1 Failure Modes, Effects and Diagnostic Analysis Project: ASCO Series 327 Solenoid Valves FMEDA Customer: ASCO Numatics Scherpenzeel, The Netherlands Contract No.: Q09/04-59 Report No.: ASC 09/04-59 R001 Version V1, Revision R3, September 15, 2010 Steven Close The document was prepared using best effort. The authors make no warranty of any kind and shall not be liable in any event for incidental or consequential damages in connection with the application of the document. All rights reserved.

2 Management summary This report summarizes the results of the Failure Modes, Effects, and Diagnostic Analysis (FMEDA) of the ASCO Series 327 Solenoid Valves. A Failure Modes, Effects, and Diagnostic Analysis is one of the steps to be taken to achieve functional safety certification per IEC of a device. From the FMEDA, failure rates and Safe Failure Fraction are determined. The FMEDA that is described in this report concerns the hardware of the ASCO Series 327 Solenoid Valves. For full functional safety certification purposes all requirements of IEC must be considered. The Series 327 Solenoid Valves are 3/2 solenoid valves that are direct operated with a balanced poppet. The Models 327B are basic flow models with ¼ inch pipe connections. The Models 327A are high flow models with ¼ and ½ inch pipe connections. The Models 327B are available in a redundant configuration. The Series 327 Solenoid Valves are offered in four coil power levels. Table 1 lists the model numbers and coil versions for the Series 327 Solenoid Valves covered by this FMEDA. Table 1 Coil Options Basic Model Number Coil Power 327B0/8327G Basic Power (10.0 to 14 W) 327B1 Medium Power ( W) 327B2 Reduced Power ( W) 327B3 Low Power (1.8 W) 327A6 Basic Power (10.0 to 14 W) Table 2 gives an overview of the different versions that were considered in the FMEDA of the ASCO Series 327 Solenoid Valves. Table 2 Version Overview Model 327B0/8327G 327B1 327B2 327B3 327A6 Redundant 327B0 Redundant 327B1 Redundant 327B2 Redundant 327B3 MO 1 (Manual Operator) NVR 2 (Manual Operator) Configuration to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed to trip / to trip, Normally Closed to trip / to trip, Normally Closed to trip / to trip, Normally Closed to trip to trip 1 The MO manual operator option is used to reset the solenoid manually. It is not part of the safety function of the solenoid valve but does contribute to the failure rates of the solenoid valve. 2 The NVR manual operator option is used to reset the solenoid manually. It is not part of the safety function of the solenoid valve but does contribute to the failure rates of the solenoid valve. Steven Close Page 2 of 25

3 to trip applications failure rates do not take into account the loss of power to the solenoid. Failure rates for the Series 327 Solenoid Valves are listed in Table 3, Table 4 and Table 5. Failures rates are listed both with and without partial valve stroke tests (PVST). See section 6 for a definition of PVST. The failure rates for the manual operators are also listed in Table 5. Table 3 Failure Rates in FIT for Series 327B Solenoid Valves Failure Category 327B0/8327G 327B1 & 2 327B3 Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Failure Category w/pvst Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Steven Close Page 3 of 25

4 Table 4 Failure Rates in FIT for Series 327B Solenoid Valves (Redundant) 327B0 Redundant 327B1&2 Redundant 327B3 Redundant Failure Category Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Failure Category w/pvst Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Table 5 Failure Rates in FIT for Series 327A6 Solenoid Valves and Manual Operators Failure Category to 327A6 MO NVR To to to Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Failure Category w/pvst to To to to Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Steven Close Page 4 of 25

5 Table 6 lists the failure rates for the Series 327 Solenoid Valves according to IEC Table 6 Failure Rates in FIT According to IEC Model Failure Category λ sd λ su 3 327B0/8327G 327B1&2 327B3 327B0 Redundant 327B1&2 Redundant 327B3 Redundant 327A6 MO NRV λ dd λ du SFF % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % W/PVST % % W/PVST % When using the MO or NRV options the failure rates for these options must be added to the failure rates of the Solenoid Models they are used with. 3 It is important to realize that the Residual failures are included in the safe undetected failure category according to IEC Note that these failures on their own will not affect system reliability or safety, and should not be included in spurious trip calculations 4 The SFF must be calculated for the complete final element. These values are only valid when the solenoid valve constitutes the entire final element. Steven Close Page 5 of 25

6 The ASCO Series 327 Solenoid Valves are classified as a Type A 5 devices according to IEC 61508, having a hardware fault tolerance of 0. The Safe Failure Fracture must be calculated for the entire final element assembly of which the ASCO Series 327 Solenoid Valves are typically a component of. If the ASCO Series 327 Solenoid Valves are the complete final element then Safe Failure Fractions listed in Table 6 can be used. The failure rates listed in this report do not include failures due to wear-out of any components. They reflect random failures and include failures due to external events, such as unexpected use, see section These failure rates are valid for the useful lifetime of the ASCO Series 327 Solenoid Valves, see Appendix A: Lifetime of critical components. A user of the Series 327 Solenoid Valves can utilize these failure rates in a probabilistic model of a safety instrumented function (SIF) to determine suitability in part for safety instrumented system (SIS) usage in a particular safety integrity level (SIL). A full table of failure rates is presented in section 4 along with all assumptions. 5 Type A component: Non-Complex component with well-defined failure modes, for details see of IEC Steven Close Page 6 of 25

7 Table of Contents Management summary Purpose and Scope Project management exida Roles of the parties involved Standards / Literature used Reference documents Documentation provided by ASCO Numatics Documentation generated by exida Product Description Failure Modes, Effects, and Diagnostics Analysis Description of the failure categories Methodology FMEDA, Failure rates FMEDA Failure rates Assumptions Results Using the FMEDA results Air quality failures PFD AVG calculation Series 327 Solenoid Valves Terms and Definitions Status of the document Liability Releases Future Enhancements Release Signatures Appendix A: Lifetime of critical components Appendix B: Proof tests to reveal dangerous undetected faults B.1 Proof test Steven Close Page 7 of 25

8 1 Purpose and Scope Generally three options exist when doing an assessment of sensors, interfaces and/or final elements. Option 1: Hardware assessment according to IEC Option 1 is a hardware assessment by exida according to the relevant functional safety standard(s) like IEC or EN The hardware assessment consists of a FMEDA to determine the fault behavior and the failure rates of the device, which are then used to calculate the Safe Failure Fraction (SFF) and the average Probability of Failure on Demand (PFD AVG ). When appropriate, fault injection testing will be used to confirm the effectiveness of any selfdiagnostics. This option provides the safety instrumentation engineer with the required failure data as per IEC / IEC This option does not include an assessment of the development process. Option 2: Hardware assessment with proven-in-use consideration per IEC / IEC Option 2 extends Option 1 with an assessment of the proven-in-use documentation of the device including the modification process. This option for pre-existing programmable electronic devices provides the safety instrumentation engineer with the required failure data as per IEC / IEC When combined with plant specific proven-in-use records, it may help with prior-use justification per IEC for sensors, final elements and other PE field devices. Option 3: Full assessment according to IEC Option 3 is a full assessment by exida according to the relevant application standard(s) like IEC or EN 298 and the necessary functional safety standard(s) like IEC or EN The full assessment extends Option 1 by an assessment of all fault avoidance and fault control measures during hardware and software development. This option provides the safety instrumentation engineer with the required failure data as per IEC / IEC and confidence that sufficient attention has been given to systematic failures during the development process of the device. This assessment shall be done according to option 1. This document shall describe the results of the hardware assessment in the form of the Failure Modes, Effects and Diagnostic Analysis carried out on the ASCO Series 327 Solenoid Valves. From this, failure rates, Safe Failure Fraction (SFF) and example PFD AVG values are calculated. The information in this report can be used to evaluate whether a final element subsystem meets the average Probability of Failure on Demand (PFD AVG ) requirements and the architectural constraints/minimum hardware fault tolerance requirements per IEC 61508/IEC Steven Close Page 8 of 25

9 2 Project management 2.1 exida exida is one of the world s leading knowledge companies specializing in automation system safety and availability with over 300 years of cumulative experience in functional safety. Founded by several of the world s top reliability and safety experts from assessment organizations and manufacturers, exida is a partnership with offices around the world. exida offers training, coaching, project oriented consulting services, internet based safety engineering tools, detail product assurance and certification analysis and a collection of on-line safety and reliability resources. exida maintains a comprehensive failure rate and failure mode database on process equipment. 2.2 Roles of the parties involved ASCO Numatics exida Manufacturer of the ASCO Series 327 Solenoid Valves Project leader of the FMEDA ASCO Numatics contracted exida in October 2009 with the FMEDA of the above-mentioned device. 2.3 Standards / Literature used The services delivered by exida were performed based on the following standards / literature. [N1] IEC : 2000 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems [N2] [N3] Electrical & Mechanical Component Reliability Handbook, 2nd Edition, 2008 Safety Equipment Reliability Handbook, 3rd Edition, 2007 exida L.L.C, Electrical & Mechanical Component Reliability Handbook, Second Edition, 2008, ISBN exida L.L.C, Safety Equipment Reliability Handbook, Third Edition, 2007, ISBN [N4] Goble, W.M Control Systems Safety Evaluation and Reliability, ISA, ISBN Reference on FMEDA methods [N5] IEC : , second edition [N6] Goble, W.M. and Cheddie, H., 2005 [N7] Electrical & Mechanical Component Reliability Handbook, 2nd Edition, 2008 Industrial-process measurement and control equipment Operating conditions Part 1: Climatic condition Safety Instrumented Systems Verification, Practical Probabilistic Calculations, ISA, ISBN X Section 6: Reliability Data Mechanical Components [N8] O Brien, C & Bredemeyer, L 2009 exida L.L.C, Final Elements & the IEC and IEC Functional Safety Standards, 2009, ISBN-13: Steven Close Page 9 of 25

10 2.4 Reference documents Documentation provided by ASCO Numatics [D1] PIC GB Solenoid Valves - Redundant, Direct Operated basic flow, balanced poppet [D2] PIC-6-50-GB Solenoid Valves - Direct Operated, for linear actuators (VDE 3845) 1/4, Direct Mount [D3] PIC-6-20-GB Solenoid Valves - Redundant, Direct Operated, NAMUR [D4] PIC GB Solenoid Valves - no voltage release (tamperproof) manual reset construction [D5] PIC-2-50-GB Solenoid Valves - Direct Operated basic flow, balanced poppet 1/4 [D6] /2 Direct Operated Universal Construction [D7] Reduced Power Construction [D8] /2 Universal Direct Operated [D9] PIC-2-55-GB Solenoid Valves - Direct Operated high flow, balanced poppet 1/4 to 1/2 [D10] PIC GB Solenoid Valves - no voltage release (tamperproof) manual reset construction [D11] 3/2 Series 8327 High Flow Direct acting valves [D12] [D13] [D14] No date or Revision 327, MO & NVR Documentation generated by exida 327 DN6, NVR Tamperproof 3/2 Series 8327 High Flowing Direct Acting Valves [R1] ASCO_090459_327_FMED A_R5.xls [R2] ASC _327_FMEDA R001 V1R3.doc, 9/15/2010 Failure Modes, Effects and Diagnostic Analysis, Series 327 Solenoid Valves (internal document) FMEDA report, Series 327 Solenoid Valves (this report) Steven Close Page 10 of 25

11 3 Product Description The Series 327 Solenoid Valves are 3/2 solenoid valves that are direct operated with a balanced poppet. The Models 327B are basic flow models with ¼ inch pipe connections. The Models 327A are high flow models with ¼ and ½ inch pipe connections. The Models 327B are available in a redundant configuration. The Series 327 Solenoid Valves are offered in four coil power levels. The Series 327 Solenoid Valves are available with manual operators that are used to reset the solenoid to the energized position after a trip. The manual operators do not serve a safety function. Table 7 lists the model numbers and coil versions of the Series 327 Solenoid Valves covered by this FMEDA. Table 7 Coil Options Basic Model Number Coil Power 327B0/8327G Basic Power (10.0 to 14 W) 327B1 Medium Power ( W) 327B2 Reduced Power ( W) 327B3 Low Power (1.8 W) 327A6 Basic Power (10.0 to 14 W) Figure 1 shows a direct operated, basic flow, balanced poppet Series 327 Solenoid Valve. Figure 1: Series 327 Solenoid Valve Steven Close Page 11 of 25

12 Table 8 gives an overview of the different versions that were considered in the FMEDA of the ASCO Series 327 Solenoid Valves. Table 8 Version Overview Model 327B0/8327G 327B1 327B2 327B3 327A6 Redundant 327B0 Redundant 327B1 Redundant 327B2 Redundant 327B3 MO 6 (Manual Operator) NVR 7 (Manual Operator) Configuration to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed / Normally Open to trip / to trip, Normally Closed to trip / to trip, Normally Closed to trip / to trip, Normally Closed to trip / to trip, Normally Closed to trip to trip to trip applications failure rates do not take into account the loss of power to the solenoid. The Series 327 Solenoid Valves are classified as a Type A 8 devices according to IEC 61508, having a hardware fault tolerance of 0. 6 The MO manual operator option is used to reset the solenoid manually. It is not part of the safety function of the solenoid valve but does contribute to the failure rates of the solenoid valve. 7 The NVR manual operator option is used to reset the solenoid manually. It is not part of the safety function of the solenoid valve but does contribute to the failure rates of the solenoid valve. 8 Type A component: Non-Complex component with well-defined failure modes, for details see of IEC Steven Close Page 12 of 25

13 4 Failure Modes, Effects, and Diagnostics Analysis The Failure Modes, Effects, and Diagnostic Analysis was performed based on documentation obtained from ASCO Numatics and is documented in [R1]. 4.1 Description of the failure categories In order to judge the failure behavior of the Series 327 Solenoid Valves, the following definitions for the failure of the transmitter were considered. Fail-Safe State Fail Safe State where solenoid is de-energized and spring is extended. State where solenoid is energized and spring is compressed. Failure that causes the valve to go to the defined fail-safe state without a demand from the process. Failure that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state). Undetected Failure that is dangerous and that is not being diagnosed by an automatic diagnostic such as partial valve stroke testing. Detected Residual Failure that is dangerous but is detected by an automatic diagnostic such as partial valve stroke testing. Failure of a component that is part of the safety function but that has no effect on the safety function. The failure categories listed above expand on the categories listed in IEC 61508, Edition 2000, which are only safe and dangerous, both detected and undetected. In IEC the No Effect failures are defined as safe undetected failures even though they will not cause the safety function to go to a safe state. Therefore they need to be considered in the Safe Failure Fraction calculation. 4.2 Methodology FMEDA, Failure rates FMEDA A Failure Modes and Effects Analysis (FMEA) is a systematic way to identify and evaluate the effects of different component failure modes, to determine what could eliminate or reduce the chance of failure, and to document the system in consideration. An FMEDA (Failure Mode Effect and Diagnostic Analysis) is an FMEA extension. It combines standard FMEA techniques with extension to identify online diagnostics techniques and the failure modes relevant to safety instrumented system design. It is a technique recommended to generate failure rates for each important category (safe detected, safe undetected, dangerous detected, dangerous undetected, fail high, fail low) in the safety models. The format for the FMEDA is an extension of the standard FMEA format from MIL STD 1629A, Failure Modes and Effects Analysis. Steven Close Page 13 of 25

14 4.2.2 Failure rates The failure rate data used by exida in this FMEDA is from the Electrical and Mechanical Component Reliability Handbook which was derived using field failure data from multiple sources and failure data from various databases. The rates were chosen in a way that is appropriate for safety integrity level verification calculations. The rates were chosen to match exida Profile 3, see Table 9. It is expected that the actual number of field failures due to random events will be less than the number predicted by these failure rates. Table 9 exida Environmental Profiles EXIDA ENVIRONMENTAL PROFILE Cabinet Mounted Equipment Low Power /Mechanical Field Products General Field Equipment Unprotected Mechanical Field Products GENERAL DESCRIPTION Cabinet mounted equipment typically has significant temperature rise due to power dissipation but is subjected to only minimal daily temperature swings Mechanical / low power electrical (twowire) field products have minimal self heating and are subjected to daily temperature swings General (four-wire) field products may have moderate self heating and are subjected to daily temperature swings Unprotected mechanical field products with minimal self heating, are subject to daily temperature swings and rain or condensation. PROFILE PER IEC AMBIENT TEMPERATURE [ C] AVERAGE (EXTERNAL) MEAN (INSIDE BOX) TEMP CYCLE [ C / 365 DAYS] B C C D For hardware assessment according to IEC only random equipment failures are of interest. It is assumed that the equipment has been properly selected for the application and is adequately commissioned such that early life failures (infant mortality) may be excluded from the analysis. Failures caused by external events however should be considered as random failures. Examples of such failures are loss of power, physical abuse, or problems due to intermittent instrument air quality. The assumption is also made that the equipment is maintained per the requirements of IEC or IEC and therefore a preventative maintenance program is in place to replace equipment before the end of its useful life. Corrosion, erosion, coil burnout etc. are considered age related (late life) or systematic failures, provided that materials and technologies applied are indeed suitable for the application, in all modes of operation. The user of these numbers is responsible for determining their applicability to any particular environment. Accurate plant specific data may be used for this purpose. If a user has data collected from a good proof test reporting system that indicates higher failure rates, the higher numbers shall be used. Some industrial plant sites have high levels of stress. Under those conditions the failure rate data is adjusted to a higher value to account for the specific conditions of the plant. Steven Close Page 14 of 25

15 4.3 Assumptions The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis of the Series 327 Solenoid Valves. Only a single component failure will fail the entire solenoid valve Failure rates are constant, wear out mechanisms are not included. Propagation of failures is not relevant. All components that are not part of the safety function and cannot influence the safety function (feedback immune) are excluded. The stress levels are average for an industrial environment and can be compared to the Ground Fixed classification of MIL-HNBK-217F. Alternatively, the assumed environment is similar to: o IEC , Class Dx (outdoor location) with temperature limits within the manufacturer s rating. Other environmental characteristics are assumed to be within manufacturer s rating. If Partial Valve Stroke Testing is claimed as a diagnostic it must be automatically executed. Partial Valve Stroke testing of the Safety Instrumented Function provides a timed full cycle test of the solenoid valve The solenoid valves are generally applied in relatively clean gas, therefore no severe service has been considered in the analysis. Solenoid valves are used with clean, dry air or inert gas filtered to 50 micrometers or better. Materials are compatible with process conditions The solenoid valves are installed per manufacturer s instructions. Failure rates do not include loss of power to the solenoid. 4.4 Results Using reliability data extracted from the exida component reliability database, the following failure rates resulted from the ASCO Numatics Series 327 Solenoid Valves FMEDA. Failure rates for the Series 327 Solenoid Valves are listed in Table 10, Table 11, and Table 12. Failures rates are listed both with and without partial valve stroke tests (PVST). See section 6 for a definition of PVST. The failure rates for the manual operators are also listed in Table 12. Steven Close Page 15 of 25

16 Table 10 Failure Rates in FIT for Series 327B Solenoid Valves Failure Category 327B0/8327G 327B1 & 2 327B3 Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Failure Category w/pvst Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Table 11 Failure Rates in FIT for Series 327B Solenoid Valves (Redundant) 327B0 Redundant 327B1&2 Redundant 327B3 Redundant Failure Category Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Failure Category w/pvst Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Steven Close Page 16 of 25

17 Table 12 Failure Rates in FIT for Series 327A6 Solenoid Valves Failure Category to 327A6 MO NVR To to to Fail Safe Detected Fail Safe Undetected Detected Undetected Residual Failure Category w/pvst to To to to Fail Safe Detected Fail Safe Undetected Detected Undetected Residual The failure rates that are derived from the FMEDA for the Series 327 Solenoid Valves are in a format different from the IEC format. Table 13 lists the failure rates for Series 327 Solenoid Valves according to IEC According to IEC [N1], the Safe Failure Fraction (SFF) of the Series 327 Solenoid Valves should be calculated. The Safe Failure Fraction is the fraction of the overall failure rate of a device that results in either a safe fault or a diagnosed unsafe fault. This is reflected in the following formulas for SFF: SFF = 1 λdu / λtotal Note that according to IEC61508, Edition 2000, definition the No Effect failures are classified as safe and therefore need to be considered in the Safe Failure Fraction calculation and are included in the total failure rate. Steven Close Page 17 of 25

18 Table 13 Failure Rates in FIT According to IEC Model Failure Category λ sd λ su 9 327B0/8327G 327B1&2 327B3 327B0 Redundant 327B1&2 Redundant 327B3 Redundant 327A6 MO NRV λ dd λ du SFF % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % % W/PVST % W/PVST % % W/PVST % % W/PVST % When using the MO or NRV options the failure rates for these options must be added to the failure rates of the Solenoid Models they are used with. 9 It is important to realize that the no effect failures are included in the safe undetected failure category according to IEC Note that these failures on their own will not affect system reliability or safety, and should not be included in spurious trip calculations 10 The SFF must be calculated for the complete final element. These values are only valid when the solenoid valve constitutes the entire final element. Steven Close Page 18 of 25

19 The ASCO Series 327 Solenoid Valves are classified as a Type A 11 devices according to IEC 61508, having a hardware fault tolerance of 0. The Safe Failure Fracture must be calculated for the entire final element assembly of which the ASCO Series 327 Solenoid Valves are typically a component of. If the ASCO Series 327 Solenoid Valves are the complete final element then Safe Failure Fractions listed in Table 6 can be used. The failure rates listed in this report do not include failures due to wear-out of any components. They reflect random failures and include failures due to external events, such as unexpected use, see section These failure rates are valid for the useful lifetime of the ASCO Series 327 Solenoid Valves, see Appendix A: Lifetime of critical components. A user of the Series 327 Solenoid Valves can utilize these failure rates in a probabilistic model of a safety instrumented function (SIF) to determine suitability in part for safety instrumented system (SIS) usage in a particular safety integrity level (SIL). A full table of failure rates is presented in section 4 along with all assumptions. The architectural constraint type for the Series 327 Solenoid Valves is A. The hardware fault tolerance of the device is 0. The SFF and required SIL determine the level of hardware fault tolerance that is required per requirements of IEC [N1] or IEC The SIS designer is responsible for meeting other requirements of applicable standards for any given SIL as well. 11 Type A component: Non-Complex component with well-defined failure modes, for details see of IEC Steven Close Page 19 of 25

20 5 Using the FMEDA results 5.1 Air quality failures The product failure rates that are displayed in section 4.4 are failure rates that reflect the situation where the device is used with clean filtered air. Additionally, contamination from poor control air quality may affect the function or air flow in the device. For applications where these assumptions do not apply, the user must estimate the failure rates due to contaminated air and add this failure rate to the product failure rates. 5.2 PFD AVG calculation Series 327 Solenoid Valves An average Probability of Failure on Demand (PFD AVG ) calculation is performed for a single (1oo1) Series 327 Solenoid Valve. The failure rate data used in this calculation is displayed in section 4.4. A mission time of 10 years has been assumed and a Mean Time To Restoration of 24 hours. Table 14 lists the proof test coverage, PFD AVG, and percent of SIL range for the various configurations when the proof test interval equals 1 year (see Appendix B). For SIL 2 applications, the PFD AVG value needs to be 10-3 and < It is the responsibility of the Safety Instrumented Function designer to do calculations for the entire SIF. exida recommends the accurate Markov based exsilentia tool for this purpose. Table 14 Sample Results for a proof test interval of 1 year. Device Proof Test Coverage PFD AVG % of SIL 2 Range 327B0/8327G 99% 8.98E % 327A6 99% 1.02E % 327B0 Redundant 99% 1.70E % Figure 2 shows the PFD AVG for various proof test intervals for the Series 327 Solenoid Valves. PFD AVG vs. Proof Test Interval 1.80E B0/8327G 327A6 327B0 Redundant 1.60E E E-02 PFDAVG 1.00E E E E E E Years Figure 2: PFD AVG (t) vs, Proof Test Interval for the Series 327 Solenoid Valves When performing partial valve stroke testing at regular intervals, the Series 327 Solenoid Valves minimally contributes to the overall PFD AVG of the Safety Instrumented Function. Steven Close Page 20 of 25

21 These results must be considered in combination with PFD AVG values of other devices of a Safety Instrumented Function (SIF) in order to determine suitability for a specific Safety Integrity Level (SIL). It is the responsibility of the Safety Instrumented Function designer to do calculations for the entire SIF. exida recommends the accurate Markov based exsilentia software tool for this purpose. Steven Close Page 21 of 25

22 6 Terms and Definitions FIT FMEDA HFT Low demand mode PVST PFD AVG SFF SIF SIL SIS Type A component Type B component Failure In Time (1x10-9 failures per hour) Failure Mode Effect and Diagnostic Analysis Hardware Fault Tolerance Mode, where the frequency of demands for operation made on a safetyrelated system is no greater than one per year and no greater than twice the proof test frequency. Partial Valve Stroke Test It is assumed that the Partial Stroke Testing, when performed, is performed at least an order of magnitude more frequent than the proof test, therefore the test can be assumed an automatic diagnostic. Because of the automatic diagnostic assumption the Partial Stroke Testing also has an impact on the Safe Failure Fraction. Average Probability of Failure on Demand Safe Failure Fraction summarizes the fraction of failures, which lead to a safe state and the fraction of failures which will be detected by diagnostic measures and lead to a defined safety action. Safety Instrumented Function Safety Integrity Level Safety Instrumented System Implementation of one or more Safety Instrumented Functions. A SIS is composed of any combination of sensor(s), logic solver(s), and final element(s). Non-Complex component (using discrete elements); for details see of IEC Complex component (using micro controllers or programmable logic); for details see of IEC Steven Close Page 22 of 25

23 7 Status of the document 7.1 Liability exida prepares FMEDA reports based on methods advocated in International standards. Failure rates are obtained from a collection of industrial databases. exida accepts no liability whatsoever for the use of these numbers or for the correctness of the standards on which the general calculation methods are based. 7.2 Releases Version: V1 Revision: R3 Version History: V1; R3 Added 8327G, S. Close Sep 15, V1; R2: Revised failure rates for 327A, S. Close, Dec 11, V1; R1: Released to Customer V0; R1 Initial Draft; Nov 20, 2009 Authors: Steven Close Review: V0; R1: Chris O Brien Release status: Released 7.3 Future Enhancements At request of client. 7.4 Release Signatures Steven Close, Safety Engineer Chris O Brien Partner Steven Close Page 23 of 25

24 Appendix A: Lifetime of critical components Although a constant failure rate is assumed by the probabilistic estimation method (see section 4.2) this only applies provided that the useful lifetime of components is not exceeded. Beyond their useful lifetime the result of the probabilistic calculation method is therefore meaningless, as the probability of failure significantly increases with time. The useful lifetime is highly dependent on the subsystem itself and its operating conditions. This assumption of a constant failure rate is based on the bathtub curve. Therefore it is obvious that the PFD AVG calculation is only valid for components that have this constant domain and that the validity of the calculation is limited to the useful lifetime of each component. According to section of IEC , a useful lifetime, based on experience, should be assumed. Major factors influencing useful life are the air quality, ambient temperature and the air circulation around the solenoid. If the Series 327 Solenoid Valves are used with clean air in an ambient with air circulation (draft air) and an ambient temperature average of 40ºC, then a useful life of 30,000 hours for the coil and 10 years is expected for the assembly. Table 15 lists the useful life for the Series 327 Solenoid Valves. Table 15 Useful Life Component Coil Valve Assembly Valve Assembly Useful Life 30,000 hours 10 years 200,000 cycles It is the responsibility of the end user to establish a preventative maintenance process to replace all solenoids before the end of the useful life. Steven Close Page 24 of 25

25 Appendix B: Proof tests to reveal dangerous undetected faults According to section f) of IEC proof tests shall be undertaken to reveal dangerous faults which are undetected by diagnostic tests. This means that it is necessary to specify how dangerous undetected faults which have been noted during the FMEDA can be detected during proof testing. B.1 Proof test The Proof test consists of a full stroke of the solenoid, as described in Table 16. This test will detect >99% of possible DU failures in the Series 327 Solenoid Valves. Table 16 Steps for Proof Test Step Action 1 Bypass the safety function and take appropriate action to avoid a false trip. 2 Send a signal to the solenoid to perform a full stroke and verify that this is achieved within the specified time. 3 Inspect the solenoid for any visible damage or contamination. 4 Remove the bypass and otherwise restore normal operation. Steven Close Page 25 of 25

IEC 61508 Functional Safety Assessment. ASCO Numatics Scherpenzeel, The Netherlands

IEC 61508 Functional Safety Assessment. ASCO Numatics Scherpenzeel, The Netherlands IEC 61508 Functional Safety Assessment Project: Series 327 Solenoid Valves Customer: ASCO Numatics Scherpenzeel, The Netherlands Contract No.: Q09/04-59 Report No.: ASC 09-04-59 R003 V1 R3 61508 Assessment

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Plant-STOP 9475 Company: R. STAHL Schaltgeräte GmbH Waldenburg Germany Contract No.: STAHL 13/04-027 Report No.: STAHL 13/04-027 R024 Version V1,

More information

IEC 61508 Functional Safety Assessment. Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter.

IEC 61508 Functional Safety Assessment. Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter. 61508 SIL 3 CAPABLE IEC 61508 Functional Safety Assessment Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter Customer: K-TEK Corporation Prairieville, LA USA Contract No.:

More information

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany FMEDA and Proven-in-use Assessment Project: Inductive NAMUR sensors Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 03/11-10 Report No.: P+F 03/11-10 R015 Version V1, Revision R1.1, July

More information

Final Element Architecture Comparison

Final Element Architecture Comparison Final Element Architecture Comparison 2oo2 with diagnostics: Lower False Trip Rate and High Safety Project: Safety Cycling Systems Architecture Review Customer: Safety Cycling Systems, L.L.C. 1018 Laurel

More information

SAFETY MANUAL SIL RELAY MODULE

SAFETY MANUAL SIL RELAY MODULE PROCESS AUTOMATION SAFETY MANUAL SIL RELAY MODULE KFD0-RSH-1.4S.PS2 ISO9001 3 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

Hardware safety integrity Guideline

Hardware safety integrity Guideline Hardware safety integrity Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se Quoting of this report is allowed

More information

Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator

Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator Instruction Manual Supplement ED, ES, ET, EZ, HP, HPA Valves with 657/667 Actuator Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator Purpose This safety manual provides information

More information

Effective Compliance. Selecting Solenoid Valves for Safety Systems. A White Paper From ASCO Valve, Inc. by David Park and George Wahlers

Effective Compliance. Selecting Solenoid Valves for Safety Systems. A White Paper From ASCO Valve, Inc. by David Park and George Wahlers Effective Compliance with IEC 61508 When Selecting Solenoid Valves for Safety Systems by David Park and George Wahlers A White Paper From ASCO Valve, Inc. Introduction Regulatory modifications in 2010

More information

Selecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004)

Selecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004) Selecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004) Dale Perry Worldwide Pressure Marketing Manager Emerson Process Management Rosemount Division Chanhassen, MN 55317 USA

More information

Basic Fundamentals Of Safety Instrumented Systems

Basic Fundamentals Of Safety Instrumented Systems September 2005 DVC6000 SIS Training Course 1 Basic Fundamentals Of Safety Instrumented Systems Overview Definitions of basic terms Basics of safety and layers of protection Basics of Safety Instrumented

More information

Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments

Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments Introduction The Industrial process industry is experiencing a dynamic growth in Functional Process Safety applications.

More information

SAFETY MANUAL SIL SWITCH AMPLIFIER

SAFETY MANUAL SIL SWITCH AMPLIFIER PROCESS AUTOMATION SAFETY MANUAL SIL SWITCH AMPLIFIER KF**-SR2-(Ex)*(.LB), KFD2-SR2-(Ex)2.2S ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable:

More information

Version: 1.0 Latest Edition: 2006-08-24. Guideline

Version: 1.0 Latest Edition: 2006-08-24. Guideline Management of Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se Quoting of this report is allowed but please

More information

MXa SIL Guidance and Certification

MXa SIL Guidance and Certification MXa SIL Guidance and Certification SIL 3 capable for critical applications Experience In Motion Functional Safety in Plants Safety and instrumentation engineers demand that a functional safety system s

More information

SAFETY MANUAL SIL Switch Amplifier

SAFETY MANUAL SIL Switch Amplifier PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SR-(Ex)*(.LB)(.SP), HiC282* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The General

More information

SAFETY MANUAL SIL SMART Transmitter Power Supply

SAFETY MANUAL SIL SMART Transmitter Power Supply PROCESS AUTOMATION SAFETY MANUAL SIL SMART Transmitter Power Supply KFD2-STC4-(Ex)*, KFD2-STV4-(Ex)*, KFD2-CR4-(Ex)* ISO9001 2 3 With regard to the supply of products, the current issue of the following

More information

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE FUNCTIONAL SAFETY CERTIFICATE This is to certify that the hardware safety integrity of the Valvetop ESD Valve Controller manufactured by TopWorx Inc. 3300 Fern Valley Road Louisville Kentucky 40213 USA

More information

A methodology For the achievement of Target SIL

A methodology For the achievement of Target SIL A methodology For the achievement of Target SIL Contents 1.0 Methodology... 3 1.1 SIL Achievement - A Definition... 4 1.2 Responsibilities... 6 1.3 Identification of Hazards and SIL Determination... 8

More information

Certification Report of the STT25S Temperature Transmitter

Certification Report of the STT25S Temperature Transmitter Certification Report of the STT25S Temperature Transmitter Revision No.: 1.2 Date: Report Number: Product: Customer: Order Number: Authority: Responsible: 2009-Jul-10 SAS-135/2006T STT25S Temperature Transmitter

More information

,g) rrrs {fd fi. f il'ltdä. Failure Modes, Effects and Diagnostic Analysis. ABB Automation Products GmbH Alzenau Germany

,g) rrrs {fd fi. f il'ltdä. Failure Modes, Effects and Diagnostic Analysis. ABB Automation Products GmbH Alzenau Germany ' I rrrs {fd fi 1;;,g) -.- f il'ltdä Failure Modes, Effects and Diagnostic Analysis Project: Temperature transmitters TSP***, TT*200-*H and TT*3*0-*H with 4..20 ma output Customer: ABB Automation Products

More information

Safety Requirements Specification Guideline

Safety Requirements Specification Guideline Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary Safety Requirement

More information

SAFETY LIFE-CYCLE HOW TO IMPLEMENT A

SAFETY LIFE-CYCLE HOW TO IMPLEMENT A AS SEEN IN THE SUMMER 2007 ISSUE OF... HOW TO IMPLEMENT A SAFETY LIFE-CYCLE A SAFER PLANT, DECREASED ENGINEERING, OPERATION AND MAINTENANCE COSTS, AND INCREASED PROCESS UP-TIME ARE ALL ACHIEVABLE WITH

More information

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. March 2009. Valves

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. March 2009. Valves Valves Guidelines Safety Integrity Level - SIL - Valves and valve actuators March 2009 VDMA German Engineering Federation Valves Manufacturers Association Chairman: Prof.-Dr.-Ing. Heinfried Hoffmann Managing

More information

Using a Failure Modes, Effects and Diagnostic Analysis (FMEDA) to Measure Diagnostic Coverage in Programmable Electronic Systems.

Using a Failure Modes, Effects and Diagnostic Analysis (FMEDA) to Measure Diagnostic Coverage in Programmable Electronic Systems. Using a Failure Modes, Effects and Diagnostic Analysis (FMEDA) to Measure Diagnostic Coverage in Programmable Electronic Systems. Dr. William M. Goble exida.com, 42 Short Rd., Perkasie, PA 18944 Eindhoven

More information

SIL manual. Structure. Structure

SIL manual. Structure. Structure With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central

More information

IEC 61508 Functional Safety Assessment. United Electric Controls Watertown, MA USA

IEC 61508 Functional Safety Assessment. United Electric Controls Watertown, MA USA IEC 61508 Functional Safety Assessment Project: One Series Safety Transmitter Customer: United Electric Controls Watertown, MA USA Contract No.: Q12/10-073 Report No.: UEC 1210073 R002 Version V1, Revision

More information

Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability

Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability 2 Improving Safety Instrumented System Reliability Improving Safety Instrumented System Reliability 3 Safety Instrumented

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions The exida 61508 Certification Program V1 R8 October 19, 2007 exida Geneva, Switzerland Sellersville, PA 18960, USA, +1-215-453-1720 Munich, Germany, +49 89 4900 0547 1 Exida

More information

Value Paper Author: Edgar C. Ramirez. Diverse redundancy used in SIS technology to achieve higher safety integrity

Value Paper Author: Edgar C. Ramirez. Diverse redundancy used in SIS technology to achieve higher safety integrity Value Paper Author: Edgar C. Ramirez Diverse redundancy used in SIS technology to achieve higher safety integrity Diverse redundancy used in SIS technology to achieve higher safety integrity Abstract SIS

More information

Viewpoint on ISA TR84.0.02 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President

Viewpoint on ISA TR84.0.02 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President Viewpoint on ISA TR84.0.0 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President Presented at Interkama, Dusseldorf, Germany, October 1999, Published in ISA Transactions,

More information

Safety Manual BT50(T) Safety relay / Expansion relay

Safety Manual BT50(T) Safety relay / Expansion relay Safety Manual BT50(T) Safety relay / Expansion relay ABB Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this document

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions The exida Certification Program Functional Safety (SIL) Cyber-Security V2 R3 June 14, 2012 exida Sellersville, PA 18960, USA, +1-215-453-1720 Munich, Germany, +49 89 4900 0547

More information

IEC 61508 Overview Report

IEC 61508 Overview Report IEC 61508 Overview Report A Summary of the IEC 61508 Standard for Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems exida Sellersville, PA 18960, USA +1-215-453-1720

More information

Mobrey Magnetic Level Switches

Mobrey Magnetic Level Switches Horizontal Float Switch Mobrey Magnetic Level Switches www.emersonprocess.com Horizontal Float Switch Contents Introduction Scope and Purpose of the Safety Manual...page 3 Skill Level Requirement...page

More information

WELLHEAD FLOWLINE PRESSURE PROTECTION USING HIGH INTEGRITY PROTECTIVE SYSTEMS (HIPS)

WELLHEAD FLOWLINE PRESSURE PROTECTION USING HIGH INTEGRITY PROTECTIVE SYSTEMS (HIPS) WELLHEAD FLOWLINE PRESSURE PROTECTION USING HIGH INTEGRITY PROTECTIVE SYSTEMS (HIPS) Angela E. Summers, Ph.D., P.E., President, SIS-Tech Solutions, LP Bryan A. Zachary, Director, Product & Application

More information

Machineontwerp volgens IEC 62061

Machineontwerp volgens IEC 62061 Machineontwerp volgens IEC 62061 Insert Photo Here Safety solution Architect Safety Local Business Leader Benelux. Stephen Podevyn Safety Solution Seminar Agenda deel 1 1. Richtlijnen en normen 2. Safety

More information

Logic solver application software and operator interface

Logic solver application software and operator interface Logic solver application software and operator interface By RJ Perry, Control Systems Consultant Correctly implemented and structured functional logic, together with operator interface displays, can improve

More information

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4" to 1" NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4 to 1 NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power .55 W Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies /" to " NPT / 3/ / 5/ 5/3 Features Molded one-piece solenoid with highly efficient solenoid cartridge and.55 W low wattage coil Standard

More information

Safety controls, alarms, and interlocks as IPLs

Safety controls, alarms, and interlocks as IPLs Safety controls, alarms, and interlocks as IPLs Angela E. Summers, Ph.D., P.E. SIS-TECH Solutions 12621 Featherwood Dr. Suite 120, Houston, TX 77034 Keywords: safety controls, alarms, interlocks, SIS,

More information

Overview of IEC 61508 - Design of electrical / electronic / programmable electronic safety-related systems

Overview of IEC 61508 - Design of electrical / electronic / programmable electronic safety-related systems Overview of IEC 61508 - Design of electrical / electronic / programmable electronic safety-related systems Simon Brown The author is with the Health & Safety Executive, Magdalen House, Bootle, Merseyside,

More information

Vetting Smart Instruments for the Nuclear Industry

Vetting Smart Instruments for the Nuclear Industry TS Lockhart, Director of Engineering Moore Industries-International, Inc. Vetting Smart Instruments for the Nuclear Industry Moore Industries-International, Inc. is a world leader in the design and manufacture

More information

SIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen. 61508 Compliance of Actuators and Life Cycle Considerations. SAMSON AG Dr.

SIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen. 61508 Compliance of Actuators and Life Cycle Considerations. SAMSON AG Dr. SIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen SAMSON AG Dr. Thomas Karte 61508 Compliance of Actuators and Life Cycle Considerations 2015-04-23 SAMSON AG Dr. Karte - 61508 Compliance of

More information

SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR

SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR The information and any recommendations that may be provided herein are not intended

More information

Reducing Steps to Achieve Safety Certification

Reducing Steps to Achieve Safety Certification Reducing Steps to Achieve Safety Certification WP-01174-1.0 White Paper This white paper describes the successful steps in achieving certification for an FPGA implementation of an application certified

More information

SILs and Software. Introduction. The SIL concept. Problems with SIL. Unpicking the SIL concept

SILs and Software. Introduction. The SIL concept. Problems with SIL. Unpicking the SIL concept SILs and Software PG Bishop Adelard and Centre for Software Reliability, City University Introduction The SIL (safety integrity level) concept was introduced in the HSE (Health and Safety Executive) PES

More information

A PROCESS ENGINEERING VIEW OF SAFE AUTOMATION

A PROCESS ENGINEERING VIEW OF SAFE AUTOMATION A PROCESS ENGINEERING VIEW OF SAFE AUTOMATION Published in Chemical Engineering Progress, December 2008. Angela E. Summers, SIS-TECH Solutions, LP This step-by-step procedure applies instrumented safety

More information

Michael A. Mitchell, Cameron Flow Control, DYNATORQUE Product Manager

Michael A. Mitchell, Cameron Flow Control, DYNATORQUE Product Manager SIL Made Simple Michael A. Mitchell, Cameron Flow Control, DYNATORQUE Product Manager KEY WORDS: Safety Integrity Level (SIL) Safety Instrumented Systems (SIS) ISA 84.01, IEC 61511 Partial Stroke Test

More information

INSIDE THIS ISSUE KUWAIT SECTION. December NEWSLETTER 2009 FROM SECTION PRESIDENT S DESK TECHNICAL WINDOW MEMBERS AREA PRODUCT REVIEW

INSIDE THIS ISSUE KUWAIT SECTION. December NEWSLETTER 2009 FROM SECTION PRESIDENT S DESK TECHNICAL WINDOW MEMBERS AREA PRODUCT REVIEW KUWAIT SECTION December NEWSLETTER 2009 INSIDE THIS ISSUE TECHNICAL WINDOW MEMBERS AREA PRODUCT REVIEW FROM SECTION PRESIDENT S DESK I am pleased to release the December 2009 Newsletter of ISA- Kuwait

More information

Safety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September 2010. Answers for industry.

Safety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September 2010. Answers for industry. SIMATIC Safety Matrix The Management Tool for all Phases of the Safety Lifecycle Brochure September 2010 Safety Integrated Answers for industry. Functional safety and Safety Lifecycle Management Hazard

More information

ISO 26262:2011 Functional Safety Assessment Report. Texas Instruments Richardson, TX USA. Project: TDA2X ADAS SoC. Customer:

ISO 26262:2011 Functional Safety Assessment Report. Texas Instruments Richardson, TX USA. Project: TDA2X ADAS SoC. Customer: ISO 26262:2011 Functional Safety Report Project: TDA2X ADAS SoC Customer: Texas Instruments Richardson, TX USA Contract No.: Q13/09-037 Report No.: TI 13-09-037 R002 Version V1, Revision R1, January 23,

More information

Mary Ann Lundteigen. Doctoral theses at NTNU, 2009:9 Mary Ann Lundteigen. Doctoral theses at NTNU, 2009:9

Mary Ann Lundteigen. Doctoral theses at NTNU, 2009:9 Mary Ann Lundteigen. Doctoral theses at NTNU, 2009:9 Mary Ann Lundteigen Doctoral theses at NTNU, 2009:9 Mary Ann Lundteigen Safety instrumented systems in the oil and gas industry: Concepts and methods for safety and reliability assessments in design and

More information

Mitigating safety risk and maintaining operational reliability

Mitigating safety risk and maintaining operational reliability Mitigating safety risk and maintaining operational reliability Date 03/29/2010 Assessment and cost-effective reduction of process risks are critical to protecting the safety of employees and the public,

More information

Is your current safety system compliant to today's safety standard?

Is your current safety system compliant to today's safety standard? Is your current safety system compliant to today's safety standard? Abstract It is estimated that about 66% of the Programmable Electronic Systems (PES) running in the process industry were installed before

More information

IEC 61508 Where do the lambda values originate?

IEC 61508 Where do the lambda values originate? IEC 61508 Where do the lambda values originate? Introduction Dipl.-Ing. (Univ.) Stephan Aschenbrenner, exida.com GmbH Why to ask this question? IEC 61508 SIL PFD / PFH SFF Calculate λ safe, λ dd, λ du

More information

Valves and Solenoid Valves testet and certified byrheinhold & Mahla according to IEC 61508/61511

Valves and Solenoid Valves testet and certified byrheinhold & Mahla according to IEC 61508/61511 Valves and Solenoid Valves testet and certified byrheinhold & Mahla according to IEC 61508/61511 Manfred Dietz Manfred.dietz@rum.de +49-69-305 2663 SAMSON Dr. Thomas Karte Tkarte@samson.de +49-69-4009

More information

Safety Integrity Level (SIL) Assessment as key element within the plant design

Safety Integrity Level (SIL) Assessment as key element within the plant design Safety Integrity Level (SIL) Assessment as key element within the plant design Tobias WALK ILF Consulting Engineers GmbH Germany Abstract Special attention has to be provide to safety instrumented functions

More information

Application Technique. Safety Function: Magnetic Door Switch Monitoring

Application Technique. Safety Function: Magnetic Door Switch Monitoring Application Technique Safety Function: Magnetic Door Switch Monitoring Products: MC1 Magnetically-coded Door Switch, Guardmaster Dual-input Safety Relay Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008

More information

DeltaV SIS for Burner Management Systems

DeltaV SIS for Burner Management Systems January 2011 Page 1 DeltaV SIS for Burner Management Systems RESULTS Inhibit startup when unsafe conditions exist Protect against unsafe operating conditions, including improper fuel quantities Provide

More information

ISO 26262 Introduction

ISO 26262 Introduction ISO 26262 Introduction Prof. Christian Madritsch 2012 Table of Contents Structure of ISO 26262 Management of Functional Safety Product Development System Level Product Development Hardware Level Product

More information

Fisher FIELDVUE DVC6200 SIS Digital Valve Controller for Safety Instrumented Systems (SIS)

Fisher FIELDVUE DVC6200 SIS Digital Valve Controller for Safety Instrumented Systems (SIS) DVC6200 SIS Digital Valve Controller Product Bulletin Fisher FIELDVUE DVC6200 SIS Digital Valve Controller for Safety Instrumented Systems (SIS) The FIELDVUE DVC6200 SIS digital valve controller is a HART

More information

Reduce Risk with a State-of-the-Art Safety Instrumented System. Executive Overview... 3. Risk Reduction Is the Highest Priority...

Reduce Risk with a State-of-the-Art Safety Instrumented System. Executive Overview... 3. Risk Reduction Is the Highest Priority... ARC WHITE PAPER By ARC Advisory Group SEPTEMBER 2004 Reduce Risk with a State-of-the-Art Safety Instrumented System Executive Overview... 3 Risk Reduction Is the Highest Priority... 4 Safety Standards

More information

TECHNICAL SPECIFICATION. StirLIN-1 Economy Liquid Nitrogen System

TECHNICAL SPECIFICATION. StirLIN-1 Economy Liquid Nitrogen System TECHNICAL SPECIFICATION StirLIN-1 Economy Liquid Nitrogen System Reference 80 8120_01 Issue Date August 1, 2015 1. INTRODUCTION Since more than sixty years Stirling Cryogenics has designed and manufactured

More information

SOFTWARE-IMPLEMENTED SAFETY LOGIC Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions, LP

SOFTWARE-IMPLEMENTED SAFETY LOGIC Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions, LP SOFTWARE-IMPLEMENTED SAFETY LOGIC Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions, LP Software-Implemented Safety Logic, Loss Prevention Symposium, American Institute of Chemical Engineers,

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

USING INSTRUMENTED SYSTEMS FOR OVERPRESSURE PROTECTION. Dr. Angela E. Summers, PE. SIS-TECH Solutions, LLC Houston, TX

USING INSTRUMENTED SYSTEMS FOR OVERPRESSURE PROTECTION. Dr. Angela E. Summers, PE. SIS-TECH Solutions, LLC Houston, TX USING INSTRUMENTED SYSTEMS FOR OVERPRESSURE PROTECTION By Dr. Angela E. Summers, PE SIS-TECH Solutions, LLC Houston, TX Prepared for Presentation at the 34 th Annual Loss Prevention Symposium, March 6-8,

More information

TÜV Rheinland Functional Safety Program Functional Safety Engineer Certification

TÜV Rheinland Functional Safety Program Functional Safety Engineer Certification TÜV Rheinland Functional Safety Program Functional Safety Engineer Certification The TÜV Rheinland Functional Safety Program is a unique opportunity to provide certified evidence of competency in functional

More information

The updated PDS method With a focus on systematic failures

The updated PDS method With a focus on systematic failures The updated PDS method With a focus on systematic failures ESReDA, 07. June 2006 Stein Hauge, SINTEF Content 1. Introduction - what is PDS? 2. Related standards 3. Systematic failures in PDS 4. Summary

More information

FMEA FMEA basic concept Rigorous FMEA - State Explosion This talk introduces Failure Mode Effects Analysis, and the different ways it is applied. Thes

FMEA FMEA basic concept Rigorous FMEA - State Explosion This talk introduces Failure Mode Effects Analysis, and the different ways it is applied. Thes FMEA FMEA basic concept Rigorous FMEA - State Explosion 1 / 161 FMEA FMEA basic concept Rigorous FMEA - State Explosion This talk introduces Failure Mode Effects Analysis, and the different ways it is

More information

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs) Oct 2010 Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs) A study on worldwide relays market found the market size of solid state relays to be between $200M and $600M, which represent 17% of

More information

PABIAC Safety-related Control Systems Workshop

PABIAC Safety-related Control Systems Workshop Health and and Safety Executive PABIAC Safety-related Control Systems Workshop KEY STANDARDS FOR ELECTRICAL & FUNCTIONAL SAFETY OF PAPERMAKING MACHINES: APPLICATION & USE Steve Frost HM Principal Electrical

More information

I requisiti delle Norme IEC EN 61508 Ed 2: 2010 e IEC EN 61511 Ed. 2: 2016

I requisiti delle Norme IEC EN 61508 Ed 2: 2010 e IEC EN 61511 Ed. 2: 2016 I requisiti delle Norme IEC EN 61508 Ed 2: 2010 e IEC EN 61511 Ed. 2: 2016 18 Febbraio 2016 G. Picciolo Agenda The Norm IEC EN 61508 Ed. 2: 2010 overview Normative & informative requirements The new Norm

More information

Announcement of a new IAEA Co-ordinated Research Programme (CRP)

Announcement of a new IAEA Co-ordinated Research Programme (CRP) Announcement of a new IAEA Co-ordinated Research Programme (CRP) 1. Title of Co-ordinated Research Programme Design and engineering aspects of the robustness of digital instrumentation and control (I&C)

More information

Space project management

Space project management ECSS-M-ST-80C Space project management Risk management ECSS Secretariat ESA-ESTEC Requirements & Standards Division Noordwijk, The Netherlands Foreword This Standard is one of the series of ECSS Standards

More information

University of Paderborn Software Engineering Group II-25. Dr. Holger Giese. University of Paderborn Software Engineering Group. External facilities

University of Paderborn Software Engineering Group II-25. Dr. Holger Giese. University of Paderborn Software Engineering Group. External facilities II.2 Life Cycle and Safety Safety Life Cycle: The necessary activities involving safety-related systems, occurring during a period of time that starts at the concept phase of a project and finishes when

More information

AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6

AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6 AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2

More information

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04 Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping

More information

Automation, Software and Information Technology. Test report of the type approval safety-related automation devices

Automation, Software and Information Technology. Test report of the type approval safety-related automation devices Automation, Software and Information Technology Test report of the type approval safety-related automation devices GuardPLC 1200 GuardPLC 1600 GuardPLC 1800 GuardPLC 2000 GuardPLC Distributed I/O Report-No.:

More information

What is CFSE? What is a CFSE Endorsement?

What is CFSE? What is a CFSE Endorsement? ENDORSEMENT PROGRAM The CFSE endorsement program helps current holders of CFSE and CFSP certification build /demonstrate expertise and knowledge in specific focus areas of functional safety. What is CFSE?

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

Version: 1.0 Last Edited: 2005-10-27. Guideline

Version: 1.0 Last Edited: 2005-10-27. Guideline Process hazard and risk Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary This report will try

More information

ESTIMATION AND EVALUATION OF COMMON CAUSE FAILURES IN SIS

ESTIMATION AND EVALUATION OF COMMON CAUSE FAILURES IN SIS ESTIMATION AND EVALUATION OF COMMON CAUSE FAILURES IN SIS Angela E. Summers, Ph.D., Director Kimberly A. Ford, Senior Risk Analyst, and Glenn Raney, Technical Specialist Premier Consulting + Engineering,

More information

Take a modern approach to increase safety integrity while improving process availability. DeltaV SIS Process Safety System

Take a modern approach to increase safety integrity while improving process availability. DeltaV SIS Process Safety System Take a modern approach to increase safety integrity while improving process availability. DeltaV SIS Process Safety System Whether standalone or integrated, choose a smart, modern safety system designed

More information

A descriptive definition of valve actuators

A descriptive definition of valve actuators A descriptive definition of valve actuators Abstract A valve actuator is any device that utilizes a source of power to operate a valve. This source of power can be a human being working a manual gearbox

More information

Application Engineering

Application Engineering Application Engineering February 2012 Digital Capacity Control for Copeland Scroll Refrigeration Compressors INDEX Page 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 1 4. Digital

More information

TÜV FS Engineer Certification Course www.silsupport.com www.tuv.com. Being able to demonstrate competency is now an IEC 61508 requirement:

TÜV FS Engineer Certification Course www.silsupport.com www.tuv.com. Being able to demonstrate competency is now an IEC 61508 requirement: CC & technical support services TÜV FS Engineer Certification Course www.silsupport.com www.tuv.com Being able to demonstrate competency is now an IEC 61508 requirement: CAPITALISE ON EXPERT KNOWLEDGE

More information

Safety Integrity Levels

Safety Integrity Levels Séminaire de Sûreté de Fonctionnement de l X Safety Integrity Levels Antoine Rauzy École Polytechnique Agenda Safety Integrity Levels and related measures as introduced by the Standards How to interpreted

More information

Wet Bulb Temperature and Its Impact on Building Performance

Wet Bulb Temperature and Its Impact on Building Performance Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?

More information

Methods of Determining Safety Integrity Level (SIL) Requirements - Pros and Cons

Methods of Determining Safety Integrity Level (SIL) Requirements - Pros and Cons Methods of Determining Safety Integrity Level (SIL) Requirements - Pros and Cons 1 Introduction by W G Gulland (4-sight Consulting) The concept of safety integrity levels (SILs) was introduced during the

More information

Safety Integrity Level (SIL) Studies Germanischer Lloyd Service/Product Description

Safety Integrity Level (SIL) Studies Germanischer Lloyd Service/Product Description Safety & Risk Management Services Safety Integrity Level (SIL) Studies Germanischer Lloyd Service/Product Description Germanischer Lloyd Service/Product Description Safety Integrity Level (SIL) Studies

More information

Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives

Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives User Manual Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives Catalog Number 20A-DG01 Topic Page General Description 2 What Is the DriveGuard Safe Torque Off

More information

ELECTROTECHNIQUE IEC INTERNATIONALE 61508-3 INTERNATIONAL ELECTROTECHNICAL

ELECTROTECHNIQUE IEC INTERNATIONALE 61508-3 INTERNATIONAL ELECTROTECHNICAL 61508-3 ª IEC: 1997 1 Version 12.0 05/12/97 COMMISSION CEI ELECTROTECHNIQUE IEC INTERNATIONALE 61508-3 INTERNATIONAL ELECTROTECHNICAL COMMISSION Functional safety of electrical/electronic/ programmable

More information

UNDERSTANDING SAFETY INTEGRITY LEVEL

UNDERSTANDING SAFETY INTEGRITY LEVEL UNDERSTANDING SAFETY INTEGRITY LEVEL S p e c i a l A p p l i c a t i o n S e r i e s 2 THE NEW STANDARDS IN SAFETY On the morning of 12/11/05, the largest detonation since the end of WWII rocked the Buncefield

More information

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT ALARM SYSTEMS Peace of Mind Agri-Alert is a complete alarm system for monitoring temperature, power, feed and watering systems, burglary,

More information

Reliability Block Diagram RBD

Reliability Block Diagram RBD Information Technology Solutions Reliability Block Diagram RBD Assess the level of failure tolerance achieved RELIABIL ITY OPTIMIZATION System reliability analysis for sophisticated and large scale systems.

More information

4 Dynamic Solutions. Leadership and Innovation in Valve Products and Valve Systems

4 Dynamic Solutions. Leadership and Innovation in Valve Products and Valve Systems Dynamic Solutions Leadership and Innovation in Valve Products and Valve Systems At ASCO, Valve Performance Begins and Ends With People 4 First of all, it begins with the people we serve. It is from them

More information

No. : EX##-OMF0004 OPERATION MANUAL. SI unit EX12#-SMB1

No. : EX##-OMF0004 OPERATION MANUAL. SI unit EX12#-SMB1 No. : EX##-OMF0004 OPERATION MANUAL EX12#-SMB1 Contents 1. Safety instructions ------------------------------------------------------ P3 2. Notes ------------------------------------------------------

More information

Functional safety in process instrumentation with SIL rating Questions, examples, background

Functional safety in process instrumentation with SIL rating Questions, examples, background Functional safety in process instrumentation with SIL rating Questions, examples, background Brochure April 2007 Since the rlease of IEC 61508, the topic of "Functional safety" in the process industry

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.

More information