Inspection Report. Happy 2 Flat Owner. Property Address: Focal Point Home Inspection Ltd.

Size: px
Start display at page:

Download "Inspection Report. Happy 2 Flat Owner. Property Address: Focal Point Home Inspection Ltd."

Transcription

1 Page 1 of 50 Inspection Report Happy Property Address: 3653 N. Bernard Rear Focal Point Home Inspection Ltd. Joseph Poelsterl W. Grace st Chicago Illinois

2 Page 2 of 50 Table of Contents Cover Page Table of Contents Intro Page General Summary Electrical Summary Plumbing Summary Structural Summary Heating Cooling / Summary 1 Roofing, Roof Structure, Chimneys, and Attic 2 Exterior 3 Structural Components 4 Plumbing System for Building 5 Garage 6(A) First Floor 6(B) Second Floor Invoice

3 Page 3 of 50 Date: 3/12/2013 Time: Report ID: Property: Customer: Happy Comment Key or Definitions Real Estate Professional: Glen Tomlinson Century 21 United II The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this building. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property. Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear. Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting. Not Present (NP) = This item, component or unit is not in this building or building. Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement. Standards of Practice: NACHI National Association of Certified Home Inspectors, Illinois In Attendance: Customer Type of building: Multi-family Style of Home: 2 Flat Brick Approximate age of building: 80 Home Faces: West Temperature: 32 Weather: Cloudy Ground/Soil surface condition: Frozen, Staurated, Rain in last 3 days: Yes Radon Test: No Water Test: No

4 Page 4 of 50 General Summary Focal Point Home Inspection Ltd W. Grace st Chicago Illinois Customer Happy Address The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report. 2. Exterior 2.0 WALL CLADDING FLASHING AND TRIM Baseball size hole in East elevation.inspector recommend hole be covered to prevent vermin entering house. (Picture 1) (Picture 2) Large hole in siding South elevation, (Picture 3) 2.1 DOORS (Exterior) Exterior doors front and rear do not open freely. Front entry door threshold loose.(picture 1) 2.2 WINDOWS Inspected All windows appear new on 1st and 2nd floor.basement windows are glass block with vents. 1 glass block window on the South elevation has been installed improperly,it has a wood frame surrounding the glass block window. This should be filled with masonry.(picture 1) Screen ripped on 2nd window east elevation.(picture 2) 2.5 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) Sidewalk on South elevation are slanted towards building. This will increase chances of water infiltration. Inspector recommends new walks slanted away from property for proper water run off.(picture 1)(Picture 2) 2.8 Masonry Tuckpointing repairs on West elevation at parapet wall.(picture 1) (Picture 2)(Picture 3) North elevation needs tuckpointing repairs.(picture 4)(Picture 5)

5 Page 5 of Exterior Chimney need installation of rain cap and tuckpointing.(picture 6)(Picture 7) South elevation needs brick replacement and tuckpointing.(picture 8)(Picture 9)(Picture 10) 3. Structural Components 3.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) (1) I am unable to determine the extent of water intrusion or how often it will occur. (2) Visible signs of water intrusion in the basement are present from water stains on. Water intrusion can lead to more costly repairs and increase damage if not corrected.. Sloping the ground or trenching may be needed to direct water. 3.6 VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT) Not Present Houses of this era did not have vapor retarder below basement floor. Inspector recommends installation of vapor retarder under back porch area. 3.7 VENTILATION OF FOUNDATION AREAS (crawlspace or basement) Not Present Inspector recommends installation of vents under enclosed back porch. 5. Garage 5.3 GARAGE DOOR (S) Metal door has been dented (Picture 1) 5.4 OCCUPANT DOOR FROM GARAGE TO INSIDE STRUCTURE Wood frame and brick mould have not been painted with a finish coat of paint.(picture 1) 6(A). First Floor 6.0.A CEILINGS Kitchen ceiling needs patching from pantry removal. Ceiling damage in hall closet.(picture 1) 6.1.A 6.23.A WALLS Repair hole in drywall enclosed back porch.(picture 1) CARBON MONOXIDE DETECTORS There is no carbon monoxide detector found in building. It is recommended that one be installed according to the manufacturer's instructions.

6 Page 6 of 50 6(B). Second Floor 6.0.B CEILINGS Ceiling and wall damage in pantry from active roof leak.(picture 1) Ceiling damage in kitchen due to active roof leak.(picture 2) Ceiling damage in dinning room due to active roof leak.(picture 3)(Picture 4) 6.1.B WALLS Hole above bathroom mirror.(picture 1) North wall of front stairwell is bulging. Repairs needed.(picture 2) Walls appear to be normal for a house of this era B 6.12.B RANGES/OVENS/COOKTOPS Cook top tested OK oven tested at 420 degrees when set at 350 degrees. STEPS, STAIRWAYS, BALCONIES AND RAILINGS Hand rails should be added to front stairway.(picture 1) building inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. building inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the building inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property. Prepared Using HomeGauge : Licensed To Joseph Poelsterl

7 Page 7 of 50 Electrical Summary Focal Point Home Inspection Ltd W. Grace st Chicago Illinois Customer Happy Address The following Electrical items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report. 5. Garage 5.6 POLARITY AND GROUNDING OF RECEPTACLES IN GARAGE All garage receptacles must be changed to a gfci type. Polarity reversed garage receptacle.(picture 1)(Picture2) Light fixture falling down from garage patio.(picture 3) Open junction box in garage.(picture 4) Wire for electric eye is loose and should be stapled down.(picture 5) 6(A). First Floor 6.9.A OUTLETS AND WALL SWITCHES Receptacle on enclosed back porch does not have a ground (3 prong)(picture 1) Kitchen light fixture not installed properly.(picture 2) All bare bulb light fixtures in closets must have a globe to protect bulb.(picture 3) Dimmer switch cover missing in dinning room.(picture 4) Open and live wires at basement entrance.this can be dangerous.(picture 5) Receptacle tested with reverse polarity in front basement recreation room.(picture 6) Bare bulb light fixtures must have a globe to protect bulb.(basement bedroom)(picture 7) Open electrical junction box on ceiling of boiler room.(picture 8) 6.18.A

8 Page 8 of 50 6(A). First Floor 6.20.A SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Arrow on top of photo indicates main service conductors not attached to breaker panel. Lower arrow indicates main ground wire conduit not attached to breaker panel. ground wire not attached to bus bar properly.(picture 1) POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE Gfci receptacle in bathroom tested with a open ground.(picture 1) 6(B). Second Floor 6.9.B OUTLETS AND WALL SWITCHES Receptacle on enclosed rear porch needs to be replaced with a grounded type(3 Prong)(Picture 1) Receptacle in pantry needs replacement.(note water streaks on wall from active roof leak.(picture 2) Receptacles within 6 feet of a water source must be changed to gfci type.(picture 3)(Picture 4) GFCI receptacle in bathroom would not reset.test failed replacement needed.(picture 5) Many receptacles in the apartment have not been updated to a grounded type.(3 prong)(picture 6)(Picture 8) All light fixtures in closets must have a globe type cover to protect bulb.(picture 7)(Picture 9) Light fixture in kitchen has not been installed properly. (wire splices exposed and wires are not attached with wire nuts.(picture 10) 6.18.B SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Top of electrical panel has been damaged at service cable entrance.(picture 1) open junction boxes near breaker panel.(picture 2) 6.20.B POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE I did not find any outside outlets. Many receptacles were tested and reverse polarity was common. Inspector recommends licensed electrical contractor correct all electrical defects B SMOKE DETECTORS Inspector recommend replacement of smoke detectors now and every 5 years.smoke detectors were chirping low battery warning. (Picture 1) The smoke detector should be tested at common hallway to bedrooms upon moving in to building. The smoke detector needs locating at least 4 inches from ceiling/wall junction and no further than 12 inches away B CARBON MONOXIDE DETECTORS

9 Page 9 of 50 6(B). Second Floor There is no carbon monoxide detector found in building. It is recommended that one be installed according to the manufacturer's instructions. Prepared Using HomeGauge : Licensed To Joseph Poelsterl

10 Page 10 of 50 Plumbing Summary Focal Point Home Inspection Ltd W. Grace st Chicago Illinois Customer Happy Address The following Plumbing items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report. 1. Roofing, Roof Structure, Chimneys, and Attic 1.4 ROOF DRAINAGE SYSTEMS Newer aluminum gutter and downspout at rear of house. Inspector recommends filling in gap in downspout sewer with mortar to prevent vermin from entering. (Picture 1) 2. Exterior 2.6 PLUMBING WATER FAUCETS (hose bibs) Inspected Hose bib on South elevation tested and working. Inspector recommends in winter inside valve be shut off and exterior hose bib be opened or replace with freeze proof hose bib. 4. Plumbing System for Building 4.0 PLUMBING DRAIN, WASTE AND VENT SYSTEMS Inspector checked house drain catch basin. Masonry appears to be in good condition. Inspector recommends cleaning by qualified sewer contractor. (note installation of sump pump and pit into basement floor for kitchen and laundry drains it appears that catch basin only serves roof downspout. (Picture 1)(Picture 2) 4.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Water piping is galvanized and has begun to corroded inside reducing water volume and pressure at all plumbing fixtures.inspector recommends water pipe replacement. 4.5 SUMP PUMP Newly added sump pump and pit tested working at time of inspection. Inspector recommends cleaning of pit from soap and grease residue.(picture 1)

11 Page 11 of 50 6(A). First Floor 6.6.A PLUMBING SUPPLY, FIXTURES IN THIS UNIT Poor water pressure to kitchen sink.(picture 1) Shower diverter spout is loose in wall.(picture 2) 6.7.A PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT All drains checked with no leaks at time of inspection. Pop up plug did not work in washroom.(picture 1) 6(B). Second Floor 6.6.B PLUMBING SUPPLY, FIXTURES IN THIS UNIT Bathtub missing drain plug.(picture 1) Prepared Using HomeGauge : Licensed To Joseph Poelsterl

12 Page 12 of 50 Structural Summary Focal Point Home Inspection Ltd W. Grace st Chicago Illinois Customer Happy Address The following Structural items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report. 1. Roofing, Roof Structure, Chimneys, and Attic 1.0 ROOF COVERINGS Not Inspected Inspector unable to inspect roof due to a closet that has been built below roof scuttle hatch. 2nd floor ceiling in kitchen has a 10 square foot hole and water damage appears in dinning room ceiling. Reinspection April 24,2013. Inspector viewed new roof installation. Roof covering and flashing have been replaced with a heat applied rubber roof membrane.(note inspection was held at 10:00 am and Chicago had experienced a 24 hour rain, Note how dry the roof the roof is at time of inspection.roof sheds away water well.(picture 1)(Picture 2)(Picture 3)(Picture 4)(Picture 5)(Picture 6)(Picture 7)(Picture 8) 1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS Chimney is in need of a rain cap and tuckpointing work. 3. Structural Components 3.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) (2) Visible signs of water intrusion in the basement are present from water stains on. Water intrusion can lead to more costly repairs and increase damage if not corrected.. Sloping the ground or trenching may be needed to direct water. 3.4 CEILINGS (structural) It is unknown if structural damage has occurred on 2nd floor ceiling from active roof water leak. Prepared Using HomeGauge : Licensed To Joseph Poelsterl

13 Page 13 of 50 Heating Cooling / Summary Focal Point Home Inspection Ltd W. Grace st Chicago Illinois Customer Happy Address The following Heating and Cooling items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report. 4. Plumbing System for Building 4.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Hot water tank flue has not been mortared in to chimney properly. Installer used foam insulation.(picture 1) 6(A). First Floor 6.13.A HEATING EQUIPMENT Gas supply to wall space heater in basement should be hard piped not flex connection.(picture 1) Inspector viewed the heating pipe insulation near the boiler and found 2 areas where seal is broken. Inspector did not test material for asbestos but in his experience the insulation does contain it. These broken areas are now considered fryable. This should be incapsulated or abated asap to prevent air born contamination. (Picture 2) (Picture 3)(Picture 4) Gas service valve for boiler.(picture 5) Inspector recommends cleaning and general maintenance of boiler by qualified heating contractor. Prepared Using HomeGauge : Licensed To Joseph Poelsterl

14 Page 14 of Roofing, Roof Structure, Chimneys, and Attic The building inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The building inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The building inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors. IN NI NP RR 1.0 ROOF COVERINGS 1.1 ROOF FLASHINGS 1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS 1.3 ROOF VENTILATION 1.4 ROOF DRAINAGE SYSTEMS 1.5 ROOF STRUCTURE AND ATTIC (report leak signs or condensation) IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Styles & Materials Roof-Type: Flat Roof Covering: Built-up Chimney (exterior): Brick Sky Light(s): None Roof Ventilation: None found Method used to observe attic: Inaccessible Roof Structure: Not visible Ceiling Structure: Not visible Attic info: Attic is sealed no access Attic Insulation: Unknown Comments:

15 Page 15 of Inspector unable to inspect roof due to a closet that has been built below roof scuttle hatch. 2nd floor ceiling in kitchen has a 10 square foot hole and water damage appears in dinning room ceiling. Reinspection April 24,2013. Inspector viewed new roof installation. Roof covering and flashing have been replaced with a heat applied rubber roof membrane.(note inspection was held at 10:00 am and Chicago had experienced a 24 hour rain, Note how dry the roof the roof is at time of inspection.roof sheds away water well.(picture 1)(Picture 2)(Picture 3)(Picture 4) (Picture 5)(Picture 6)(Picture 7)(Picture 8) 1.0 Item 1(Picture) 1.0 Item 2(Picture) 1.0 Item 3(Picture) 1.0 Item 4(Picture)

16 Page 16 of Item 5(Picture) 1.0 Item 6(Picture) 1.0 Item 7(Picture) 1.0 Item 8(Picture) 1.2 Chimney is in need of a rain cap and tuckpointing work. 1.3 Flat roof building built in this era did not have roof ventilation installed. 1.4 Newer aluminum gutter and downspout at rear of house. Inspector recommends filling in gap in downspout sewer with mortar to prevent vermin from entering. (Picture 1) 1.4 Item 1(Picture) Inspector recommends filling gap with mortar. 1.5 Attic is sealed with no access.

17 Page 17 of 50 The roof of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

18 Page 18 of Exterior The building inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The building inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The building inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The building inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility. IN NI NP RR 2.0 WALL CLADDING FLASHING AND TRIM 2.1 DOORS (Exterior) 2.2 WINDOWS 2.3 FOUNDATION WALLS AND MORTAR JOINTS DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) 2.6 PLUMBING WATER FAUCETS (hose bibs) 2.7 POLARITY AND GROUNDING OF RECEPTACLES ON EXTERIOR WALLS OF INSPECTED STRUCTURE 2.8 Masonry IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Comments: Styles & Materials Siding Style: Drop Brick Siding Material: Full brick Aluminum 8" drop siding Exterior Entry Doors: Wood Steel Appurtenance: Porch Sidewalk Driveway: Street Parking

19 Page 19 of Baseball size hole in East elevation.inspector recommend hole be covered to prevent vermin entering house.(picture 1) (Picture 2) Large hole in siding South elevation, (Picture 3) 2.0 Item 1(Picture) Baseball size hole in East elevation.inspector recommend hole be covered to prevent vermin entering house. 2.0 Item 2(Picture) 2.0 Item 3(Picture) Large hole in siding South elevation,

20 Page 20 of Exterior doors front and rear do not open freely. Front entry door threshold loose.(picture 1) 2.1 Item 1(Picture) Front entry door threshold loose. 2.2 All windows appear new on 1st and 2nd floor.basement windows are glass block with vents. 1 glass block window on the South elevation has been installed improperly,it has a wood frame surrounding the glass block window. This should be filled with masonry.(picture 1) Screen ripped on 2nd window east elevation.(picture 2) 2.2 Item 1(Picture) Glass block window on South elevation not installed properly. 2.2 Item 2(Picture) Screen ripped on 2nd window east elevation. 2.3 Foundation walls were inspected where exposed and appear fine, most of the basement has had studs and drywall installed preventing further inspection. 2.4 Exterior and interior steps and porches appear to be in good order for buildings built in this era.

21 Page 21 of Sidewalk on South elevation are slanted towards building. This will increase chances of water infiltration. Inspector recommends new walks slanted away from property for proper water run off.(picture 1)(Picture 2) 2.5 Item 1(Picture) South elevation sidewalk facing east 2.5 Item 2(Picture) 2.6 Hose bib on South elevation tested and working. Inspector recommends in winter inside valve be shut off and exterior hose bib be opened or replace with freeze proof hose bib. 2.7 The building does not have exterior receptacles.

22 Page 22 of Tuckpointing repairs on West elevation at parapet wall.(picture 1) (Picture 2)(Picture 3) North elevation needs tuckpointing repairs.(picture 4)(Picture 5) Chimney need installation of rain cap and tuckpointing.(picture 6)(Picture 7) South elevation needs brick replacement and tuckpointing.(picture 8)(Picture 9)(Picture 10) 2.8 Item 1(Picture) Tuckpointing repairs on West elevation at parapet wall. 2.8 Item 2(Picture) 2.8 Item 3(Picture) West elevation near top of porch 2.8 Item 4(Picture) North elevation needs tuckpointing repairs. 2.8 Item 5(Picture) 2.8 Item 6(Picture) Chimney need installation of rain cap and tuckpointing.

23 Page 23 of Item 7(Picture) 2.8 Item 8(Picture) South elevation needs brick replacement and tuckpointing. 2.8 Item 9(Picture) 2.8 Item 10(Picture) The exterior of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

24 Page 24 of Structural Components The building Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The building inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The building inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The building inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the building inspector or other persons. 3.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) 3.1 WALLS (Structural) 3.2 COLUMNS OR PIERS 3.3 FLOORS (Structural) IN NI NP RR 3.4 CEILINGS (structural) 3.5 INSULATION UNDER FLOOR SYSTEM 3.6 VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT) 3.7 VENTILATION OF FOUNDATION AREAS (crawlspace or basement) Styles & Materials Foundation: Poured concrete Method used to observe Crawlspace: Walked Floor Structure: 2 X 8 Not visible Wall Structure: Masonry Brick Columns or Piers: Not Visable Floor System Insulation: NONE IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Comments: 3.0 (1) I am unable to determine the extent of water intrusion or how often it will occur. (2) Visible signs of water intrusion in the basement are present from water stains on. Water intrusion can lead to more costly repairs and increase damage if not corrected.. Sloping the ground or trenching may be needed to direct water. 3.1 Walls appear to be in good order for homes built of this era. 3.2 Columns have been covered with drywall and could not be inspected Floors do not appear to be out of level. 3.4 It is unknown if structural damage has occurred on 2nd floor ceiling from active roof water leak. 3.5 Houses of this era did not have floor insulation. 3.6 Houses of this era did not have vapor retarder below basement floor. Inspector recommends installation of vapor retarder under back porch area. 3.7 Inspector recommends installation of vents under enclosed back porch. The structure of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

25 Page 25 of Plumbing System for Building The building inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The building inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The building inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The building inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials. IN NI NP RR 4.0 PLUMBING DRAIN, WASTE AND VENT SYSTEMS 4.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES 4.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS 4.3 MAIN WATER SHUT-OFF DEVICE (Describe location) 4.4 MAIN FUEL SHUT OFF (Describe Location) 4.5 SUMP PUMP IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Styles & Materials Water Source: Public Water Filters: None Plumbing Water Supply (into building): Lead hose Plumbing Water Distribution (inside building): Galvanized Washer Drain Size: Laundry tub Plumbing Waste: PVC Cast iron Water Heater Power Source: Gas (quick recovery) Water Heater Capacity: 40 Gallon (1-2 people) Water Heater Manufacturer: HOTPOINT Water Heater Location: Basement Washer Dryer Room Comments: 4.0 Inspector checked house drain catch basin. Masonry appears to be in good condition. Inspector recommends cleaning by qualified sewer contractor. (note installation of sump pump and pit into basement floor for kitchen and laundry drains it appears that catch basin only serves roof downspout. (Picture 1)(Picture 2) 4.0 Item 1(Picture) 4.0 Item 2(Picture) 4.1 Water piping is galvanized and has begun to corroded inside reducing water volume and pressure at all plumbing fixtures.inspector recommends water pipe replacement.

26 Page 26 of Hot water tank flue has not been mortared in to chimney properly. Installer used foam insulation.(picture 1) 4.2 Item 1(Picture) Improper flue pipe installation. 4.3 The main shut off is the knob located in the basement near gas floor. This is for your information)(picture 1) 4.3 Item 1(Picture) Main water shut off valve. 4.4 Gas meter and shut off valves located in small closet Southwest corner of basement.(picture 1)(Picture 2) 4.4 Item 1(Picture) 4.4 Item 2(Picture)

27 Page 27 of Newly added sump pump and pit tested working at time of inspection. Inspector recommends cleaning of pit from soap and grease residue.(picture 1) 4.5 Item 1(Picture) Sump pump pit needs cleaning. The plumbing in the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant building waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

28 Page 28 of Garage 5.0 GARAGE CEILINGS AND ROOF SYSTEM. 5.1 GARAGE WALLS (INCLUDING FIREWALL SEPARATION) 5.2 GARAGE FLOOR IN NI NP RR 5.3 GARAGE DOOR (S) 5.4 OCCUPANT DOOR FROM GARAGE TO INSIDE STRUCTURE 5.5 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance) 5.6 POLARITY AND GROUNDING OF RECEPTACLES IN GARAGE IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Comments: 5.0 Garage does not have ceiling open to underside of roof. Styles & Materials Garage Door Type: One automatic Two automatic Garage Door Material: Metal Auto-opener Manufacturer: GENIE LIFT-MASTER 5.1 Garage appears to be less than 9 months old. 5.2 Garage floor is older from pre existing garage. 5.3 Metal door has been dented (Picture 1) 5.3 Item 1(Picture) Metal door has been dented

29 Page 29 of Wood frame and brick mould have not been painted with a finish coat of paint.(picture 1) 5.4 Item 1(Picture) Wood frame and brick mould have not been painted with a finish coat of paint. 5.5 Good working order for both openers.(picture 1) 5.5 Item 1(Picture) Both tested and passed safety tests.

30 Page 30 of All garage receptacles must be changed to a gfci type. Polarity reversed garage receptacle.(picture 1)(Picture2) Light fixture falling down from garage patio.(picture 3) Open junction box in garage.(picture 4) Wire for electric eye is loose and should be stapled down.(picture 5)

31 Page 31 of Item 1(Picture) Polarity reversed garage receptacle. 5.6 Item 2(Picture) 5.6 Item 3(Picture) Light fixture falling down from garage patio. 5.6 Item 4(Picture) Open junction box in garage.

32 Page 32 of Item 5(Picture) Wire for electric eye is loose and should be stapled down.

33 Page 33 of 50 6(A). First Floor The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms. IN NI NP RR 6.0.A CEILINGS 6.1.A WALLS 6.2.A FLOORS 6.3.A DOORS (REPRESENTATIVE NUMBER) 6.4.A WINDOWS (REPRESENTATIVE NUMBER) 6.5.A COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS 6.6.A PLUMBING SUPPLY, FIXTURES IN THIS UNIT 6.7.A PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT 6.8.A VENTING SYSTEMS IN THIS UNIT (Kitchens, baths and laundry if applicable) 6.9.A OUTLETS AND WALL SWITCHES 6.10.A RANGES/OVENS/COOKTOPS 6.11.A RANGE HOOD 6.12.A STEPS, STAIRWAYS, BALCONIES AND RAILINGS 6.13.A HEATING EQUIPMENT 6.14.A PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM 6.15.A 6.16.A DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) 6.17.A SERVICE ENTRANCE CONDUCTORS 6.18.A 6.19.A 6.20.A SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE 6.21.A LOCATION OF MAIN AND DISTRIBUTION PANELS 6.22.A SMOKE DETECTORS 6.23.A CARBON MONOXIDE DETECTORS IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Styles & Materials Ceiling Materials: Drywall Plaster Wall Material: Drywall Plaster Floor Covering(s): Hardwood T&G Tile Interior Doors: Wood Window Types: Double-hung Thermal/Insulated Tilt feature Heat Type: Circulating boiler Energy Source: Natural gas Number of Heat Systems (excluding wood): One Heat System Brand: PEERLESS Ductwork: N/A Filter Type: N/A Filter Size: N/A Bath Exhaust Fans: None Dishwasher Brand: NONE Disposer Brand: NONE Exhaust/Range hood: NUTONE Range/Oven: KENMORE Built in Microwave: NONE Trash Compactors: NONE Dryer Power Source: Gas Connection Dryer Vent: Flexible Vinyl Electrical Service Conductors: Overhead service Copper 220 volts Panel capacity: 100 AMP Panel Type: Circuit breakers Branch wire 15 and 20 AMP: Copper Wiring Methods: Conduit BX cable

34 Page 34 of 50 Comments: 6.0.A Kitchen ceiling needs patching from pantry removal. Ceiling damage in hall closet.(picture 1) 6.0.A Item 1(Picture) Ceiling damage in hall closet. 6.1.A Repair hole in drywall enclosed back porch.(picture 1) 6.1.A Item 1(Picture) Repair hole in drywall enclosed back porch. 6.2.A Floors appear to be straight and level. 6.3.A All doors are in working order. 6.4.A Windows are newer with tilt feature. 6.5.A Counters and cabinets are in good working order.

35 Page 35 of A Poor water pressure to kitchen sink.(picture 1) Shower diverter spout is loose in wall.(picture 2) 6.6.A Item 1(Picture) Poor water pressure to kitchen sink. 6.6.A Item 2(Picture) Shower diverter spout is loose in wall. 6.7.A All drains checked with no leaks at time of inspection. Pop up plug did not work in washroom.(picture 1) 6.7.A Item 1(Picture) Pop up plug did not work in washroom. 6.8.A The building does not have active power ventilation.

36 Page 36 of A Receptacle on enclosed back porch does not have a ground (3 prong)(picture 1) Kitchen light fixture not installed properly.(picture 2) All bare bulb light fixtures in closets must have a globe to protect bulb.(picture 3) Dimmer switch cover missing in dinning room.(picture 4) Open and live wires at basement entrance.this can be dangerous.(picture 5) Receptacle tested with reverse polarity in front basement recreation room.(picture 6) Bare bulb light fixtures must have a globe to protect bulb.(basement bedroom)(picture 7) Open electrical junction box on ceiling of boiler room.(picture 8) 6.9.A Item 1(Picture) Receptacle on enclosed back porch does not have a ground (3 prong) 6.9.A Item 2(Picture) Kitchen light fixture not installed properly. 6.9.A Item 3(Picture) All bare bulb light fixtures in closets must have a globe to protect bulb. 6.9.A Item 4(Picture) Dimmer switch cover missing in dinning room.

37 Page 37 of A Item 5(Picture) Open and live wires at basement entrance.this can be dangerous. 6.9.A Item 6(Picture) Receptacle tested with reverse polarity in front basement recreation room. 6.9.A Item 7(Picture) Bare bulb light fixtures must have a globe to protect bulb.(basement bedroom) 6.9.A Item 8(Picture) Open electrical junction box on ceiling of boiler room.

38 Page 38 of A Gas supply to wall space heater in basement should be hard piped not flex connection.(picture 1) Inspector viewed the heating pipe insulation near the boiler and found 2 areas where seal is broken. Inspector did not test material for asbestos but in his experience the insulation does contain it. These broken areas are now considered fryable. This should be incapsulated or abated asap to prevent air born contamination. (Picture 2)(Picture 3)(Picture 4) Gas service valve for boiler.(picture 5) Inspector recommends cleaning and general maintenance of boiler by qualified heating contractor.

39 Page 39 of A Item 2(Picture) 6.13.A Item 1(Picture) Gas supply to wall space heater in basement should be hard piped not flex connection A Item 3(Picture) 6.13.A Item 4(Picture) 6.13.A Item 5(Picture) Gas service valve for boiler.

40 Page 40 of A Arrow on top of photo indicates main service conductors not attached to breaker panel. Lower arrow indicates main ground wire conduit not attached to breaker panel. ground wire not attached to bus bar properly.(picture 1) 6.18.A Item 1(Picture) Arrow on top of photo indicates main service conductors not attached to breaker panel. Lower arrow indicates main ground wire conduit not attached to breaker panel. ground wire not attached to bus bar properly A Gfci receptacle in bathroom tested with a open ground.(picture 1) 6.20.A Item 1(Picture) Gfci receptacle in bathroom tested with a open ground A The main panel box is located at the basement laundry room A The smoke detector should be tested at common hallway to bedrooms upon moving in to building. The smoke detector needs locating at least 4 inches from ceiling/wall junction and no further than 12 inches away A There is no carbon monoxide detector found in building. It is recommended that one be installed according to the manufacturer's instructions.

41 Page 41 of 50 The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

42 Page 42 of 50 6(B). Second Floor The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms. IN NI NP RR 6.0.B CEILINGS 6.1.B WALLS 6.2.B FLOORS 6.3.B DOORS (REPRESENTATIVE NUMBER) 6.4.B WINDOWS (REPRESENTATIVE NUMBER) 6.5.B COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS 6.6.B PLUMBING SUPPLY, FIXTURES IN THIS UNIT 6.7.B PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT 6.8.B VENTING SYSTEMS IN THIS UNIT (Kitchens, baths and laundry if applicable) 6.9.B OUTLETS AND WALL SWITCHES 6.10.B RANGES/OVENS/COOKTOPS 6.11.B RANGE HOOD 6.12.B STEPS, STAIRWAYS, BALCONIES AND RAILINGS 6.13.B HEATING EQUIPMENT 6.14.B PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM 6.15.B 6.16.B DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) 6.17.B SERVICE ENTRANCE CONDUCTORS 6.18.B 6.19.B 6.20.B SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE 6.21.B LOCATION OF MAIN AND DISTRIBUTION PANELS 6.22.B SMOKE DETECTORS 6.23.B CARBON MONOXIDE DETECTORS IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Styles & Materials Ceiling Materials: Drywall Plaster Wall Material: Drywall Plaster Floor Covering(s): Hardwood T&G Tile Interior Doors: Wood Window Types: Double-hung Thermal/Insulated Tilt feature Heat Type: Circulating boiler Energy Source: Natural gas Number of Heat Systems (excluding wood): One Heat System Brand: PEERLESS Ductwork: N/A Filter Type: N/A Filter Size: N/A Bath Exhaust Fans: None Dishwasher Brand: NONE Disposer Brand: NONE Exhaust/Range hood: NUTONE Range/Oven: UNKNOWN Built in Microwave: NONE Trash Compactors: NONE Dryer Power Source: Gas Connection Dryer Vent: Flexible Vinyl Electrical Service Conductors: Overhead service Copper 220 volts Panel capacity: 100 AMP Panel Type: Circuit breakers Branch wire 15 and 20 AMP: Copper Wiring Methods: Conduit BX cable

43 Page 43 of 50 Comments: 6.0.B Ceiling and wall damage in pantry from active roof leak.(picture 1) Ceiling damage in kitchen due to active roof leak.(picture 2) Ceiling damage in dinning room due to active roof leak.(picture 3)(Picture 4) 6.0.B Item 1(Picture) Ceiling and wall damage in pantry from active roof leak. 6.0.B Item 2(Picture) Ceiling damage in kitchen due to active roof leak. 6.0.B Item 3(Picture) Ceiling damage in dinning room due to active roof leak. 6.0.B Item 4(Picture)

44 Page 44 of B Hole above bathroom mirror.(picture 1) North wall of front stairwell is bulging. Repairs needed.(picture 2) Walls appear to be normal for a house of this era. 6.1.B Item 1(Picture) Hole above bathroom mirror. 6.1.B Item 2(Picture) North wall of front stairwell is bulging. Repairs needed. 6.2.B Floors appear to be straight and level. 6.3.B All doors are in working order. 6.4.B All windows are newer vinyl with tip out feature. 6.5.B Counters and cabinets are in good working order. 6.6.B Bathtub missing drain plug.(picture 1) 6.6.B Item 1(Picture) Bathtub missing drain plug. 6.8.B This building does not have any active venting.

45 Page 45 of B Receptacle on enclosed rear porch needs to be replaced with a grounded type(3 Prong)(Picture 1) Receptacle in pantry needs replacement.(note water streaks on wall from active roof leak.(picture 2) Receptacles within 6 feet of a water source must be changed to gfci type.(picture 3)(Picture 4) GFCI receptacle in bathroom would not reset.test failed replacement needed.(picture 5) Many receptacles in the apartment have not been updated to a grounded type.(3 prong)(picture 6)(Picture 8) All light fixtures in closets must have a globe type cover to protect bulb.(picture 7)(Picture 9) Light fixture in kitchen has not been installed properly. (wire splices exposed and wires are not attached with wire nuts. (Picture 10)

46 Page 46 of B Item 1(Picture) Receptacle on enclosed rear porch needs to be replaced with a grounded type(3 Prong) 6.9.B Item 2(Picture) Receptacle in pantry needs replacement.(note water streaks on wall from active roof leak. 6.9.B Item 3(Picture) Receptacles within 6 feet of a water source must be changed to gfci type. 6.9.B Item 4(Picture) 6.9.B Item 5(Picture) GFCI receptacle in bathroom would not reset.test failed replacement needed. 6.9.B Item 6(Picture) Many receptacles in the apartment have not been updated to a grounded type.(3 prong)

47 Page 47 of B Item 7(Picture) All light fixtures in closets must have a globe type cover to protect bulb. 6.9.B Item 8(Picture) 6.9.B Item 9(Picture) 6.9.B Item 10(Picture) Light fixture in kitchen has not been installed properly. (wire splices exposed and wires are not attached with wire nuts B Cook top tested OK oven tested at 420 degrees when set at 350 degrees B Nutone kitchen exhaust hood is of a recirculating type.

48 Page 48 of B Hand rails should be added to front stairway.(picture 1) 6.12.B Item 1(Picture) Hand rails should be added to front stairway B Comments will be shown on first floor section of report B Top of electrical panel has been damaged at service cable entrance.(picture 1) open junction boxes near breaker panel.(picture 2) 6.18.B Item 2(Picture) open junction boxes near breaker panel B Item 1(Picture) Top of electrical panel has been damaged at service cable entrance B I did not find any outside outlets. Many receptacles were tested and reverse polarity was common. Inspector recommends licensed electrical contractor correct all electrical defects B The main panel box is located at the basement in laundry room.

49 Page 49 of B Inspector recommend replacement of smoke detectors now and every 5 years.smoke detectors were chirping low battery warning. (Picture 1) The smoke detector should be tested at common hallway to bedrooms upon moving in to building. The smoke detector needs locating at least 4 inches from ceiling/wall junction and no further than 12 inches away B Item 1(Picture) Smoke detectors were chirping low battery warning B There is no carbon monoxide detector found in building. It is recommended that one be installed according to the manufacturer's instructions. The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

50 Page 50 of 50 INVOICE Focal Point Home Inspection Ltd W. Grace st Chicago Illinois Inspected By: Joseph Poelsterl Inspection Date: 3/12/2013 Report ID: Customer Info: Happy 2453 N. Tripp ave. Chicago Il Inspection Property: Customer's Real Estate Professional: Glen Tomlinson Century 21 United II Inspection Fee: Service Price Amount Sub-Total Payment Method: Payment Status: Note: Tax $0.00 Total Price $0.00

Inspection Report. Mr. Happy 2 flat owner. Property Address: Focal Point Home Inspection Ltd.

Inspection Report. Mr. Happy 2 flat owner. Property Address: Focal Point Home Inspection Ltd. Page 1 of 35 Inspection Report Mr. Happy Property Address: Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 35 Table of Contents Cover Page Table of Contents

More information

Inspection Report Atlanta Strip Mall Commercial Building Property Address:

Inspection Report Atlanta Strip Mall Commercial Building Property Address: Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of

More information

Inspection Report. Mr. Sample Sample. Property Address: 1234 USA Drive Indianapolis IN 12345. 1234 USA Drive. Morris Home Inspection Group, LLC

Inspection Report. Mr. Sample Sample. Property Address: 1234 USA Drive Indianapolis IN 12345. 1234 USA Drive. Morris Home Inspection Group, LLC Inspection Report Mr. Sample Sample Property Address: 1234 USA Drive Indianapolis IN 12345 1234 USA Drive Morris Home Inspection Group, LLC Cedric Morris HI01200039 Fishers, IN 46037 317-550-6281 Table

More information

Inspection Report. Mr. JOHN SMITH. Property Address: 12345 S. Main St Denver Co 12349. A Happy House Home Inspection, LLC

Inspection Report. Mr. JOHN SMITH. Property Address: 12345 S. Main St Denver Co 12349. A Happy House Home Inspection, LLC Inspection Report Mr. JOHN SMITH Property Address: 12345 S. Main St Denver Co 12349 A Happy House Home Inspection, LLC Hans Coleman Centennial, Co 80015 720-988-4830 Table of Contents Cover Page...1 Table

More information

Inspection Report TPCC. Property Address: 22 Touisset Road Warren RI 02885. Lane's Perfection Inspections

Inspection Report TPCC. Property Address: 22 Touisset Road Warren RI 02885. Lane's Perfection Inspections Inspection Report TPCC Property Address: 22 Touisset Road Warren RI 02885 Lane's Perfection Inspections Lane Ukura Ma.# 578 7 St.Louis Avenue Bristol, R.I. 02809 401-255-0726 Table of Contents Cover Page...1

More information

South Carolina Home Inspector Standards of Practice

South Carolina Home Inspector Standards of Practice South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,

More information

Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections

Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections This is a summary of your rights and responsibilities when having a home inspection done by an Oregon certified

More information

Inspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants

Inspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants Page 1 of 53 Inspection Report Jacksonville Property Address: Jacksonville FL 32204 South East Building Consultants Ray Thoroman Inspecting Jacksonville FL and entire South East Page 2 of 53 Table of Contents

More information

STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE:

STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: 61-30.801 Standards of Practice, General. (1) Home inspections performed to these Standards of Practice are intended to provide the client with information

More information

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000 Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,

More information

Inspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections

Inspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections Page 1 of 37 Inspection Report Prepared For: Sampath Sample Property Address: Alpharetta, GA 30004 Atlanta Home Inspections Matthew A Thoroman 6625 Hwy. 53 E. Ste. 410-151 Dawsonville Ga 30534 (678)-410-8062

More information

Home Inspection Report

Home Inspection Report 4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 [email protected] Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:

More information

SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS

SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS.1101 DEFINITIONS The following definitions apply to this Section: (1) Automatic safety controls means devices designed and installed

More information

Inspection Report. Property Address: St. Marks Ave. Brooklyn NY 11213. Five Borough Home Inspection, LLC. Derek Lomer

Inspection Report. Property Address: St. Marks Ave. Brooklyn NY 11213. Five Borough Home Inspection, LLC. Derek Lomer Inspection Report Property Address: St. Marks Ave. Brooklyn NY 11213 Five Borough Home Inspection, LLC Derek Lomer NYS Licence Lic # 16000051234 790 Washington Ave., Unit 112 Brooklyn, NY, 11238 917-494-8474

More information

HOME INSPECTION CHECKLIST

HOME INSPECTION CHECKLIST CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

COMPREHENSIVE PROPERTY INSPECTIONS

COMPREHENSIVE PROPERTY INSPECTIONS COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited

More information

Total Home Inspection Checklist

Total Home Inspection Checklist Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are

More information

Inspecton Report. Property Address:

Inspecton Report. Property Address: Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 [email protected] www.nationalhomeservices.com Property Address: 873

More information

Inspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066

Inspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066 Page 1 of 58 Inspection Report Prepared For: Atlanta Commercial Customer Property Address: Building 5 Marietta, GA 30066 Superior Home Inspections Ray Thoroman 8070 Ivy Shaw Dr. Gainesville,GA 30506 678-410-3005

More information

License Requirements for Persons Engaging in the Business of Inspection Practice:

License Requirements for Persons Engaging in the Business of Inspection Practice: SC Standards of Practice SOUTH CAROLINA RESIDENTIAL BUILDERS COMMISSION HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998 PURPOSE: The purpose of a residential

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

Inspection Report. Condo Association. Property Address: 2222 W. Water St. Swamptown, IL. William Decker, IL Lic. # 450.0002240.

Inspection Report. Condo Association. Property Address: 2222 W. Water St. Swamptown, IL. William Decker, IL Lic. # 450.0002240. Page 1 of 21 Inspection Report Condo Association Property Address: Swamptown, IL Front View William Decker, IL Lic. # 450.0002240 Page 2 of 21 Date: 10/10/2008 Time: 1:00 PM Report ID: Sample 4 Property:

More information

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist

More information

Self-Home Inspection Checklist

Self-Home Inspection Checklist To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional

More information

Inspection Report. Mr. John Homebuyer. Property Address: 123 Main Street Houston TX 77007. Front View. EDP Consulting Engineers, PLLC

Inspection Report. Mr. John Homebuyer. Property Address: 123 Main Street Houston TX 77007. Front View. EDP Consulting Engineers, PLLC Page 1 of 14 Inspection Report Mr. John Homebuyer Property Address: 123 Main Street Houston TX 77007 Front View EDP Consulting Engineers, PLLC Gerald C. Reece, PE TREC #7825 14119 Willowsong Ct Missouri

More information

Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668

Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668 Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:

More information

PROPERTY INSPECTION REPORT

PROPERTY INSPECTION REPORT (850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304

More information

Inspection Report. sample sample. Property Address: 333 Wild Rasberry Lane. Etowah NC. Hubert Lowe Home Inspections

Inspection Report. sample sample. Property Address: 333 Wild Rasberry Lane. Etowah NC. Hubert Lowe Home Inspections Page 1 of 44 Inspection Report Property Address: Etowah NC Hubert Lowe Home Inspections Hubert Lowe North Carolina # 1602 4 Deerwood Cir Oak Island NC 28465 Cell 910-279-4728 Office 910-278-1542 Page 2

More information

HOMEOWNER S PERMIT GUIDE

HOMEOWNER S PERMIT GUIDE HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448

More information

BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER

BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE

More information

HOME INSPECTION REPORT

HOME INSPECTION REPORT Edgewood Home Inspections, Inc. 407 W. Smith Valley Rd. #1032 Greenwood, IN 46142 (317) 833-6048 HOME INSPECTION REPORT Indianapolis IN 46000 Inspector's Name: License Number: Scott Kissel HI00800073 TABLE

More information

Inspection Tech. (330) 310-6559 http://www.inspectiontech.us [email protected] Inspected By: Aaron Westerburg

Inspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech (330) 310-6559 http://www.inspectiontech.us [email protected] Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property

More information

A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111

A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 Inspector Name: Tim Knight, ASHI Member 202490 Inspection No: 12121212 Inspection Date: 1/1/2012 Client: Address: John

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

2. What building projects are exempted? (permit not required)

2. What building projects are exempted? (permit not required) BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and

More information

GENERAL WIRING RULES FOR HOUSES

GENERAL WIRING RULES FOR HOUSES GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat

More information

Orlando Home Inspection Services

Orlando Home Inspection Services PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com

More information

Inspection Report. Sample Client. Property Address: XXXX N. Atolia Drive Tucson AZ 85743. House and Home

Inspection Report. Sample Client. Property Address: XXXX N. Atolia Drive Tucson AZ 85743. House and Home Inspection Report Sample Property Address: XXXX N. Atolia Drive Tucson AZ 85743 House and Home Brian Pemble #45238 6909 E. Kingston Drive Tucson, AZ. 85710. 520-245-7897 Table of Contents Cover Page...1

More information

Does Wall Township require an inspection by the building department on resale of a home?

Does Wall Township require an inspection by the building department on resale of a home? Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,

More information

SWF Home Inspections

SWF Home Inspections Cover Page SWF Home Inspections Property Inspection Report Inspection prepared for: Mr & Mrs Home Buyer Real Estate Agent: My Favorite Agent - Date of Inspection: 7/4/2013 Age of Home: 2004 Size: 1568

More information

Home Inspection Report

Home Inspection Report Report# 21009 Page 1 of 24 Home Inspection Report Property Address: 123 Maple Lane, St. Augustine, FL 32092 Prepared For: Mr. Smith Prepared By: EDGE Inspections www.edgeinspections.com PO Box 601055 Jacksonville,

More information

Propery Inspection Report

Propery Inspection Report Propery Inspection Report Cover Page,, Ok Inspection prepared for: Date of Inspection: 9/28/2014 Time: 8:30 AM Age of Home: 2011 MOL Weather: Clear 62 degrees Inspector: License #130 5400 Hwy 177, Marland,

More information

Inspection Report. Mr. John Doe. Property Address: 123 Somewhere Jacksonville FL 32224. Tabor Hill & Associates LLC

Inspection Report. Mr. John Doe. Property Address: 123 Somewhere Jacksonville FL 32224. Tabor Hill & Associates LLC Inspection Report Mr. John Property Address: 123 Somewhere Jacksonville FL 32224 Tabor Hill & Associates LLC James Cox HI4634 P.O. Box 65699 Orange Park FL 32065 Table of Contents Cover Page...1 Table

More information

Inspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748

Inspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748 Inspection Report provided by: Delaware Property Inspection Inspector: Richard Hiddemen (302)355-1748 ASHI # 243377 DPR #H4-0000018 DDA #06-444 Delaware 1992105842 Wilmington #03857 New Castle #2010-845

More information

Printed Monday, August 27, 2007 Inspected By: Michelle Teague. Client Information: Inspection, Condo City Lane Chicago, IL. Inspected 8/22/07 8:00 AM

Printed Monday, August 27, 2007 Inspected By: Michelle Teague. Client Information: Inspection, Condo City Lane Chicago, IL. Inspected 8/22/07 8:00 AM Pa g e 1 o f 1 5 All About Homes, LLC Michelle M. Teague Owner 312-371-7414 Phone 773-508-6209 Fax www.michelleinspects.com [email protected] 1725 W. Granville Ave. Chicago, IL 60660 Printed

More information

Georgia Home Inspection Services

Georgia Home Inspection Services Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in

More information

BUILDING ANALYSIS REPORT. John Doe 1234 Smith Road Atlanta, Georgia 30396

BUILDING ANALYSIS REPORT. John Doe 1234 Smith Road Atlanta, Georgia 30396 BUILDING ANALYSIS REPORT July 25, 2014 John Doe 1234 Smith Road Atlanta, Georgia 30396 Agent: Ausker and Barbara Morris AT Morris Realty Group, Inc. 3162 Johnson Ferry Road, Suite 260-25 Marietta, Georgia

More information

ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS

ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS 1. INTRODUCTION 1.1 This ASHI Standard of Professional Practice for Home Inspections (Standard) defines the scope of home inspections performed

More information

A Residential Owner s Guide to PERMITS. Elgin CITY OF PLANNING & NEIGHBORHOOD SERVICES

A Residential Owner s Guide to PERMITS. Elgin CITY OF PLANNING & NEIGHBORHOOD SERVICES A Residential Owner s Guide to PERMITS CITY OF Elgin PLANNING & NEIGHBORHOOD SERVICES CITY OF Elgin A Residential Owner s Guide Welcome! This booklet has been prepared to provide residential property owners

More information

Inspection Report. Joe Smith. Property Address: 2222 SW 20 St Miramar FL 33028. Coast to Coast Property Inspections

Inspection Report. Joe Smith. Property Address: 2222 SW 20 St Miramar FL 33028. Coast to Coast Property Inspections Inspection Report Joe Property Address: 2222 SW 20 St Miramar FL 33028 Coast to Coast Property Inspections Edmund Villacis HI8060 2114 N Flamingo Rd. #1277 Pembroke Pines, FL 33028 (954) 435-4443 Table

More information

Accurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois

Accurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois Accurate Home Inspection of Illinois 815-260-1727 1213 Norley st. Joliet, illinois 60435 [email protected] We Inspect to Protect!!! Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave.,

More information

Inspection Report. Sample Report. Property Address: 1234 Anywhere street Phoenix AZ. Veteran Inspection Professionals

Inspection Report. Sample Report. Property Address: 1234 Anywhere street Phoenix AZ. Veteran Inspection Professionals Inspection Report Property Address: 1234 Anywhere street Phoenix AZ Veteran Inspection Professionals Mark Mandery 040901 4725 W. Aire Libre Ave Glendale AZ, 85306 480-694-2111 Table of Contents Cover Page...1

More information

Building Permits: When are they required?

Building Permits: When are they required? Building Permits: When are they required? Generally, you need to obtain a building permit from the City whenever you construct, enlarge, alter, repair, move, remove, improve, convert, or demolish a building

More information

I NI NP R Inspected Items

I NI NP R Inspected Items 6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and

More information

RRIO Checklist. Use of checklist: Definitions: Limitations

RRIO Checklist. Use of checklist: Definitions: Limitations CITY OF SEATTLE RENTAL REGISTRATION AND INSPECTION ORDINANCE (RRIO) RRIO Checklist Use of checklist: Property owners will use the RRIO Checklist to confirm that their rental housing properties and units

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]

More information

A comfortable house is a great source of happiness. - Sydney Smith. Home Maintenance Guide

A comfortable house is a great source of happiness. - Sydney Smith. Home Maintenance Guide A comfortable house is a great source of happiness. - Sydney Smith Home Maintenance Guide HOME GUIDE By conducting regular maintenance checks, you can prevent small inexpensive repairs from becoming more

More information

Inspection Report. Joe Smith Report. Property Address: 111 Main Street St Augustine FL 32080. Eagle Eye Home Inspections

Inspection Report. Joe Smith Report. Property Address: 111 Main Street St Augustine FL 32080. Eagle Eye Home Inspections Inspection Report Joe Report Property Address: 111 Main Street St Augustine FL 32080 Eagle Eye Home Inspections Rick Glodowski HI 4677 5255 Atlantic View St Augustine, FL 32080 904-461-2550 111 Main Street

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

Vari Inspection Services

Vari Inspection Services Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54

More information

Inspection Report. Prepared Exclusively For:Joe Sample. Property Address: 552 Brindway. Raleigh NC

Inspection Report. Prepared Exclusively For:Joe Sample. Property Address: 552 Brindway. Raleigh NC Page 1 of 22 Inspection Report Prepared Exclusively For:Joe Property Address: Raleigh NC By: Steve Smallman, N.C. Home Inspector License #3 2611 Sherborne Place Raleigh N.C. 27612 919-669-3639 Page 2 of

More information

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 [email protected] INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction

More information

PROPERTY INSPECTION REPORT Property Address:

PROPERTY INSPECTION REPORT Property Address: Scott Certified Member P. O. Box 9007 Indianapolis, IN 690-007 (7)-750-60 Fax: 7-876-8 PROPERTY INSPECTION REPORT Property Address: Prepared for: Inspection Inspector: Lou Buehler Inspection #: BUYERS

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792

More information

The City of Basehor, Kansas

The City of Basehor, Kansas The City of Basehor, Kansas Residential and Miscellaneous Permits This list provides general information regarding permit requirements for various residential construction and maintenance activities. The

More information

PROPERTY INSPECTION REPORT

PROPERTY INSPECTION REPORT Burns Home Inspections, LLC 14232 Marsh Lane #262 Addison, Texas 75001 Tel. 972-241-6033 cell 469-644-9429 fax 972-406-9809 E-Mail [email protected] PROPERTY INSPECTION REPORT Prepared For: Mr. John

More information

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector

More information

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live! U.S. Department of Housing and Urban Development Office of Public and Indian Housing A Good Place to Live! Introduction Having a good place to live is important. Through your Public Housing Agency (or

More information

EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST

EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST DATE TIME EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST INSPECTOR: LICENSE # ADDRESS: PROPERTY OWNER: SINGLE: DOUBLE: MULTI-UNIT # OF UNITS POINT OF INSPECTION Sanitation IPMC 302.1

More information

Estimating Database Checklist

Estimating Database Checklist Estimating Database Checklist If you are creating a new estimating database for projects, the following list offers a thorough listing of Main and Sub Categories. You can also use it as a checklist to

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

CHRIS CURLES and ASSOCIATES INSPECTION SERVICES

CHRIS CURLES and ASSOCIATES INSPECTION SERVICES CHRIS CURLES and ASSOCIATES INSPECTION SERVICES Inc. Chris Curles, President www.homeinspectionsatlanta.com [email protected] Office: 770-493-0227 Professional Member Of: GAHI # 93006 ASHI # 211725

More information

Code Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division

Code Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division Code Enforcement Inspection Manual City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division LIVING ROOM 304.15 EXTERIOR DOOR(S) Check door(s) and trim for condition,

More information

Rehab Inspection Report Page 1

Rehab Inspection Report Page 1 Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation

More information

Home Maintenance Checklist

Home Maintenance Checklist Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your

More information

Simplify. Homeownership

Simplify. Homeownership Simplify Homeownership Home Pulse An Innovative Program To Maintain Your Home. The Home Pulse Preventive Maintenance Plan will keep your home looking great, dramatically slow the deterioration process

More information

Arizona Health Care Association DISASTER PLANNING AND EMERGENCY MANAGEMENT GUIDE POST INCIDENT DAMAGE ASSESSMENT CHECKLIST

Arizona Health Care Association DISASTER PLANNING AND EMERGENCY MANAGEMENT GUIDE POST INCIDENT DAMAGE ASSESSMENT CHECKLIST It is essential to perform a Basic Damage Assessment (BDA) following an adverse event to help ensure the safety of building occupants as well as prevent additional losses from occurring. This checklist

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA

More information

healthy homes assessment

healthy homes assessment healthy homes assessment Date of Inspection: Inspector s Name: Agency: Address of Property: Resident s Name: Phone Number: Primary Reason for Visit: Asthma Lead Poisoning Voluntary Referral Other: GENERAL

More information

159 Morningside Avenue, Toronto

159 Morningside Avenue, Toronto 159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in

More information