Strategic Decision Making For Zero Energy Buildings in Jordan
|
|
|
- Ursula Shelton
- 10 years ago
- Views:
Transcription
1 Strategic Decision Making For Zero Energy Buildings in Jordan Shady Attia, PhD, LEED AP ASHRAE Member Samer Zawaydeh, ABSTRACT This paper presents the results of combined economic and computational study of different integrated passive and active design strategies for the Jordanian residential building sector. A representative house prototype, located in Amman is selected as a case study for the zero energy design and performance objective. The aim of the study is to investigate the potential of achieving thermal comfort and delivering thermal and electrical energy demands for existing buildings on site for different Jordanian Cities. Jordan has a semi-arid climate with an annual total irradiation above 2000 bankable kwh/m 2 per year with approximately 2000 hours of full sunshine. Therefore, different passive and active design strategies are discussed and compared to reach an annual net zero energy demand for the existing building stock. In order to achieve zero energy buildings certain strategies are examined. For example, internal loads reduction, envelope insulation in addition to the installation of solar water heater and photovoltaic. Based on a month-by month demand analysis, internal loads and envelope performance are analyzed in order to explore the existing economical potential. Simulation software DesignBuilder is used to examine the strategies proposed to achieve annual net zero energy performance for a prototype. The final result of this study compares the potential and constraints of each strategy and assesses them based on economical feasibility. For the considered location and weather conditions the prototype can provide thermal comfort for occupants and meets the zero energy objectives. The research also proofs that some strategies are cost effective rewarding with a payback period ranging from 3 to 9 years. INTRODUCTION Solar energy is one of the most abundant renewable resources in Jordan. The average annual total irradiation is between bankable kwh/m 2 per annum with approximately 2330 hours of full sunshine (Etier et al 2010). However, this resource is generally not yet exploited in the building sector at any scale. On the other hand, due to the heavy dependence on fossil fuel exports and the exponential population growth, Jordan completed the first stage of a tender for its nuclear energy program and intends to have at least one reactor connected to the grid by 2020 (JAEC 2013). As a response to the previously mentioned contradicting facts it is of the utmost urgency that the existing building stock gets retrofitted to achieve an annual net zero energy performance (Biggs, 2005 and Green Peace 2013). There is potential for bioclimatic design in all climatic regions of Jordan (Johansson and Ouahrani, D. 2009). Similar to neighboring countries and with the assistance of active solar systems the building stock can easily achieve the zero energy objectives due to match between electric/thermal solar energy supply and cooling dominant demand (Attia 2010). For that reason, the research set a zero energy retrofit objective. The zero energy objectives will expand the architect s bank of ideas, broaden the range of choices and allows assessing their sensitivity. Thus to put the Net Zero Energy Building (NZEB) Concept in the regional context and better adapt it to the local traditional architectural practice, the remit of this paper is to assess existing rating systems for the development and measurement of sustainable buildings in the Jordan (Attia 2012a). Needless to say, any Shady Attia, PhD and LEED AP, is a researcher and lecturer at the Interdisciplinary Laboratory of Performance-Integrated Design (LIPID) School of Architecture, Civil and Environmental Engineering, École Polytechnique Féderale de Lausanne (EPFL), Lausanne, Switzerland.
2 design decision will require energy performance verification. Therefore in this research, different passive and active design strategies are compared, with the aid of simulation tools based on performance. Moreover, an economic analysis is presented. METHODOLOGY In order to eliminate the need for non-renewable sources, energy and renewable energy measures were analyzed in five different climates of Jordan. The tasks performed for this study included: selection of five locations; simulation of the baseline apartment; analysis of on-site availability of renewable energy, minimization of building energy use with passive design and energy efficiency measures, and the sizing of systems for the collection and storage of renewable energy to meet the reduced building needs. Building energy use analysis was performed using the ZEBO program (Attia et al. 2012b). Analyses of solar thermal and PV systems were performed using EnergyPlus program. TMY2 weather data were used for analyzing the building energy use and sizing the solar systems, respectively (Remund 2008). The research started with determining the annual average of kwh usage, to determine the user s seasonal electric consumption patterns and spikes. By this, the research acquires a starting point for comparing the energy output of various systems. Then, passive and active design strategies will be implemented in order to achieve a zero energy performance without compromising human comfort. The passive and active design strategies include the installation of thermal insulation, shading devices, energyefficient lighting systems and appliances, double glazing, flat plate collectors and photovoltaic panels. Finally, the paper investigates the potential and constraints of each strategy then assess them based on the economical feasibility of each of them. Location Selection Jordan can be divided into three climatic regions as indicated in Jordan Thermal Insulation Code, Appendix (B) (JNBC 2009): (Zone 1) the Rift Valley in the west, (Zone 2) the highlands in the center and the (Zone 3) desert in the east, see Fig.1a. The agricultural Rift Valley runs along the entire western length of Jordan at an altitude of below 600 m. It includes the Jordan Valley, the Dead Sea, Wadi Araba and in the south, Aqaba. The central highlands comprise of mountainous and hilly regions that run through Jordan from north to south, with varying altitudes of 600 to 1600 m. This is the most densely populated region, including the capital city Amman, and other major cities such as Irbid, Ajloun Zarqa, Karak, Ma an and Petra. The climate of this region is characterized by hot summers and fairly cold winters. The average temperature in Amman ranges from 8.1 C in January to 25.1 C in July. The semi-arid desert region in east comprise of nearly two-thirds of the area of Jordan. The climate varies dramatically between day and night as well as between the summer and winter seasons. Summers are hot, dry and windy where temperatures can exceed 40 C, while winter nights can be bitterly cold, dry and windy. This distinct variation in climate within Jordan advocates for different approaches for energy efficient building. In the highlands the heating season is dominant whereas in the Rift Valley and the desert regions the cooling season is dominant. Basecase Selection The simulations were performed using TMY2 weather data for major cities in each of the 3 climate zones. Based on these results, five locations with distinct climatic characteristics were selected, which fall under three different climate zones classified by the Jordanian Thermal Insulation Code (JNBC 2009). These include: Amman, AM (moderate cold), Ajloun, AJ (moderate cold), Al Shouna Al Janubiyah, GH (hot humid), Aqaba, AQ (hot-humid) and Al Ruwaished, RU (hot-dry). Table 1 lists the base-case building characteristics, including climate-specific characteristics for the selected five locations. To select locations with distinct base-case energy use characteristics, a compliant single-family, semi-detached apartment was run in 5 climate zones. The size of the apartment, construction type, HVAC and DHW system types were determined from the housing survey data by the Public Action Project and Jordan Green Building Council (JNBC 2012). The Public Action Project (PAP), a public education and behavior change project funded by the US Agency for International Development to support its technical and policy investments in the Water, Energy and Environment sectors in Jordan (USAID/Jordan, 2013). The characteristics of the building envelope, efficiency of the HVAC and DHW systems, and
3 internal loads were chosen for PAP reports, and the usage profiles were adopted from Zawaydeh and Jaber (2013). Table 1: Basecase building characteristics Climate-specific characteristics City Aqaba, AQ Al Shouna, SH Amman, AM Ajloun, AJ Al-Ruwaished, AR Latitude and Longitude Altitude ASHRAE Zone 3 2b General Characteristics Building configuration: 130 m 2, three bedroom, rectangle-shape, one-story, single family Construction type: Reinforced-concrete post and beam structure with brick infill walls Exterior walls: Stone Cladding, Concrete wall, no Insulation, Brick, Mortar Roof: Flat roof: tiles, cement mortar, water proofing layer, 5 cm extruded polystyrene, sand, reinforced concrete Windows: Window area: 25% of conditioned floor area, distributed equally on all three sides; Clear Single Pane in aluminium frame, operable window without exterior shading Shading: Venetian Blinds Close if Indoor Temp is above comfort HVAC systems: LPG Heater with a 85% efficiency + Heat pumps without ducts and without ventilation system DHW system: 80-litre electric water heater, 0.86 energy factor Thermostat set point: 20 C (68 F) for heating, 25.5 C (78 F) for cooling, 5 F set back and set up in winter and summer, respectively Natural Ventilation Windows and Doors are manually OPENED if cooling is needed Fan Forced Ventilation No Fans for Comfort Cooling CASE STUDY ENERGY ANALYSIS For the three major climate regions, passive and energy-efficiency measures for the building envelope, lighting, appliances, and systems were applied to minimize the basecase energy use. While considering these measures, certain performance objectives were defined to ensure maintaining comfort conditions, and to conform to the life style of an average Jordanian family (5 person/apartment). In the case when renewable sources were used, their use was specified not to interfere with the normal operation and usage of the residence. For the Zero Energy apartment, the basecase space heating, cooling and DHW systems would be replaced by a solar thermal system and the basecase space cooling and plug load systems would be replaced by a solar electric system. Therefore, the objective of this analysis was to determine inputs required for simulating equivalent space heating, cooling and DHW loads in EnergyPlus simulation program. Basecase The apartment is a typical unit that is found in most Jordanian residential building blocks. The floor layout is rectangular with a total area of 130 m 2 with a net conditioned area of 80 m 2, representing four rooms per apartment. The basic building construction is a reinforced-concrete post and beam structure. Windows are single glazed and transparent. The total amount of glass in the North, East and South facades is estimated to be between 20% and 30% of the total wall area. There is no solar protection for the facades and most wooden windows are tight. A multi-thermal-zone configuration was used in conducting energy simulations. To address the different orientation of the surveyed apartments, the basecase model performance was generated by simulating the building with its actual orientation and again after rotating the entire building 90, 180, and 270 degrees, then averaging the results. Table 1, lists the general description of the sample building and some properties for the construction material used. Energy Demand Analysis To obtain inputs for space heating, cooling loads DHW, plug loads and lighting loads, one set of simulations analyzing the impact of energy-efficiency measures were performed. Figure 2 shows the energy use of the base-case house in 5 locations. Strategy 1: Reduce Heat Losses: Envelope Insulation: The first step that can reduce heat gain significantly is to conform to the 2009 Jordanian Thermal Insulation Code design as shown in Figure 1b (JNBC 2009). The strategy suggests building new external walls, 250mm wide, from silt-brick working as a second-skin façade over the original. Also a 60mm extruded polystyrene insulation is recommended to increase the wall resistance up to U-0.57 W/m 2 K (Jordanian Code). For the roof, an 80mm
4 extruded polystyrene insulation will increase the resistance up to U-0.55 W/m2 K (Jordanian Code). This includes avoiding thermal bridges and bridging the insulation layers. Also the envelope air infiltration is reduced. Figure 1a Jordan three climatic regions, Figure 1b Jordanian Thermal Insulation Code Requirements (JNBC 2009) and Jordan Energy Saving Buildings Code (JNBC 2010) Strategy 2: Reduce Heat Gains Shading and Windows: To avoid the solar gains in the apartment and consequently reduce the cooling loads, openings require improved glass surfaces and shading devices. Overhang shading devices should admit low angle sun in the morning or winter when passive heating is needed, screen the sun in the middle of the day and in summer when overheating is a risk. The first step is to replace all single pane windows with U-2.3 W/m 2 K (Jordanian Code) double-pane windows (low-e) with a 12mm air space. Second, is to add venetian blinds or rolling shutters and shading devices (overhangs and fins) to the south, east and west façade. The overhang will be cantilevered for 1 meter, to protect the living room from the sun between May and September. Moreover, to achieve low emissivity of the envelope, the insulation is covered with a radiant barrier aluminum foil (ε=0.04). The total emissivity of the envelope is 0.8 and the absorption coefficient is 0.2. Strategy 3: Reduce Internal Loads Lighting and Appliances: All artificial lighting sources are going to be replaced with high efficient energy lamps (CFL and LED) and Energy Star appliances. The interior lighting power density was reduced respectively to 8, 6, 12 and 10 W/m 2 for the Living Room, Bed Room, Kitchen and toilet. Strategy 4: Passive Cooling: During spring and autumn, passive cooling can be provided through natural ventilation. The building should be prepared to allow air to flow through the building at day and night and when outside temperature is lower than inside the building. The apartment design was revised to make sure that openings and doors with built-in vents will allow cross air ventilation. Strategy 5: HVAC System: Based on the study of the KAP Household-baseline survey (USAID/MRO 2010) most residential buildings do not have a central heating or ventilation system. Most homes have a LPG gas (68%) or Kerosene (54%) heater for space heating. A very few percentage uses electric heaters (13%) or boilers coupled to radiators (7%). In regions where cooling is needed most homes install a window type or split air conditioner. However, for this study we suggested two different central HVAC systems. For Zone 1 and 3, electric heats pump for heating and cooling and for Zone 2, a gas boiler with radiators and electric heat pump. Strategy 6: Solar Thermal System (STS): A market survey suggested using the Flat Plate Collector for DHW due to economic reasons. The penetration of solar water heater in the Jordanian residential sector is around 11.1% (USAID/Jordan 2011). According to the field assessment of domestic solar water heaters done by the PAP project 51% of
5 homes use diesel boilers for water heating as a back up to the solar water-heating system, 34% use electrical heaters and 15% use LPG boiler. The Flat Plate Collector has an annual solar fraction of 93% (±5 %) and the daily consumption is 200 liter/day with an average temperature of 50 o C. The expected energy produced by this system is equivalent to 3000 kwh/yr. The 5m 2 unit will be installed on the roof and coupled to a 200 liter tank and inclined to the south with a tilt angle of 45 o from the horizontal (Amman). Besides, the existing electric water heater would be kept as an instantaneous back up water heater. Strategy 7: Solar Electric System: The electricity consumption analysis shows that the apartment consumes approximately 5 MWh/yr. After implementing the previous mentioned strategies to the model, EnergyPlus simulation estimated a reduction of 3.57 MWh/yr (see Figure 2). This step was fundamental prior to sizing the PV panels where the annual daily average solar irradiance ranges between 5-7 kwh/m 2. Now, the apartment needs approximately 3 MWh/yr. After consulting several companies in Jordan, most of them agreed that 15 m 2 of PV panels will yield approximately 3 MWh annually. The apartment is considered as grid-connected with a 1.5 kwp system. In fact, the available modules in the Jordanian market are assembled from polycrystalline cells (module efficiency 14.5%) and can be mounted on the flat roof with 31 o inclination. RESULTS Energy Performance First, the basecase was modeled. Several iterations took place to match the predicted electric consumption with billed consumption. The calibration work involved comparing the baseline to similar cases found in literature (Mohsen & Akash 2001, Hans et al. 2010, AlZyood et al. 2010, Khasawneh 2011, Abdalla and Tawalbeh 2012, Qasaimeh 2012 and Bhar 2012).According to the Electric Regulatory Commission Annual Report the average Jordanian household consumer bill (only electricty) is 3573 kwh/year (ERC 2011). Secondly, each strategy was separately integrated in the model and compared to the basecase to determine the energy savings that would be achieved. Table 2 lists the basecase and code compliance characteristics in addition to measures for achieving maximum energy efficiency (NZEB). For the code compliance these include mainly: a well-insulated, air-tight building envelope; high performance windows, infiltration control, air tightness and installation of SHW system. For the NZEB retrofit the measures included shading, energy efficient lighting, appliances and high-efficiency HVAC system; as well as roof mounted PV panels. The impact of combined application of these measures on the heating energy use and cooling energy use is shown in Figure 2. Figure 2 shows the results of energy-efficiency and renewable energy analysis, using the methods described in the previous section. Table 2: Basecase, code compliance and maximum energy efficiency characteristics Properties Basecase characteristics Measures for Code Compliance Measures for maximum efficiency NZEB 1 Roof U-value: U=1 W/m 2.K U=0.55 W/m 2.K U=0.1 W/m 2.K with radiant barrier 2 Wall R-value: U=2 W/m 2.K (no radiant barrier) U=0.57 W/m 2.K (no radiant barrier) U=0.2 W/m 2.K with radiant barrier 3 Window system: U=5.8 W/m 2.K), SHGC:- Single Pane in aluminium frame U=3.1 W/m 2.K), SHGC:0.75 Double Pane Low-E aluminium frame U-value: 0.5, SHGC: 0.25, Double Pane Low- E, Argon, Fiberglass frame 4 Operable Shading: operable window without exterior shading operable window without exterior shading Venetian Blinds Close if Sun on Window & Indoor Temp above comfort 5 Overhang: none none 1m overhang and fins (E,W, S) 6 Night insulation: not considered not considered 50% reduction in glass conductance, Insulated roller shutter 7 Infiltration: 0.7 ACH 0.5 ACH 0.35 ACH 8 Internal heat gain*: 0.19 kw from lighting, 0.71 kw from appliances 0.14 kw from lighting, 0.67 kw from appliances 0.05 kw from lighting, 0.50 kw from appliances 9 Natural Ventilation Windows and Doors are manually OPENED if cooling is needed Windows and Doors are manually OPENED if cooling is needed Windows and Doors are manually OPENED if cooling is needed 10 Fan Forced Ventilation no Fans for Comfort Cooling No Fans for Comfort Cooling Fans for Comfort Cooling 11 Thermostat set point: 20 C (68 F) for heating, 25.5 C (78 F) for cooling (RH=60%) 20 C (68 F) for heating, 25.5 C (78 F) for cooling (RH=60%) 20 C (68 F) for heating, 25.5 C (78 F) for cooling (RH=60%) 12 Heating system: Gas Furnace: AFUE 65% Gas Furnace: AFUE 65% Gas Furnace AFUE: 90% 13 Cooling system: Split System: Heat Pump EER 13/7.7 Split System: Heat Pump EER 13/7.7 Split System: Heat Pump EER 19/8.5 (Energy Star) 14 Ventilation system: none none Mechanical Ventilation with heat recovery:
6 85%, fresh air 7.5 cfm/person 15 DHW system: none 200 litre electric water heater, 0.86 energy factor 200 litre electric water heater, 0.86 energy factor 16 PV system: none none 15m 2 mono-crystalline., 14%, Nominal peak 1.5 kwp, l yield: 3000 KWh/year *Constant internal gains were obtained from annual equipment and lighting energy use, using conventional vs. energy-efficient appliances, 0.8 W/m 2 (incandescent) vs W/ m 2 (CFL) Installed lighting wattage and identical usage profiles for the base-case and maximum efficiency option. Figure 2 Basecase energy, code compliance energy and maximum efficiency energy use for 5 locations The simulation results illustrated in Figure 2 are in line with the climatic classification for the three zones of Jordan. Homes in Zone 1 (Aqaba and Al Shouna al-janubiyah) are cooling dominated, homes in Zone 2 (Amman and Ajloun) are heating dominated and homes in Zone 3 (Al-Ruwaished) are mixed, cooling and heating, dominated. Figure 2 shows the annual space heating and cooling energy use are reduced by incremental application of passive and energy-efficiency measures for the building envelope, lighting and appliances, annual DHW and systems energy use. Overall complying with the Jordanian Thermal Insulation Code Requirements (JNBC 2009) could reduce the energy use up to 40% (equivalent to 32 kwh/m 2 /year). The figure shows that in the Jordanian climate up to 66% energy use could be reduced for the NZEB objective (equivalent to 18 kwh/m 2 /year), by combining the entire passive and energy-efficiency measures analyzed in the three zones. Measures for heat losses reduction including efficient envelope and air-tightness contributed the highest energy use reduction in heating dominated locations. In Zone 2, up to 40% space heating energy use could be reduced by using measures for maximizing winter-time solar gains and minimizing heat losses. Measures for heat gains reduction including radiant barriers, shading, heat dissipation (artificial and natural ventilation) contributed the highest energy use reduction in cooling dominated locations. The reduction in fossil based DHW use resulted in an equivalent SHW energy savings (5.5 kwh/m 2 /year). Surprisingly in Zone 2 and 3, the building envelope measures that resulted in large heating energy savings increased the cooling energy use and exceeded the heating energy use. The zero energy objective reduced the need for heating energy in the five locations and increased the cooling requirement. Since solar energy is a potential source in Jordan and cooling loads are dominant in the five zero energy buildings scenarios, PV panels were simulated. For that scenario, PV panels energy will feed the heat-pump for space cooling and heating, using a split system, while using the electricity grid as a buffer/storage. This objective, a 15 square meter PV panel array installed at 31 tilt from horizontal and oriented the south was considered. Economic Feasibility The aim of the economic analysis is to compare the cost-effectiveness of the energy-savings or generation for each design strategy. The analysis was performed using economic analysis method described in ASHRAE (2009) and by Haberl
7 (1993). The cost analysis is based on the utility rate in Jordan for the year There are many inputs for the economical feasibility analysis (see Table 3) that was verified through previous studies (USAID/Jordan 2011 and Hans et al. 2010). In Jordan, he effective tax rate is 14% and the utility inflation rate is assumed as 8%. Starting with the envelope, the cost for code compliance and zero energy retrofit is 3500$ and 8000$ respectively. The retrofit included the new wall construction, insulation, shading devices and new windows. For the code compliance retrofit the SHW system is the most cost effective measure (payback=3-4 years) followed by the envelope insulation and tightness (payback=9 years). From an economic point of view installing a SHW system is economically rewarding. The system is manufactured in Jordan and can be easily installed and maintained. On the other side, the NZEB retrofit strategy is too ambitious. According to Table 3 the total payback time will be long. The payback including the property value appreciation is 44 years. Thus the PV panels investment cost is very high. However, upgrading the envelope and HVAC system (payback=5 years) might be an interesting objective for the coming years in Jordan because they it will allow reducing the consumption to meet almost the Passive House Standard requirements of 15 kw/m 2 /year (Feist 2007). Table 3: Results of cost analysis and payback time Electric Rates in Tiers (2013) T1=0.05 $, T2=0.1 $, T3=0.12 $, T4=0.15 $, T5=0.19 $ Fuel Rates 2 Propane, $/therm Baseline, $/therm Above Baseline, Propane: 3$/Gallon, Heating Oil: 2.9$/Gallon Cost (Code Payback (Code Cost (Maximum Payback (Maximum Efficiency) Compliance) Compliance ) Efficiency) Envelope 3500 $ 9 years $ 18 years HVAC $ 10 years Flat Solar Water Heater (5m 2 ) 900 $ 3 years 900 $ 3 years PV panels (15m 2 ) = 3000 KWh $ 12 years Average Annual Energy Consumption/ Total Payback 32 kw/m 2 /year 9 years 18 kw/m 2 /year 44 years CONCLUSION This study investigated passive and active design strategies for an existing apartment in order to reach a code complaint and zero energy retrofit. In this way the study is deliberately forward looking, evaluating and assessing the energy potential and economic feasibility providing an examination and vision for designs that may soon be implemented. On the energy level, the code compliance could reduce the energy use up to 40% (equivalent to 32 kwh/m 2 /year) and the NZEB retrofit could reduce energy use up to 66% (equivalent to 18 kwh/m 2 /year), by combining the entire passive and energyefficiency measures analyzed in the three zones. One of the most significant results of the study is that the bioclimatic site potential can sustain zero energy developments. The intensity of solar irradiation is indeed present year round and is strong enough for this purpose. The study present conclusive results following a methodological validated simulation approach and demonstrate that a, which considers passive design, efficiency and use of renewable sources, can deliver a zero energy residence in the Jordanian climate for the existing typical building stock. For Amman, AM, passive and energy-efficiency measures reduced the heating energy use by 60%. On the economical level, the code compliance strategies are economically feasible. The Solar Flat Collector for DHW has a payback period from 3-4 years payback period, which goes in line with literature findings and the PAP project (USAID/Jordan 2011 and 2013). However, the NZEB objective is too ambitious with 30 year payback time. There are two main reasons behind that. The first, electricity prices are still low because the Jordanian government does not tax the energy for small consumers. The second, the lack of incentives for PV panels installation. Nevertheless, in the PV panels future cost can change rapidly. Also, cost can vary significantly if the Jordanian institutions adapt policies for urban solar electric systems. However, the study remains theoretical with certain limitations. Selecting an existing residential typology did not allow other passive measures such as the urban setting, orientation, form and window to wall ratio. Also the study did not explore the potential of thermal mass and two other important systems. The geothermal heat pumps for space heating and cooling and evacuated tubes option for space heating and DHW. Finally, the research highlighted the energy and economic potential for different design strategies for an existing individual residential apartment. Until now, the barriers are mainly economical in Jordan. The economic success of code compliance measures is proofed. Future research might consider moving from the 32 kwh/m 2 /year performance range to
8 the Passive House Standard performance range (15 kwh/m 2 /year) exploring more cost effective design measures. District scale retrofits and up scaling renovation intervention might reduce the investment cost and payback time. Any strategic future vision should take into consideration the future increase of cooling demand in the Jordanian residential sector. The effect of heat island effect and climate change will have an impact too. The study highlights the importance of meeting the increasing electric demand due to ventilation and cooling through solar electric systems. This will require regulating the urban built environment and addressing issues such as urban solar rights and urban solar access. ACKNOWLEDGEMENTS The authors expresses his appreciation and thanks to Hala Jaber. REFERENCES Abdalla, N., Tawalbeh, M Validated TRNSYS Model for Solar Assisted Space Heating System, Proceedings of the International Conference on Solar energy for MENA region INCOSOL, Amman, Jordan, AlZyood, M., Harahsheh, H., Hammad, M Thermal economical analysis of renewable energy buildings: towards low energy house in Jordan, International Renewable Energy Congress November 5-7, 2010 Sousse, Tunisia. Awadallah, T., Adas, H., Obaidat, T., Jarrar, I Energy efficiency building code for Jordan, GCREEDER, Amman. ASHRAE, ASHRAE Handbook HVAC Applications. Atlanta, GA: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. Attia, S Active solar retrofit of a residential house, a case study in Egypt, ASES, Buffalo, USA. Attia, S. 2012a. A Tool for Design Decision Making-Zero Energy Residential Buildings in Hot Humid Climates,PhD Thesis, UCL, Diffusion universitaire CIACO, Louvain La Neuve, ISBN Attia, S., Gratia, E., De Herde, A, Hensen, J. 2012b. Simulation-based decision support tool for early stages of zero-energy building design, Energy and Building, Vol. 49, June 2012, Pages 2-15, ISSN , /j.enbuild Bhar, R Energy Efficiency in the Construction Sector in the Mediterranean, Energy Efficient Building Project Dead Sea Development Zone Project, MED-ENEC, Jordan. Biggs, C Building What? The Challenge of Introducing Alternative Building Practices into the Aqaba Built Environment. Lund University, Int. Institute for Industrial Env. Economics - IIIEE, Sweden: Lund University. ERC, Electricity Regulatory Commission, The Hashemite Kingdom of Jordan, Annual Report Etier, I., Al Tarabsheha, A., & Ababneh, M Analysis of solar radiation in Jordan. JJMIE, 4(6). Feist, W Certification as" Quality Approved Passive House" Criteria for Residential-Use. Passive Haus Institut. Green Peace, Jordan s Future Energy, retrieved July 2013: Haberl, J Economic Calculations for ASHRAE Handbook. EST-TR College Station, TX: Energy Systems Laboratory, Texas A&M University. Hans, R., Tareq, E., & Florentine, V Building Green in Jordan? Performance Evaluation of the Aqaba Residential Energy Efficiency Pilot Project (AREE). 2nd Int. Conference on Sustainable Architecture and Urban Development. JAEC, Jordan Atomic Energy Commission, retrieved July 2013: JNBC, Thermal Insulation Code, Jordanian National Building Council, 2nd edition, Amman, Jordan. JNBC, Energy Saving Buildings Code, Jordanian National Building Council, 1st edition, 2010, Amman, Jordan. Johansson, E., & Ouahrani, D. (2009). Climate conscious architecture and urban design in Jordan: towards energy efficient buildings and improved urban microclimate. Housing Development & Management, Lund University. Khasawneh, J AREE - Aqaba Residence Energy Efficiency: The Complete Experience, The Center for the Study of the Built Environment (CSBE), Amman, Jordan. Qasaimeh, A Solar Energy Optimization through Seasons: Case Study in Jordan, Smart Grid & Renewable Energy, 3, Mohsen, M., Akash, B Some prospects of energy savings in buildings. Energy conversion & management, 42(11), Remund, J Quality of Meteonorm Version 7.0. Europe, 6(1.3), 1-1. USAID/MRO, Final KAP Household-baseline survey, PAP for Water, Energy and Environment project, Report 2.
9 USAID/Jordan, Field Assessment of Domestic Solar Water Heaters, Public Action Project for Water, Energy and Environment project, Report 22. USAID/Jordan GBC, Situational analysis for home owners, Building a smart program for saving water & energy through design and construction, Public Action Project, Report 22, retrieved July 2013: USAID/Jordan Energy field assessment of Desert Camp sites in Wadi Rum, Public Action Project, Report 18. USAID/Jordan, Public Action Project for Water, Energy and Environment project. Zawaydeh, S., Jaber, H., PAP Modeling Information Sheets, Public Action Project USAID, at the Jordan GBC.
3.2 Bioclimatic Site Conditions
ZERO ENERGY RETROFIT: CASE STUDY OF A CHALET IN AIN-SUKHNA, EGYPT Shady Attia Architecture et Climat, Université Catholique de Louvain, 1348- Louvain La Neuve, Belgium [email protected] ABSTRACT
Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi
Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction
Passive house rehabilitation of post war residential building in Zug, Switzerland
Passive house rehabilitation of post war residential building in, Switzerland Owner: Erbengemeinschaft Ducret Architect: Miloni & Partner, Wettingen Energy concept designer: Zurfluh & Lottenbach, Luzern
Energy Efficiency in Buildings
Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:
Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls
PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,
Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality
Delivering on innovation and market uptake. Best-in-cases of nzeb. Ramon Pascual Bucharest May 8th, 2015
www.zebra2020.eu Delivering on innovation and market uptake. Best-in-cases of nzeb Ramon Pascual Bucharest May 8th, 2015 Outline nzeb Database Best in cases of nzeb Climates in Europe Preliminary results
Directorate for the Built Environment Building Standards Division
Directorate for the Built Environment Building Standards Division Energy Management Solutions Ltd Investigation of measures to improve the energy performance of a existing building: Retail JUNE 2009 Report
Klosterenga, Oslo, Norway, 1998-2000 page - 1
Klosterenga, Oslo, Norway, 1998-2000 page - 1 Introduction Klosterenga is an urban revitalisation project close to the city centre of Oslo. The 3 apartments were built with a focus on energy saving. Next
3-D Modeller Rendered Visualisations
Recognised energy Dynamic Simulation Modelling (DSM) software DesignBuilder is a user interface to the EnergyPlus DSM. EnergyPlus builds on the most popular features and capabilities of BLAST and DOE-2
Solar Energy Utilisation in Buildings
Solar Energy Utilisation in Buildings P. Karava, PhD Assistant professor Department of Civil and Environmental Engineering University of Western Ontario 2 Modern Buildings Change in architectural style
Integrated Solar Radiant Systems
Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant
BPC Green Builders. Green building for new and existing homes. Health Comfort Energy
BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Existing Housing Stock
1 How Old and New Houses Use Energy Total Consumption per Household, 2001 120 100 2: RENOVATION - CONCORD, MA million per household 80 60 40 20 Space Heating Electric Air Conditioning Water Heating Refrigerators
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro Dept. Building Environment Science &Technologies Politecnico di Milano Italy Research funded
Exemplary Retrofitting of an Old School in Stuttgart - EROS -
Exemplary Retrofitting of an Old School in Stuttgart - EROS - City of Stuttgart, Summary The objective of the project was to demonstrate the potentials of a retrofitting process for a typical school in
Sustainable Design and Energy-Efficient Building Techniques for Existing Housing
Sustainable Design and Energy-Efficient Building Techniques for Existing Housing PATH Energy Retrofit Project Henderson, Nevada NREL Research Site, Lebanon NJ Energy Retrofit Goals PROJECT GOALS Identify,
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings J A NUARY 2015 INTRODUCTION This Research Report explores best practices and approaches for reducing greenhouse gas (GHG)
Differentiating Energy Modeling Software!
Differentiating Energy Modeling Software! What works, what doesn t, and when it matters! A Boulder Green Building Guild brownbag presentation by! Adam Stenftenagel! Principal! Sustainably Built! Heat Movement
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
Energy Savings with Window Retrofits
Center for Energy and Environment Energy Savings with Window Retrofits Presentation to Energy Design Conference & Expo Duluth, MN February 25, 2014 Agenda v Background v Introduction: What are window retrofits?
Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE
Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE Abuimara, Tareq A 1 ; Tabet Aoul, Kheira A. 1 1 Department of Architectural Engineering, United Arab
Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse
Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse Dan Chiras, Ph.D. Director, The Evergreen Institute Gerald, MO 63037 www.evergreeninstitute.org Topics Creating a 100% solar operation Efficiency
ENERGY STAR Certified Homes, Version 3 Cost & Savings Estimates
November 1, 2013 Contents ENERGY STAR Certified Homes, Version 3 Section 1: Executive Summary... 3 Section 2: Detailed Incremental Cost Estimates... 6 Section 3: Incremental Cost & Savings of the Thermal
Adaptive strategies for office spaces in the UK climate
International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate
Selecting Energy Efficient New Windows in Georgia
Selecting Energy Efficient New Windows in Georgia www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS
DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS Ing. Maria-Anna Segreto LAERTE Laboratory - 1 EUROPEAN DIRECTIVE 2010/31/UE It 's well known that higher
Could a European Super Energy Efficient Standard Be Suitable for the U.S.?
Could a European Super Energy Efficient Standard Be Suitable for the U.S.? John Broniek, IBACOS Inc., Pittsburgh, PA Abstract The European Passive House residential energy efficiency standard has produced
White Paper Nest Learning Thermostat Efficiency Simulation for France. Nest Labs September 2014
White Paper Nest Learning Thermostat Efficiency Simulation for France Nest Labs September 2014 Introduction This white paper gives an overview of potential energy savings using the Nest Learning Thermostat
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA
Selecting Energy Efficient Replacement Windows in Nevada
Selecting Energy Efficient Replacement Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows
Solar Thermal Systems
Solar Thermal Systems Design and Applications in the UAE Murat Aydemir Viessmann Middle East FZE General Manager (M.Sc. Mech.Eng., ASHRAE) Dubai Knowledge Village Congress Centre, Dubai 20.4.2009 Viessmann
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
This report presents the findings and recommendations of the assessment of energy use and
This report presents the findings and recommendations of the assessment of energy use and environmental stewardship of Arlington Street Church, Boston, MA. As stewards of the earth it is important that
Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels. W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd.
Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd. 1 The Kingspan Group Energy independent buildings for a sustainable
Energy Savings in High-Rise Buildings Using High-Reflective Coatings
Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold
Selecting Energy Efficient New Windows in Arizona
Selecting Energy Efficient New Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
PENNSYLVANIA GREEN ENERGY LOAN FUND
PENNSYLVANIA GREEN ENERGY LOAN FUND Procedures Manual for Quantifying Energy Savings A. Introduction A building project applying for a GELF energy loan must demonstrate that it will result in a 25% reduction
The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable buildings
International Conference Passive and Low Energy Cooling 935 for the Built Environment, May 25, Santorini, Greece The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
FACTSHEET Assessing the Feasibility of Using Solar-Thermal Systems for Your Agricultural or Agri-Food Operation
FACTSHEET Assessing the Feasibility of Using Solar-Thermal Systems for Your Agricultural or Agri-Food Operation Solar-thermal systems collect the sun's energy and convert it into heat. This energy can
The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study
The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study WARAPORN RATTANONGPHISAT 1,2,*, FEDERICO M. BUTERA 2, R.S. ADHIKARI 2 AND CHALERMPORN YOOPRATETH
Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet'
Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet' We ve prepared this information sheet to help you to minimise energy consumption and energy costs while maximising thermal comfort at home.
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING LI CHUNYING DOCTOR OF PHILOSOPHY CITY UNIVERSITY OF HONG KONG FEBRUARY 2012 CITY UNIVERSITY OF HONG KONG 香 港 城 市 大 學 Performance Evaluation of Water-flow
IEA SHC Task 47 Renovation of Non-Residential Buildings towards Sustainable Standards
Date of revision: 15.6.2012 Osram Culture Centre Copenhagen, Denmark Valhalsgade 4, 2200 Copenhagen N 1. INTRODUCTION PROJECT SUMMARY Construction year: 1953 Energy renovation: 2009 No past energy renovations
Hybrid heat pumps. saving energy and reducing carbon emissions
Hybrid heat pumps saving energy and reducing carbon emissions Bart Aspeslagh Product planning and new technology manager, Daikin Europe NV. [email protected] Stefanie Debaets Design engineer,
RESSÒ: energy efficiency urban rehabilitation
RESSÒ: energy efficiency urban rehabilitation Authors: Bodelon, Carmen 1 ; Gascón, Eduardo 1 ; Ramon, Guillem 1 ; Obiols, Martí 1 ; Palomar, Pablo 1 ; Escoda, Quim 1 ; Prat, Sandra 1 ; Illa, Sergi 1 ;
RosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof.
RosevilleProject Glass Products You can reduce your cooling energy usage by 25% or more. Here is the proof. Hot-Button Issues Residents of California, Arizona, and Nevada don t need a weather forecast
Economics of Passive Solar and Zero Energy Homes
Economics of Passive Solar and Zero Energy Homes Jeff Tiller, PE ASU Energy Center / Department of Technology Southface North Carolina [email protected] 828-262-6355 Projected Residential Energy Use
Current Programs available to Limited Income Customers. Residential and Multifamily
Current Programs available to Limited Income Customers Residential and Multifamily CAP Program- Residential and Multifamily The City of Austin offers programs to help customers facing temporary and long-term
RESEARCH HIGHLIGHT. Solar Energy Potential for the Northern Sustainable Houses
RESEARCH HIGHLIGHT March 2015 Technical Series Solar Energy Potential for the orthern Sustainable Houses ITRODUCTIO Renewable energy technologies, such as solar photovoltaic (PV) or solar thermal systems,
Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Dr. Wolfgang Feist Rheinstr. 44/46 D-64283 Darmstadt www.passiv.de Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses Passive Houses are
Case study on residential building renovation and its impact on the energy use and thermal comfort
Case study on residential building renovation and its impact on the energy use and thermal comfort Hanne Kauko, Maria Justo Alonso, Ole Stavset and Ingrid Camilla Claussen SINTEF Energy Research Motivation
ENERGY STATEMENT for a proposed new residential care home at Great North Road, Doncaster, South Yorkshire, DN6 7EJ
ENERGY STATEMENT for a proposed new residential care home at Great North Road, Doncaster, South Yorkshire, DN6 7EJ Ref. No: 12/02870/FULM Contents 1. General... 2 2. Planning Condition... 2 3. Development...
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
Diego Ibarra Christoph Reinhart Harvard Graduate School of Design
Building Performance Simulation for Designers - Energy DesignBuilder // EnergyPlus Tutorial #2 Load Schedules GEOMETRY LOADS RESULTS Diego Ibarra Christoph Reinhart Harvard Graduate School of Design OVERVIEW
Case Study Family Room Renovation 3br family home, Melbourne
Family Room Renovation 3br family home, Melbourne In a Nutshell With time and budget constraints we often renovate just one room at a time. This case study looks at a family room renovation where the key
Potential of Energy Efficiency and Renewable Energy Savings To Impact Florida s Projected Energy Use in 2014
Potential of Energy Efficiency and Renewable Energy Savings To Impact Florida s Projected Energy Use in 2014 Author Fairey, Philip Publication Number FSEC-RR-58-06 Copyright Copyright Florida Solar Energy
Residential Windows, 3 rd edition Corrected index 1
Residential Windows, 3 rd edition Corrected index 1 A absorptance definition, 78 determinants of, 78 79 energy performance and, 78 tinted glass, 84 acoustical properties of windows, 60 61 acrylic glazing
Below are detailed instructions for using the EMS load calculator.
Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process
Energy Efficiency for the Homeowner
Efficiency for the Homeowner How to Reduce Your Home s Bills October 2009 National Mall Washington, DC A Quick Test Using Efficient Products and Practices Can: A. Make your home more affordable B. Make
Uncovering Myths and Opportunities of Advanced Building Envelope Technologies: BIPV, Roofing and Windows
Uncovering Myths and Opportunities of Advanced Building Envelope Technologies: BIPV, Roofing and Windows Marc LaFrance Technology Development Manager US Department of Energy Building Technology Program
ENERGY PRODUCING SYSTEMS
ENERGY PRODUCING SYSTEMS SOLAR POWER INTRODUCTION Energy from the sun falls on our planet on a daily basis. The warmth of the sun creates conditions on earth conducive to life. The weather patterns that
PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation
PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation INTRODUCTION As the use of spray polyurethane foam (SPF) insulation is increasing in both
Solar and Wind Energy for Greenhouses. A.J. Both 1 and Tom Manning 2
Solar and Wind Energy for Greenhouses A.J. Both 1 and Tom Manning 2 1 Associate Extension Specialist 2 Project Engineer NJ Agricultural Experiment Station Rutgers University 20 Ag Extension Way New Brunswick,
Sustainable water heating solutions through solar systems
VIESMANN Sustainable water heating solutions through solar systems Murat Aydemir Managing Director Viessmann Middle East FZE Viessmann is a Registered Provider with The American Institute of Architects
Net Zero Station Design for The Cooper Centre for the Environmental Learning in Tucson, Arizona: Improving the performance of existing buildings
Net Zero Station Design for The Cooper Centre for the Environmental Learning in Tucson, Arizona: Improving the performance of existing buildings Alya Al-Hashim 1, Lena Spiric 2,and Nader Chalfoun 3 1,2
PV THERMAL SYSTEMS - CAPTURING THE UNTAPPED ENERGY
PV THERMAL SYSTEMS - CAPTURING THE UNTAPPED ENERGY John Hollick Conserval Engineering Inc. 200 Wildcat Road Toronto Ontario [email protected] ABSTRACT PV modules generate electricity, but the electrical
Achieving Net Zero. Bradley Berneche, President Alouette Homes. National Marketing Committee Canadian Home Builders Association Ottawa, June 6, 2008
Achieving Net Zero Bradley Berneche, President Alouette Homes National Marketing Committee Canadian Home Builders Association Ottawa, June 6, 2008 Overview Who Is Alouette Homes? The EQuilibrium Initiative
Certified Residential Energy Auditor (REA) Study Guide
Certified Residential Energy Auditor (REA) Study Guide This guide provides an overview of the Certified Residential Energy Auditor (REA) Program, including how to register for the REA Training Seminar
Solar Decathlon Load Profiling. Project Report
Solar Decathlon Load Profiling Project Report Prepared by Alexander Kon Alexander Hobby Janice Pang Mahan Soltanzadeh Prepared for TTP 289: A Path to Zero Net Energy 6/10/14 Executive Summary The U.S.
Passive Solar Design and Concepts
Passive Solar Design and Concepts Daylighting 1 Passive Solar Heating Good architecture? The judicious use of south glazing coupled with appropriate shading and thermal mass. Summer Winter Passive solar
Home Energy Efficiency and Conservation: Call to Action. July 23, 2015 Dave Blake and David Wood REEP Green Solutions
Home Energy Efficiency and Conservation: Call to Action July 23, 2015 Dave Blake and David Wood REEP Green Solutions Today s Agenda Background Understanding where you are: Energy Usage EnerGuide Home Energy
Connecticut Energy Efficiency Fund Home Performance Program Application (Tier II)
9111 05-10 Connecticut Energy Efficiency Fund Home Performance Program Application (Tier II) This application is for energy efficiency retrofit proposals for existing residential unit(s). The application
First Time Home Buyers Energy Efficiency Workshop Guide
First Time Home Buyers Energy Efficiency Workshop Guide Why is efficiency important when buying a home? Affordability: lower utility bills Environmental responsibility: reduces your carbon footprint and
Extra Low Energy Housing in Ireland How far should we go to the Passive House? Jonathan Jennings Head of R&D Kingspan Century Homes
Extra Low Energy Housing in Ireland How far should we go to the Passive House? Jonathan Jennings Head of R&D Kingspan Century Homes Current Status % CO 2 emissions Transport 30% Agriculture 2% Housing
Home Energy Evaluation Report
Home Energy Evaluation Report Nate Begeman, 1550 Saint Francis Dr San Jose, CA 95125 Air Infiltration Current Air Leakage 2,852 Current Air Changes Per Hour 0.91 Recommended Air Changes Per Hour 0.35 Percent
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings Version 2006.1 AUSTRALIAN BUILDING CODES BOARD JANUARY 2006 TABLE OF CONTENTS Foreword 1. Scope 2. Purpose and context
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple
CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the
Energy savings in the residential area are essential in
Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations
Energy Analysis for Internal and External Window Film Applications for Existing Homes in Florida
Energy & Environmental Solutions Energy Analysis for Internal and External Window Film Applications for Existing Homes in Florida PREPARED FOR: INTERNATIONAL WINDOW FILM ASSOCIATION P.O. BOX 3871 MARTINSVILLE,
Norwegian Tax Authority - Oslo Norway
1. INTRODUCTION Norwegian Tax Authority - Oslo Norway PROJECT SUMMARY Year of construction - 1980 No previous energy renovations SPECIAL FEATURES Main topics in the renovation are: High insulated pre fabricated
Market Potential Study for Water Heater Demand Management
Market Potential Study for Water Heater Demand Management Rebecca Farrell Troutfetter, Frontier Associates LLC, Austin, TX INTRODUCTION Water heating represents between 13 and 17 percent of residential
Comparative Analysis of Retrofit Window Film to Replacement with High Performance Windows
Comparative Analysis of Retrofit Window Film to Replacement with High Performance Windows By Steve DeBusk, CEM, CMVP Global Energy Solutions Manager CPFilms, a Subsidiary of Solutia Inc. Abstract Energy
Introduction to Energy Codes & Green Building Programs
Introduction to Energy Codes & Green Building Programs David Neiger B.S. Arch, LEED AP Homes, Certified HERS Rater Principal Populus Sustainable Design Consulting Why green homes? The Building Sector:
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
2009 Seattle Energy Code Impacts: See below for a recap of Changes in Envelope performance from 2006 to 2009
2009 Seattle Energy Code Impacts: Building Envelope Impacts: Below is a Summary of Changes that impact building envelope construction planned for 624 Yale. There are several modifications are required