s coolant, refer to the Cummins Engine Operation and Maintenance manual included with your generator. 18 InfraStruXure Generator
25 Fuel Overview The InfraStruXure generator runs on diesel fuel. The fuel is one of the most critical components of your generator s reliability. Unlike on-road diesel engines which continuously use up the fuel in their tanks, the fuel in a standby generator sits in the tank for an extended period of time. Diesel fuel that sits unused for a period of time can present problems. This section describes some of the problems that may occur and offers recommendations for preventing these problems. Adhere to the recommendations provided in this section to increase the probability of reliable operation for your generator. See also Refer to the Cummins Engine Operation and Maintenance manual for complete fuel system maintenance instructions. Problems with diesel fuel The following list addresses some issues that can lead to problems with diesel fuel especially when it will be sitting in a standby state for an extended period of time. 1. Temperature Diesel fuel naturally contains paraffin wax. In warm temperatures this wax is in a liquid state and is suspended throughout the fuel. When the temperature drops below 20 F ( 7 C), the wax crystallizes causing the fuel to cloud up. These wax crystals can clog your fuel filter and can prevent the generator from starting, or cause the generator to stall after it has started. In addition, if a summer blend fuel is used in the winter, the paraffin wax can gel, turning the fuel into the consistency of jelly. If this occurs, the fuel pump will not be able to draw the fuel, and the generator will not start. InfraStruXure Generator 19
26 Fuel 2. Water Water can enter the fuel system through either the fuel itself or through condensation of the moisture normally in the air above the fuel. Water in diesel fuel is normally present as both free and emulsified water. Free water settles to the bottom of the fuel tank. Emulsified water stays suspended in the fuel, the way that oil and vinegar separate in salad dressing, and can enter the fuel lines, fuel pump, and injectors. From there it can cause corrosion and failure of the fuel pump and injectors. In addition, emulsified water can freeze at low temperatures and the resulting ice crystals can clog the fuel filter. This clog can prevent the generator from starting or cause the generator to stall after it has started. 3. Microbial contamination Microorganisms, primarily bacteria and fungi, exist harmlessly in moisture-free fuel. However, in the presence of water, these microorganisms can grow and reproduce. In turn, they can clog your fuel filter and prevent the generator from starting or cause the generator to stall after it has started. 4. Cetane number Cetane number is a measure of the starting and warm-up characteristics of a fuel. A minimum number of 40 is required. In cold weather, or in service with prolonged low loads, a cetane number of 45 is desired. Fuel with a cetane number greater than 55 may cause increased torque peak smoke. 5. Viscosity Viscosity is a measure of the fuel s pumping and lubricating characteristics. Low viscosity causes rapid wear of the fuel pump and injectors. High viscosity causes hard starting, white smoke when cold, and failures of the fuel injector train. 6. Fuel quality Use of fuel that does not meet all of the fuel specifications may cause problems with the generator. See Fuel specifications on page 21 for generator-specific specifications. Preventing potential problems with diesel fuel Follow these suggestions to help prevent any of the potential diesel fuel problems and help ensure your generator s reliability. 1. Only purchase premium diesel fuel from a qualified diesel distributor. 2. If the generator is located in an environment with temperatures 20 F ( 7 C) and above, only purchase ASTM D975 No. 2-D diesel fuel with a minimum cetane number of If the generator is located in an environment with temperatures below 20 F ( 7 C), only purchase Winter Blended 50% ASTM D975 No. 1-D/ 30% No. 2-D with a minimum cetane number of If the generator is located in an environment with temperatures below 20 F ( 29 C), a fuel filter heater is required. Note ASTM D975 No. 1-D fuel is less dense than ASTM No. 2-D fuel and has a lower paraffin wax content. 20 InfraStruXure Generator
27 Fuel 5. Fuel must be dry. Keep the fuel tank full to reduce the air space above the fuel in the tank. Have the generator s fuel filter/water separator serviced annually. 6. Do not add new or used engine lubricating oil to the fuel as it could reduce engine performance. 7. Do not mix gasoline, gasohol, or alcohol with diesel fuel as it creates an extreme fire and explosive hazard. 8. Have the fuel tested for water content and microbial contamination, at least annually, or when new fuel is added or fuel is suspect. If microbial contamination has occurred, after it has been remedied, use Fleetguard s Fleet- Tech TM Microbicide fuel additive to prevent the future growth of microorganisms. If water in the fuel is a persistent problem, Fleetguard s Fleet-tech TM Winter Conditioner can be used to prevent fuel line freeze-up. Fuel specifications When adding diesel fuel to your generator, be sure that it adheres to the following specifications: Viscosity Cetane number Sulfur content 1.3 to 5.8 centistrokes (1.3 to 5.8mm per second) at 104 F (40 C) 40 minimum above 32 F (0 C); 45 minimum below 32 F (0 C) Not to exceed 0.5 mass-percent Active sulfur Copper strip corrosion not to exceed Number 2 rating after 3 hours at 122 F (50 C) Water and sediment Carbon residue Density Cloud point Ash Distillation Lubricity (SLBOCLE or HFRR) Not to exceed 0.5 volume-percent Not to exceed 0.35 mass-percent on 10 volume-percent residuum to grams per cubic centimeter (g/cc) at 60 F (15 C) Temperature at which paraffin crystals form. Should be 10 F (6 C) below lowest ambient temperature at which the generator is expected to operate. Not to exceed 0.02 mass-percent 90 volume-percent at 680 F (360 C) Minimum of 3100 grams SLBOCLE or maximum of 0.45mm wear scar diameter at 140 F (60 C) HFRR Fuel tank size For the 80kW and 125kW generator, the fuel tank size is 109 gallons (413 liters). For the 200kW generator, the fuel tank size is 173 gallons (655 liters). InfraStruXure Generator 21
28 Fuel Fuel monitoring/runtime calculation Fuel monitoring is a unique feature of the InfraStruXure Power Generation System. Fuel level is monitored at the generator (if purchased through APC) and load is measured at the ATS. These measurements are used to calculate runtime, as explained in the following paragraph: Fuel is monitored by a level sensor in the generator fuel tank (calibrated to the bottom of the fuel tank) that changes readings every 1/2-inch of fuel level change. From these fixed level points, the ATS counts the number of gallons or liters of fuel used (based on load over time) and subtracts this from the fixed level fuel amount to give an accurate estimate of fuel level. The remaining runtime is then calculated based on the fuel usage rate at the current load and the remaining fuel in the tank. Once a new fuel level point is reached, the value of the calculated fuel used is reset and the consumption begins again. The Fuel Level and Runtime Estimate are displayed on the Generator Status screen on the ATS display interface, and you can set the following Fuel Alarm Limits in the Alarms menu of the display interface: Percent Fill: If the amount of fuel as a percentage falls below this value, an alarm condition exists. Runtime: If the estimated runtime falls below this value, an alarm condition exists. Generator runtimes and fuel consumption The following table provides the estimated runtime of the generator based on the load capacity when there is a full tank of diesel fuel. Load Capacity 80kW 125kW 200kW At full load 12 hours 12 hours 12 hours At 3/4 load 22.7 hours 14.5 hours 17.3 hours At 1/2 load 31.1 hours 19.8 hours 23.7 hours At 1/4 load 47.4 hours 33.0 hours 37.6 hours The following table provides the fuel consumption of the generator based on the load capacity. Load Capacity 80kW 125kW 200kW At full load 6.1 gal/hr 9.5 gal/hr 17.3 gal/hr At 3/4 load 4.8 gal/hr 7.5 gal/hr 11.8 gal/hr At 1/2 load 3.5 gal/hr 5.5 gal/hr 7.8 gal/hr At 1/4 load 2.3 gal/hr 3.3 gal/hr 4.3 gal/hr 22 InfraStruXure Generator
29 E-Stop Button Overview The E-stop button allows you to immediately stop the generator in the event that it requires an emergency shutdown. After the generator is shut down using the E-stop button, it cannot be started either at the generator or at the ATS until the button has been reset. The following illustration shows the location of the E-stop button located on the generator controller. E-stop button Note If an emergency power off is performed at the ATS, it will automatically trip the E-stop button of the generator. If this situation occurs, the E-stop button must be manually reset at the generator using the procedure described on the following page. Stopping the generator using the E-stop button To stop the generator using the E-stop button, push it in. InfraStruXure Generator 23
30 E-Stop Button Resetting the E-stop button to return the generator to automatic operation E-stop shutdown status can only be reset at the generator control panel. Note Pull the emergency stop button out. Turn the generator s /Manual/Auto switch to. Press the front panel Fault Acknowledge/Reset button. Place the /Manual/Auto switch on the generator controller to the Auto position. Shutdown Warning Shutdown Warning Press Fault Acknowledge/Reset Fault Acknowledge/Reset Panel Lamp/Lamp Test Panel Lamp/Lamp Test Manual Run/Stop Manual Run/Stop Manual Auto Manual Auto See also To ensure that your entire InfraStruXure Power Generation System is configured correctly to run in automatic operation, see the Operation section of the ATS with Power Distribution Operation manual. This section also provides instructions on how to start the generator locally in the event that it is necessary. 24 InfraStruXure Generator
31 Clearing a Shutdown Fault You cannot restart the generator when a shutdown fault lamp is lit, even if the fault has been cleared. Once you have corrected the fault, you must reset the shutdown indicators before the generator can restart. To reset the shutdown indicators: Turn the /Manual/Auto switch to the position. Press the Fault Acknowledge/Reset button. Shutdown Warning Press Fault Acknowledge/Reset Panel Lamp/Lamp Test Manual Run/Stop Manual Auto Note With the exception of generator EPO and remote EPO shutdown faults, most shutdown faults, even if cleared, will occur again when the generator is restarted. For this reason, if a shutdown fault occurs, call customer service at a phone number listed on the back of this manual for assistance. InfraStruXure Generator 25
32 Batteries See also Caution For more information on charging and replacing the generator s batteries, refer to the Battery Charger Operator s Manual that came with your generator. Servicing of batteries must be performed or supervised by a person knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. Replacement battery type When replacing generator batteries, be sure to use the same number and type of battery as the original. The generator uses 12V, 225A, 1400 cold cranking amps, sealed lead acid batteries. Keeping the batteries clean Ensure that the batteries remain clean by wiping them with a damp cloth whenever dirt appears excessive. Charging the batteries The InfraStruXure generator is equipped with a battery charger to continuously charge the batteries and ensure reliable operation. Refer to InfraStruXure Generator Components on page 7 for the location of the battery charger on your InfraStruXure generator model. You can tell if your generator s batteries are charging by looking at the battery charger. If the battery charger is charging the batteries correctly, the green Power On LED will be lit. In addition, the voltmeter will indicate the voltage at the battery and the DC ammeter will show the charger output current, which should be between 0 and 2 amperes when the battery is at its float voltage. The illustration on the following page shows battery charger and the location of these items. For proper operation, the On/Off switch of the battery charger should always be in the On position, unless you are installing or replacing the batteries. If you are installing or replacing the batteries, ensure that the battery charger s On/Off switch is in the Off position. The illustration on the following page shows the location of the On/Off switch on the generator s battery charger. 26 InfraStruXure Generator
33 Batteries Voltmeter Ammeter DC VOLTS DC AMPERES Equalize Charge Timer (Hours) AC Failure High Bat. Low Bat. Power On Equalize Voltage Float Voltage High Alarm Low Alarm Power Turn Past 2 Then Set Time On Fuse AGC 15 Fuse Fuse Off Power On LED On/Off switch Ensure that the battery charger is plugged in to one of the 120VAC receptacles on the generator. If the On/Off switch is in the On position, but the batteries are not charging, check that the charger is plugged into the correct receptacle. The following illustration shows the proper receptacle for the battery charger. If the charger is plugged in to the correct outlet and the On/Off switch is switched to On, but the batteries are still not charging, call customer service at a number listed on the back of this manual. Plug the battery charger into one of these two standard 120V receptacles. Do not plug the charger into one of the GFCI receptacles. For more information on the location of the outlet box, see InfraStruXure Generator Components on page 7. InfraStruXure Generator 27
34 Block Heater Checking the block heater The block heater reduces wear of the generator s motor and should be plugged in at all times. Check the operation of the block heater by verifying that it is warming the coolant. If the block heater is not working, it will cause an alarm on the ATS indicating that the engine temperature is too low. If this alarm occurs, check that the block heater is operating correctly. At the generator, feel the block heater with your hand. If it is warm to the touch then it is operational. If the block heater is cool to the touch and should be running, check to ensure that it is properly plugged in to one of the 120VAC receptacles on the generator s outlet box. Plug the block heater into one of these two standard 120V receptacles. Do not plug the heater into one of the GFCI receptacles. Refer to InfraStruXure Generator Components on page 7 for the location of your generator s block heater and outlet box. 28 InfraStruXure Generator
35 Specifications Electrical 80kW 125kW 200kW Output Power (kw/kva) 80/ / /250 Power Factor 1.0/ / /0.8 Alternator Brushless 4-pole drip proof revolving field, 12 lead with separately excited PMG Alternator Temperature Rise 257 F (125 C) 257 F (125 C) 221 F (105 C) Alternator Insulation Class Class H Class H Class H Voltage 120V/208V 120V/208V or 277V/480V 120V/208V or 277V/480V Output Type 4W + G 4W + G (208V) 3W + G or 4W + G (480V) 4W + G (208V) 3W + G or 4W + G (480V) Frequency 60Hz 60Hz 60Hz Battery Charger Output 10A at 12V 10A at 12V 10A at 12V Battery Charger Input 120V at 200W 120V at 200W 120V at 200W Coolant Heater 120V at 1125/1500W 120V at 1125/1500W 120V at 1125/1500W Physical 80kW 125kW 200kW Dimensions (H W D) Generator in ( mm) in ( mm) Shipping in ( mm) in ( mm) Weight Generator 4210lb (1914kg) 4160lb (1891kg) 5259lb (2390kg) Shipping 4300lb (1955kg) 4500lb (2045kg) 5675lb (2580kg) Env Environmental 80kW 125kW 200kW Operating Temperature 22 to 40 F ( 30 to 40 C) Operating Relative Humidity 5 to 100% RH 5 to 100% RH 5 to 100% RH Operating Elevation 12,800ft (3900m) 12,800ft (3900m) 12,800ft (3900m) Thermal Dissipation (full load) 1386BTU/min 1330BTU/min 2680BTU/min Audible Noise Emission 75dbA at 7m 75dbA at 7m 75dbA at 7m Compliance Approvals UL, cul 2200, Tier 2 EPA Emissions certified InfraStruXure Generator 29
36
37 Warranty APC warrants that all components of the InfraStruXure system will be free from defect in material and workmanship for a period of two years from the date of start up when start up has been performed by APC authorized service personnel*. If assembly services are included in the original purchase and are also performed by APC authorized service personnel, APC offers an additional year of parts warranty and the first year of on site coverage at no additional charge. In the event that the system fails to meet the forgoing warranty, APC shall repair or replace, at its sole discretion, any such defective parts. Under this warranty, APC will ship all parts to your site at no cost to be available for you the next business day after APC is notified of this requirement. If you choose to upgrade the system to include an on site contract, APC offers modular service packages to match your needs. Each point product incorporated into the system has a separate factory warranty that is applied when sold as a standalone unit. When incorporated into an InfraStruXure solution, the unit will be covered by the InfraStruXure warranty. In cases where one warranty favors the customer over the other, the stronger of the two warranties will take precedence. The InfraStruXure factory warranty covers only those parts appearing on the bill of materials for that solution. Megawatt UPS systems are not covered under the InfraStruXure factory warranty. Battery functionality is typically impacted by age and environmental conditions, and therefore certain requirements must be met by the end-user. Failure to adhere to these requirements may put the battery warranty at risk. APC-supplied batteries must always be kept (whether stored or installed) in a climate-controlled environment, and should be re-charged at a minimum of every three (3) months. The battery environment must be free of excessive moisture, construction dirt, corrosive elements, or other contaminants. The temperature range must be maintained at 41 to 95 F (5 to 35 C). *All warranties are null and void unless startup is performed by authorized an APC Global Services service center. APC SHALL NOT BE LIABLE UNDER THIS WARRANTY IF ITS TESTING AND EXAMINATION DISCLOSE THAT THE ALLEGED DEFECT IN THE PRODUCT DOES NOT EXIST OR WAS CAUSED BY PURCHASER'S OR ANY THIRD PERSON'S MISUSE, NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD. THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APC'S EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC'S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN InfraStruXure Generator 31
38 Warranty CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE. CONSTITUTE APC'S SOLE LIABILITY AND PURCHASER' EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC'S WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES. IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. 32 InfraStruXure Generator
39 Life-Support Policy American Power Conversion Corporation (APC) and its affiliates and subsidiaries worldwide do not recommend the use of any of their products in life-support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life-support device or to significantly affect its safety or effectiveness. APC does not permit the use of any of its products in direct patient care. APC will not knowingly sell its products for use in such applications unless the life-support system or direct patient care device is part of a whole facility/building into which the UPS is integrated, and unless APC receives, in writing, assurances satisfactory to APC that: a. The UPS system will be configured in a manner that will provide N+1 power redundancy to the critical load, b. The end-user customer assumes all risks and signs the APC System Configuration and Use Form, and c. The customer and operators of the APC UPS system agree to indemnify and hold APC and its affiliates and subsidiaries harmless for any and all claims arising out of the systems use in such applications. The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), autotransfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults and infants), anesthesia ventilators, infusion pumps, and any other devices designated as critical by the U.S. FDA. Hospital-grade wiring devices and leakage current protection may be ordered as options on many APC UPS systems. APC does not claim that units with these modifications are certified or listed as hospital-grade by APC or any other organization. Therefore these units do not meet the requirements for use in direct patient care. InfraStruXure Generator 33
40 Service How to contact APC Customer support for this or any other APC product is available at no charge in any of the following ways: Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. Global support searching APC Knowledge Base and using e-support. Contact an APC Customer Support center by telephone or . Regional centers: Direct InfraStruXure Customer Support Line APC headquarters U.S., Canada Latin America Europe, Middle East, Africa (1)(877) (toll free) (1)(800) (toll free) (1)(401) (USA) (353)(91) (Ireland) Japan (0) Australia, New Zealand, South Pacific area (61) (2) (Australia) Local, country-specific centers: go to for contact information. Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support. 34 InfraStruXure Generator
41 Index A Agency approvals, 29 B Batteries charging, replacing, 26 warnings, 5 6 Battery charger, 7 9 Block heater checking, 28 location, 8 9 block heater location, 7 C Companion manuals, i Compliance, 29 Control panel, Coolant, location of components for maintenance, 7 9 maintenance, 18 type and capacity, 17 D Digital display, 10 E Electric shock warnings, 4 Electrical specifications, 29 Engine components, 7 9 Environmental specifications, 29 E-stop button, Exhaust gas warnings, 3 F Fault acknowledge/reset button, 10 Fuel monitoring and runtime, 22 problems with, specifications, 21 warnings, 2 G Generator controller, 7 9 H Home button, 10 I Indicator lights description of, 11 location of, 10 L Lamp test button, 10 Life-support policy, 33 M Maintenance factors affecting schedule, 13 items checked during, 14 Manual run/stop switch, 10 Manual start of generator, 11 Menu selection button, 10 O O/Manual/Auto switch, location, 10 Oil, location of components for maintenance, 7 9 reading the dipstick and changing, 16 type, capacity, and level, 15 Operation warnings, 3 Outlet box, location, 7 9 Output circuit breaker, 7 9 P Panel lamp button, 10 Physical specifications, 29 S Safety instructions and symbols, 1 Service, obtaining, 34 Shutdown faults clearing, 25 indicator lights, 11 Specifications, 29 Starting the generator manually, 11 T Turbo charger, 7 9 U Updates, to this manual, i W Warnings, 2 6 Warranty, 31 InfraStruXure Generator 35
42
43
44 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. Global support searching APC Knowledge Base and using e-support. Contact an APC Customer Support center by telephone or . Regional centers: Direct InfraStruXure Customer Support Line APC headquarters U.S., Canada Latin America Europe, Middle East, Africa (1)(877) (toll free) (1)(800) (toll free) (1)(401) (USA) (353)(91) (Ireland) Japan (0) Australia, New Zealand, South Pacific area (61) (2) (Australia) Local, country-specific centers: go to for contact information. Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support. Entire contents 2005 American Power Conversion. All rights reserved. Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and InfraStruXure are trademarks of American Power Conversion Corporation and may be registered in some jurisdictions. All other trademarks, product names, and corporate names are the property of their respective owners and are used for informational purposes only. * A* A 01/2005
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
Battery Tester. GxT Incorporated, Cheboygan MI, U.S.A. All Rights Reserved E040-01G. 40 & 42HD Operator s Manual
Battery Tester GxT Incorporated, Cheboygan MI, U.S.A. All Rights Reserved E040-01G 40 & 42HD Operator s Manual SPECIFICATIONS Measurement Range...Ferret 40... Ferret 42HD Battery Volts... 4.0 to 19.99...
Installation Guide Smart-UPS X External Battery Pack SMX120BP
Installation Guide Smart-UPS X External Battery Pack SMX120BP Inventory Inspect the contents upon receipt. Notify the carrier and dealer if there is damage. Two bezels Tie brackets used to secure multiple
Triple Expansion Chassis
Triple Expansion Chassis AP9604 Installation Manual Contents Introduction............................. 1 Installation.............................. 2 Power Considerations...................... 5 Operations..............................
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
6 & 12 Volt Battery and Systems Tester with 100 Amp Load
6 & 12 Volt Battery and Systems Tester with 100 Amp Load Form No. 841-731 -000 DESCRIPTION This Load Tester tests 6 or 12 volt automotive-size lead-acid batteries under load. It will also test 6 or 12
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U SURT192RMXLBP2 SURT192RMXLBP2J English 990-2485B 02/2009 Introduction About this UPS The American Power Conversion (APC ) SURT192RMXLBP2 external
3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: [email protected] Website: www.kellogg-american.com
Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor
Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00
E Refrigerant Charging Unit ICOGD 020AH1000 Operating Manual FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 Contents Technical Specifications... 20 Safety... 21 A/C System... 22 Components... 23 Control Panel...
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.
BC-5000 BATTERY CAPACITY TESTER OPERATIONS MANUAL COFKO LLC. COPYRIGHT 2010 1 UNPACKING As you unpack your new BC-5000 battery capacity tester, inspect the tester for signs of shipping damage. If shipping
Ride-on Car OWNER S MANUAL KT1151TG. Keep instructions for future reference
Audi TT Ride-on Car KT1151TG OWNER S MANUAL Keep instructions for future reference 1 Safety The owner s manual contains assembly, use and maintenance instructions. The vehicle must be assembled by an adult
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
Wine Cooler with Thermo-Electric Cooling & Heating Technology
Wine Cooler with Thermo-Electric Cooling & Heating Technology Model number: WC-0888H (8-bottles capacity) Instruction Manual Please read carefully and follow all safety rules and operating instructions.
APC Step-Down Transformer. User s Manual
APC Step-Down Transformer Models: AP9621, SURT005, SURT006, SUTF3, SYTF2, SYTF2J, SYTF3 and SYTF3J User s Manual English 990-7820D, July 2003 TABLE OF CONTENTS APC Contact Numbers and Support Visit the
FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK
FIREPLACE HEATER FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK If you have any questions about the operation of your fireplace heater, please contact Crane Customer Care. Toll Free: 888-599-0992
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Installation and Operating Instructions (for chargers shown below)
Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
Installation. Basic Rack Power Distribution Unit AP9559
Installation Basic Rack Power Distribution Unit AP9559 This manual is available in English on the enclosed CD. Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar. Este manual está disponible
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
Installation and Operating Instructions (for chargers shown below)
Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
User Manual (English)
User Manual (English) Table of Contents General Safety Information...2 Fueltank UNO Components...3 Charging the Fueltank UNO...4 Using the Fueltank UNO...5 Power Saving Mode...6 Checking the Fueltank UNO
Operation Manual. Smart-UPS C. Uninterruptible Power Supply. Tower 1000/1500 VA. 120/230 Vac. su0813a
Operation Manual Smart-UPS C Uninterruptible Power Supply Tower 1000/1500 VA 120/230 Vac su0813a Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power
Leak Detection System
Instructions - Parts List Leak Detection System 311200A For detecting leaks in your diaphragm pump system. Not for use in explosive atmospheres. Part No. 234576 120 psi (0.8 MPa, 8 bar) Maximum Air Input
Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075
Part No. 89047 Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075 Cincinnati, OH 45241-4807 USA ELECTRIC FRYER SAFETY PRECAUTIONS Installation
WWW.CALIFORNIAAIRTOOLS.COM Customer Support 1-866-409-4581
sound proof AIr CoMprEssor CAbInEt owner's MAnuAl spc03 WWW.CALIFORNIAAIRTOOLS.COM Customer Support 1-866-409-4581 TAbLe OF CONTeNTS INTROduCTION IntroductIon 2 Important Safety InStructIonS 5 components
Instructional & Operating Manual
Instructional & Operating Manual For CoolFreeze Series Portable Refrigerators/Freezers CF-18, CF-25, CF-35, CF-40, CF-50, CF-80, CF-110 WAECO USA Clinton, CT www.waecousa.com ! Safety indications in the
Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:
Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
INSPECTION AND TESTING OF EMERGENCY GENERATORS
INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE. AeroVironment EV Solutions
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE AeroVironment EV Solutions 2013 AeroVironment, Inc. All rights reserved. AeroVironment, EV Solutions, and the AeroVironment logo are trademarks
Meaco 30L and Meaco 40L dehumidifier instruction manual
Meaco 30L and Meaco 40L dehumidifier instruction manual Please read this instruction manual before using the dehumidifier and keep safe for future reference SAFETY INSTRUCTIONS PLEASE READ ALL INSTRUCTIONS
Unpacking, Installation, and Customization
Unpacking, Installation, and Customization NetShelter WX Enclosure AR100 AR100HD Contents Unpacking... 1 How to Unpack the Enclosure............................... 1 Please Recycle..........................................
NFPA Hazard Class: * Physical Form: Solid. Health: 0 (Least) * Appearance: Yellow Flammability: 1 (Slight)
Safety Data Sheet Microcrystalline Wax 1. Chemical Product Identification Generic Name: Microcrystalline Wax INCI Name: Microcrystalline Wax Chemical Family: Mineral Emergency Telephone Numbers: Page 1
Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.
1.0 IMPORTANT RECEIVING INSTRUCTIONS Visually inspect all components for shipping damage. Shipping Damage is not covered by warranty. If shipping damage is found, notify carrier at once. The carrier is
Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE
Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will
VLT Series 300 Watt True Sine Wave Inverter
VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS
EzFlex Combustible Gas Leak Detector Model EZ40
User's Guide EzFlex Combustible Gas Leak Detector Model EZ40 Introduction Congratulations on your purchase of the Extech EZ40 Combustible Gas Leak Detector. The EZ40 detects the presence of combustible
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477
Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger
Digital echo-charge Owner s Manual Xantrex Digital echo-charge Battery Charger Thank you for purchasing a Xantrex Digital echo-charge. Xantrex Technology Inc. takes pride in manufacturing quality products
Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
Ultrasonic support removal tank
Ultrasonic support removal tank User guide and safety manual See inside for use and safety information. The Ultrasonic support removal tank automatically removes PLA support material from a printed ABS
PC1130 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
What you can expect from your Solar Hot Water System
Owner s Manual Your Solar Hot Water System Thank you for your investment in the FAFCO Solar Hot Water System. Since 1969 our goal has been to design, test, and produce solar heating systems that save you
IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
DC400 Dispensing Cutoff System
DC400 Dispensing Cutoff System DC404 and DC406 Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
600-GD & 600-GDL 600 SERIES GAS DETECTOR
600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
Installation and safety instructions for AC/DC built-in devices
The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
IMPORTANT SAFETY NOTICE
IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds
OWNERS MANUAL FOR CORDLESS INFLATOR AIR260
OWNERS MANUAL FOR CORDLESS INFLATOR AIR260 POWER SUPPLY OUTLET: AIR OUTPUT: BATTERY: RECHARGING TIME: WEIGHT: DIMENSIONS: FUSE: LIGHT BULB: SPECIFICATIONS DC 12V 15 AMP 180W MAX 260 PSI MAX PRESSURE SEALED
POWER TO GET THE JOB DONE
52720 1.5 AMP SLOW 12 VOLT BATTERY CHARGER OWNER S MANUAL KEEPS BATTERIES FULLY CHARGED IN STORAGE Automatic over-charging protection Short circuit protection Reverse hook-up protection Overheat protection
400 Amp Rechargeable Jump Start System RAC-HP082
400 Amp Rechargeable Jump Start System RAC-HP082 MAINTENANCE Always inspect the tool before use to ensure the cables are in good condition and the clamps are clean and free from corrosion. Keep clean by
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
INSTANT HOT WATER RECIRCULATING SYSTEM
INSTANT HOT WATER RECIRCULATING SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS Save manual for future reference MODEL 500800 Warning Please read carefully before proceeding with installation. Your failure
Use and Care Manual. Model CPA12KH AIR CONDITIONER
Use and Care Manual Model CPA12KH AIR CONDITIONER Introduction Thank you for choosing this air conditioner to provide you and your family with all of the "Home Comfort" requirements for your home, cottage
CAUTION. CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury.
Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts,
XC120 XC180. Owner's Guide Conforms to / Conforme à UL std. 458, Toll Free 1 866 295 6775. www.powerbright.com
WARNING: This Unit employs Components that tend to produce arcs or sparks To prevent fire or explosion, do not install in compartments containing batteries or flammable materials - SHOCK HAZARD. DO NOT
12V Portable Diaphragm Compressor Operating and Maintenance Instructions
12V Portable Diaphragm Compressor Operating and Maintenance Instructions (Part No. DC2) Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Guidelines for Product Use...2 Operation
COOLING SYSTEM Section Page
5 COOLING SYSTEM Section Page 5.1 COOLANT PRE-HEATER... 5-3 5.2 COOLANT PUMP NON-EGR ENGINE... 5-7 5.3 COOLANT PUMP EGR ENGINE... 5-13 5.4 FRONT CONNECTOR HOUSING NON-EGR ENGINE... 5-17 5.5 FRONT CONNECTOR
The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.
i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive
CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual
CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual Goodway Technologies Corporation 420 West Avenue Stamford, CT 06902-6384 (203)359-4708 Sales: 1-800-333-7467 Customer Service: 1-800-370-2855
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
User s Guide. Oreck Air Purifier with HEPA Filtration. Important! Read this manual carefully, and keep for future reference.
User s Guide Oreck Air Purifier with HEPA Filtration Important! Read this manual carefully, and keep for future reference. Enjoy Congratulations on your purchase of the Oreck Air Purifier with HEPA Filtration.
Electrical Installation
Electrical Installation InfraStruXure TM Power Generation System 250 A 208/480 V About This Manual Audience This manual is intended for certified electricians who will be installing the InfraStruXure
Battery Charger. Instruction Manual 309502G
Instruction Manual Battery Charger 309502G EN Part No. 117427, Single Bay Charger, Series B, North America (N.A.) Part No. 120110, Single Bay Charger, Series B, Australia Part No. 117429, Four Bay Charger,
1 / 4 IN. FFL x 4 FT. 9 IN. 1 / 2 IN. ACME x 4 FT. 9 IN. Gauge Accuracy +/-2% Set includes Quick Disconnect Valves
Specifications Blue (Low) Gauge 0-120 PSI Blue Hose 1 / 4 IN. FFL x 4 FT. 9 IN. Red (High) Gauge 0-500 PSI Red Hose 1 / 4 IN. FFL x 4 FT. 9 IN. Yellow Hose 1 / 2 IN. ACME x 4 FT. 9 IN. Gauge Accuracy +/-2%
PC1131 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
P 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.
This generator set has been designed to meet ISO 88 regulation. This generator set is manufactured in facilities certified to ISO 900. This generator set is available with CE certification. Enclosed product
National- Spencer Inc.
9-27-2010 National- Spencer Inc. 19.2V HEAVY DUTY GREASE GUN PRODUCT SPECIFICATION Charger Input Power 110 VAC Battery Output Power 19.2V Battery Capacity 1500 MAH Battery Pack Charge Time 1 Hour Maximum
Powerware 5110 UPS User s manual
Powerware 5110 UPS 2005 Eaton Corporation All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
BEP FD-2 CONTOUR MATRIX FUME DETECTOR
BEP FD-2 CONTOUR MATRIX FUME DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING GAS SENSORS...3 4 FEATURES...4 5 SPECIFICATION...4 6
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
1/3 HP Submersible Sump Pump with Vertical Float Switch
1/3 HP Submersible Sump with Vertical Float Switch Item 68476 Specifications Float Switch Operation Height 7.1 IN. ON / 2.8 IN. OFF Electrical Requirements 120V~ / 60Hz / 7.6A Power Length Maximum Capacity
Wilo SP Series Submersible Sump Pumps ECS. ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions
Wilo SP Series Submersible Sump Pumps ECS ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions PREINSTALLATION CHECK Inspect this pump before it is used. Occasionally, pumps can
3053 Electrical Safety Training Program Course Outline
3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting
INSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
Trouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
350, 500, 650 and 1000 MODELS
P D Technology Ltd PDT Power Series Instruction Manual Domestic, Commercial & Industrial PLEASE READ THE INSIDE FRONT COVER BEFORE INSTALLING THE PDT POWER SERIES 350, 500, 650 and 1000 MODELS P D Technology
Operating instructions in the back. www.blackanddecker.co.uk PD1020L
Operating instructions in the back www.blackanddecker.co.uk PD1020L 2 ENGLISH (Original instructions) Intended use Your Black & Decker Dustbuster handheld vacuum cleaner has been designed for vacuum cleaning
LESTRONIC DV AUTOMATIC 12 OR 24 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/24EL40-10ET
LESTRONIC DV AUTOMATIC 12 OR 2 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/2EL0-10ET PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment,
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Electric Water Heater
Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.
Out-of-Band Management Card
Out-of-Band Management Card AP9608 Installation Manual Related Documents For information on using the Out-of-Band Management Card after installation and startup, see the online User s Guide specific to