CT DISINFECTION MADE SIMPLE
|
|
|
- Russell McCoy
- 9 years ago
- Views:
Transcription
1 CT DISINFECTION MADE SIMPLE (Brock Rush, M. Eng., P. Eng., Alberta Environment) The following discussion is about CT Disinfection. It was prepared as a presentation for the Alberta Water and Wastewater Operator s Association annual conference in Banff, Alberta on March 13, It is intended to outline an easy to follow procedure that will allow operators of surface water and groundwater under the direct influence of surface water treatment plants to ensure that they are providing good disinfection to the water they treat, that they are producing the safest water possible and to demonstrate that they have done so. The following discussion will briefly cover the What Is, the Who Uses, and the Why you need CT Disinfection. However, the main focus of the discussion will be on how to use CT Disinfection to demonstrate that you are producing good quality water from your water treatment plants. We will review how CT Disinfection works and then work through an example. The main goal is to demonstrate that CT Disinfection is pretty simple to use. What is CT Disinfection? CT Disinfection is Alberta s current disinfection standard. It s used to demonstrate the level of disinfection treatment in your water. CT is simply the concentration of chlorine in your water times the time of contact that the chlorine has with your water. CT = Concentration of Chlorine x Time of Contact The concept itself is easy to understand. Who needs CT Disinfection? Every waterworks in Alberta that uses a raw water source that is either: (i) (ii) surface water; or groundwater under the influence of surface water (GWI), must disinfect the treated water to kill any pathogens that make it through the water treatment plant. CT Disinfection demonstrates that the required disinfection is being achieved.
2 March 13, 2002 Alberta s disinfection standard s have evolved over the years and will continue to evolve as we learn more about water borne pathogens and how to inactivate them. Where once the standards targeted only bacteria and viruses, using 20 minutes of chlorine contact time, we now also target Giardia, using CT disinfection, and in the near future we will target cryptosporidium as well, using ultra violet (UV) radiation. However, right now, Alberta s disinfection standard is CT Disinfection. All surface and GWI water systems should be using CT Disinfection to demonstrate that you are achieving sufficient water treatment to inactivate both Giardia and viruses. Disinfection with free chlorine that inactivates Giardia will usually provide enough CT to kill viruses as well. This discussion will focus on Giardia inactivation, but bare in mind the same principals apply to viruses as well. Why Practice CT Disinfection? Practicing CT Disinfection is the safe thing to do. CT Disinfection is the disinfection standard in Alberta. The standard has changed because we know we can do better than just 20 minutes of chlorine contact time. As of today, CT Disinfection is also the water treatment industry standard for disinfection. It is the best method to ensure that the water you are providing your customers is safe. If your water has been exposed to the surface, it has also been exposed to surface contamination, whether from livestock, wild animals or other human activity. It will most likely be biologically contaminated. If you can show that you have provided a safe level of treatment, then you can demonstrate that you have been duly diligent in performing your duty. CT disinfection protects your water, and by protecting your water, you are also protecting yourself. And whether you like it or not, you need to protect yourself too. How to Use CT Disinfection Let s start with the basics. CT = Concentration x Time CT is the concentration of chlorine in your water times the time the water is in contact with that chlorine. To use CT to demonstrate that you have sufficient water treatment, you need to do the following three things. 2
3 March 13, Determine how much CT you need. 2. Determine how much CT you have achieved. 3. Ensure CT achieved is more than CT required. Using CT Disinfection is a straightforward three step process. So let s look at these steps. How to Determine the Required CT (CT required ) Water treatment can be broken into two phases: 1. the water treatment plant; and 2. the disinfection. CT Disinfection focuses on the second phase, but let s focus for a moment on the entire process. Today s water treatment standards are based on the removal of Giardia from raw water. Giardia removal requirements for the entire water treatment process are based on the quality of the raw water. Therefore, an operator must test the raw water for Giardia to know the water treatment requirements. The water quality target for treated potable water is no more than one Giardia cyst per 100,000 litres of water. Treated Water Giardia Target < 1 cyst / 100,000 L The required treatment then, is the difference between the existing Giardia concentration in the raw water and the treatment target Giardia concentration for treated water. But even for pristine water, the absolute minimum Giardia inactivation requirement is 3.0 Log. But what does that mean, 3 Log inactivation? Let s look at an example. Typically, Giardia sampling requires 1000 litres to be passed through a special filter. The filter is sent to an accredited lab for analysis. If for example, your raw water has 100 cysts in a 1000 litre sample, this is the same as saying the sample has 10,000 cysts/100,000 litre. We have just multiplied the 100 cysts and the 1,000 litres each by 100. We have done this in order to compare the concentration of Giardia in the raw water sample with the treated water target. We know our treated water Giardia target is less than 1 cyst / 100,000 L, therefore we must reduce the Giardia concentration in the raw water by 10,000 times in order to meet the treated water Giardia target. 3
4 March 13, 2002 Another way to express this 10,000 times reduction is by counting the zero s, in this case 10,000 has 4 zero s (10,000 = 10 4 ). Therefore we need 4 Log reduction. This can also be stated as 99.99% reduction. Again count the 9 s. 4 Log is expressed with four nines, 99.99%. Two Log removal would be 99%; three Log 99.9%. But, as operators you do not need to worry about this math. You do the sampling, you get the Giardia analysis done, and we folks at Alberta Environment will be more than happy to work with you to determine how many Log removals of Giardia are required. The required level of Giardia reduction is summarized in Table 1, based on quarterly samples of Giardia concentrations in the raw water entering the water treatment plant. Table 1: LEVEL OF GIARDIA REDUCTION Raw Water Giardia Levels* Recommended Giardia Log Reduction < 1 cyst/100 L 3-log 1 cyst/100 L - 10 cysts/100 L 3-log - 4-log 10 cysts/100 L cysts/100 L 4-log - 5-log > 100 cysts/100 L > 5-log *Use geometric means of data to determine raw water Giardia levels for compliance. Table 4-1 from The Standards and Guidelines for Municipal Water, Wastewater and Storm Drainage Systems, AENV 1997 A list of Alberta Environments Municipal Approvals contacts is included at the end of this discussion. Any one of these contacts will help you determine the required disinfection to meet your overall treatment requirement. How to Achieve Required Giardia Log Inactivation The obvious next question is, How do we achieve this required Log inactivation of Giardia? As we already saw, there are two phases to water treatment: 1. the water treatment plant; and 2. the disinfection. If your water treatment plant is treating water in accordance with Alberta Environment's 1997 water treatment plant performance standards, then you will be given credit for an appropriate level of Giardia reduction. For a conventional water treatment plant, you would receive 2.5 Log credits for Giardia reduction, if your treatment meets the 1997 performance standard. The water treatment plant performance standards that must be met in order to receive Giardia inactivation credits are listed in Section 2.2 of Alberta Environment s 1997 Standards and Guidelines for Municipal Water Wastewater and Storm Drainage Facilities. But, as mentioned previously, the minimum over all treatment requirement, even in a pristine water source is 3.0 Log reduction of Giardia. The balance of the Giardia 4
5 March 13, 2002 inactivation treatment requirements must be made up by disinfection. This is where CT Disinfection is used. Example: Let s look at an example of the water treatment requirements for a raw water source with 10,000 cysts per 100,000 litres. Since this is equal to 10 cysts per 100 litres, we see from Table 1 that the total treatment requirement would be at least 4.0 Log inactivation of Giardia cysts. If a conventional water treatment plant with coagulation, flocculation, sedimentation and filtration is treating the water and meeting the 1997 performance standards, a 2.5 Log credit is given for Giardia inactivation at the water treatment plant. The remaining 1.5 Log Giardia inactivation requirement must be achieved by disinfection. Step 1: Determining the Required CT (CT required ) The first step in using CT Disinfection is to determine the required CT (CT required ) to demonstrate that enough disinfection is occurring. Chlorine s effectiveness to inactivate Giardia cysts is dependent on temperature, ph, concentration of chlorine and time of contact. To determine CT required we need to know: 1 The minimum temperature of the water during disinfection. The minimum temperature of the water in the chlorine contact chamber must be monitored. Minimum temperature is used because chlorine s ability to disinfect becomes less with lower temperatures. By using the lowest temperature of the water when determining CT required, we know that the disinfection that occurred was at least as good as the lowest temperature allowed. 2 The maximum ph of the water during disinfection. The maximum ph of the water in the chlorine contact chamber must be monitored. Chlorine s ability to disinfect becomes less as ph increases. By using the maximum ph when determining CT required, we know that the disinfection that occurred was at least as good as the disinfection that occurs at the maximum ph. 3 The minimum chlorine residual in the water during disinfection. The minimum chlorine residual in the water must be monitored at the end of the disinfection chamber. We know that higher chlorine dosages disinfects better. The lowest chlorine residual is used because the water in the chlorine contact chamber has been exposed to at least that concentration of chlorine. 5
6 March 13, The required Log reduction of Giardia by disinfection must also be known. As discussed previously, the required Log reduction by disinfection is based on the raw water Giardia concentration with allowances for the treatment at the water treatment plant. With this information, we use Giardia CT tables to determine the CT required. CT required Tables An example of a CT required table for inactivation of Giardia is included on the following page. A full set of CT required tables are found in Appendix A of the Standards and Guidelines for Municipal Water, Wastewater and Storm Drainage Systems, AENV Hard copies of this document can be purchased from the Queen s Printer in either Calgary or Edmonton. As well, you can download this document from the Internet at the following website. The CT tables are located in Chapter 10 in the downloaded electronic format. The CT Tables are used as follows: 1 Make sure you are using the correct table. The tables are specific to the target organism and the type of disinfectant. Most likely you will use the Giardia inactivation table for free chlorine. Most surface and GWI water treatment plants disinfect with free chlorine. Free chlorine is more than ten times better at inactivating Giardia than chloramines. 2 The tables are also temperature specific. You must use the table that corresponds to your measured minimum temperature. 3 The tables are divided into ph sections. Locate the section of the table that corresponds to your measured maximum ph. 4 Within the appropriate ph section, locate the column for your required disinfection Log inactivation for Giardia. 5 Within the appropriate ph section, locate the row for your measured minimum free chlorine residual concentration on the left side of the table. 6 Read the CT required value from the table where the chlorine residual row meets the required Log inactivation column. 6
7 March 13, 2002 CT required Table A-2 from The Standards and Guidelines for Municipal Water, Wastewater and Storm Drainage Systems, AENV 1997 CT required is read directly from the table. Using these CT tables is straight forward. It will become a routine procedure once you ve done it a few times. The CT required tables are temperature specific for water temperatures at 5 C increments. If your temperature falls between two temperatures for which tables exist, for example 8 C, then you need to determine the CT required by one of the following methods: 1 Determine the CT required at both 5 C and 10 C from the corresponding tables and estimate the CT required value for 8 C using the CT required values for 5 C and 10 C; or 2 Use the CT required table that exists for the next lower temperature. To determine CT required for 8 C we could use the CT required value for 5 C. This will produce a value that is conservative (i.e. higher) and adds an extra measure of safety. 7
8 March 13, 2002 Similarly, the ph sections within each table are in 0.5 ph unit increments. To determine the CT required value for a ph that does not correspond to one of the given ph sections, the CT required value can be estimated using the ph sections higher and lower than your measured ph or by using the CT required value at the next higher ph section. Step 2: Determining the Actual CT (CT achieved ) The second step to using CT Disinfection is determining the actual CT we are achieving with disinfection. Remember that CT equals concentration times time. CT achieved = Concentration x Time To determine CT achieved, we need to know the actual minimum chlorine concentration and the actual time that the water is in contact with the chlorine. Multiplying these together gives us the actual CT achieved at the time the parameters were measured. But, we want to know the Minimum CT achieved every day. Therefore we need to use the Minimum Chlorine Residual that occurs each day. This is the same minimum chlorine residual concentration that we used to determine CT required. It will be measured at the outlet of the chlorine contact chamber in mg/l. To determine the minimum chlorine residual in a 24 hour period, the chlorine residual must be measured throughout that 24 hour period. Collecting a single grab sample once per day in no way indicates that the chlorine residual did not vary to a lower concentration since the last sample was collected the previous day. One of the important recommendations from the Walkerton Inquiry was that every surface water or GWI water treatment plant should have on-line chlorine analyzers. If you don t have one, due diligence would require that you get one. Not only will you be able to ensure your water is safe 24 hours a day, in the event that something does go wrong in your system, you can identify whether or not it was due to disinfection. The Minimum Chlorine Residual is therefore the lowest chlorine residual monitored each day. We also need to know the Actual Time that water is in contact with the chlorine. This is where it gets a little tricky, so this is where you need to pay close attention. 8
9 March 13, 2002 Determining Actual Contact Time Consider for a minute a length of pipe as illustrated in Figure 1. If a litre of water passes through the pipe, it comes out the other end as a litre of water. There is No Mixing and No Short-Circuiting. Water travels through the pipe as a unit. All the water travels at an Average Velocity through the pipe. Figure 1: Water Pipeline with No Mixing and No Short Circuiting (F SC = 1.0) Top View Now consider a water reservoir as illustrated in Figure 2. Figure 2: Water Reservoir with No Mixing and No Short Circuiting (F SC = 1.0) Cl 2 Top View If all the water travelled through the reservoir at an average velocity, the water would travel into the reservoir through the inlet pipe and across the reservoir as a single unit, at an average velocity. There would be No Mixing and No Short-Circuiting. But this is not what really happens. At least not for a reservoir where there is only maximum separation of the inlet and outlet pipes, but no baffles to reduce short circuiting between the inlet and outlet pipes. What really happens is that water will flow into the reservoir through the inlet pipe, then across the reservoir as illustrated in Figure 3, not at the average velocity as a single unit, but with some 9
10 degree of Mixing and Short-Circuiting. Due to hydraulic and temperature gradients, some water will follow a direct path, right to the outlet pipe. Figure 3: Water Reservoir with Mixing and Short Circuiting (F SC = 0.1) Cl 2 Top View When determining the time of contact of the chlorine with the water in the chlorine contact chamber, we therefore must account for short-circuiting. To do this, we use a time parameter, which we call T 10, the time it takes for 10 % of the water to pass through the reservoir. Mathematically we say: T 10 = F SC x T MIN T 10 equals a short-circuiting factor (F SC ) times the minimum time it takes a unit of water to travel through the reservoir at the average speed if no mixing or short circuiting occurred (T MIN ), as was the case in the length of pipe that was discussed. The short-circuiting factor will vary with different chlorine contact chamber configurations from 0.1 to for poorly baffled reservoirs, as illustrated in Figure 3 to 1.0 in the case of a pipe, as illustrated in Figure 1. The short circuiting factor (F SC ) is also called the baffling factor or the T 10 /T ratio in CT Disinfection literature. The short-circuiting factor is determined either by tracer tests of the actual reservoir, or it will be assigned, based on tracer tests for similarly configured reservoirs. Typical short circuiting (i.e. baffling) factors are found in Table 4.3 of Alberta Environment s 1997 Standards and Guidelines for Municipal Water Wastewater and Storm Drainage Facilities. This table is shown here as Table 3. Page 10
11 Table 3: TYPICAL BAFFLING CONDITIONS Baffling Condition Unbaffled (mixed flow) T 10 /T Ratio Baffling Description 0.1 None, agitated basin, very low length to width ratio, high inlet and outlet flow velocities Poor 0.3 Single or multiple unbaffled inlets and outlets, no intra-basin baffles Average 0.5 Baffled inlet or outlet with some intra- basin baffles Superior 0.7 Perforated inlet baffle, serpentine or perforated intra-basin baffles, outlet weir or perforated launders Perfect (plug flow) 1.0 Very high length to width ratio (pipeline flow), perforated inlet, outlet, and intra- basin baffles Table 4-3 from The Standards and Guidelines for Municipal Water, Wastewater and Storm Drainage Systems, AENV 1997 T MIN is the minimum time that the average unit of water is in the reservoir, or if you will, the minimum contact time on any day. T MIN = minimum volume of water in the reservoir (m 3 ) maximum hourly flow rate (m 3 /min) I indicated previously that the T in CT is where it gets a little tricky. T MIN is the key concept to grasp. Let s look at the top of the T MIN equation: minimum volume of water in the reservoir (m 3 ) We know that water levels in your disinfection reservoir will fluctuate throughout the day. Everything else being equal, when the level of water in the reservoir is at its lowest point, (i.e. when you have your minimum volume of water in storage) the water will spend the least amount of time in the reservoir and you will therefore have the least amount of time available for chlorine contact. Similarly, for the bottom of the T MIN equation: maximum hourly flow rate (m 3 /min) (from the reservoir) Everything else being equal, when the flow rate from the disinfection reservoir is at it s highest, the water will spend the least amount of time in the reservoir and you will have the least amount of time available for chlorine contact. Page 11
12 Combining these two scenarios, we get: T MIN = minimum volume of water in the reservoir (m 3 ) maximum hourly flow rate (m 3 /min) Substituting our details into the CT equation, we get the full CT achieved equation: CT achieved = Conc. of Cl 2 x F SC x minimum volume of water in the reservoir (m 3 ) maximum hourly flow rate (m 3 /min) Step 3: Comparing CT Values The third and final step is to compare CT acheived to CT required to determine if we meet the disinfection requirement. If not, we need to determine why not, and take the appropriate actions to ensure CT disinfection requirements are met. Summary of Required Steps Used in CT Disinfection Let s quickly review the three steps used in CT Disinfection. Step 1: Determine CT required using the correct CT Table. Step 2: Calculate CT achieved using the formula. Step 3: Compare CT achieved to CT required. If CT acheived > CT required, then you will have met your disinfection requirement. If not, you must take the appropriate actions to ensure CT Disinfection requirements are met. Summary of Required Information to Use CT Disinfection Let s do a quick review of the required information to use CT Disinfection. 1 The required Giardia inactivation by disinfection will be determined in conjunction with Alberta Environment based on the Giardia concentration in your raw water and the configuration and treatment of your water treatment plant. 2 The short circuiting or baffling factor (F SC ) of your chlorine contact chamber (i.e. clearwell or disinfection reservoir) will be assigned in conjunction with Alberta Environment, based on tracer studies done on your reservoir or by comparing your reservoir configuration with other similarly configured reservoirs with known short circuiting factors. Table 4.3 of Alberta Environment s 1997 Standards and Page 12
13 Guidelines for Municipal Water Wastewater and Storm Drainage Facilities provides typical baffling factors. 3 The maximum flow rate through your chlorine contact chamber will either be known from previous determination of the flow rate or the maximum flow rate must be monitored each day. 4 The minimum storage within the chlorine contact chamber will either be known, for example the volume in storage at distribution pump shut off, or if the system is operated with a fluctuating water level well above the minimum, the minimum volume in storage must be monitored each day. 5 The minimum temperature of your water during chlorine contact must be monitored each day. The need for online monitoring equipment will vary depending on the daily temperature fluctuation range. 6 The maximum ph of your water during chlorine contact must be monitored each day. The need for online monitoring equipment will very depending on the daily ph fluctuation range. 7 The minimum free chlorine residual of your water during chlorine contact must be determined by monitoring your chlorine residual throughout each day with an online chlorine analyzer at the outlet of the chlorine contact chamber. Example CT Disinfection Calculation Let s work through an example: This example is for a small water system in a small Provincial Park. However, the procedures are directly applicable to any sized water treatment system. The system has a poorly baffled reservoir. Data: Short Circuiting Factor, F SC = 0.10 Minimum water temperature = 5 C maximum ph of water = 8.0 required Giardia Log inactivation by disinfection = 0.5 Log minimum free chlorine residual concentration = 0.8 mg/l total reservoir volume = 20 m 3 minimum reservoir storage at pump shut off = 5 m 3 maximum pumping rate from the reservoir = 0.05 m 3 /min Page 13
14 Step 1: Determine CT required Use Table A-2 in the Standards and Guidelines for Giardia Inactivation at 5 C. Locate the ph 8 section. Within the ph = 8.0 section find the Log inactivation 0.5 column and the chlorine concentration 0.8 mg/l row. We read the required CT from the table CT required = 35 mg min/l Step 2: Determine CT achieved To determine CT achieved we use our formula: CT achieved = Conc. of Cl 2 x F SC x minimum volume of water in the reservoir (m 3 ) maximum hourly flow rate (m 3 /min) We plug in our data values: 1. Monitored chlorine residual at the contact chambers outlet, 0.8 mg/l; 2. Our known short circuiting factor, F SC = 0.1; 3. Our minimum volume of water in storage, in our case that s where the distribution pumps are set to shut down, 5 m 3 ; and, 4. the maximum pumping rate from the contact chamber, 0.05 m 3 /min. CT achieved = 0.8 mg/l x 0.10 x 5 (m3) 0.05 (m3/min) We do the math, and calculate CT achieved = 8 mg min/l Step 3: Compare CT Values Now we compare CT acheived to CT required Clearly, CT acheived (8) is less than CT required (35) This means that we do not achieve the required disinfection. So we must change the operation to improve CT acheived to ensure the required disinfection is met. The first impulse might be to increase the chlorine dosage. However, the dosage would have to be increased to extremely high levels to achieve the required Giardia inactivation. So let s look at the configuration of the disinfection chamber illustrated in Figure 4. Page 14
15 Figure 4: Water Reservoir with Mixing and Short Circuiting (F SC = 0.1) Cl 2 Top View The only thing we have going for us in this reservoir with respect to disinfection, is the maximum separation of the inlet and outlet pipes. With this configuration we know that there is significant short-circuiting and mixing of the water in our reservoir. This is reflected in the use of a very poor short circuiting factor, F SC = 0.1. If we add two baffles to the reservoir as illustrated in Figure 5, we elongate the flow path and reduce the potential for short circuiting. This is reflected by an improved (i.e. larger) short circuiting factor. In this case, adding two baffles could get us a three fold increase in the short circuiting factor (F SC ) to 0.3. This is equivalent to increasing the time of chlorine contact three times. Figure 5: Water Reservoir with Two Baffles Reduced Short Circuiting (F SC = 0.3) Cl 2 Top View Adding baffles can be done at a reasonable cost by hanging sheets of plastic from stainless steel hangers and using stainless steel angle iron to hold the plastic tight to the wall and floor. It is very important that the plastic is approved for use in a potable water situation. NSF certification is required on the plastic, but these products are available. Next let s look at the minimum volume of water in storage in the reservoir. We have potentially 20 m 3 of storage available. Current practice is to operate the reservoir with the distribution Page 15
16 pumps kicking out when the volume of water in storage drops to 5 m 3. This practice is illustrated in Figure 6. Figure 6: Water Reservoir with Minimum Volume of Water in Storage = 5m 3 5 m 3 Side View Increasing the minimum volume of water in storage to 15 m 3, increases the minimum contact time three fold. We can do this by resetting our flyght bulbs so that the distribution pumps kick out when the water in storage drops to 15 m 3, or we can install a weir that holds back at least 15 m 3 at all times as illustrated in Figure 7. Figure 7: Water Reservoir with Minimum Volume of Water in Storage = 15m 3 15 m 3 Side View To recap our system modifications to increase chlorine contact time: 1. we increased the flow path and thereby reduced short circuiting; and, 2. we increased the minimum volume of water in storage in the disinfection reservoir. Both modifications increased the chlorine contact time in the disinfection reservoir. Now we want to recalculate CT achieved and compare the new CT acheived to CT required to determine if these modifications will improve the disinfection enough to meet the Giardia reduction requirement. Page 16
17 Repeat Step 2: Determine the revised CT achieved Plugging in our revised data we calculate: CT achieved = C x FSC x minimum volume of water (m3) maximum flow rate (m3/min) CT achieved = 0.8 mg/l x 0.3 x 15 (m3) CT achieved = 72 mg min/l.05 (m3/min) Step 3: Compare CT Values Comparing the revised CT acheived to CT acheived we find: CT acheived (72) exceeds CT req'd (35) So we now meet the required disinfection for Giardia inactivation That is all there is to this discussion of CT disinfection. Evaluating Your Own Disinfection System Now as operators, you need to take a hard look at your waterworks systems to determine how well you are doing with your own disinfection. Do you meet the CT disinfection standard? Are you providing the safest water possible? Are you protecting yourself by practicing due diligence? If you answer No to any of these questions, you need to make some changes at your waterworks. Page 17
18 Reservoir configurations Let s take a look at some basic reservoir configurations. A reservoir s configuration affects the flow of water through the reservoir. The degree of short circuiting within the reservoir is for the most part dependent on the reservoir s configuration. There are likely still a few reservoirs in Alberta that have almost no separation between the inlet and outlet pipes. This scenario is illustrated in Figure 8. These reservoirs have virtually no chlorine contact time. Much of the water within the reservoir does not turn over (i.e. it is not replaced with fresher water) and the water may become stagnant, with no chlorine. In addition to the risk from insufficient disinfection, the inability to turn over the water in the reservoir with fresh water, increases the potential for aquatic floral and fauna growths. Figure 8: Water Reservoir with Mixing and Short Circuiting (F SC << 0.1) Cl 2 Top View As an absolute minimum, the distance from the inlet to the outlet pipes should be maximized as illustrated in Figure 9. Although short circuiting is still significant, this configuration is a big improvement over the adjacent inlet and outlet pipe scenario. Figure 9: Water Reservoir with Mixing and Short Circuiting (F SC = 0.1) Cl 2 Top View Page 18
19 Installation of baffles within the reservoir will elongate the flow path and reduce the potential for short circuiting as demonstrated by our previous example and illustrated here as Figure 10. The baffles also ensure chlorinated water is distributed throughout a greater portion of the reservoir. However, with only two baffles there will likely be some areas where water becomes stagnant due to a lack of water turn over with chlorinated water. Figure 10: Water Reservoir with Two Baffles Reduced Short Circuiting (F SC = 0.3) Cl 2 Top View Installation of a multiple baffles within a disinfection reservoir greatly lengthens the flow path. Figure 11 shows a reservoir configuration with 8 curtain type baffles. The short circuiting factor for this type of configuration would likely exceed 0.7. Tracer tests of the reservoir would be required to determine the actual short circuiting factor. The likelihood of any stagnant water existing with this configuration would be minimal. Flow through a reservoir with this configuration is approaching the scenario of flow through a pipe that we observed in Figure 1. Figure 11: Water Reservoir with Multiple Baffles with Minimal Short Circuiting (F SC = ) Cl 2 Top View The addition of baffles has increased the chlorine contact time by at least seven times over the configuration in Figure 9, where only maximum separation of the inlet and outlet pipes existed. This is equivalent to increasing the size of the Figure 9 reservoir by seven times at a fraction of the cost. Page 19
20 Final Note I ve included a list of contacts at Alberta Environment for all the municipal approvals coordinators throughout the province. If you need help with understanding CT, or if you are setting Giardia reduction requirements or short circuiting factors for your chlorine contact reservoirs, call us. We want to ensure that you are heading in the right direction with your move to CT Disinfection. Simple modifications to your system may be all that is needed to meet the current disinfection standard, CT disinfection. You owe it to your customers, your employers and yourself to produce the safest water possible. If you are not using CT Disinfection, you are not doing all you can and are not practicing due diligence. You are an important public health professional. Practicing CT disinfection, in conjunction with a well operated and monitored surface water or GWI water treatment plant, allows you to produce the safest water possible and also to demonstrate that you have done so. Page 20
21 ALBERTA ENVIRONMENT CONTACTS MUNICIPAL APPROVAL COORDINATORS REGION NAME & LOCATION PHONE FAX Southern Region- Calgary Office Frank Lotz, P. Eng. (403) Brock Rush, P. Eng. (403) Craig Reich, A. Sc. T. (403) Southern Region- Ben Lichtenwald, EIT (403) Lethbridge Office Wayne Williams,CET (403) Northern Region- Edmonton Office (Twin Atria) Northern Region Grande Prairie/Peace River Office Central Region Red Deer Office Central Region Stony Plain Office Asoke Weerasinghe, P. Eng. (780) Nicola Harper, EIT (780) Terry McGinn (780) George Neurohr, P. Eng. (780) David Curran, EIT (780) Steve Johnson, P. Eng. (403) Win Tun, EIT (403) Alvin Beier, RET (403) Randy Lewis, P. Eng. (780) / Renato Chiarella, P. Eng. (780) / David Dowhaniuk (780) / Page 21
Nova Scotia Treatment Standards for Municipal Drinking Water Systems
Nova Scotia Treatment Standards for Municipal Drinking Water Systems Approval Date: March 12, 2012 Effective Date: March 12, 2012 Approved By: S. J. Snook, Deputy Minister Version Control: Replaces: Treatment
COSTS AND THE CHOICE OF DRINKING WATER TREATMENT TECHNOLOGY IN SMALL AND RURAL SYSTEMS
COSTS AND THE CHOICE OF DRINKING WATER TREATMENT TECHNOLOGY IN SMALL AND RURAL SYSTEMS By: Mohammed H.I. Dore, Arian Khaleghi- Moghadam, Rajiv G. Singh, and Gopal Achari Res'Eau-Waternet_Project 4.2-DORE
Ultra Violet Disinfection 01422 833121 [email protected]
[email protected] Applications Overview Ultraviolet (UV) disinfection is used to treat three billion litres of water every day around the world as it is a highly effective treatment method
Practice Tests Answer Keys
Practice Tests Answer Keys COURSE OUTLINE: Module # Name Practice Test included Module 1: Basic Math Refresher Module 2: Fractions, Decimals and Percents Module 3: Measurement Conversions Module 4: Linear,
EPB 311- Strategies for Dealing with Groundwater Treatment Systems Having High Natural Ammonia
EPB 311- Strategies for Dealing with Groundwater Treatment Systems Having High Natural Ammonia Background The occurrence of ammonia (NH 3 ) in the water source is often associated with pollution due to
OPTIMISE TANK DESIGN USING CFD. Lisa Brown. Parsons Brinckerhoff
OPTIMISE TANK DESIGN USING CFD Paper Presented by: Lisa Brown Authors: Lisa Brown, General Manager, Franz Jacobsen, Senior Water Engineer, Parsons Brinckerhoff 72 nd Annual Water Industry Engineers and
THESIS INTERNAL HYDRAULICS OF BAFFLED DISINFECTION CONTACT TANKS USING COMPUTATIONAL FLUID DYNAMICS. Submitted by. Qing Xu
THESIS INTERNAL HYDRAULICS OF BAFFLED DISINFECTION CONTACT TANKS USING COMPUTATIONAL FLUID DYNAMICS Submitted by Qing Xu Department of Civil and Environmental Engineering In partial fulfillment of the
Water Quality Contingency Planning Standard EPB 540B
Water Quality Contingency Planning Standard EPB 540B November 15, 2012 Water Quality Contingency Planning Standard The Water Quality Contingency Plan Standard is provided to aid waterworks owners and operators
Electronic Reporting of Drinking Water Quality Monitoring Information. User Manual for Drinking Water Operators. Web Form Data Submission
Electronic Reporting of Drinking Water Quality Monitoring Information User Manual for Drinking Water Operators Web Form Data Submission Prepared by: Alberta Environment Environmental Assurance Monitoring,
4 Water supply description
4 Water supply description A description of the drinking-water system is equally applicable to large utilities with piped distribution systems, piped and non-piped community supplies, including handpumps
RESERVOIR CFD MODELLING WHAT ARE THE BENEFITS OF USING A 3D MODEL?
RESERVOIR CFD MODELLING WHAT ARE THE BENEFITS OF USING A 3D MODEL? Nasrine Tomasi AWT Water Limited,Robert White AWT Water Limited, Thomas Joseph AWT Water Limited ABSTRACT Water utilities own and operate
Coagulation and Flocculation in Water and Wastewater Treatment
W, A. R, Coagulation and Flocculation in Water and Wastewater Treatment Second Edition 02,/f John Bratby,» :.'; '5 s " - ' '! ' " ; i '. ', ' j ',... -,..,.,.-* ;, 0 61^/16*36 S "+ "J6 27 48 FAX 0 6151/16
How do you treat water based on water quality from different water sources?
How do you treat water based on water quality from different water sources? Why? Authors: Wendy Lane and Kim Sciarrone Seattle Public Schools; Seattle, WA Water from different sources will contain different
Mission Hill Water Treatment Plant & Kalamalka Lake Pump Station Upgrades
Mission Hill Water Treatment Plant Treatment Plant Pilot Testing Regional District of North Okanagan, assisted by Sandwell Engineering Services and four manufacturers conducted pilot scale water treatment
7/99 Technical Support Document for the Evaluation of Aerobic Biological Treatment Units with Multiple Mixing Zones
7/99 Technical Support Document for the Evaluation of Aerobic Biological Treatment Units with Multiple Mixing Zones I. OVERVIEW AND PURPOSE This document is intended to provide information to assist anyone
Source Water Protection Practices Bulletin Managing Sanitary Sewer Overflows and Combined Sewer Overflows to Prevent Contamination of Drinking Water
United States Office of Water EPA 916-F-01-032 Environmental Protection (4606) July 2001 Agency Source Water Protection Practices Bulletin Managing Sanitary Sewer Overflows and Combined Sewer Overflows
Ground Water Rule Request for 4-log Certification Chlorination
Massachusetts Department of Environmental Protection - Drinking Water Program Ground Water Rule Request for 4-log Certification Chlorination Form: GWR D: 4-Log Certification - Chlorination Important Note:
Water Supply. Simulation of Water Distribution Networks. Mohammad N. Almasri. Optimal Design of Water Distribution Networks Mohammad N.
Water Supply Simulation of Water Distribution Networks The Use of EPANET Mohammad N. Almasri 1 Introduction This presentation focuses on two issues: The simulation of water distribution networks (WDNs)
Residual Chlorine Decay Simulation in Water Distribution System
The 7 th International Symposium on Water Supply Technology, Yokohama 2006, November 22-24, 2008, Yokohama, Japan Residual Chlorine Decay Simulation in Water Distribution System Toru Nagatani (Osaka Municipal
Experts Review of Aerobic Treatment Unit Operation and Maintenance. Bruce Lesikar Texas AgriLife Extension Service
Experts Review of Aerobic Treatment Unit Operation and Maintenance Bruce Lesikar Texas AgriLife Extension Service Overview Overview of Aerobic Treatment Units Installing for accessibility to system components
Protecting your private water supplies. The possible causes of contamination and their remediation to prevent this risk.
Protecting your private water supplies The possible causes of contamination and their remediation to prevent this risk. Contamination from a variety of sources can occur potentially at any point throughout
Stenner Pump Chlorinator Installation & Start Up Guide
Clean Water Made Easy www.cleanwaterstore.com Stenner Pump Chlorinator Installation & Start Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance
Deriving Demand Functions - Examples 1
Deriving Demand Functions - Examples 1 What follows are some examples of different preference relations and their respective demand functions. In all the following examples, assume we have two goods x
The 3rd Busan Global Water Forum 2015. Multi-Parameter Water Quality Monitoring System. Aqua2000. 3 of Sep 2015 Kyung-Yup Hwang
The 3rd Busan Global Water Forum 2015 Multi-Parameter Water Quality Monitoring System Aqua2000 3 of Sep 2015 Kyung-Yup Hwang CONTENTS 1. Company Profile 2. Tap Water Management Issues 3. Overview of Aqua2000
ENVIRONMENTAL CODE OF PRACTICE FOR CONCRETE BATCH PLANT & ROCK WASHING OPERATIONS
ENVIRONMENTAL CODE OF PRACTICE FOR CONCRETE BATCH PLANT & ROCK WASHING OPERATIONS PREPARED BY: DEPARTMENT OF ENVIRONMENT AND LANDS INDUSTRIAL ENVIRONMENTAL ENGINEERING DIVISION APRIL 16, 1992 - TABLE OF
Odyssey of the Mind Technology Fair. Simple Electronics
Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right
CFD Modeling as a Tool for Clarifier Design
WEF Webcast: Optimizing Clarifier Design and Performance CFD Modeling as a Tool for Clarifier Design Outline of Presentation What is CFD? Typical Applications Activated Sludge Example Projects Benefits
Coagulation and Flocculation
Coagulation and Flocculation Groundwater and surface water contain both dissolved and suspended particles. Coagulation and flocculation are used to separate the suspended solids portion from the water.
Power consumption (kw)
OS Series Series description LIT OS systems are applied to wastewater disinfection. The models of this series were developed on base of high-efficiency low-pressure amalgam lamps and have all components
Water Water Treatment Plant Tour
Water Water Treatment Plant Tour Don Rankin, Superintendent Topeka, KS 66606 785-368-3111 Tel 785-368-3825 FAX For a complete list of contacts with phone numbers, FAX numbers and email addresses, click
Septic Tank to Cistern Conversions. Saving Water & Saving Money
Florida Keys Aqueduct Authority 1100 Kennedy Drive Key West, Florida 33040 Septic Tank to Cistern Conversions Saving Water & Saving Money One of the benefits of connecting to the Central Wastewater System
Nitrification TCEQ. Public Drinking Water Conference Austin, Texas August 16, 2006. A System s Perspective after 20 years of Chloramination
Nitrification A System s Perspective after 20 years of Chloramination Presented by: Daniel K. Nix Water Source/Purification Superintendent City of Wichita Falls Public Drinking Water Conference Austin,
MEMCOR membranes for drinking water applications. Water Technologies
MEMCOR membranes for drinking water applications Water Technologies Memcor membranes Why choose membrane filtration? As ever-tightening water regulations continue to challenge the limits of conventional
BULK WATER HAULING GUIDELINES
BULK WATER HAULING GUIDELINES Under The Public Health Act regulations, Bulk Water Haulers must obtain a permit to sell or convey water for sale for domestic purposes. For the purposes of this guideline,
WC flushing cistern single or dual flush 0.13 0.05 2 to fill in 2 minutes WC trough cistern 0.15 per WC 0.10 2 Wash basin tap size 1 2
HAC_C0.qxd 7/4/08 9: Page 74 Chapter Pipe sizing Pipes and fittings should be sized so that the flow rates for individual draw-offs are equal to the design flow rates shown in table.. During simultaneous
There are two sheets, Diesel and Electric, identified by tabs at the bottom of the sheet.
Willard Says Absolutely fascinating information about practical hydraulic dredging. How To Use the Dredge Production Cost Spreadsheet This program guide describes the various dredge operating cost parameters
Experiment 2: Conservation of Momentum
Experiment 2: Conservation of Momentum Learning Goals After you finish this lab, you will be able to: 1. Use Logger Pro to analyze video and calculate position, velocity, and acceleration. 2. Use the equations
DESCRIPTION OF STORMWATER STRUCTURAL CONTROLS IN MS4 PERMITS
DESCRIPTION OF STORMWATER STRUCTURAL CONTROLS IN MS4 PERMITS Phase I MS4 permits require continuous updating of the stormwater system inventory owned and operated by the MS4. They also include inspection
Cyanotoxin Removal in Drinking. Recreational Waters. Judy Westrick April 14, 2011 2011 Northeast Regional Cyanobacteria Workshop
Cyanotoxin Removal in Drinking Water Treatment Process and Recreational Waters Judy Westrick April 14, 2011 2011 Northeast Regional Cyanobacteria Workshop NEIWPCC Overview Water Treatment Source and Recreational
Session 7 Fractions and Decimals
Key Terms in This Session Session 7 Fractions and Decimals Previously Introduced prime number rational numbers New in This Session period repeating decimal terminating decimal Introduction In this session,
Water Treatment. Session Objectives
Water Treatment Session Objectives To demonstrate the need for treatment of surface waters and some groundwaters for drinking purposes. To introduce the concept of the multiple barrier principle and to
Innovation and Progress in Water Treatment Technology
Innovation and Progress in Water Treatment Technology Degree of separation of ultrafiltration Summary of the various processes The water will be pressed through the between the raw water side and the filtrate
Storm Drainage Systems 11.9-1
Storm Drainage Systems 11.9-1 11.9 Gutter Flow Calculations 11.9.1 Introduction Gutter flow calculations are necessary in order to relate the quantity of flow (Q) in the curbed channel to the spread of
Let s explore the content and skills assessed by Heart of Algebra questions.
Chapter 9 Heart of Algebra Heart of Algebra focuses on the mastery of linear equations, systems of linear equations, and linear functions. The ability to analyze and create linear equations, inequalities,
IB Maths SL Sequence and Series Practice Problems Mr. W Name
IB Maths SL Sequence and Series Practice Problems Mr. W Name Remember to show all necessary reasoning! Separate paper is probably best. 3b 3d is optional! 1. In an arithmetic sequence, u 1 = and u 3 =
DRAFT July, 2006 Page 1 of 18
DRAFT July, 2006 Page 1 of 18 Swimming Pool Venue Environmental Health Outbreak Investigation Survey: An Environmental Health Systems Approach to Recreational Water Illness Prevention - Information Collection
Alberta Environment Standards for Advanced Waste Systems
Alberta Environment Standards for Advanced Waste Systems + Alberta Rural Organic Waste to Resources Network + George Neurohr Regional Municipal Engineer Grande Prairie, Alberta May 1, 2012 Contents: Introduction
1.85 WATER AND WASTEWATER TREATMENT ENGINEERING FINAL EXAM DECEMBER 20, 2005
1.85 WATER AND WASTEWATER TREATMENT ENGINEERING FINAL EXAM DECEMBER 20, 2005 This is an open-book exam. You are free to use your textbook, lecture notes, homework, and other sources other than the internet.
Teacher Answer Key: Measured Turns Introduction to Mobile Robotics > Measured Turns Investigation
Teacher Answer Key: Measured Turns Introduction to Mobile Robotics > Measured Turns Investigation Phase 1: Swing Turn Path Evaluate the Hypothesis (1) 1. When you ran your robot, which wheel spun? The
Lead Understanding Lead Exposure
Lead Understanding Lead Exposure School officials and child care providers need to know whether the students, teachers and staff consume elevated levels of lead when drinking water in their facility, because
Applying Life Cycle Assessment to Drinking Water Treatment
Applying Life Cycle Assessment to Drinking Water Treatment W.Takashima*, S.Takizawa**and M. Fujiwara* *Japan Water Research Center, Minato-ku, Tokyo, 105-0001, Japan ([email protected]) ** University
CERTIFICATION TO OPERATE WATER AND WASTEWATER TREATMENT SYSTEMS APPLICATION INSTRUCTIONS
COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION STATE BOARD FOR CERTIFICATION OF WATER AND WASTEWATER SYSTEMS OPERATORS CERTIFICATION TO OPERATE WATER AND WASTEWATER TREATMENT SYSTEMS
CHAPTER 2 HYDRAULICS OF SEWERS
CHAPTER 2 HYDRAULICS OF SEWERS SANITARY SEWERS The hydraulic design procedure for sewers requires: 1. Determination of Sewer System Type 2. Determination of Design Flow 3. Selection of Pipe Size 4. Determination
Tokyo Waterworks supports the capital of Tokyo
Tokyo Waterworks supports the capital of Tokyo Tokyo, the Japanese capital, is the largest city in Japan with a population of about 13.16 million, which is about 10% of the country s entire population
December 2003 EPB 241B. Some sections are completed, some are partially complete and some are left blank.
Note: As of October 1, 2012 The Water Security Agency and Saskatchewan Ministry of Environment share responsibility and authority for the administration of The Environmental Management and Protection Act,
MULTIPLE REGRESSION WITH CATEGORICAL DATA
DEPARTMENT OF POLITICAL SCIENCE AND INTERNATIONAL RELATIONS Posc/Uapp 86 MULTIPLE REGRESSION WITH CATEGORICAL DATA I. AGENDA: A. Multiple regression with categorical variables. Coding schemes. Interpreting
CHAPTER 8 UPGRADING EXISTING TREATMENT FACILITIES
CHAPTER 8 UPGRADING EXISTING TREATMENT FACILITIES 8-1. General. Upgrading of wastewater treatment plants may be required to handle increased hydraulic and organic loadings to meet existing effluent quality
Guidelines for Four-Log Virus Treatment of Ground Water Drinking Water Section Florida Department of Environmental Protection October 2009
Guidelines for Four-Log Virus Drinking Water Section Florida Department of Environmental Protection October 2009 2600 Blair Stone Road, MS 3520 Tallahassee, Florida 32399-2400 www.dep.state.fl.us Contents
for Sediment Removal desired levels. The filtered water then can be chemically treated to ensure its safety. Municipal water Preliminary settling
Treating Water for Sediment Removal J.R. Miner Lakes, ponds, and streams are important sources of water for many farms, rural camps, and households as well as for many municipalities in Oregon. Even under
FAMILY PROTECTION FROM WATERBORNE DISEASES
A Product by : GIVE A 100% FAMILY PROTECTION FROM WATERBORNE DISEASES CATALOGUE 100% SAFE WATER LATEST JAPAN TECHNOLOGY ABOUT US We are introducing a unique Water Purifier with the proud name of Harshali
The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.
260 17-1 I. THEORY EXPERIMENT 17 QUALITATIVE STUDY OF INDUCED EMF Along the extended central axis of a bar magnet, the magnetic field vector B r, on the side nearer the North pole, points away from this
Open Channel Flow Measurement Weirs and Flumes
Open Channel Flow Measurement Weirs and Flumes by Harlan H. Bengtson, PhD, P.E. 1. Introduction Your Course Title Here Measuring the flow rate of water in an open channel typically involves some type of
HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS
HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS Shiwei William Guan, Ph.D. Vice President, R&D and International Business Madison Chemical Industries Inc. 490
Basic numerical skills: EQUATIONS AND HOW TO SOLVE THEM. x + 5 = 7 2 + 5-2 = 7-2 5 + (2-2) = 7-2 5 = 5. x + 5-5 = 7-5. x + 0 = 20.
Basic numerical skills: EQUATIONS AND HOW TO SOLVE THEM 1. Introduction (really easy) An equation represents the equivalence between two quantities. The two sides of the equation are in balance, and solving
Standard Hydraulic Piping Flushing Procedure
Page 1 of 6 1.0 Scope This procedure covers the minimum technical requirements for cleaning and flushing of Hydraulic and Piping, and related accessories. 2.0 Introduction In hydraulic fluid power systems,
Steps in the design process. The draft Ultraviolet Disinfection Guidance Manual (USEPA, 2003) recommends the following steps in the design:
DESIGN OF UV DISINFECTION SYSTEMS FOR DRINKING WATER In EPA s economic analyses for the proposed LT2ESWTR, EPA estimated that 500 to 1000 filtration plants will choose UV disinfection as part of their
Dynamic Modeling Of An Ozone Disinfection Facility
Dynamic Modeling Of An Ozone Disinfection Facility Michael Etheridge Black & Veatch 8400 Ward Parkway Kansas City, MO 64114 Presented to the Fourteenth Ozone World Congress August 25 th, 1999 ABSTRACT
Elasticity. I. What is Elasticity?
Elasticity I. What is Elasticity? The purpose of this section is to develop some general rules about elasticity, which may them be applied to the four different specific types of elasticity discussed in
SALES EMAIL TEMPLATES. for prospecting, scheduling meetings, following up, networking, and asking for referrals.
36 SALES EMAIL TEMPLATES for prospecting, scheduling meetings, following up, networking, and asking for referrals. INTRODUCTION: A LOST OPPORTUNITY Here was the scenario: We make a valuable connection
UV Disinfection Systems A Series. Main Applications: Drinking Water, Process Water, Warm Water / Legionellae. IT T Industries Engineered for life
DIN EN ISO 9001 DIN EN ISO 9001 DIN EN ISO 14001 UV Disinfection Systems A Series Main Applications: Drinking Water, Process Water, Warm Water / Legionellae DIN EN ISO 14001 UV Disinfection Systems A Series
WASTEWATER MANAGEMENT SYSTEM
WASTEWATER MANAGEMENT SYSTEM PROTECT WHAT S MOST IMPORTANT TO YOU... Choosing to live in a suburban or rural area without a municipal sewer no longer means having to live with the problems associated with
City of Kenora Water Treatment and Distribution System. Drinking Water Quality Management System. Operational Plan Version 11
City of Kenora Water Treatment and Distribution System Drinking Water Quality Management System Operational Plan Version 11 Uncontrolled Printed Copy Revision 11 March 3, 2015 Page 1 Table of Contents
Site Attendance Guidelines for Automated/Unattended Monitoring and Process Controlled Facilities
Site Attendance Guidelines for Automated/Unattended Monitoring and Process Controlled Facilities June 2015 EPB #428 The guidelines will be revised and updated as new information warrants change. Please
Alberta Onsite Wastewater Management Association Installer Training Program
Alberta Onsite Wastewater Management Association Installer Training Program OWTS 100 Overview and Principles of Wastewater Treatment Systems Brief Review of All Types of Systems 1. Know the general principles
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
2. AUDIT OBSERVATIONS
Drinking Water Audit Report Local Authority: Kerry County Council Date of Audit: 16/09/08 Plant Inspected: Dromin Water Treatment Plant Listowel File Reference: DW2008/554 Supply Code (1300PUB1204) Auditors:
How To Water System
Mid-Monroe Water System: Soluble Iron and Manganese Removal via Oxidation & Filtration Daniel Rickard, P.E. Engineering Project Manager Pennsylvania-American Water Company Who Is American Water We are
IMPACT OF CHEMICALS ADDITION IN WATER/WASTEWATER TREATMENT ON TDS CONCENTRATION AND SLUDGE GENERATION Jurek Patoczka, PhD, PE Hatch Mott MacDonald 27 Bleeker Str., Millburn, NJ 07041 (973) 912 2541 [email protected]
Part 1 Expressions, Equations, and Inequalities: Simplifying and Solving
Section 7 Algebraic Manipulations and Solving Part 1 Expressions, Equations, and Inequalities: Simplifying and Solving Before launching into the mathematics, let s take a moment to talk about the words
TALLINN WATER TREATMENT AND SEWERAGE Tuuli Myllymaa
TALLINN WATER TREATMENT AND SEWERAGE Tuuli Myllymaa Tallinn is the capital of Estonia. It has approximately 450,000 inhabitants and the town area is about 150 km 2. Tallinn Water Ltd., owned by the City
WATER TREATMENT IN AUCKLAND
WATER TREATMENT IN AUCKLAND Auckland's water (like water throughout New Zealand) is a combination of water from dams and water from underground springs. Depending on the source of the water, it has different
1051-232 Imaging Systems Laboratory II. Laboratory 4: Basic Lens Design in OSLO April 2 & 4, 2002
05-232 Imaging Systems Laboratory II Laboratory 4: Basic Lens Design in OSLO April 2 & 4, 2002 Abstract: For designing the optics of an imaging system, one of the main types of tools used today is optical
What is Chlorination?
What is Chlorination? What is chlorination? Microorganisms can be found in raw water from rivers, lakes and groundwater. While not all microorganisms are harmful to human health, there are some that may
February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities
FIRE CODE VARIANCE February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5 ISSUE: Fire Safety and Hand Hygiene in Healthcare Facilities This Variance covers alcohol based hand hygiene products used in healthcare
Town of New Castle Utility Department Introduction
Town of New Castle Utility Department Introduction Town of New Castle Utility Department Mission Statement Our commitment is to ensure that our customers receive high quality water and wastewater treatment
Microeconomics Sept. 16, 2010 NOTES ON CALCULUS AND UTILITY FUNCTIONS
DUSP 11.203 Frank Levy Microeconomics Sept. 16, 2010 NOTES ON CALCULUS AND UTILITY FUNCTIONS These notes have three purposes: 1) To explain why some simple calculus formulae are useful in understanding
AP ENVIRONMENTAL SCIENCE 2007 SCORING GUIDELINES
AP ENVIRONMENTAL SCIENCE 2007 SCORING GUIDELINES Question 1 Read the Fremont Examiner article below and answer the questions that follow. (a) Identify ONE component of the sewage that is targeted for removal
Does my drinking water contain Fluoride?
Does my drinking water contain Fluoride? Yes, all New York City tap water contains fluoride. In accordance with Article 141.08 of the New York City Health Code, DEP, as the New York City water supplier,
Confidence intervals
Confidence intervals Today, we re going to start talking about confidence intervals. We use confidence intervals as a tool in inferential statistics. What this means is that given some sample statistics,
If A is divided by B the result is 2/3. If B is divided by C the result is 4/7. What is the result if A is divided by C?
Problem 3 If A is divided by B the result is 2/3. If B is divided by C the result is 4/7. What is the result if A is divided by C? Suggested Questions to ask students about Problem 3 The key to this question
How To Ensure Safety At A Swimming Pool Or Spa
Index Purpose... 2 Application... 2 Referral Agency... 2 Associated Requirements... 2 Referenced standards... 2 Definitions... 2 Disinfection System... 4 Filtration equipment... 4 Small child safety...
Mathematics. What to expect Resources Study Strategies Helpful Preparation Tips Problem Solving Strategies and Hints Test taking strategies
Mathematics Before reading this section, make sure you have read the appropriate description of the mathematics section test (computerized or paper) to understand what is expected of you in the mathematics
Case Study: Research Leads To Large-Scale Microfiltration Plants 10/01/1999
Case Study: Research Leads To Large-Scale Microfiltration Plants 10/01/1999 What are the advantages of low-pressure membrane treatment processes for surface water supplies? How are the requirements of
MATHEMATICS FOR WATER OPERATORS
MATHEMATICS FOR WATER OPERATORS Chapter 16: Mathematics The understanding of the mathematics of water hydraulics (flows, pressures, volumes, horsepower, velocities) and water treatment (detention time,
INTRODUCTION TO MATHEMATICAL MODELLING
306 MATHEMATICS APPENDIX 2 INTRODUCTION TO MATHEMATICAL MODELLING A2.1 Introduction Right from your earlier classes, you have been solving problems related to the real-world around you. For example, you
TURBIDITY AND MICROBIAL RISK IN DRINKING WATER
TURBIDITY AND MICROBIAL RISK IN DRINKING WATER Prepared by: Martin J. Allen, Ronald W. Brecher, Ray Copes, Steve E. Hrudey (Chair), and Pierre Payment Ministerial Technical Advisory Committee February
