TE-6300P Series Temperature Sensors
|
|
|
- Scot Pitts
- 9 years ago
- Views:
Transcription
1 TE-6300P Series Temperature Sensors Installation Instructions TE-63xxP , Rev. N Part No , Rev. N Issued March 2016 Applications To meet plenum rating where Underwriters Laboratories Inc. UL 1995 rating is accepted, replace the existing thermoplastic cover with the TE Metal Cover. To meet International Mechanical Code standards, use all-metal components. Table 1: TE-6300P Applications Duct Probe Temperature Sensor Model Description and Probe, in. (mm) TE-6311P-1 1k ohm Thin-Film Nickel, 8 (203) TE-6351P-1 1k ohm Thin-Film Platinum, 8 (203) TE-6341P-1 2.2k ohm Negative Temperature Coefficient (NTC) Thermistor, 8 (203) TE-6361P-1 10k ohm Johnson Controls Type II, NTC Thermistor, 8 (203) Well Insertion Temperature Sensor Model Description and Probe, in. (mm) TE-6312P-1 TE-631AP-1 TE-6352P-1 Threaded 1k ohm Thin-Film Nickel, 8 (203) Threadless 1k ohm Thin-Film Nickel, 6 (152) Threaded 1k ohm Thin-Film Platinum, 8 (203) TE-635AP-1 Threadless 1k ohm Thin-Film Platinum, 6 (152) Note: See Figure 9 and Figure 10 for threadless and threaded connections. Duct Averaging Temperature Sensor Model Description and Probe, in. (mm) TE-6315P-1 1k ohm Nickel Wire, 8 (2.4) TE-6316P-1 1k ohm Nickel Wire, 17 (5.2) TE-6327P-1 TE-6328P-1 TE-6337P-1 TE-6338P-1 1k ohm Platinum Equivalent Wire, 10 (3.0) 1k ohm Platinum Equivalent Wire, 20 (6.1) 100 ohm Platinum Equivalent Wire, 10 (3.0) 100 ohm Platinum Equivalent Wire, 20 (6.1) Refer to the QuickLIT website for the most up-to-date version of this document. IMPORTANT: The TE-6300P Series Temperature Sensor is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the sensor. IMPORTANT : Le TE-6300P Series Temperature Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du sensor. Installation IMPORTANT: Do not install the TE-6300P Series Temperature Sensor probe in ambient temperatures beyond the specified -50 to 220 F (-46 to 104 C) temperature range. Installing the temperature sensor probe in ambient temperatures beyond this range may damage the unit and void the warranty. TE-6300P Series Temperature Sensors Installation Instructions 1
2 FIG: 6300_dim Dimensions Figure 1: Duct Probe Sensor Dimensions, in. (mm) 6.0 (152) maximum 2.75 (69.9) 1.72 (43.7) 1/2-14 NPT Threads Mounting Plate: 3 x 3 (76 x 76) 1/2-14 NPT Threads Figure 2: Duct Averaging Sensor Dimensions, in. (mm) FIG: 6300_dim2 Mounting Location Considerations Consider the following mounting location guidelines: Avoid areas subject to excessive vibration, electrical noise, direct sunlight, or the effects of radiant heat. Keep electrical wiring as short as possible to minimize temperature error. Install sensors in areas where sufficient mixing of the sensed medium occurs or use an averaging sensor. Cutting the Sensor Probe (Duct and Well Models Only) If necessary, cut the sensor probe at the wiring end using the following procedure: 1. Mark the desired length, measuring from the end of the tube without leads. The final sensor probe length must be at least 3 inches (76 mm). 2. Cut the probe using a tubing cutter with a sharp blade, as shown in Figure 4. (Cut slowly, using minimal pressure to decrease burr size and help avoid damaging the leads.) 2.75 (69.9) 6.0 (152.4) maximum 7.5 (190.5) maximum (8 in.) 5.5 (139.7) maximum (6 in.) 0.52 (13) Measure from this end Models with 6-inch sensors have threadless sensor holders. 1/2-14 NPT Threads Figure 3: Well Insertion Sensor Dimensions, in. (mm) FIG: 6300_dim3 Figure 4: Cutting the Sensor Probe 3. Slide the loose tubing carefully over the leads to remove. 4. Insert the leads into shrink tube (included) or use other material to protect the leads from potential sharp edges where the probe was cut. (Heat the shrink tube using a heat gun.) FIG: cut_sns 2 TE-6300P Series Temperature Sensors Installation Instructions
3 FIG: ins_sns Securing or Removing the Sensor Holder The retainer is a gray plastic tube approximately 1-1/4 in. (32 mm) long x 1/2 in. (13 mm) in diameter. Use the retainer to lock the sensor holder into the conduit box. Using the retainer prevents the snap finger from deflecting, locking the sensor holder into the conduit box. To install the retainer, slide the retainer over the sensor wires and probe, and into the sensor holder. (See Figure 5.) 7. Reposition the cover and tighten the retention screws. Mounting the Duct Averaging Sensor See Figure 6 to mount a single duct averaging sensor. See Figure 7 to mount four duct averaging sensors in series-parallel for larger ducts. Sensor Holder Retainer Figure 6: Installing the Duct Averaging Sensor To Controller Figure 5: Installing the Duct Sensor To remove the sensor holder from the conduit box, slide the retainer off of the sensor probe. Push the snap finger toward the center of the sensor holder and pull the holder out of the conduit box. Note: It may be necessary to loosen the set screw and remove the sensor probe to obtain adequate clearance to slide the sensor holder out of the conduit box. Mounting the Temperature Sensors Mounting the Duct Sensor See Figure 5 and mount the sensor as follows: 1. Drill a 1-3/8 in. (35 mm) diameter hole at the desired mounting location. 2. Use the mounting plate as a template to drill four 1/8 in. (3 mm) holes for the screws. 3. Mount the probe assembly to the duct using the four screws provided. 4. Pull the wires into the conduit box and snap the conduit box onto the sensor holder. 5. Install the retainer into the sensor holder. 6. Wire the sensor to the controller using the wire nuts provided. Figure 7: Series-Parallel Mounting Configuration Mount the duct averaging sensor as follows: 1. Drill a 1-3/8 in. (35 mm) diameter hole at the desired mounting location. 2. Use the mounting plate as a template to drill four 1/8 in. (3 mm) holes for the screws. 3. Mount the averaging sensor probe inside the duct using a TE or equivalent 3 in. (76 mm) minimum radius temperature element holder. IMPORTANT: Do not bend the sensor probe tighter than a 3 in. (76 mm) radius, a 6 in. (152 mm) diameter, to avoid permanently damaging the sensor. Note: Platinum sensor models include two TE Element Holders. FIG: mnt_cnfg TE-6300P Series Temperature Sensors Installation Instructions 3
4 4. Insert the sensor probe into the sensor holder and mounting plate assembly. Firmly tighten the sensor holder set screw. 5. Follow Steps 3 through 7 in Mounting the Duct Sensor. Mounting the Well Insertion Sensor The TE-63xxP-1 well models include a sensor holder with built-in thermowell adaptor. No additional well adaptor is required for installation when the sensor is used with TE-6300W thermowells. See Figure 8 and mount the sensor as follows: (Included, assembled to Conduit Box) Insert the sensor holder, then tighten the well set screws. Sensor Holder Figure 9: Installing the TE-63xAP-1 Sensor Holder TE-6300W-110 (TE-63x2P-1), see Figure 10 and screw the sensor holder into the thermal well (the TE-6300W-110 does not contain thermal grease). Conduit Box (Included) Figure 8: Installing the Well Insertion Sensor Note: Add thermal grease (F , or equivalent) before inserting the probe if the well does not include thermal grease. For proper sensor function, mount the well so that any condensation that forms drains out of the probe. 1. Remove the sensor holder from the conduit box (See Securing or Removing the Sensor Holder on page 3). 2. Loosen the sensor holder setscrew and remove the probe. 3. If the thermal well is: TE-6300W-103 (TE-63xAP-1), see Figure 9 and loosen the two well set screws (the TE-6300W-103 contains thermal grease). Figure 10: Installing the TE-63x2P-1 Sensor Holder 4. Insert the sensor probe through the sensor holder and into the thermal well until it just touches the bottom of the well. 5. Back the probe out approximately 1/8 in. (3 mm) and tighten the sensor holder set screw. 6. Pull the sensor wires into the conduit box and snap the conduit box onto the sensor holder. 7. Install the retainer over the sensor wire leads and into the sensor holder. 8. Wire the sensor to the controller using the wire nuts provided. 9. Reposition the cover and tighten the retention 4 TE-6300P Series Temperature Sensors Installation Instructions
5 Fig: wrng Wiring For 1k ohm nickel temperature sensors, wire resistance can cause approximately 1F (0.56C ) of error for every 250 ft (76 m) run of 18 AWG wire, or every 100 ft (31 m) run of 22 AWG wire. For 1k ohm platinum temperature sensors, wire resistance can cause approximately 1F (0.56C ) of error for every 150 ft (46 m) run of 18 AWG wire, or every 50 ft (15 m) run of 22 AWG wire. To minimize error due to field wiring, limit the total resistance of all nickel temperature sensor wiring to 3 ohms, and all 1k ohm platinum temperature sensor wiring to 2 ohms. To minimize wiring error in applications using 100 ohm platinum equivalent sensors, use the TQ , 4 to 20 ma transmitter. Using a 4 wire (Kelvin) connection can also eliminate wiring error. The 2.2k and 10k ohm thermistor applications permit wiring to be relatively long before wire resistance adds significantly to total resistance measured at the controller. As a general rule, a 150 ft (46 m) two-wire 18 AWG run contributes 2 ohms of error, or less than 1F (0.56C ) error over the sensor operating temperature range. Refer to the appropriate controller documentation for recommended sensor wiring. See Table 2 for an explanation of the lead wiring color convention. Table 2: Lead Wiring (22 AWG, 6 in.) Color Code Sensor Type Lead Color 1k ohm Nickel White 1k ohm Nickel Averaging 1 White 100 ohm Platinum Averaging Red 1k ohm Platinum White with blue strip 1k ohm Platinum Averaging Blue 2.2k ohm Thermistor Red 10k ohm Thermistor White with green stripe Note: Always use sensors of the same value and type throughout the network.! CAUTION: Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. MISE EN GARDE : Risque de dégâts matériels. Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement. IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the TE-6300P Series Temperature Sensor s electrical ratings. Repair Information If the TE-6300P Series Temperature Sensor fails to operate within its specifications, refer to the TE-6300 Series Temperature Sensor Product Bulletin (LIT ) for a list of repair parts available. 1. Nickel Averaging sensors use 18 AWG wire Series-Parallel Wiring To wire a duct averaging sensor, or another model in series-parallel configuration, see Figure 11. Four Sensors Figure 11: Series-Parallel Wiring Network TE-6300P Series Temperature Sensors Installation Instructions 5
6 Technical Specifications TE-6300P Series Temperature Sensors Sensor Reference 1k ohm Thin-Film Nickel 1k ohms at 70 F (21 C) Resistance 1k ohm Nickel Averaging 1k ohms at 70 F (21 C) 1k ohm Thin-Film Platinum 1k ohms at 32 F (0 C) 100 ohm Platinum Averaging 100 ohms at 32 F (0 C) 1k ohm Platinum Averaging 1k ohms at 32 F (0 C) 2.2k ohm Thermistor 2,252 ohms at 77 F (25 C) 10k ohm Thermistor 10k ohms at 77 F (25 C) Sensor Accuracy 1k ohm Thin-Film Nickel ± 0.34F at 70 F (± 0.19C at 21 C) 1k ohm Nickel Averaging ± 3.4F at 70 F (± 1.9C at 21 C), 1k ohm Thin-Film Platinum ± 0.35F at 70 F (± 0.19C at 21 C), DIN Class A 100 ohm Platinum Averaging ± 1.0F at 70 F (± 058C at 21 C) 1k ohm Platinum Averaging ± 1.0F at 70 F (± 058C at 21 C) 2.2k ohm Thermistor ± 0.36F (± 0.2C ) in the range: 32 to 158 F (0 to 70 C) 10k ohm Thermistor ± 0.9F (±0.5C ) in the range: 32 to 158 F (0 to 70 C) Sensor Temperature 1k ohm Thin-Film Nickel Approximately 3 ohms/f (5.4 ohms/c ) Coefficient 1k ohm Nickel Averaging Approximately 3 ohms/f (5.4 ohms/c ) 1k ohm Thin-Film Platinum Approximately 2 ohms/f (3.9 ohms/c ) 3,850 ppm/k 100 ohm Platinum Averaging Approximately 0.2 ohms/f (.39 ohms/c ) 1k ohm Platinum Averaging Approximately 2 ohms/f (3.9 ohms/c ) 2.2k ohm Thermistor Nonlinear, Negative Temperature Coefficient (NTC) 10k ohm Thermistor Nonlinear, NTC, Johnson Controls Type II Materials Probe.25 in. (6.4 mm) Outside Diameter (O.D.) x 6 in. (152 mm) or 8 in. (203 mm) Long, Stainless Steel Tubing Nickel Averaging Probe in. (2.4 mm) O.D. x8 ft (2.4 m) or 17 ft (5.2 m) Long, Copper Tubing Platinum Averaging Probe 0.19 in. (4.8 mm) O.D. x 10 ft (3.0 m) or 20 ft (6.1 m) Long, Aluminum Tubing Conduit Box Rigid Thermoplastic Sensor Holder Rigid Thermoplastic Mounting Plate Aluminum Operating Conditions Probe Assembly -50 to 220 F (-46 to 104 C) Conduit Box -50 to 122 F (-46 to 50 C) The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact: JOHNSON CONTROLS WESTENDHOF ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI USA JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE CHINA Building Efficiency 507 E. Michigan Street, Milwaukee, WI Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc. 6 TE-6300P Series Temperature Sensors Installation Instructions Published in U.S.A.
OLS-2100 Occupancy Light Switch
OLS-2100 Occupancy Light Switch Product/Technical Bulletin OLS-2100-1 24-7691- 25, Rev. E Part No. 24-7691-25, Rev. E Code No. LIT-216270 Issued March 2016 The OLS-2100 Occupancy Lighting Switch is a passive
HE-6800 Series Humidity Transmitters with Temperature Sensor
HE-6800 Series Humidity Transmitters with Installation Instructions HE-68xx-xN00WS Applications The HE-6800 Series Humidity Transmitters with provide both humidity and temperature sensing in room wall-mount
T25 Two-Stage Room Thermostat
Installation Instructions T25 Issue Date 05/27/14 T25 Two- Room Thermostat Application Requirements T25 thermostats are for line- or low-voltage service requiring accurate control of two operating functions.
Product/Technical Bulletin
EP-8000 eries Electro-Pneumatic Transducers convert a voltage or current signal from an electronic controller into a pneumatic output pressure signal. An increase or decrease in the input signal proportionally
VG7000 Series Bronze Control Valves
VG7000 Series Bronze Control Valves Installation Instructions VG7000 1 4-1 0 7 8-6, Re v. K Part No. 14-1078-6, Rev. K Issued March 2016 Applications VG7000 Series Bronze Control Valves are primarily designed
A99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
M9208-Bxx-3 Series On/Off Electric Spring Return Actuators
34-636- 2103, Rev. E M9208-Bxx-3 Series On/Off Electric Spring Return Actuators Installation Instructions M9208-BAA-3, M9208-BAC-3, M9208-BDA-3, M9208-BDC-3, M9208-BGA-3, M9208-BGC-3 Part No. 34-636-2103,
System 350 A350A/B Electronic Temperature Control
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350 Issue Date 0614 System 350 A350A/B Electronic Temperature Control The A350A/B Series is an on/off electronic temperature control with a Single-Pole,
P499 Series Electronic Pressure Transducers
P499 Series Electronic Transducers Product/Technical Bulletin P499xxx-x Code No. LIT-12011190 Part No. 24-7664-2659, Rev. F Issued August 4, 2015 The P499 Series Electronic Transducers are compact, economical,
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,
CST29A Adapter Block for Carlyle Compressors
Product/Technical Bulletin Issue Date April 28, 2014 CST29A Adapter Block for Carlyle Compressors The Johnson Controls/PENN CST29A Adapter Block is designed for use on Carlyle compressors (models O6CC,
A-4000 Oil Indicator
64-272- 0, Rev. B Product Bulletin A-4000 Issue Date 0316 A-4000 Oil Indicator The A-4000 Oil indicator is a calibrated measuring instrument used to detect aerosol-mist levels of oil entrainment that may
I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter
CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter Product Bulletin CD-Pxx-00-1 Code No. LIT-216525 Issued December 6, 2010 Supersedes September 12, 2008 Johnson Controls offers a complete line of Carbon Dioxide
P66 Series Electronic Fan Speed Controls
P66 Series Electronic Fan Speed Controls Product Bulletin Code No. LIT-125465 Issued September 30, 2009 Supersedes March 23, 2006 The P66 Series Electronic Fan Speed Controls are refrigerant pressure actuated,
READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. DANGER RISK OF SHOCK DISCONNECT POWER BEFORE INSTALLATION
UR Series LED Upgrade Kit Includes: 48" Linear Option IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: READ AND FOLLOW ALL
P266 Series Single-Phase Condenser Fan Speed Controls
Application P66 Series Single-Phase Condenser Fan Speed Controls Installation Instructions P66xxA-xx The P66 Series Single-Phase Condenser Fan Speed Controls are cost-effective, weather-resistant, durable
MP8000 Series Pneumatic Valve Actuators
14-1161- 9, Rev. A Technical Bulletin MP8000 Issue Date March 2016 MP8000 Series Pneumatic Valve Actuators Pre-Assembly Details Page 3 MP8000 Actuator Components 3 Tools Required to Assemble an MP8000
Submersion/Insertion Toroidal Sensor
Instruction Sheet PN 51A-228/rev.P December 2010 Model 228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.emersonprocess.com/raihome/liquid/. CAUTION SENSOR/PROCESS
DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual
DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR Installation and Operation Manual 1 ENGLISH Safety Instructions 2 Features 2-3 Specifications 3 Installation 4-5 Wiring Diagrams 6-7 Warranty 8
Duct Temperature Sensors
Duct s Model TE-701 / 702 RoHS More than 16 types of interchangeable NTC thermistors, precision platinum, nickel or balco RTDs are available for universal compatibility. Five installation options probe
ATL Fuel Level Sender Probes
T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of
VG2000 Series Cast Iron Flanged Globe Valves
VG2000 Series ast Iron Flanged Globe Valves Installation Instructions Part No. 14-1161-106, Rev. Issued November 15, 2013 Supersedes June 15, 2007 pplications VG2000 Series ast Iron Flanged Globe Valves
3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE
4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement
Threaded Resistance Thermometers Model TR10-D, Miniature Design
Electrical Temperature Measurement Threaded Resistance Thermometers Model TR10-D, Miniature Design WIKA Data Sheet TE 60.04 Applications Machine building, plant and tank construction Power transmission
Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors
European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for
DPT-2015 Differential Pressure Transmitter for VAV Box Applications
FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential
Technical Instructions Document No. 155-021P25 ET 141-5 September 28, 2004. ET 141 High Limit Control Thermostat. Description.
Document No. 155-021P25 ET 141-5 ET 141 High Limit Control Thermostat Description Application The ET 141 high limit control thermostat is duct mounted and has a rigid bulb, bi-metal rod and tube construction.
P70, P72, and P170 Series Controls for Dual Pressure Applications
P70, P72, and P170 Series Controls for Dual Pressure Applications Product Bulletin Code No. LIT-125455 Issued August 30, 2012 Supersedes September 1, 2000 The P70, P72, and P170 controls for dual pressure
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
Tubing and Accessories
Section 7 Tubing and Accessories Inch Industrial Tubing................................FIT-7-2 Metric Industrial Tubing...............................FIT-7-3 Inch D.O.T. Tubing...................................FIT-7-3
3/4 PIPE CLAMP WITH STAND
3/4 PIPE CLAMP WITH STAND Model 94053 ASSEMBLY AND OPERATING INSTRUCTIONS (3/4 DIAMETER PIPE NOT INCLUDED.) 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our Web site at: http://www.harborfreight.com
Toroidal Conductivity Sensor
Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:
Installation Guidelines: Resistance Thermometers and Temptran Thermometers for Building Automation Systems
APPLICATION AID SAA20 Installation Guidelines: Resistance Thermometers and Temptran Thermometers for Building Automation Systems Duct Air page 4 Thermal-Ribbon pages 6-7 Room Air Compact Room Air page
758 Heavy-duty Ratchet Guy Wire Cutter
INSTRUCTION MANUAL 758 Heavy-duty Ratchet Guy Wire Cutter Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Register this product
Pipe Temperature Sensors
Pipe Temperature Sensors Model TE-703 / 704 RoHS Four immersion thermowell installation options brass adapter with 304 SS probe for adjustable insertion, plastic, galvanized steel or NEMA-4/IP-65 steel
Installation Guide. WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers. February, 2011
WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers Installation Guide February, 2011 Pace Scientific Inc www.pace-sci.com Tel: 704-799-0688 [email protected] 1 Disclaimer The following warranty
Part I - Installation
400 Series Pressure and Differential Pressure Switches Types: H400, H402, H403, H400K, H402K, J400, J402, J403, J400K, J402K UNITED ELECTRIC CONTROLS Installation and Maintenance Instructions Please read
DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered
Electrical Temperature Measurement DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered WIKA Data Sheet TE 60.75 Applications Machinery, plant and tank construction
Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02.
Directory chapter 02 - () Types D, E, F, FM, 2F, F9, interface connectors I/U Page Technical characteristics types D and E.............................. 02.10 Type D connectors.................... 02.11
PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS
PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000
Lumination TM LED Luminaires Light Bar Retrofit Kit Series
GE Lighting Installation Guide Lumination TM LED Luminaires Light Bar Retrofit Kit Series BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING AVERTISSEMENT RISK OF FIRE OR ELECTRIC
Hot-End Replacement Guide. BFB 3000 plus & 3D Touch
Hot-End Replacement Guide BFB 3000 plus & 3D Touch Pre assembly checks: Testing the hot-end before fitting: Check the heating cable: Set the multi-meter to read resistance (2000 ohms) Test the two outside
Submersion/Insertion Toroidal Sensor
Instruction Manual 228 Sensor LIQ_MAN_ABR_228 May 2014 PN 51A-228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.rosemountanalytical.com CAUTION SENSOR/PROCESS
PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller
BLZPTS-1 NOVEMBER 19, 2013 TS350 TS752 BLPS PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller DESCRIPTION The BLPS, TS350
HP 16/18-Port Cable Management Kit Installation Guide
HP 16/18-Port Cable Management Kit Installation Guide Abstract This document describes how to attach the HP 16 Port or 18 Port Cable Management Kit to an HP rack. The cable management bracket is designed
FEATURES BODY DIA. MAX. Type M AWG 30: 0.0100 [0.254] Type C AWG 28: 0.0126 [0.320] Type T AWG 30: 0.0100 [0.254]
M, C, T NTC Thermistors, Coated FEATURES Small size - conformally coated. Wide resistance range. Available in 11 different R-T curves. DESCRIPTION Models M, C, and T are conformally coated, leaded thermistors
Mounting Instructions for SP4 Power Modules
Mounting Instructions for SP4 Power Modules Pierre-Laurent Doumergue R&D Engineer Microsemi Power Module Products 26 rue de Campilleau 33 520 Bruges, France Introduction: This application note gives the
DLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
M9220-HGx-3 Proportional Electric Spring Return Actuators
M9220-HGx-3 Proportional Electric Spring Return ctuators Installation Instructions 34-636- 1700, Rev. F Part No. 34-636-1700, Rev. F Issued March 2016 pplications The M9220-HGx-3 Proportional Electric
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.
System 350 A350E Electronic Cooling Control
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw
Portable BACnet /IP to MS/TP Router
Portable BACnet /IP to MS/TP Router Installation Instructions TL-BRTRP-0 Part No. 24-10414-2, Rev. F Issued April 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Applications
TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
T7079A,B Solid State Remote Temperature Controllers
T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature
USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2
Remote Faucet Pump System USE &CARE GUIDE See Important Safeguards on page 2 An exclamation point within an equilateral triangle is intended to alert user to the presence of important operating and maintenance
TECHNICAL GUIDE. For Self-Shielded Guns - 300, 400 and 500 amp SAFETY AND WARRANTY INFORMATION INSTALLATION MAINTENANCE GUIDE TECHNICAL DATA OPTIONS
TECHNICAL GUIDE For Self-Shielded Guns - 300, 400 and 500 amp SAFETY AND WARRANTY INFORMATION INSTALLATION MAINTENANCE GUIDE TECHNICAL DATA OPTIONS EXPLODED VIEW & PARTS LIST TROUBLESHOOTING ORDERING INFORMATION
AMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
Installation Instructions
Installation Instructions Built-In Dishwasher If you have questions, call 1-800-4-MY-HOME (1-800-469-4663) or visit our website at: www.sears.com BEFORE YOU BEGIN Read these instructions completely and
Model/Sprinkler Identification Numbers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-L 5.6 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description
INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
Directory chapter 04
M Directory chapter 04 D-Sub Mixed subminiature D connectors New Page D-Sub mixed connector system general information................... 04.02 Contact arrangements............................................
PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V
PHOTOVOLTAIC SYSTEM CONTROLLERS OPERATOR S MANUAL SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V 6A / 12V 10A / 12V 10A / 24V 20A / 12V 20A
BLUE RIBBON CORP. BC001 Birdcage Installation Manual
Product Overview: This manual is applicable for the BC001 Birdcage Submersible Level Transmitters. If the product you have has a different prefix part number than listed above please contact the factory
UV100A Ultraviolet Air Treatment System
UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism
Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors
Installation Manual Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors SW602206 Rev B Table of Contents Chapter 1: Safety Warning... 3 Chapter 2: Kit Contents... 4 Included in Kit...
Backup Scanner Module
Backup Scanner Module Catalog Number 1747-BSN Installation Instructions 2 Backup Scanner Module Important User Information Because of the variety of uses for the products described in this publication,
Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases
Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases
Series 510 Submersible Level Transmitters
Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable
Model 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
SLC 500 Analog Input Module
Installation Instructions SLC 500 Analog Input Module (Catalog Number 1746NI8) Inside Important User Information... 2 For More Information... 3 Hazardous Location Considerations... 4 Environnements dangereux...
5800 Temperature Sensor Cable Assembly
5800 Temperature Sensor Cable Assembly Removal and Replacement Instruction Sheet #60-4702-070 Revision D, January 14, 2013 Overview The 5800 has two refrigeration temperature sensors, one attached to the
Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family
Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family Part of the Kiva Lighting Family Custom Lighting and Fans Since 1992 1312 12th St NW Albuquerque,
AMF112 Instruction Manual
AMF112 Instruction Manual Scan here to view product demo and install videos or visit san.us/103 Milestone AV Technologies 6436 City West Parkway Eden Prairie, MN 55344 USA Customer Service Americas: 800-359-5520
Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement
Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement This work instruction describes the methods and means for which to remove and reinstall optional scanner cable configurations
Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
QR12 (1.22 ) Diameter Optical Encoder
Improving the Quality of Life through the Power in Light QPhase QR12 (1.22 ) Diameter Optical Encoder Design Features: Low profile assembled height of Bearing design simplifies encoder attachment Resolutions
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html TECHNICAL SERVICE DEPARTMENT Removal, Cleaning, & Reinstallation of the Burner Assembly For models 74 & GT199 Required tools -
Wall-Mounting your HP computer. User Guide
Wall-Mounting your HP computer User Guide The only warranties for Hewlett-Packard products and services are set forth in the express statements accompanying such products and services. Nothing herein should
Direct AC Wiring Option Installation Guide
Revision A Direct AC Wiring Option Installation Guide The direct AC wiring option enables you to wire AC power directly in to the ADP InTouch. The option kit contains the following parts. 25mm 12mm Caution:
3M Wrist Strap and Footwear Tester 740. User s Guide
3M Wrist Strap and Footwear Tester 740 User s Guide Table of Contents Section Page Safety Information...3 1.0 General...4 2.0 Description...4 3.0 Operation...5 4.0 Wall Mounting...5 5.0 Wrist Strap Test...6
Table of Contents. www.hunterfan.com. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing.
www.hunterfan.com Table of Contents What to Expect with Your Installation 30 inches Hanging the Fan Wiring 8 Maintenance, Operation & Cleaning Light Kit 13??? 14 1 9 Troubleshooting 11 5 Blades Motor Housing
Micrio WS1 Replacement Wind Speed Sensor and WC1 Replacement Wind Compass Sensor for Raymarine ST50 and ST60 Wind Instruments. Rev 4.
Micrio WS1 Replacement Wind Speed Sensor and WC1 Replacement Wind Compass Sensor for Raymarine ST50 and ST60 Wind Instruments. Rev 4.1 The Micrio WS1 Wind Speed Sensor and WC1 Compass Sensor are direct
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool. Tool P/N HT-0095
HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool Tool P/N HT-0095 FCI MANUAL P/N 415988-001 Issued: Date (03/12/99) Page 1 of 18 HT-0095 Issued: Date (03/12/99) Page 2 of 18 Introduction Table
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
LED Security Spotlight User Manual
MOT ION-TR ACKING LED Security Spotlight User Manual www.jascoproducts.com 1-800-654-8483 2 TABLE OF CONTENTS Parts List 3 Questions? Missing Parts? 4 Installation (Wall mount) 6-9 Installation (Eave mount)
AMF112 (6904-002010 <00>) 13mm (1/2 in.)
AMF112 () Concrete Wood 13mm (1/2 in.) 5.5mm (7/32 in.) 10mm (3/8 in.) Sanus Systems 2221 Hwy 36 West Saint Paul, MN 55113 USA Customer Service Americas: 800-359-5520 651-484-7988 [email protected] Europe,
SNQ-60x0-320 Series Data Center Switch. Quick Installation Guide
Introduction This guide is to assist the reader with the most basic form of installation and connection to switches in this series. As there is more than one switch in this series, the diagrams might slightly
Name: Bicycle Cellphone Charger Circuit Assembly Manual Device: Nokia/Blackberry List of Components:
Name: Bicycle Cellphone Charger Circuit Assembly Manual Device: Nokia/Blackberry List of Components: Serial numbername Quantity Component number 1 5 V Regulator 1 U2 2 10 MicroFarad Capacitor 1 C1 3 22
GSM-EXT Cable Assembly Installation Guide
GSM-EXT Cable Assembly Installation Guide For Documentation and Online Support: http://www.security.honeywell.com/hsc/resources/mywebtech General Information The GSM-EXT cable assembly is used to connect
T-5800-1 and T-5800-2 Single Input Receiver-Controllers Installation and Calibration
T-5800-1 and T-5800-2 Single Input Receiver-Controllers Installation and Calibration 24-7028- 6, Rev. A Technical Bulletin T-5800-1/-2 Issue Date 0316 The T-5800 Series Receiver- Controllers are designed
Trillium 40 Axis Spring Tensioner Wire Replacement Instructions
Trillium 40 Axis Spring Tensioner Wire Replacement Instructions 1 Overview The objective is to replace the broken axis spring tensioner wire. This requires the following tasks: 1. Remove the seismometer
A701 (6904-002018 <01>)
A70 () Wood Stud mm (7/6 in.).4 mm (3/3 in.) 6 mm (5/64 in.) 3 mm (/8 in.) Sanus Hwy 36 West Saint Paul, MN 553 USA Customer Service Americas: 800-359-550 65-484-7988 [email protected] Europe, Middle East,
Document number RS-PRD-00130 Revision 05 Date 20/10/2009 Page 1/30
Date 20/10/2009 Page 1/30 1. Purpose This document describes the field replacement of the footscan plate cable for these models: 2m hi-end plate SN 11/5/xxx 2m pro plate SN 7/5/xxx 0.5m 2003 hi-end plate
Ceiling Fan Installation Instructions
Ceiling Fan Installation Instructions 1525..series OWNER S MANUAL READ AND SAVE THESE INSTRUCTIONS Total fan wieght with light kit 1-1525-CUL-English INSTALLATION CH-545 Safety Tips WARNING: TO REDUCE