Installation and Maintenance instructions for MV-Power Capacitors

Size: px
Start display at page:

Download "Installation and Maintenance instructions for MV-Power Capacitors"

Transcription

1 MV Power Capacitors Power Factor Correction Installation and Maintenance instructions for MV-Power Capacitors Series/Type : Ordering Code : B2516 Date : Feb 2009 Version : 1.1 EPCOS AG 2008, Reproduction, Publication and dissemination of this data sheet, enclosures hereto and the information contained therein without EPCOS prior consent is prohibited 1

2 Installation and maintenance instructions for MV Power Capacitors Preliminary data Installation and Maintenance Instructions Read This First : About this manual For your safety! Read the following >> Installation and maintenance instructions << carefully before installing a Capacitor into your application. The information stated in this manual applies to typical, approved usage. Please refer to our product specifications, or request our approval for your own individual specifications, before installing Capacitor Disregarding the guidelines in this manual can result in operational failure bursting and fire. In case of doubt, contact your local EPCOS sales organization or distributor for assistance. General safety notes for Ensure you are using the right Capacitor for your application, please refer to installation and operation the EPCOS product catalogue and application notes for proper selection of Capacitor and its configuration. Maintain good and effective grounding for Capacitor Provide the means to isolate any faulty units/ banks in the system Follow proper engineering practices Storage and operation Conditions Donot use or keep Capacitor in corrosive atmosphere, especially where as, sulphide gas, acid, alkali, salt or similar substances are present. In a dusty environment, regular maintenance and cleaning, especially of the contacts, is required to avoid a conductive path between phases and /or phases and ground. The panel has to be stored with outer packing intact in a covered area under protection from rain. The panel should stand in vertical position as indicated in the packing crate. Ambient temperature : The ambient temperature category for most standard types is -40D. This means a max. temperature of 55DegC, an average temperature over 24 hours of 45DegC, and the average temperature in one year should not exceed 35 Deg C. 2

3 Installation and maintenance instructions for MV Power Capacitors Preliminary data Caution: 3

4 Installation and maintenance instructions for MV Power Capacitors Preliminary data Unpacking & Inspection While taking the delivery of capacitors, check for any visual damage to the boxes/crates and for any trace of oil on the cases. In case of damage or leakage insist on open delivery and obtain open delivery certificate. Open the cases carefully and check whether the ratings of capacitors are in line with the order, packing list or bill of materials. Check for any damage especially for a) Any breakage of bushings or insulators b) Leakage of oil from the bushing top/base or from capacitor container and c) Any denting or damage to terminal cover, bank frames, bus bars and other accessories. In case capacitor units/other material found damaged insurance claim must be lodged. If insurance is done by EPCOS, intimation should be sent within 10 days giving details of damage. Open delivery certificate should accompany if the cases were damaged. If the cases were intact and damage was found subsequently after opening the cases it should be mentioned in the letter and the cases should be kept in safe custody for inspection and further advice from insurer. If the bushings are broken or lot of oil has leaked out from the capacitor making it un-repairable at site, such capacitors should be sent back to EPCOS for possible repairs after taking consent of EPCOS. Minor leakage can be repaired at site by applying EPCOS recommended adhesive. If site for installation is not ready, capacitors should be stored at a proper place with bushing in upward position. Any hair crack developed during handling may not show the leakage at the time of storing the capacitor and may show up afterwards; hence it is advisable to check once again after a week. Store in a place where capacitors are not required to be handled for removing or keeping other 4

5 equipments in the Store. Do not keep anything on the capacitors to avoid damage to the bushing. Installation Install capacitors in cool dry place, which should also be free from excessive dust and chemical fumes. Capacitors should be installed away from the heat generating bodies. Upper limit of temperature category in C, Clean the bushings of capacitors with cloth for dust and oil stains. Tighten all electrical and mechanical connections. Avoid over tightening of capacitor bushing terminals. Also take care while connecting bus bars so that no stress comes on capacitor bushing. Ensure that the ambient temperature at capacitor location does not exceed beyond the limits specified in the table below: Mean over 1 hour Maximum ambient temperature in C Mean over 24 hours Mean over 1 Year EPCOS Capacitors are made as per 50 C upper limit of temperature category. Ambient temperature at capacitor location should be measured 1 to 2 meters away from capacitors. Ensure free circulation of air around the capacitors. Adequate clearance (minimum 300 mm) should be provided between walls and capacitors for heat radiation. Cooling temperature should not be more than 5 C above ambient measured at the hottest point in the bank i.e. mid way between two capacitor units or at 30 cm away from a capacitor at its 3/4 height in case one capacitor is involved. The site work such as banking of capacitor units, connections of bus bars / fuses should be done as per the drawings provided. Adequate clearances should be maintained. Minimum clearance required as per BS: 162 are given below for guidance. 5

6 Rated Clearance in mm. Voltage Indoor Out door In KV Phase to Phase Phase to Earth Phase to Phase Phase to Earth Up to When capacitors are mounted on an open structure of angles and channels, their live parts are exposed and accessible. Such banks are required to be elevated to minimum 2.5 mtrs from ground level by providing elevating structures or fencing is erected all round the capacitor bank keeping adequate clearances as given above to eliminate the possibility of any one touching the live parts of the bank. Elevating structure or the fencing should be earthed as per IS:3043. When capacitor has an external fuse protection it should be ensured that fuse is connected to individual capacitor unit. Do not connect one fuse to more than one capacitor unit. It should be ascertained that the breaker used for capacitor switching is restrike free, if on-load isolators are used for pole mounted capacitors or for small banks, it should be ensured that they are suitable for capacitor duty. Whenever off-load isolator is connected between capacitors and the breaker, it is advisable to interlock the isolator with the breaker in such a way that the isolator can be opened or closed only when the breaker is in open condition. When capacitors are directly connected to the motors, it is advised that the capacitor current is not more than 90% of the no load motor current. Motor draws lesser current from the source when connected with the capacitors. Hence its over current setting should be reduced accordingly. Unless specifically agreed capacitors are provided with discharge resistors to discharge the capacitors within 600 seconds to safe voltage. When capacitors are required to be reswitched earlier than 600 seconds PT/RVT can be provided for quick discharge. PTs/RVTs have secondary winding which can be connected to indicating lamps to show that capacitors have discharged. When capacitors are required to be reswitched within couple of seconds 6

7 an interlock through secondary winding of PT/RVT can be provided to ensure that at the time of reswitching capacitors have discharged to safe value. Capacitor units and the bank should be earthed at earth points provided. Capacitors with live containers and banking structure should not be earthed. All auxiliary equipments should also be earthed at earthing points provided. Commissioning Before energizing the bank check all the equipments as per the checks mentioned in commissioning report format given at the end. Megger the capacitor bank between phases and earth. The megger reading for individual capacitor should not be less than 50 Mega ohms, for more than one unit in parallel minimum acceptable megger value can be derived by dividing 50 Mega ohms by the number of units connected in parallel. Complete installation with all the equipments connected to capacitors should be meggered between shorted phases and earth and should be in line with acceptable capacitor megger value. Now the capacitor bank is ready for energization. Before switching on capacitor bus voltage, system incoming load current and power factor (if meter available) can be noted. After energizing check that capacitor draws almost balance current in all the 3 phases and is near to its rated value. Note the change in bus voltage, load current and system power factor. Normally after capacitors are energised, there will be little rise in the bus voltage and some reduction in the system load current and naturally improvement in power factor. In case load current increases instead or reducing, it shows that capacitors connected are more than required for the load and in this case the power factor shall be leading. When PT/RVT is used for unbalance protection, measure open delta voltage, which should be negligible. In case capacitors are connected in double star with neutral CT, the current on the secondary side of neutral CT can be measured, which should also be negligible. 7

8 After a few hours (12 to 24 hrs.) of continuous operation capacitor bank can be switched off and the capacitor units should be checked for any leakage, excess temperature rise of the container and of other equipments. Series Reactors if provided should have temperature rise within prescribed limit. In an event everything is in order then capacitor bank can be re-energized and kept in operation. Operation Voltage on the capacitors should be near to its rated voltage. It should be ensured that the voltage including fluctuations in the system do not exceed 110% of the capacitor name plate voltage. Variation in currents in the three phases should be within ±5% and rating should be within 5 to +10% of rated current. If there are harmonics present in the system, it may increase the current in capacitor. However, this current should not exceed 13O% of rating mentioned on the name plate. Temperature of capacitor container can be measured by fixing a thermometer on the wall of the container, its bulb being at one fourth of the height of capacitor down from the top. Hourly readings of capacitor current, voltage should be maintained. Open delta voltage of RVT or current of neutral CT can be measured once in a day and logged. If capacitors installed are for indoor applications, their ambient temperature should be logged at least three times a day, morning, noon time and in the evening. If exhaust fans or air circulators are provided to maintain ambient, it should be ensured that they are always ON, when capacitors are in operation. Internal discharge resistances are fitted across capacitor terminals to reduce the voltage on switching off to less than 50 volts within 10 minutes. Capacitor should not be handled during this period. For human safety it is advisable to ground the capacitor bank with grounding rod before handling. Preventive Maintenance Capacitors should be maintained periodically, preferably once a month. Capacitors including bushings should be cleaned of dust etc. All connections should be checked for its proper tightness. 8

9 Any rusty portion should be cleaned and then given a coat of paint. Capacitor units should be checked for any leakage. Other associated equipments specially breakers should be maintained as per manufacturer s recommended practice. Oil of series reactor and RVT should be checked for its breakdown strength periodically. Normally capacitors once installed and operated as recommended practice should give long and trouble free service. However, in the event of encountering any trouble, users may refer to the table below which gives some of the common troubles encountered with its causes and remedies to take appropriate action. Trouble Cause Remedial action 1. Leakage of oil from capacitor bushing or welded joints. a) Minor transit damage which remained undetected. b) Due to tension coming on bushing. c) Due to overheating of unit a) For minor leakage apply adhesive or solder on leaky welded joints. if leakage does not stop replace the unit and refer to manufacturer for possible repairs. (Refer Note 1) b) Check & tighten the connections to avoid tension coming on bushing, repair capacitor as stated above. c) Refer Serial No. 2 for action. 2. Over heating of units a) Poor ventilation, a) Provide free circulation of cooling air. b) Excessive ambient. b) Arrange forced ventilation c) Drawing excessive current. c) Refer Sr. No. 3 for action 3. Capacitor drawing high current d) None of the above d) Refer to the manufacturer causes. a) High voltage, a) Reduce voltage by changing transformer taps or switch off the bank. 9

10 b) Harmonic current flowing b) It current beyond permissible limit, switch-off capacitor bank and take remedial measures to reduce harmonics flowing in capacitors. 4. Capacitors drawing less current. a) Low voltage, a) Current directly proportional to voltage No repairs required. b) Failure of capacitor unit with blown fuses. b) If one or more units have failed and it has not been detected by neutral unbalance relay, check whether unit has failed or fuse has spuriously blown. If unit fails replace the unit. Refer Note 2. c) Partial failure of unit. c) In case of internal fused capacitors sometimes partial failure in various units may occur which cannot be detected by neutral unbalance relay. Check the whole bank for capacitance and regroup them. Remove units having capacitance less than 95% of the rated value. Also check if neutral unbalance limit is set Correctly. Refer Note Expulsion fuses blowing too frequently but unit is healthy. 6. Expulsion fuse not blowing but unit has failed. 7. Abnormal bulging/bursting. 8. Abnormal sound and black marks noticed on bushing a) Expulsion fuse rating may not be of adequate value. b) Expulsion fuse for one unit connected to more than one unit. a) Expulsion fuse rating may be high. a) Gas formation due to internal arcing Causing unit to bulge or burst. a) External earth fault between terminal and container. a) Check expulsion fuse rating. Consult manufacturer by providing complete bank details. Refer Note 3(a). b) Connect one fuse with one unit. a) Check expulsion fuse rating. Consult manufacturer by providing complete bank & system details. Refer Note 3(a). a) Replace the unit and refer to the manufacturer. a) Clean the bushings and check installation for any short circuit. 10

11 and near by. b) High voltage surges due to lightning or due to restriking of breaker. b) Consult the manufacturer s application engineer. Refer Note 3(b). 9. Terminal overheated or melted a) Loose contact. a) Tighten the connections. Replace the damaged capacitors. 10. Capacitor bank tripping on unbalance protection but expulsion fuse not blown. a) Co-ordination of expulsion fuse blowing with neutral protection is not proper. a) Check and consult with manufacturer s application Engineer. Note: 1. Minor leakage from bushing can be repaired as follows: Turn the unit and place in such a way that the leaky portion will remain on the top. Clean the area by carbon tetra chloride and wipe of with a clean cloth. Apply Araldite and then allow it to cure in that position for 8 hours. Put the unit back in to the circuit after 24 hours. For minor leakages on the welded joints or metal terminals turn the unit to keep the leaky portion on the top. Clean the surface with carbon tetra chloride and wipe the area with clean cloth. Solder the leaky portion using soldering iron of suitable wattage. Avoid using excess solder. Wipe/ clean the soldered area for any residual flux. Keep the unit for 10 minutes in that position and then put the unit back in to the service. 2. Following methods can be adopted to check failure of a capacitor unit: (a) Capacitor with external fuse: (b) Capacitor with internal element fuse: Megger with 500V megger between 2 terminals of capacitors. Completely failed unit will show zero megger value and healthy unit will show megger value of a few M.ohms, which corresponds the value of internal resistors. In case of capacitors with internal element fuse, megger will always show a few M. ohms corresponding to internal discharge resistor s value, whether unit is healthy or partially/completely failed. However, if the terminals are shorted immediately by shorting link, the spark can be noticed in case of healthy or partially failed unit. To distinguish between healthy and partially failed unit, 11

12 capacitance can be measured. If Capacitance Bridge is not available at site then 440 volts supply can be given across the two terminals and current drawn by the unit can be measured, which should be in direct proportion to the voltage applied. For example a 200 KVAR 7300 volts, 1- Phase capacitor has rated current of Amps. When tested at 440 volts the current will reduce in the ratio of 440/7300 to 1.65 Amps. Current drawn lower than this will show partial failure. 3.(a) (c) While referring to the manufacturer, provide the details of complete capacitor bank rating, individual unit rating, expulsion fuse rating whether series reactor used or not, if not cable length from breaker to capacitor, bank details of any parallel connected bank on the same bus, actual system fault level or incoming transformer rating with % impedance. Also arrange to furnish the single line diagram of the power system along with harmonic details if available. Please furnish full particulars of capacitor bank as well as the breaker used. Provide the complete details of lightning arrestors and its location with respect to capacitor if used for surge protection. If lightning arrestors are not used, state so. 12

13 Important Notes : The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of an electronic component could endanger human life or health (e.g. in accident prevention or lifesaving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of an electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as hazardous). Useful information on this will be found in our Material Data Sheets on the Internet ( Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. The aforementioned does not apply in the case of individual agreements deviating from the foregoing for customer-specific products. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the General Terms of Delivery for Products and Services in the Electrical Industry published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSSP, CTVS, DSSP, MiniBlue, MKK, MLSC, MotorCap, PCC, PhaseCap, PhaseMod, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at 13

Film Capacitors AC Capacitors

Film Capacitors AC Capacitors Series/Type: Ordering code: Date: Nov 2012 Version: 9 Super MotorCap, 450 V Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the table and

More information

xdsl splitter transformers

xdsl splitter transformers Series/Type: Ordering code: Date: 2010-06-01 Version: 1 Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the table and then change the color

More information

SMT inductors. SIMID series, SIMID 1812-A. Date: March 2008

SMT inductors. SIMID series, SIMID 1812-A. Date: March 2008 SMT inductors SIMID series, Series/Type: Data Sheet Date: March 2008 EPCOS AG 2008. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein

More information

NTC thermistors for temperature measurement

NTC thermistors for temperature measurement Series/Type: Ordering code: Date: 2008-12-18 Version: 1 Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the table and then change the color

More information

B3440 B39871B3440U410 May 28, 2015 2.2

B3440 B39871B3440U410 May 28, 2015 2.2 Short range devices Series/type: Ordering code: Date: Version: B39871U410 May 28, 2015 2.2 EPCOS AG 2015. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information

More information

Film Capacitors Power Electronic Capacitors

Film Capacitors Power Electronic Capacitors Film Capacitors Power Electronic Capacitors Series/Type: MKP C : B3236* ate: ugust 2013 Version: 5.0 Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please

More information

Ferrites and accessories

Ferrites and accessories EFD 25/13/9 Core and accessories Series/Type: B66421, B66422 Date: June 2013 Data Sheet EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the information

More information

Ferrites and accessories

Ferrites and accessories ETD 29/16/10 Core and accessories Series/Type: B66358, B66359 Date: June 2013 Data Sheet EPCOS AG 2013. Reproduction, publication and dissemination of this data sheet and the information contained therein

More information

PTC thermistors for overcurrent protection

PTC thermistors for overcurrent protection PTC thermistors for overcurrent protection Series/Type: B599*5 Date: February 2012 EPCOS AG 2012. Reproduction, publication and dissemination of this publication, enclosures hereto and the information

More information

GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT

GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT GENERAL: 1. The selection of switchgear for switching the capacitors should be done carefully. The circuit breaker

More information

Ferrites and accessories

Ferrites and accessories Toroids R 3.94 1.78 1.78 Series/Type: B64290P0732 Date: July 2014 Data Sheet EPCOS G 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained

More information

PTC thermistors as point level sensors

PTC thermistors as point level sensors PTC thermistors as point level sensors Glass-encapsulated, oil level sensing Series/Type: B59011E0160A040 Date: January 2016 EPCOS AG 2016. Reproduction, publication and dissemination of this publication,

More information

PTC thermistors for overcurrent protection

PTC thermistors for overcurrent protection PTC thermistors for overcurrent protection Series/Type: B598** Date: April 2014 EPCOS AG 2014. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained

More information

Ferrites and accessories

Ferrites and accessories Ferrites and accessories E 13/7/4 (EF 12.6) Core and accessories Series/Type: Date: June 2013 Data Sheet B66305, B66202, B66306, B66414 EPCOS AG 2015. Reproduction, publication and dissemination of this

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

PTC thermistors for overcurrent protection in telecom applications

PTC thermistors for overcurrent protection in telecom applications PTC thermistors for overcurrent protection in telecom applications Series/Type: Date: April 2014 EPCOS AG 2014. Reproduction, publication and dissemination of this publication, enclosures hereto and the

More information

Ferrites and accessories

Ferrites and accessories Ferrites and accessories RM 14, RM 14 LP Cores and accessories Series/Type: B65887, B65888 Date: June 2013 Data Sheet EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures

More information

12. Inspection and Maintenance

12. Inspection and Maintenance 12. and Maintenance Mandatory Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment of use, such as temperature, humidity, dust and vibration,

More information

NTC thermistors for inrush current limiting

NTC thermistors for inrush current limiting NTC thermistors for inrush current limiting Leaded and coated disks Series/Type: Date: October 2013 EPCOS AG 2013. Reproduction, publication and dissemination of this publication, enclosures hereto and

More information

SIOV metal oxide varistors

SIOV metal oxide varistors SIOV metal oxide varistors Leaded varistors, Series/Type: B722* Date: December 2011 EPCOS AG 2011. Reproduction, publication and dissemination of this publication, enclosures hereto and the information

More information

SIOV metal oxide varistors

SIOV metal oxide varistors SIOV metal oxide varistors Leaded varistors, Series/Type: B722* Date: December 2011 EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the information

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is

More information

NTC thermistors for temperature measurement

NTC thermistors for temperature measurement NTC thermistors for temperature measurement Series/Type: Date: February 2009 EPCOS AG 2009. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained

More information

PTC thermistors as limit temperature sensors

PTC thermistors as limit temperature sensors PTC thermistors as limit temperature sensors Series/Type: B59300 Date: January 2016 EPCOS AG 2016. Reproduction, publication and dissemination of this publication, enclosures hereto and the information

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual 12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

Unit 4: Electricity (Part 2)

Unit 4: Electricity (Part 2) Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Kit 106. 50 Watt Audio Amplifier

Kit 106. 50 Watt Audio Amplifier Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications

More information

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

NI-ZN BATTERY SPECIFICATION

NI-ZN BATTERY SPECIFICATION NI-ZN BATTERY SPECIFICATION 252000 Model Name: AA2500mWh(Ni-Zn) Issued Date: Sept. 2010 NICKEL ZINC BATTERY SPECIFICATION 1.APPLICATION The applicable range: This specification is available only for the

More information

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The

More information

INFRARED QUARTZ WALL HEATER

INFRARED QUARTZ WALL HEATER INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this

More information

Ducoterra Radiant Heating Panel Installation Manual

Ducoterra Radiant Heating Panel Installation Manual Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,

More information

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual Instruction Manual Option Card for Frequency Divider Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual and understand the description

More information

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. *00151* FEATURES Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. Silicon diodes with inherent surge protection operated at a conservative

More information

TIG INVERTER INSTRUCTION MANUAL

TIG INVERTER INSTRUCTION MANUAL TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4

More information

400 Amp Rechargeable Jump Start System RAC-HP082

400 Amp Rechargeable Jump Start System RAC-HP082 400 Amp Rechargeable Jump Start System RAC-HP082 MAINTENANCE Always inspect the tool before use to ensure the cables are in good condition and the clamps are clean and free from corrosion. Keep clean by

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

Seven function digital multimeter

Seven function digital multimeter Seven function digital multimeter 98025 Set up And Operating Instructions Distributed exclusively by Harbor Freight Tools. 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our website at: http://www.harborfreight.com

More information

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type) OPERATION MANUAL (Ceiling mounted duct type) VAM50FB VAM500FB VAM650FB VAM800FB VAM000FB VAM500FB VAM000FB 8 7 6 9 5 7 5 0 6 8 6 9 0 5 5 7 7 6 7 A A B B 5 6 5 6 7 VAM50F VAM800F VAM500F VAM500F VAM000F

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

Lithium Ion Battery Specifications

Lithium Ion Battery Specifications Lithium Ion Battery Specifications Type: Cylindrical Lithium Iron Phosphate Battery Mode: LFP-26650-3300 AA Portable Power Corp. Prepared by Checked by Approved by 1 . Product Specifications Type ------------

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

NTC thermistors for temperature measurement

NTC thermistors for temperature measurement NTC thermistors for temperature measurement Miniature sensors with bendable wires Series/Type: Date: February 2009 EPCOS AG 2009. Reproduction, publication and dissemination of this publication, enclosures

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Regulation IO-6.0: Electrical Safety Regulations

Regulation IO-6.0: Electrical Safety Regulations Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716

BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual A515 SAVE THESE INSTRUCTIONS AND READ ALL INSTRUCTIONS BEFORE USING THE HEATER. Dear customers, Thank you for selecting

More information

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION

More information

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

Instructions for Safe Use

Instructions for Safe Use Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only

More information

TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE TROUBLESHOOTING GUIDE LESTRONIC II BATTERY CHARGER FOR MOTIVE POWER BATTERIES PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment, it is important to read

More information

NTC thermistors for temperature measurement

NTC thermistors for temperature measurement NTC thermistors for temperature measurement Leaded NTC thermistors, lead spacing 5 mm Series/Type: Date: February 2009 EPCOS AG 2009. Reproduction, publication and dissemination of this publication, enclosures

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

Pet hair clipper. Model 96822. Diagrams within this manual may not be drawn proportionally.

Pet hair clipper. Model 96822. Diagrams within this manual may not be drawn proportionally. Pet hair clipper Model 96822 Cleaning And Operation Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly from the

More information

Aluminum electrolytic capacitors

Aluminum electrolytic capacitors Aluminum electrolytic capacitors Capacitors with screw terminals Series/Type: B43704, B43724 Date: December 2014 EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures

More information

CeraDiodes. High-speed series. Series/Type: Date: April 2016

CeraDiodes. High-speed series. Series/Type: Date: April 2016 Series/Type: Date: April 2016 EPCOS AG 2016. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without EPCOS' prior express consent

More information

SMD Rework Station TABLE OF CONTENTS

SMD Rework Station TABLE OF CONTENTS SMD Rework Station Thank you for purchasing the Hakko 50B SMD Rework Station. The Hakko 50B is designed to solder and desolder surface mounted devices with hot air. Please read this manual before operating

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: info@switchgearcompany.eu

More information

Wine Cooler with Thermo-Electric Cooling & Heating Technology

Wine Cooler with Thermo-Electric Cooling & Heating Technology Wine Cooler with Thermo-Electric Cooling & Heating Technology Model number: WC-0888H (8-bottles capacity) Instruction Manual Please read carefully and follow all safety rules and operating instructions.

More information

SOLAR PV SYSTEM MAINTENANCE GUIDE

SOLAR PV SYSTEM MAINTENANCE GUIDE SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

INSTALLATION INSTRUCTION SPEC. SHEET 7/00. City of New York Calendar #40747 ETL LISTED UNDER U.L. STD. 2108 LOW VOLTAGE TRACK LIGHTING SYSTEM

INSTALLATION INSTRUCTION SPEC. SHEET 7/00. City of New York Calendar #40747 ETL LISTED UNDER U.L. STD. 2108 LOW VOLTAGE TRACK LIGHTING SYSTEM 7/00 INSTALLATION INSTRUCTION SPEC. SHEET 99052 99063 City of New York Calendar #40747 Copyright c 2000 ALFA Lighting, Inc. All rights reserved. Call:1-415-975-8080 QUICK JACK QJS R LISTED 9901483 ETL

More information

employed to ensure the continuing reliability of critical systems.

employed to ensure the continuing reliability of critical systems. 4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective

More information

BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.

BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC. BC-5000 BATTERY CAPACITY TESTER OPERATIONS MANUAL COFKO LLC. COPYRIGHT 2010 1 UNPACKING As you unpack your new BC-5000 battery capacity tester, inspect the tester for signs of shipping damage. If shipping

More information

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

Installation and safety instructions for AC/DC built-in devices

Installation and safety instructions for AC/DC built-in devices The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further

More information

Single-Phase AC Synchronous Generator

Single-Phase AC Synchronous Generator ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual A Regal Brand TABLE OF CONTENTS INTRODUCTION 2 General Data 2 Initial Inspection 2 SAFETY 2 INSTALLATION 3 Location / Environment

More information

SVENSKA.......................................................3 DANSK.........................................................10 NORSK................

SVENSKA.......................................................3 DANSK.........................................................10 NORSK................ Caddy 150 & Caddy Tig 150 LHQ 150, LTV 150 SVENSKA.......................................................3 DANSK.........................................................10 NORSK.........................................................17

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Fire Protection Notice No. 9 ELECTRICAL SAFETY

Fire Protection Notice No. 9 ELECTRICAL SAFETY Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

3000W Power Inverter

3000W Power Inverter 3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE

More information