Installation Instructions for use by heating contractor. VITODENS r 222-F IMPORTANT. Read and save these instructions for future reference.
|
|
|
- Adela Rodgers
- 9 years ago
- Views:
Transcription
1 Installation Instructions for use by heating contractor Vitodens 222-F, B2TA Series Models 19 and 35 Floor mounted, gas-fired condensing storage combi boiler For operation with natural gas and liquid propane gas Heating input: 12 to 125 MBH 3.5 to 37 kw VITODENS r 222-F H Product may not be exactly as shown IMPORTANT Read and save these instructions for future reference. 12/2015 Please file in Service Binder
2 Safety Safety, Installation and Warranty Requirements Vitodens 222-F, B2TA 19 and 35 Installation Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections). 2 Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel. For a listing of applicable literature, please see section entitled Important Regulatory and Installation Requirements. Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void. Licensed professional heating contractor The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor. Please see section entitled Important Regulatory and Installation Requirements. Contaminated air Air contaminated by chemicals can cause by-products in the combustion process, which are poisonous to inhabitants and destructive to Viessmann equipment. For a listing of chemicals which cannot be stored in or near the boiler room, please see subsection entitled Mechanical room in the Installation Instructions. Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins. WARNING Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow the Viessmann maintenance schedule of the boiler contained in this manual. Operating and Service Documentation It is recommended that all product documentation such as parts lists, operating and service instructions be handed over to the system user for storage. Documentation is to be stored near boiler in a readily accessible location for reference by service personnel. Carbon monoxide Improper installation, adjustment, service and/or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas. For information pertaining to the proper installation, adjustment, service and maintenance of this equipment to avoid formation of carbon monoxide, please see subsection entitled Mechanical room and Venting requirements in the Venting System Installation Instructions. Fresh air This equipment requires fresh air for safe operation and must be installed ensuring provisions for adequate combustion and ventilation air exist. For information pertaining to the fresh air requirements of this product, please see subsection entitled Mechanical room in the Installation Instructions. Equipment venting Never operate boiler without an installed venting system. An improper venting system can cause carbon monoxide poisoning. For information pertaining to venting and chimney requirements, please see section entitled Venting Connection. All products of combustion must be safely vented to the outdoors. WARNING This boiler requires fresh air for safe operation and must be installed with provisions for adequate combustion and ventilation air (in accordance with local codes and regulations of authorities having jurisdiction). Do not operate this boiler in areas with contaminated combustion air. High levels of contaminants such as dust, lint or chemicals can be found at construction sites, home renovations, in garages, workshops, in dry cleaning/laundry facilities, near swimming pools and in manufacturing facilities. Contaminated combustion air will damage the boiler and may lead to substantial property damage, severe personal injury and/or loss of life. Ensure boiler/burner is inspected and serviced by a qualified heating contractor at least once a year in accordance with the Service Instructions of the boiler.
3 Vitodens 222-F, B2TA 19 and 35 Installation Safety, Installation and Warranty Requirements Safety Fiberglass wool and ceramic fiber materials WARNING Inhaling of fiberglass wool and/or ceramic fiber materials is a possible cancer hazard. These materials can also cause respiratory, skin and eye irritation. The state of California has listed the airborne fibers of these materials as a possible cancer hazard through inhalation. When handling these materials, special care must be applied. Suppliers of ceramic fiber products recommend the following first aid measures: - Respiratory tract (nose and throat) irritation: If respiratory tract irritation develops, move the person to a dust free location. - Eye irritation: If eyes become irritated, flush immediately with large amounts of lukewarm water for at least 15 minutes. Eyelids should be held away from the eyeball to ensure thorough rinsing. Do not rub eyes. - Skin irritation: If skin becomes irritated, remove soiled clothing. Do not rub or scratch exposed skin. Wash area of contact thoroughly with soap and water. Using a skin cream or lotion after washing may be helpful. - Gastrointestinal irritation: If gastrointestinal tract irritation develops, move the person to a dust free environment. Suppliers of fiberglass wool products recommend the following precautions be taken when handling these materials: - Avoid breathing fiberglass dust and contact with skin and eyes. - Use NIOSH approved dust/mist respirator. - Wear long-sleeved, loose fitting clothing, gloves and eye protection. - Wash work clothes separately from other clothing. Rinse washer thoroughly. - Operations such as sawing, blowing, tear-out and spraying may generate airborne fiber concentration requiring additional protection. First aid measures - If eye contact occurs, flush eyes with water to remove dust. If symptoms persist, seek medical attention. - If skin contact occurs, wash affected areas gently with soap and warm water after handling. WARNING Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause serious injury or loss of life and which are known to the State of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby the appliance. About these Installation Instructions Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include WARNING, CAUTION, and IMPORTANT. See below. WARNING Indicates an imminently hazardous situation which, if not avoided, could result in loss of life, serious injury or substantial product/property damage. CAUTION Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/ property damage. Warnings draw your attention to the presence of potential hazards or important product information. Cautions draw your attention to the presence of potential hazards or important product information. IMPORTANT Helpful hints for installation, operation or maintenance which pertain to the product. This symbol indicates that additional, pertinent information is to be found. This symbol indicates that other instructions must be referenced. 3
4 Table of Contents Vitodens 222-F, B2TA 19 and 35 Installation Safety General Information Page Safety, Installation and Warranty Instructions...2 Product documentation...2 Warranty...2 Licensed professional heating contractor...2 Contaminated air...2 Advice to owner...2 Carbon monoxide...2 Fresh air...2 Equipment venting...2 About these Installation Instructions...3 Important Regulatory and Installation Requirements...6 Codes...6 Instructing the system user...6 Initial start-up...6 Working on the equipment...6 Technical literature...6 For installations on the Commonwealth of Massachusetts...7 CSD-1 field testing of high limit switches...7 Applicability...8 Product Information...8 Mechanical Room...9 Set-up Boiler Connections Before Set-up...10 Minimum Clearances...10 Recommended minimum service clearances...10 Connections...13 Boiler venting...13 Connecting power...13 Connecting heating system...13 Proper piping practice...13 Gas shut-off valve connection...13 Gas connection and piping...14 Gas piping pressure test...15 Flue gas connection...15 Removing the front panels...16 Accessing the control unit connections...17 External accessories connection box...20 Boiler control base...21 Condensate connection...22 Vertical piping installation...23 Side piping installation
5 Vitodens 222-F, B2TA 19 and 35 Installation Table of Contents Page Boiler Connections (continued) Safety Connections and Pressure Testing...29 Low water cut-off...29 Performing a boiler pressure test...29 Waterside Flow...30 Waterside flow (primary circuit)...30 Installation Examples...31 System Layout Alternative Connection...39 Control Connections Wiring Diagram...40 Electrical Connections...42 Power supply connection of accessories...42 Connection of accessories...42 Accessories Connection...43 Connection of accessories...43 Low voltage plug X Accessing the X3 Plug...44 Connecting the Low-loss Header Sensor...44 Connecting the Outdoor Temperature Sensor...45 External 0-10 Volt Signal Connection...48 LON Module...46 Installing the LON module to the boiler control board...46 Connecting the LON module cable...46 Routing the Connecting Cables...47 External 0-10 Volt DC Signal Connections...48 Connecting a 24 VAC Thermostat...49 Accessory Kit...50 Closing the Boiler...50 Additional Information Closing the External Accessory Connection Box...51 Reinstalling the Front Enclosure Panel...52 Fitting the front panels...52 Technical Data...53 Installation Fittings...55 Lighting and Operating Instructions
6 General Information Important Regulatory and Installation Requirements Vitodens 222-F, B2TA 19 and 35 Installation Codes The installation of this unit shall be in accordance with local codes or, in the absence of local codes, use CAN/ CSA-B149.1 or.2 Installation Codes for Gas Burning Appliances for Canada. For U.S. installations use the National Fuel Gas Code ANSI Z Always use latest editions of codes. In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/ NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction. Instructing the system user The installer of the system is responsible to ensure the system operator/ultimate owner is made familiar with the system functioning, its activation, and its shut-down. Initial start-up Initial start-up must be performed by a qualified heating contractor. Proper completion of the Maintenance Record by the heating contractor is also required. Working on the equipment The installation, adjustment, service, and maintenance of this boiler must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burners, or control. Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in all instances to avoid accidental activation of power during service work. The following topics must be covered: Proper system operation sequence. Explain the equipment. Demonstrate an emergency shut-down, what to do and what not. Explain that there is no substitute for proper maintenance to help ensure safe operation. The Maintenance Record is located in the Service Instructions Please carefully read this manual prior to attempting startup, maintenance or service. Any warranty is null and void if these instructions are not followed. For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product. We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire. Technical literature Literature for the Vitodens boiler: - Technical Data Manual - Installation Instructions - Service Instructions - Operating Instructions and User s Information Manual - Instructions of other Viessmann products utilized and installed - Installation codes mentioned in this manual The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cutoffs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc. Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies. This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required. 6
7 Vitodens 222-F, B2TA 19 and 35 Installation Important Regulatory and Installation Requirements (continued) General Information For installations on the Commonwealth of Massachusetts, the following modifications to NFPA-54 chapter 10 apply: Excerpt from 248 CMR 5-08: 2(a) For all side-wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side-wall exhaust vent termination is less than (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side-wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side-wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professional for the installation of hard-wired carbon monoxide detectors. a. In the event that the side-wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed. 2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS. 4. INSPECTION. The state or local gas inspector of the side-wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4. (b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4: 1. The equipment listed in Chapter 10 entitled Equipment Not Required To Be Vented in the most current edition of NFPA 54 as adopted by the Board; and 2. Product Approved side-wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. CSD-1 Field Testing of High Limit Switches for Vitodens boilers where required by law. VIESSMANN IS NOT RESPONSIBLE FOR ANY DAMAGES THAT THE FOLLOWING TEST PROCEDURE MAY RESULT IN BY OVERHEATING THE SYSTEM. The Vitodens 100/200 boilers are equipped with flow switches that when activated disable or enable the burner to operate. The fixed high limit, when tripped, produces a fault that will require manual reset of the boiler control. Fixed High Limit fault simulation #1: - Close the boiler valve and jumper across the flow switch. - Run the boiler at high fire and it will shut down by the coding card (in B2TA models, set coding address 06 to maximum) but should continue to stack the boiler temperature until the fixed high limit is tripped. - Once the fixed high limit is tripped, slowly open the boiler valve to safely cool the boiler down. Fixed High Limit fault simulation #2: - Throttle the boiler valve to a point where the burner will run with as little flow as possible. - Run the boiler to high fire via relays test. - When the burner shuts down on the electronic limit, close the ball valve to stop the flow. - The boiler temperature should continue a steady increase to trip the fixed high limit. - Once the fixed high limit is tripped, slowly open the boiler valve to safely cool the boiler down. Fixed High Limit fault simulation #3: - Remove one of the wires connected to limit switch, this will produce a fault in the boilers control that requires manual reset. 7
8 General Information Applicability Vitodens 222-F, B2TA 19 and 35 Installation CAUTION The boiler serial number must be provided when ordering replacement parts. IMPORTANT When ordering replacement parts, provide either the 16-digit boiler serial number (on the bar code label) or the 12-digit ASME/NB serial number, located as shown underneath boiler front enclosure panel. Refer to page 16 for instructions on how to remove front enclosure panel. Model No. B2TA 19 Serial No jjjjjjjjj Model No. B2TA 35 Serial No jjjjjjjjj A Stainless steel Inox-Radial heat exchanger for high operational reliability, a long service life and high heating output in the smallest space B Modulating MatriX cylinder gas burner for extremely clean combustion C Integral diaphragm expansion vessel D Graphical user interface E Integral, 3-speed high efficiency circulation pump F Stainless steel DHW primary storage tank. Product Information Natural gas and liquid propane gas-fired condensing heating boiler for weather-responsive operation in closed loop, forced circulation hot water heating systems for space heating and domestic hot water (DHW) production. The Vitodens 222-F, B2TA series boiler comes factory set for operation with natural gas. For a fuel conversion to liquid propane gas no conversion kit is required. The integral primary storage tank 26.5 USG (100 L) capacity offers the DHW convenience of a separate DHW tank with approximately twice that volume. Boiler model must be selected based on an accurate heat loss calculation of the building. Ensure boiler model is compatible with connected radiation. 8 Vitodens 222-F, B2TA series boilers are factory-tested and calibrated. Further gas valve adjustments are not typically required during field start-up. Follow the Vitodens Venting System Installation Instructions to vent this boiler.
9 Vitodens 222-F, B2TA 19 and 35 Installation Mechanical Room General Information During the early stages of designing a new home, we recommend that proper consideration be given to constructing a separate mechanical room dedicated to the gas- or oil-fired heating equipment and domestic hot water storage tank(s). The boiler must be located in a heated indoor area, near a floor drain, and as close as possible to a wall. Whenever possible, install the boiler near an outside wall so that it is easy to duct the venting system to the boiler. Ensure that the boiler location does not interfere with the proper circulation of combustion and ventilation air of other fuel burning equipment within the mechanical room (if applicable). The maximum room temperature of the mechanical room where the boiler is located must not exceed 104ºF (40ºC). Installation area conditions WARNING Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk. H Ensure ambient temperatures are higher than 32 F (0 C) and lower than 104 F (40 C). H Prevent the air from becoming contaminated by halogenated hydrocarbons (e.g. as contained in paint solvents or cleaning fluids) and excessive dust (e.g. through grinding or polishing work). Combustion air for the heating process, and ventilation of the boiler room must be free of corrosive contaminants. To that end, any boiler must be installed in an area that has no chemical exposure. The list to the right indicates the main, currently known sources. H Avoid continuously high levels of humidity (e.g. through frequent drying of laundry). H Never close existing ventilation openings. WARNING If you notice fire coming from the appliance, call the fire department immediately! Do not attempt to extinguish the fire unless qualified to do so. IMPORTANT The service life of the boiler s exposed metallic surfaces, such as the casing and fan housing, is directly influenced by proximity to damp and salty marine environments. In such areas, higher concentration levels of chlorides from sea spray, coupled with relative humidity, can lead to degradation of the exposed metallic surfaces mentioned above. Therefore, it is imperative that boilers installed in such environments not be installed using direct vent systems which draw outdoor air for combustion. Such boilers must be installed using room air dependent vent systems; i.e. using room air for combustion. The indoor air will have a much lower relative humidity and, hence, potential corrosion will be minimized. Sources of combustion and ventilation air contaminants Areas likely to contain contaminants: H New building construction H Swimming pools H Remodelling areas, hobby rooms H Garages with workshops H Furniture refinishing areas H Dry cleaning/laundry areas and establishments H Auto body shops H Refrigeration repair shops H Metal fabrication plants H Plastic manufacturing plants H Photo processing plants H Beauty salons Products containing contaminants: H Chlorine-type bleaches, detergents and cleaning solvents found in household laundry rooms H Paint and varnish removers H Hydrochloric acid, muriatic acid H Chlorine-based swimming pool chemicals H Spray cans containing chlorofluorocarbons H Chlorinated waxes and cleaners H Cements and glues H Refrigerant leaks H Calcium chloride used for thawing H Sodium chloride used for water softening salt H Permanent wave solutions H Adhesives used to fasten building products and other similar items H Antistatic fabric softeners used in clothes dryers WARNING Fire causes a risk of burns and explosion! H Shut down the boiler H Close fuel shut-off valves H Use a tested fire extinguisher, class ABC. 9
10 Set-up Mechanical Room (continued) IMPORTANT Boiler operation in marine environments (damp, salty coastal areas) The service life of the boiler s exposed metallic surfaces, such as the casing and fan housing, is directly influenced by proximity to damp and salty marine environments. Vitodens 222-F, B2TA 19 and 35 Installation In such areas, higher concentration levels of chlorides from sea spray, coupled with relative humidity, can lead to degradation of the exposed metallic surfaces mentioned above. Therefore, it is imperative that boilers installed in such environments not be installed using direct vent systems which draw outdoor air for combustion. Such boilers must be installed using room air dependent vent systems; i.e. using room air for combustion. The indoor air will have a much lower relative humidity and, hence, potential corrosion will be minimized. Before Set-up Before placing boiler in its installation location, ensure all necessary accessories are installed. CAUTION The boiler must be installed in such a way that gas ignition system components are protected from water (spraying, splashing, etc.) during boiler operation and service. Minimum Clearances Recommended minimum service clearances For typical Vitodens installations, Viessmann recommends installing the boiler with the service clearances shown in the illustration on the left. Note: The 12 in. (305 mm) side clearance specified is only recommended to be able to view the boiler certified rating plate, decal and also accommodate the PRV installation kit. The 2 (50 mm) clearance shown is to connect the discharge pipe on either the left or right side of the boiler for the pressure relief valve or the DHW tank temperature and pressure valve. Note: The Vitodens 222-F, B2TA boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the boiler Harmonized Standard ANSI Z CSA 4.9 (latest edition) and therefore is listed for zero clearance to combustibles when vented with a single-wall UL/ULC certified special venting system. The zero inches vent clearance to combustibles for the Vitodens boiler supercedes the clearance to combustibles listing that appears on the special venting system label. The back or side clearance shall be increased if piping installation is required. See the Vitodens 222-F B2TA Venting System Installation Instructions for details. This reduced clearance is also used in Vitodens multiple boiler installation system as described in the multiple boiler installation instructions. The Vitodens 222-F, B2TA boilers are approved for closet and alcove installation with the clearances to combustibles listed. Minimum clearances to combustibles Boiler model B2TA Top 0 0 Sides (left and right) 0 0 Vent pipe 0 0 Front (alcove or closet) 0 0 Rear 0 0 Floor combustible combustible 10
11 Vitodens 222-F, B2TA 19 and 35 Installation Connections Boiler Connections Boiler water connection and piping Use an approved pipe sealant or teflon tape when connecting the following installation fittings. This section constitutes an overview only! Refer to subsequent sections for detailed information on individual piping connections. Note: See installation fitting sets on page 55. Min. 6 (Min. 152 mm) Min. 6 (Min. 152 mm) Legend A Heating supply NPT ¾ B DHW NPT ¾ C Pressure relief valve discharge pipe NPT ¾ D DCW NPT ¾ E Heating return NPT ¾ F Temperature and pressure relief valve discharge pipe NPT ¾ 11
12 Boiler Connections Connections (continued) Vitodens 222-F, B2TA 19 and 35 Installation *1 Legend A Condensate Drain (side) Note: The dimensional drawing shows example fittings for upward connection and connection to the left/right, for installation on finished walls. Order the connection sets separately as accessories. For the dimensions of the individual connection sets, see the design information. Model B2TB 19 and 35 Model B2TB 19 and 35 a *1 in. (mm) 46.1 (1172) k *1 in. (mm) 65.6 (1665) b *1 in. (mm) 48.3 (1227) l *1 in. (mm) 68.0 (1726) c *1 in. (mm) 28 (710) approx. m in. (mm) 16.1 (410) d *1 in. (mm) 52.6 (1337) n in. (mm) 8.8 (224) f *1 in. (mm) 57.0 (1447) o in. (mm) 15.3 (389) g in. (mm) 2.0 (50) p in. (mm) 14.2 (361) h *1 in. (mm) 59.1 (1502) q in. (mm) 12.6 (320) i *1 in. (mm) 64.2 (1630) r in. (mm) 13.0 (330) j *1 in. (mm) 65.6 (1666) s in. (mm) 8.7 (220) 12 Note: All height dimensions of the boiler have a tolerance of +.6 in. (+15 mm) due to the factory installed adjustable feet *1 Add 1f in. (40 mm) when using the optional accessory seismic bracket kit. Note: All height dimensions of the boiler have a tolerance of +.5 in. (+13 mm) due to the seismic bracket adjustable feet.
13 Vitodens 222-F, B2TA 19 and 35 Installation Connections (continued) Boiler Connections Boiler venting The Vitodens 222-F B2TA boiler comes with a pre-installed vent pipe adaptor A. Run venting system, single-wall or coaxial, through the side wall or the roof, taking the shortest possible route and at a rising angle (min. 3º). WARNING Remove outer gasket if single wall (boiler room air dependant) venting system is used. Refer to the Vitodens Venting System Installation Instructions CAUTION Under certain climatic conditions some building materials may be affected by flue products expelled in close proximity to unprotected surfaces. Sealing or shielding of the exposed surfaces with a corrosion resistant material (e.g. aluminum sheeting) may be required to prevent staining or deterioration. The protective material should be attached and sealed (if necessary) to the building before attaching the vent termination. It is strongly recommended to install the vent termination on the leeward side of the building. Connecting power The Vitodens 222-F boiler has a external accessories connection box installed, which requires a 120 VAC power supply from a wall receptacle. Refer to the wiring diagram (see page 40). Connecting heating system Flush heating system thoroughly prior to connecting boiler 2 imperfect threads Leave 2 threads bare Proper piping practice Support piping by proper suspension method. Piping must not rest on or be supported by boiler. Use moderate amount of dope. Use an approved pipe sealant or teflon tape when connecting the following installation fittings. Manual gas shutoff Closed Gas shut-off valve connection 1. Make gas connections in accordance with codes CAN/CSA B149.1 and.2 or National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes. 2. Connect gas shutoff valve to the boiler gas connection. 3. Once connected close gas shutoff valve on boiler. Open 13
14 Boiler Connections Connections (continued) Vitodens 222-F, B2TA 19 and 35 Installation Gas connection and piping 1. Refer to current CAN/CSA B149.1 and.2 or National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes for gas piping requirements and sizing. Pipe size to the boiler must be determined based on: - pipe length - number of fittings - type of gas - maximum input requirements of all gas appliances in the residence. IMPORTANT Design piping layout in such a way that piping does not interfere with serviceable components. IMPORTANT The Vitodens 222-F B2TA has a factory pre-installed flexible gas line for left, right or vertical installation. Legend A Gas connection 7 ¾ in. (NPT) B Accessible manual gas shutoff valve C Ground joint union D Drip leg 2. Before connecting boiler to gas line, install ground joint union, capped drip leg and a manual equipment shutoff valve as shown. Valves must be listed by a nationally recognized testing agency. Make boiler gas connection as shown (choose one of three locations). 3. Perform gas piping pressure test as described in the following subsection. IMPORTANT Max. gas supply pressure: 14 w.c. 4. Identify shutoff valves as such with a tab and familiarize operator / ultimate owner of boiler with these valves. See Vitodens 222-F B2TA Service Instructions for applicable system coding information. WARNING The gas supply piping must be leak tested before placing the boiler in operation. CAUTION Ensure that gas piping is large enough for all appliances in the residence. No noticeable gas pressure drop in the gas line must occur when any unit (or combination of units) lights or runs. 14
15 Vitodens 222-F, B2TA 19 and 35 Installation Connections (continued) Boiler Connections Gas piping pressure test When performing the gas piping pressure test, ensure the following requirements are met. WARNING Flue gas connection Connect the balanced flue. See Venting Installation Instructions. Never check for gas leaks with an open flame. WARNING Exposing boiler gas pressure regulator and gas valve to extreme pressures renders warranty null and void. IMPORTANT ½ psig = 14 w.c. 1. Isolate the boiler from the gas supply piping system using the individual manual shutoff valve during pressure tests equal to or less than ½ psig (14 w.c.) 2. The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psig (14 w.c.) 3. Perform leak test. Use approved liquid spray solution for bubble test. Ensure that no liquid is sprayed on any electrical components, wires or connectors. Do not allow leak detection fluid to contact gas valve regulator or regulator vent opening. 4. Correct any and all deficiencies. 5. Remove air from gas line. 15
16 Boiler Connections Connections (continued) Vitodens 222-F, B2TA 19 and 35 Installation Removing the front panels 1. Tilt the lower front panel. 2. Remove the retaining screw and set aside. 3. Lift up and out to remove the lower front panel. 4. Loosen the screws at the bottom of the boiler as shown (do not remove completely). 5. Remove the front upper panel. 6. Move the boiler to the location where it is to be installed. 7. Using the adjustable legs level the unit. CAUTION The boiler must be level both vertically and horizontally to ensure proper draining of the condensate. 16
17 Vitodens 222-F, B2TA 19 and 35 Installation Connections (continued) Boiler Connections Accessing the control unit connections 1. Remove both screws from the external accessory connection box front plate and set aside. 2. Loosen both retaining screws as shown (do not remove). 3. Pull the external accessory connection box forward until the retaining screws are clear of the guides (built into the rails). 4. Swing the external accessory connection box down. 17
18 Boiler Connections Connections (continued) Vitodens 222-F, B2TA 19 and 35 Installation 5. Tilt the bottom of the external accessory connection box cover forward. 6. Pull the cover up to clear the locating pins and out to remove, then set aside. 7. Slide both sides of the programming unit cover closed. 8. Release the hinged hooks located on both sides of the control unit. 9. To open hinged cover, lift cover and then fold down the control unit. 18
19 Vitodens 222-F, B2TA 19 and 35 Installation Connections (continued) Boiler Connections 10. Release locking tabs as shown. 11. Remove cover. 12. Route all connecting cables to the appropriate areas and secure the cables to the control base using existing strain reliefs as shown. CAUTION When running and securing connecting cables on site, ensure that the maximum permissible temperatures of the cables are not exceeded. Electronic modules can be damaged by electrostatic discharges. Before commencing work, touch grounded objects (such as heating or water pipes) to discharge static loads. 19
20 Boiler Connections Connections (continued) Vitodens 222-F, B2TA 19 and 35 Installation External accessory connection box Note: See wiring diagram on page 21 for connection to the control base. ACCESSORIES (ie VITOTROL REMOTE OR MIXING VALVE) 0-10V INPUT 120/1/60 12 AMP POWER SUPPLY WITH DISCONNECT AND PROTECTION PUMP 20
21 Vitodens 222-F, B2TA 19 and 35 Installation Connections (continued) Boiler Connections Boiler control base Note: See wiring diagram on page 20 for connection to the external accessory connection box. OUTDOOR TEMPERATURE SENSOR 21
22 Boiler Connections Preparing for Installation Vitodens 222-F, B2TA 19 and 35 Installation Air gap Condensate connection The Vitodens 222-F B2TA boiler comes with a built-in condensate trap. An external trap is not required when connecting the field drain to flexible discharge tubing. Discharge tubing (field supplied) must be of 1 in. (25 mm) diameter. Use CPVC, PVC or other material approved by codes listed below. The drain pipe and fittings must conform to ANSI standards and ASTM D1785 or D2846. CPVC or PVC cement and primer must conform to ASTM D2564 or F493. In Canada use CSA or ULC listed schedule 40 CPVC or PVC drain pipe, fittings and cement. If the condensate outlet of the Vitodens 222-F B2TA boiler is lower than the drain, a condensate pump must be installed. Select a pump which is approved for condensing boiler applications. To avoid condensate spillage, select a pump with an overflow switch. The drain connection must terminate into an open or vented drain as close to the boiler as possible to prevent siphoning of the boiler drain. 1. Install the condensate drain pipe with a suitable gradient. Pull the condensate hose far out of the boiler that no unnecessary bends are created inside the boiler. Check tightness of siphon connection A. IMPORTANT As shipped, the flexible discharge tubing B will be found to be pushed up inside the boiler housing. Ensure the condensate drain pipe is pulled down and positioned to allow the condensate to properly drain. 2. Discharge condensate from the boiler into the vented drainage system, either directly or (if required) via a neutralization unit (accessory). Installation Instructions of Neutralization Unit (if applicable) IMPORTANT Pipe ventilation must take place between the siphon trap and the neutralization unit (if applicable). IMPORTANT Do not connect the drain pipe from any other appliance, such as water softener backwash pipe, to Vitodens condensate drain pipe Ensure the condensate discharge tubing is vented to the atmosphere prior to being plumbed into the neutralization unit.
23 Vitodens 222-F, B2TA 19 and 35 Installation Vertical Piping Installation Boiler Connections 1. Install the restraining rings to the restraining bar (note their position). 2. Rotate the restraining rings a turn to lock into place (the ring opening should be facing to the side). 3. Remove the tie-wrap holding the factory installed gas line. 4. Place the restraining bar (with rings) under the rear boiler frame. 5. Align the mounting holes in the boiler frame and restraining bar and secure in place with screws provided. 6. Lock the top of the gas line into the centre restraining ring. 23
24 Boiler Connections Vertical Piping Installation Vitodens 222-F, B2TA 19 and 35 Installation 1. Install the O-rings over the male connection boiler fittings. Ensure that the O-rings are properly seated in the groove. 2. Slide the insulation sleeve over the DHW pipe (as shown). 3. Install the pipes through the top cutouts of the boiler. 4. Align the pipes to the boiler fittings and push from the top until snug. 5. Secure the ends of the pipes into the appropriate restraining rings. 24
25 Vitodens 222-F, B2TA 19 and 35 Installation Vertical Piping Installation Boiler Connections 1. Install the supplied locking clips over the bottom boiler connection and pipes. 2. Remove the cap from the factory installed gas line. 3. Install the supplied tees, drain valves and gas valve as shown. 4. Install security clips to the DHW pipe retaining clips. 25
26 Boiler Connections Side Piping Installation Vitodens 222-F, B2TA 19 and 35 Installation 1. Install the restraining rings to the restraining bar (note their position). 2. Rotate the restraining rings a turn to lock into place (the ring opening should be facing down). 3. Place the restraining bar (with rings) to the side boiler frame. 4. Align the mounting holes in the boiler frame and restraining bar and secure in place with screws provided. 26
27 Vitodens 222-F, B2TA 19 and 35 Installation Side Piping Installation Boiler Connections 1. Remove the tie-wrap holding the factory installed gas line. 2. Gently form the fexible gas line by bending the gas line at the middle to the desired side. IMPORTANT Ensure not to kink the gas line during bending. 3. Secure the gas line to the centre restraining ring. 1. Install the O-rings over the male connection boiler fittings. Ensure that the O-rings are properly seated in the groove. 2. Slide the insulation sleeve over the DHW pipe (as shown). 3. Install the pipes through the side cutouts of the boiler. 4. Align the pipes to the boiler fittings and push from the top until snug. 5. Secure the ends of the pipes into the appropriate restraining rings. 6. Install the supplied locking clips over the bottom boiler connection and pipes. 7. Install security clips to the DHW pipe retaining clips. 27
28 Boiler Connections Side Piping Installation Vitodens 222-F, B2TA 19 and 35 Installation 1. Remove the cap from the factory installed gas line. 2. Install the supplied tees, drain valves and gas valve as shown. Installing boiler safety devices Left side installation 1. Remove the pressure relief valve, drain valve and fittings from the box. 2. Apply sufficient amount of pipe sealant to both ends of all pipe fittings B,D,F and H and install onto tees A, and E. 3. Install pressure relief valve G and Isolation valve C and tighten them. 4. Install discharge pipe on pressure relief valve in such a way that... - the end of the pipe is not threaded. - the pressure relief discharge pipe extends to a floor drain and ends approximately 6 in. (150 mm) above the drain. Ensure that... - there is no shutoff valve installed in the discharge pipe. - discharge pipe diameter is not reduced. - discharge is not piped to outdoors. 1. Remove the cap from the factory installed gas line. 2. Install the supplied tees, drain valves and gas valve as shown. Right side installation 28
29 Vitodens 222-F, B2TA 19 and 35 Installation Safety Connections and Pressure Testing Boiler Connections Low water cut-off A low water cut-off may be required by local codes. If boiler is installed above radiation level, a low water cut-off device of approved type (field supplied) must be installed in all instances. Do not install an isolation valve between boiler and low water cut-off. WARNING Exposing the boiler to pressures and temperatures in excess of those listed will result in damages, and will render warranty null and void. Operating pressure...2 bar (30 psig) Max. operating pressure...3 bar (45 psig) Testing pressure...4 bar (60 psig) Max. boiler water temperature...210ºf (99ºC) Min. 6 (Min. 152 mm) Legend A Heating supply NPT ¾ B DHW NPT ¾ C Pressure relief valve discharge pipe NPT ¾ D DCW NPT ¾ E Heating return NPT ¾ F Temperature and pressure relief valve discharge pipe NPT ¾ WARNING Min. 6 (Min. 152 mm) Do not install an isolation valve between boiler and pressure relief valve. The discharge pipe for the pressure relief valve must be oriented to prevent scalding of attendants. Pipe pressure relief valve discharge pipe close to floor drain. Never pipe discharge pipe to the outdoors. Performing a boiler pressure test The boiler must be leak tested before being placed in operation. Before boiler is connected to piping or electrical power supply, it must be hydrostatically pressure tested. 1. An ASME/CSA pressure relief valve is factory installed. If necessary, remove the pressure relief valve and install a temporary cap to the opening (NPT ¾ in.). 2. Cap the supply and return connections. 3. Connect ½ in. garden hose to boiler fill valve at the bottom of the boiler and fill boiler slowly until pressure gage indicates max. 4 bar (60 psig). 4. Maintain pressure for 15 minutes. During time of pressure testing, do not leave boiler unattended. 5. Inspect all pipe joint connections and safety devices with a flashlight for leaks. A lower manometer reading than 4 bar (60 psig) usually indicates loss of water due to leakage. All leaks must be repaired. 6. After 15 minutes, release water pressure from boiler by opening boiler drain valve slowly, remove caps from supply and return connections as well as ¾ in. cap from ¾ in. nipple, and install pressure relief valve immediately instead of ¾ in. cap. 7. After boiler has passed pressure test, proceed with the installation. 8. Install discharge pipe on pressure relief valve in such a way that... - the end of the pipe is not threaded. - the pressure relief discharge pipe extends to a floor drain and ends approximately 6 in. (150 mm) above the drain. Ensure that... - there is no shutoff valve installed in the discharge pipe. - discharge pipe diameter is not reduced. - discharge is not piped to outdoors. 29
30 Boiler Connections Waterside flow (continued) Vitodens 222-F, B2TA 19 and 35 Installation Supply head pressure (water) Flow rate Boiler maximum flow rate 6.2 GPM (1400 L/h) Model B2TA 19 1 boiler Output (NG/LPG) MBH 61 t for NG/LPG 20ºF (11ºC) rise GPM (L/h) 6.1 (1385) 25ºF (14ºC) rise GPM (L/h) 4.9 (1113) 30ºF (17ºC) rise GPM (L/h) 4.0 (909) 35ºF (19.5ºC) rise GPM (L/h) 3.5 (795) 40ºF (22ºC) rise GPM (L/h) 3.1 (704) Pressure drop (primary circuit) for Vitodens 222-F, B2TA 19, 35 Waterside flow (primary circuit) The Vitodens 222-F, B2TA is designed for closed loop, forced circulation hot water heating systems only. Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly recommends the installation of a low-loss header. Once the low-loss header is connected, the built-in lowloss header logic of the Vitodens 222-F boiler ensures the required t across the system through the sensory communication between the low-loss header and the boiler. An alternative method may be used, such as primary secondary piping using closely spaced tees. A low-loss header offers additional benefits not provided by a pair of closely spaced tees. Viessmann therefore strongly recommends and prefers the use of a low-loss header over closely spaced tees. Refer to the Technical Data manual for low-loss header information. Boiler maximum flow rate 6.2 GPM (1400 L/h) Model B2TA 35 1 boiler Output (NG/LPG) MBH 114 t for NG/LPG 20ºF (11ºC) rise GPM (L/h) 11.4 (2589) 25ºF (14ºC) rise GPM (L/h) 9.1 (2067) 30ºF (17ºC) rise GPM (L/h) 7.6 (1726) 35ºF (19.5ºC) rise GPM (L/h) 6.5 (1476) 40ºF (22ºC) rise GPM (L/h) 5.7 (1295) 30
31 Vitodens 222-F, B2TA 19 and 35 Installation Installation Examples Installation Examples Please note that in the following piping layout examples all pumps external to the boiler are field supplied. IMPORTANT DHW tank, heat exchanger, diverting valve and DHW circulating pump are installed in the unit with all the connections between components. DHW connecting fittings inlet and outlet are c in. NPT. DHW tank is protected with temperature pressure relief valve at 150 psi and discharge outlet of the valve is c in. NPT. Operation of the DHW system is controlled by the boiler control. IMPORTANT The examples on the following pages depict possible piping layouts of the Vitodens 222-F boiler equipped with Viessmann System Technology. Please note that the following examples are simplified conceptual drawings only! Piping and necessary componentry must be field verified. A low water cut-off (LWCO) must be installed where required by local codes. Proper installation and functionality in the field is the responsibility of the heating contractor. 31
32 Installation Examples System Layout 1 Vitodens 222-F, B2TA 19 and 35 Installation Vitodens 222-F, B2TA with a direct-connected heating circuit with integrated DHW production 32 Legend A Vitodens 222-F B2TA boiler with Vitotronic 200, HO1B outdoor reset control B Outdoor temperature sensor! C Vitotrol remote (optional) D Heating circuit E Boiler pump 20 F DHW circulating pump sa G DHW storage tank H Integral expansion tank I DCW inlet J DHW outlet K Temperature and pressure relief valve outlet L Pressure relief valve outlet Installation of... radiator heating circuit (high-temp. circuit) DHW production... with the following flow conditions: The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 222-F B2TA boiler (see page 28 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown in the applicable table on page 28, or if the system flow rates are unknown. The low-loss header is available as accessory part. See following pages for installation examples with a low-loss header.
33 Vitodens 222-F, B2TA 19 and 35 Installation System Layout 2 Installation Examples Vitodens 222-F, B2TA with one heating circuit, low-loss header and integrated DHW production Legend A Vitodens 222-F B2TA boiler with Vitotronic 200, HO1B outdoor reset control B Outdoor temperature sensor! C Vitotrol remote (optional) D Heating circuit E Boiler pump 20 F DHW circulating pump sa G DHW storage tank H Integral expansion tank I Temperature and pressure relief valve outlet J Low-loss header K Pressure relief valve outlet L Viessmann temperature sensor for low-loss header? M Heating circuit pump 28/20 N DCW inlet O DHW outlet Installation of... radiator heating circuit (high-temp. circuit) DHW production... with the following flow conditions: The flow rate of the heating circuit is greater than the maximum possible water flow rate of the Vitodens 222-F B2TA boiler (see page 28 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown on page 29, or if the system flow rates are unknown. The low-loss header is available as accessory part. 33
34 Installation Examples System Layout 3 Vitodens 222-F, B2TA 19 and 35 Installation Vitodens 222-F, B2TA with... - Integrated DHW production - one heating circuit with mixing valve and system separation 34 Legend A Vitodens 222-F B2TA boiler with Vitotronic 200, HO1B outdoor reset control B Outdoor temperature! C Vitotrol remote (optional) D Underfloor heating circuit E Mixing valve temperature sensor? F Pressure relief valve outlet G Plate heat exchanger for system separation H Accessory kit for heating circuit with mixing valve I DHW circulating pump sa J DHW storage tank K Integral expansion tank L Boiler pump 20 M Temperature and pressure relief valve outlet N DCW inlet O DHW outlet P Expansion tank Installation of... underfloor heating circuit with 3-way mixing valve and system separation (low-temp. circuit) DHW production... with the following flow conditions: The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 222-F B2TA boiler. See page 27 for maximum water flow rate of the Vitodens 222-F B2TA boilers. The use of a low-loss header is recommended if the system water flow rate is unknown. The low-loss header is available as accessory part. See following pages for installation examples with a low-loss header. IMPORTANT System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials.
35 Vitodens 222-F, B2TA 19 and 35 Installation System Layout 4 Installation Examples Vitodens 222-F, B2TA with... - Integrated DHW production - one direct-connected heating circuit - one heating circuit with a mixing valve Legend A Vitodens 222-F B2TA boiler with Vitotronic 200, HO1B outdoor reset control B Outdoor temperature sensor! C Vitotrol remote (optional) D Under floor heating circuit E Radiator heating circuit F Heating circuit pump 28/20 G Mixing valve temperature sensor? H Accessory kit for heating circuit with mixing valve I Domestic hot water storage tank J Integral expansion tank K Temperature and pressure relief valve outlet L Pressure relief valve outlet M DHW circulating pump sa N Boiler pump 20 O Low-loss header P Low-loss header sensor? Q DCW inlet R DHW outlet Installation of different heating circuits... radiator heating circuit (high-temp. circuit) under floor heating circuit with 3-way mixing valve (low-temp. circuit) DHW production... with the following flow conditions: 1. The water flow rate (output) of the radiator heating circuit is at least 30% greater than that of the under floor heating circuit. 2. The total flow rate of the two heating circuits is less than the maximum possible water flow rate of the Vitodens 222-F B2TA boiler (see page 27 for max. water flow rate). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown on page 27, or if the system flow rates are unknown. The low-loss header is available as accessory part. The 3-way mixing valve, built-in to achieve the lowtemperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve. 35
36 Installation Examples System Layout 5 Vitodens 222-F, B2TA 19 and 35 Installation Vitodens 222-F, B2TA with... - Integrated DHW production - one heating circuit with mixing valve - one heating circuit without mixing valve and low-loss header Legend A Vitodens 222-F B2TA boiler with Vitotronic 200, HO1B outdoor reset control B Outdoor temperature sensor! C Vitotrol remote (optional) D Under floor heating circuit E Radiator heating circuit F Boiler pump 20 G Mixing valve temperature sensor? H Kit for heating circuit with mixing valve I Domestic hot water storage tank J Integral expansion tank K Temperature and pressure relief valve outlet L Pressure relief valve outlet M Heating pump 28/20 N Low-loss header O Viessmann temperature sensor for low-loss header? P DCW inlet Q DHW outlet R DHW circulating pump sa Installation of different heating circuits... radiator heating circuit (high-temp. circuit) under floor heating circuit with 3-way mixing valve (low-temp. circuit) DHW production... with the following flow conditions: The total flow rate of the two heating circuits is greater than the maximum possible water flow rate of the Vitodens 222-F B2TA boiler (see page 27 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended. The low-loss header is available as accessory part. The 3-way mixing valve, built-in to achieve the lowtemperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve. 36
37 Vitodens 222-F, B2TA 19 and 35 Installation System Layout 6 Installation Examples Vitodens 222-F, B2TA with... - Integrated DHW production - one direct-connected heating circuit - one heating circuits with system separation Legend A Vitodens 222-F B2TA boiler with Vitotronic 200, HO1B outdoor reset control B Outdoor temperature sensor! C Vitotrol remote (optional) D Under floor heating circuit E Mixing valve temperature sensor? F Accessory kit for heating circuit with mixing valve G Heating circuit pumps H DHW storage tank I Integral expansion tank J Pressure relief valve outlet K Temperature and pressure relief valve outlet L Radiator heating circuit M Boiler pump 20 N DHW circulating pump sa O Plate exchanger for system separation P DCW inlet Q DHW outlet R Expansion tank Installation of different heating circuits... two heating circuits with 3-way mixing valve (low-temp. circuit) DHW production... with the following flow conditions: The total flow rate of the two heating circuits is greater than the maximum possible water flow rate of the Vitodens 222-F B2TA boiler (see page 27 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended. The low-loss header is available as accessory part. The 3-way mixing valve, built-in to achieve the lowtemperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with a mixing valve. 37
38 Installation Examples System Layout 7 Vitodens 222-F, B2TA 19 and 35 Installation Vitodens 222-F, B2TA with... - one direct-connected heating circuit - three heating circuit with mixing valve and integrated DHW production Legend A Vitodens 222-F B2TA boiler with Vitotronic 200, HO1B outdoor reset control B Outdoor temperature sensor! C Vitotrol remote (optional) D Under floor heating circuit E Radiator heating circuit F Heating circuit pump 28/20 G Mixing valve temperature sensor? H Accessory kit for heating circuit with mixing valve I DHW storage tank J Integral expansion tank K Temperature and pressure relief valve outlet L Pressure relief valve outlet M Boiler pump 20 N DHW circulating pump sa O Low-loss header P Low-loss header sensor? Q DCW inlet R DHW outlet S Vitotronic 200-H HK1B Installation of different heating circuits... radiator heating circuit (high-temp. circuit) under floor heating circuit with 3-way mixing valve (low-temp. circuit) DHW production... with the following flow conditions: The total flow rate of the two heating circuits is less than the maximum possible water flow rate of the Vitodens 222-F B2TA boiler (see page 27 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the max. boiler flow rate, or if the system flow rates are unknown. The low-loss header is available as accessory part. 38
39 Vitodens 222-F, B2TA 19 and 35 Installation Alternative Connection Installation Examples The following piping diagram reflects the connection for the DHW system to boiler. Legend A Boiler B Outdoor temperature sensor! C Vitotrol remote (optional) D DHW storage tank E Boiler pump 20 F DHW circulating pump sa G Expansion tank H Diverting valve I Boiler heat exchanger J DHW heat exchanger K Water softener L Boiler supply M Boiler return N Temperature and pressure relief valve outlet O Pressure relief valve outlet P DCW inlet Q DHW outlet R DHW users S DHW recirculation pump T Flow check valve U Integral expansion tank 39
40 Control Connections Wiring Diagram Vitodens 222-F, B2TA 19 and 35 Installation WARNING CAUTION 40 DISCONNECT POWER BEFORE SERVICING BOILER. If any of the original wires as supplied with the appliance must be replaced, it must be replaced with the exact equivalent. * Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Only one function/accessory may be assigned to each connection.
41 Vitodens 222-F, B2TA 19 and 35 Installation Wiring Diagram (continued) Control Connections Legend 1 Outdoor Temperature Sensor 2 Supply Temperature Sensor/Low Loss Header 3 Boiler Temperature Sensor 4 DHW Supply Temperature Sensor 5 DHW tank temperature sensor 11 Ionization Electrode 15 Flue Gas Temperature Sensor 20 No Function [20] Boiler Pump Connection (Internal) 21 No Function [21] DHW Pump Connection (Internal) 28/20 Heat Circuit A1 Pump Connection* 30 Diverting Valve Stepper Motor 35 Gas Valve 40 Power Supply 40A Accessory Power Output 47 Fixed High Limit [53] Powered Accessory Connection 54 Ignition Transformer 96 Powered Accessory Connection 100 Fan Motor 100A Fan Motor Control 111 Not Used 145 KM BUS Multi Powered Accessory Connection 156A Switched Output F2 156B Switched Output F1 DE1 Digital Input 1 (Dry Contact) DE2 Digital Input 2 (Dry Contact) DE3 Digital Input 3 (Dry Contact) 0-10V 0-10VDC Input 157 Fault Alarm/DHW Recirc. Pump* 190 Gas Modulation Coil * Only one function/connection may be assigned to each connection. A Boiler Control B External Accessory Connection Board C Pump Connection Interface D Extention Module EA1 E KM-BUS for External Devices F Electrical Junction Box G Field Wiring Connections A1 Main Board A2 Internal Power Supply Unit A3 Optolink A4 Burner Control Unit A5 Programming Unit A6 Coding Card A7 Connection Adaptor A8 LON Communication Module S1 ON/OFF Switch S2 Reset Button X.. Electrical Interface 41
42 Control Connections Electrical Connections Power supply connection of accessories The power supply connection of accessories can be made directly at the control. The connection is activated and deactivated with the system on/off switch. The Vitotronic 200-H, HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control require a separate 120 VAC power supply from the wall receptacle. Note: The programming unit can also be used in a wall mounting base (accessory) near the boiler Vitodens 222-F, B2TA 19 and 35 Installation Cabling required for: H outdoor temperature sensor H Vitotronic 200-H, HK1B mixing valve control H accessory kit for heating circuit with mixing valve H remote switching of operating mode H remote disable H alarm output H wall-mount base H system circulating pump IMPORTANT It is essential to route cables as illustrated to ensure freedom of movement of control unit. IMPORTANT When running and securing connecting cables on site, ensure that the maximum permissible temperatures of the cables are not exceeded. IMPORTANT Cables in the vicinity of the control unit must not be secured to the control unit bracket. Connection of accessories For details regarding other installation steps required, please reference the Installation Instructions supplied with the respective accessory part. Note: Only one accessory part or one switch contact can be connected to the contacts of a plug at a time. 42
43 Vitodens 222-F, B2TA 19 and 35 Installation Accessories Connection Control Connections If the current flowing to the connected working parts (e.g. circulation pumps) is higher than the safety level of the accessory, the output concerned should only be used to control an on-site relay. Accessories Extension kit for heating circuit with mixing valve Extension AM1 Extension EA1 Internal fuse protection 2 A 4 A 2 A Legend A Boiler control unit B Extension kit for heating circuit with mixing valve M2 C Extension kit for heating circuit with mixing valve M3 D Extensions AM1 or EA1 E Accessory modules Connection of accessories H Install a disconnect switch in the power supply line that simultaneously isolates all live conductors from the mains. We additionally recommend installing a GFCI receptical switch. H Max. fuse rating 15 A. Low voltage plug X3! Outside temperature sensor: H North or north-western wall, 6.5 ft. (2 m) to 8 ft. (2.5 m) above ground level; in multi storey buildings, in the upper half of the second floor H Not above windows, doors or ventilation outlets H Not immediately below balconies or gutters H Never render over H Cable length max. 115 ft. (35 m) with a crosssection of 15 AWG (1.5 mm 2)? Supply temperature sensor for low loss header (accessories) % DHW tank temperature sensor (factory installed) avg KM BUS participant (accessory) H Vitotrol 200A or 300A remote control H Vitocom 100 H Extension kit for one heating circuit with mixing valve H Extension EA1 or AM1 43
44 Control Connections Accessing the X3 Plug Vitodens 222-F, B2TA 19 and 35 Installation 1. Remove the control unit cover (see page 15). 2. Remove the X3 plug from the control board. Attach sensors and reinsert the X3 plug. Refer to the following sensor information. 3. Reinstall the control cover. Connecting the Low-loss Header Sensor 1. Connect the low-loss header sensor (if used) to terminals X3.4/X3.5 on the boiler control board. 44
45 Vitodens 222-F, B2TA 19 and 35 Installation Connecting the Outdoor Temperature Sensor Control Connections 1. Remove cover of outdoor temperature sensor. 2. Mount wall-mount base (cable entry must point downward). IMPORTANT The outdoor temperature sensor should be mounted 6.6 to 8.2 ft. (2 to 2.5 m) above ground level on the north or northwest wall of the building. In case of a multi-storey building, mount outdoor temperature sensor in the upper half of the second floor. Ensure that sensor is not located above windows, doors and air vents, or immediately underneath a balcony or gutter. The outdoor temperature sensor must not be covered by plaster. If mounting on an unplastered wall, make allowances for thickness of plaster or remove sensor before plastering wall. 3. Route cable from the boiler control board to the outdoor sensor. Connect cable to sensor terminals (wires are interchangeable). Cable specifications: 2-wire cable, max. cable length 95 ft. (35 m) with a wire size of min. AWG 16 copper. 4. Connect the outdoor temperature sensor to terminals X 3.1/X3.2 on the boiler control board (wires are not polarity sensitive). 5. Place cover on base and snap into place. IMPORTANT Cable to the outdoor sensor must not be laid near line voltage wiring (120/240 V). 45
46 Control Connections LON Module Vitodens 222-F, B2TA 19 and 35 Installation Installing the LON module to the boiler control board 1. Remove the control cover (see page 15). 2. Insert the LON module into the boiler control board. 3. Connect the LON connector cable to the LON module. Connecting the LON module cable See the Vitotronic 200-H HK1B Installation Instructions. Boiler Control 46
47 Vitodens 222-F, B2TA 19 and 35 Installation Routing the Connecting Cables Control Connections Note: If connecting cables touch hot components they will be damaged. When routing and securing connecting cables on site, ensure that the maximum permissible temperatures for these cables are not exceeded. Remove the existing cable grommet when using larger cross-sections [up to 9/16 in. (7 14 mm)]. Secure the cable with the cable grommet plugged into the lower casing section (black). Legend A Low voltage connections B 120V connections C Internal extension D Main PCB E Communication module (accessories) F Cable grommet for power cable G 120V from external accessories connection box 47
48 Control Connections External 0-10 Volt DC Signal Connection Vitodens 222-F, B2TA 19 and 35 Installation 1. Connect the external 0-10 VDC signal to plug 0-10VDC located in the external connection accessory box. 2. Ensure correct polarity. 3. See chart for maximum possible boiler water temperature and required signal. 48
49 Vitodens 222-F, B2TA 19 and 35 Installation Connecting a 24 VAC Thermostat Control Connections 1. Connect normally open dry contact of the switching relay ( T-T contact) to terminal DE1, DE2 or DE3 of the EA1 module located in the boiler electrical junction box. 2. Connect switching relay to thermostat and power supply as per manufacturers instructions. When the thermostat contact is closed, burner operation is load-dependent. The supply water is heated to the value set in the coding address 9b in the General group of the boiler. The supply water temperature is limited by this set value and the electronic supply temperature maximum limit. Codes Extension EA1 Set 3A, 3B or 3C in the General group to 2. Note: Live contacts lead to short circuits or phase failure. The external connection must be potentialfree. Note: When only using a thermostat (field supplied) for room temperature control, the boiler standard and reduced room temperature set points may be set to 37º F (3º C) to reduce boiler cycling. Legend A Boiler electrical junction box B Switch relay (ie Taco SR501, Honeywell RA889A-1001, field supplied) C 24VAC room thermostat (field supplied) D Internal EA1 module E 120VAC power supply for switching relay (refer to manufacturers instructions) F Dry contact connection from switching relay (to boiler T-T ) 49
50 Control Connections Accessory Kit Vitodens 222-F, B2TA 19 and 35 Installation Boiler Control The mixing valve controller kit can only be used with wall-mounted gas-fired hot water heating boilers and a weather-responsive control; it can be used as an alternative for a Vitotronic control. Extension Module EA1 For details on coding and connection to the control, refer to the Vitodens 222-F B2TA Service Instructions. For details on installation, refer to the accessory kit Installation Instructions. KM Bus Accessory Closing the Boiler Closing the control cover 1. Install the cover onto the control board. 2. Flip the control board back into position. 3. Secure the locking tabs as shown. 50
51 Vitodens 222-F, B2TA 19 and 35 Installation Closing the External Accessory Connection Box Control Connections 4. Tilt the top of the external accessory connection box cover forward. 5. Drop down over the locating pins and set the cover in place. 6. Swing the external accessory connection box up. 7. Push the external accessory connection box in until the holding screw is in place. 51
52 Control Connections Closing the External Accessory Connection Box (continued) Vitodens 222-F, B2TA 19 and 35 Installation 8. Tighten the external accessory connection box retaining screw. 9. Install the external accessory connection box cover screws. Reinstalling the Front Enclosure Panel Fitting the front panels 1. Install upper front panel. 2. Set in lower front panel. 3. Insert and tighten the retaining screw. 4. Install lower front panel. IMPORTANT Read and follow, where applicable, the safety instructions of all labels and stickers attached to boiler surfaces. Do not remove any of these instructions. Contact Viessmann if any replacement labels are required. 52
53 Vitodens 222-F, B2TA 19 and 35 Installation Technical Data Additional Information Boiler Model No. 222-F B2TA Natural Gas / Liquid Propane Gas CSA input CSA output/doe *1 heating capacity Net AHRI rating *2 Heat exchanger surface area Min. gas supply pressure Natural gas Liquid propane gas Max. gas supply pressure *3 Natural gas Liquid propane gas MBH kw MBH kw MBH kw ft.2 m w.c. w.c. w.c. w.c A.F.U.E. % Weight lbs kg Boiler water content Boiler max. flow rate *4 Expansion tank *5 (for heating system side) Precharge pressure Capacity Max. operating pressure at 210ºF (99ºC) Boiler water temperature - Adjustable high limit (AHL) range space heating (steady state) - Fixed high limit (FHL) Boiler connections Boiler heating supply and return Pressure relief valve Drain valve Boiler supply/return for indirect-fired DHW storage tank (field supplied) Gas valve connection USG L GPM L/h psig USG L psig bar ºF ºC ºF (ºC) NPTM NPTF (male thread) NPT NPTF to to (99) ¾ ¾ ¾ ¾ ¾ to to (99) ¾ ¾ ¾ ¾ ¾ *1 Output based on 140ºF (60ºC), 120ºF (49ºC) system supply/return temperature. *2 Net AHRI rating based on piping and pick-up allowance of *3 If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator must be installed upstream of the heating system. *4 See Waterside Flow starting on page 30 in this manual. *5 Determine the required size of the expansion tank to be installed in the heating system. If the integral expansion tank is insufficient, install a suitably sized expansion tank on site. 53
54 Additional Information Technical Data (continued) Vitodens 222-F, B2TA 19 and 35 Installation Boiler Model No. 222-F B2TA Dimensions Overall depth Overall width Overall height *12 Flue gas *6 Temperature (at boiler return temperature of 86ºF (30ºC) - at rated full load - at rated partial load Temperature (at boiler return temperature of 140ºF (60ºC) Average condensate flow rate *7 with natural gas and T S /T R =122/86ºF (50/30ºC) inches mm inches mm inches mm ºF (ºC) ºF (ºC) ºF (ºC) USG/h L/h 23b f (45) 95 (35) 154 (68) b f (45) 95 (35) 154 (68) Condensate connection *8 hose nozzle Ø in. ¾-1 ¾-1 Boiler flue gas connection *9 Ø in. (mm) 2 3 / 8 (60) 2 3 / 8 (60) Combustion air supply connection (coaxial) Sound Rating - at maximum input - at minimum input DHW storage tank DHW storage tank capacity Temperature and pressure relief valve (factory installed) Max. allowable operating pressure (DHW) Storage tank test pressure Continuous DHW output Continuous DHW output draw rate *10 Max. DHW draw rate (over 10 min. period) *10 Stadby losses *11 outer Ø in. (mm) 4 (100) 4 (100) db db USG (L) psig/temp psig psig MBH (kw) GPM (L/min.) USG (L) BTU/24h BTU/h º F/h (100) 150/210ºF (99ºC) (17.8) 1.8 (6.6) 44 (166) (100) 150/210ºF (99ºC) (33.4) 3.3 (12.3) 60 (227) *6 Measured flue gas temperature with a combustion air temperature of 68 F (20 C). *7 Based on typical boiler cycles, including partial load conditions. *8 Requires 1 inch (25 mm) tubing. See the Installation Instructions of the Vitodens 222-F, B2TA for details. *9 For side wall vent installations (coaxial system): Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 222-F, B2TA Venting System. Do not attempt to common-vent Vitodens 222-F, B2TA with any other appliance. Side wall coaxial vent installation must include Viessmann protective screen! For details refer to the Installation Instructions for the Vitodens 222-F, B2TA Venting System. *10 Based on a temperature rise of 70ºF (21ºC), 50ºF to 120ºF (10ºC to 49ºC). *11 Measured values are based on room temperature of 68º F (20º C) and a domestic hot water temperature of 149ºF (65ºC). *12 Add 1f in. (40 mm) when using the optional accessory seismic bracket kit. For information regarding other Viessmann System Technology componentry, please reference documentation of respective product Note: For high altitude installation at 10,000 ft. (3050 m) the input for 222-F, B2TA 19 and 35 will have an altitude de-ration of 21%.
55 Vitodens 222-F, B2TA 19 and 35 Installation Installation Fittings Additional Information Parts for Top Connection 0302 Connecting pipe, DHW/heating 0303 Support bracket with pipe clips 0304 Pipe clip (each) 0307 Connector retaining clip (Set of 2) * Pipe insulation, 19x9x740 mm 0310 Gas ball valve, ¾ brass 0311 Sediment faucet, ¾ NPT 0313 Tee, ¾ brass 0318 Security clips *1 *2 Other Parts (not illustrated) 0301 Flex pipe (NG/LP), full-length* O-Ring, 18x3 mm for supply/return 0306 Gasket, 17x24x2 mm for gas connection pipe* Accessory pack for coaxial venting fasteners 0312 Outdoor temperature sensor, NTC 0314 Air bleed key 0326 Parts List for Installation Set, top 0350 Temperature gauge, ºF* LLH temperature sensor, immersion NTC (if used) *1 Please ensure security clip (0318) is always installed on connector retaining clip (0310) of the domestic water piping. *2 Shipped affixed to rear of boiler *3 The NG/LPG flex pipe (0301) and It s gasket (0309) ship preinstalled on the Vitodens 222-F boiler. *4 Install anywhere in the supply piping near the boiler. Parts for Left/Right Side Connection 0302 Connecting pipe 90º, DHW short 0303 Connecting pipe 90º, DHW long 0304 Connecting pipe 90º, heating short 0305 Connecting pipe 90º, heating long 0306 Support bracket with pipe clips 0307 Pipe clip (each) 0310 Connector retaining clip (Set of 2)* Pipe insulation, 19x9x740 mm 0313 Gas ball valve, ¾ brass 0314 Sediment faucet, ¾ NPT 0316 Tee, ¾ brass 0318 Security clips *1 *2 Other Parts (not illustrated) 0301 Flex pipe (NG/LP), full-length* O-Ring, 18x3 mm for supply/return 0309 Gasket, 17x24x2 mm for gas connection pipe* Accessory pack for coaxial venting fasteners 0315 Outdoor temperature sensor, NTC 0317 Air bleed key 0325 Parts List for Installation Set, left/right 0350 Temperature gauge, ºF* LLH temperature sensor, immersion NTC (if used) 55
56 Lighting and Operating Instructions Vitodens 222-F, B2TA 19 and 35 Installation FOR YOUR SAFETY READ BEFORE OPERATING W A R N I N G: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electric switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor s phone. Follow the gas supplier s instructions. If you cannot reach your gas supplier, call the fire department. 1. STOP! Read the safety information above on this label. 2. Set thermostat or other operating control to lowest setting. 3. Turn off all electric power to the appliance. 4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. Manual gas shutoff Closed OPERATING INSTRUCTIONS C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. 5. Close main gas shut-off valve. 6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow B in the safety information above on this label. If you don t smell gas, go to the next step. 7. Open main gas shut-off valve. 8. Turn on all electric power to the appliance. 9. Set thermostat or other operating control to desired setting. 10. If the appliance will not operate, follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier. Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper. Open TO TURN OFF GAS TO APPLIANCE 1. Set thermostat or other operating control to lowest setting. 2. Turn off all electric power to the appliance if service is to be performed. 3. Close main gas shut-off valve.
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
Tankless Water Heater
Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not
Installation and Service Instructions for use by heating contractor VITODENS 100-W IMPORTANT. Read and save these instructions for future reference.
Installation and Service Instructions for use by heating contractor Vitodens 100-W WB1B Series Wall-Mounted, gas-fired condensing boiler with optional on demand hot water CombiPLUS Kit Heating input 37
Operating Instructions & User s Information Manual VITODENS 100-W WARNING WARNING IMPORTANT. Read and save these instructions for future reference.
Operating Instructions & User s Information Manual Vitodens 100-W WB1B Series Wall-Mounted, gas-fired condensing boiler with optional on demand hot water CombiPLUS Kit Heating input: 37 to 118 MBH 10.8
NAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
Operating Instructions & User s Information Manual VITODENS 100-W WARNING. IMPORTANT Read and save these instructions for future reference.
Operating Instructions & User s Information Manual Please file in Service Binder Vitodens 100-W WB1A Series Wall-mounted, natural gas-fired condensing boiler For natural gas only Heating input NG 29 to
Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
Installation and Service Instructions for use by heating contractor SM1 SOLAR CONTROL MODULE IMPORTANT
Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
ASX7-4-IOM-7 J30-08579
INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
Operating Instructions. VITODENS r 200/222 Series With Vitotronic 200 HO1B Controls WARNING WARNING IMPORTANT
Operating Instructions Vitodens 200-W, B2HA and B2HB Models 19 to 150 Wall-mounted, gas-fired condensing boiler For operation with natural gas and liquid propane gas Heating input: 12 to 530 MBH 3.5 to
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
Installation and Service Instructions. Neutralization System Part no. 7441823 Grünbeck part no. 410480
Installation and Service Instructions for use by heating contractors Neutralization System Part no. 7441823 Grünbeck part no. 410480 Safety and Installation Requirements Please ensure that these instructions
Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
Select Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
OTF Oil Fired Pool Heater
OTF Oil Fired Pool Heater Installation Operation Maintenance Manual Service Policy 722010 Congratulations on the purchase of your new pool heater. In order to maintain peak performance of your pool heater
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE
4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement
Installation Instructions for use by heating contractor. Common Venting with Flue Vent Damper IMPORTANT
Installation Instructions for use by heating contractor Common venting with flue vent damper for Vitocrossal 200 CM2 series equipped with Vitotronic 300 GW5B/GW6B Common Venting with Flue Vent Damper Product
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
NITROUS TRANSFER PUMP INSTRUCTIONS
NITROUS TRANSFER PUMP INSTRUCTIONS SAFETY TIPS Never directly inhale nitrous oxide. When inhaled in large quantities, nitrous oxide can cause respiratory ailments or in extreme cases, death by suffocation.
INFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type
PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL
PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
San josé OWNER S MANUAL
San josé OWNER S MANUAL Assembling & operating manual San josé 30 mbar - PORTABLE GAS BARBECUE 1. 2. 3. Improper installation, adjustment, alteration, service or maintenance can injury or property damage.
Service Instructions for use by heating contractor. VITODENS r 200-W IMPORTANT. Read and save these instructions for future reference.
Service Instructions for use by heating contracr Videns 200-W, B2HA Series Models 45, 60 Wall-mounted, gas-fired condensing boiler For operation with natural gas and liquid propane gas Heating input 60
prestige Water Boiler * I N S T A L L A T I O N A N D M A I N T E N A N C E * M A N U A L
prestige Solo 60 Solo 175 Solo 250 Solo 399 Water Boiler L I S T E D * I N S T A L L A T I O N A N D M A I N T E N A N C E * M A N U A L NOTICE Warranty Registration Card must be filled out by the customer
Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 222-F
Technical Data Manual Model Nos. and pricing: see Price List For Natural Gas and Liquid Propane Gas Gas-fired floor-mounted condensing DHW combi-boiler 12 to 125 MBH (3.5 to 37 kw) VITODENS r 222-F Product
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided)
ELECTRIC FUEL PUMPS P/N 12-801-1, 712-801-1, 12-802-1, 712-802-1, 12-815-1, & 712-815-1 FUEL PRESSURE REGULATORS P/N 12-803, 12-501, 12-804, 12-500, & 15812NOS Installation Instructions THESE INSTRUCTIONS
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation
Solar Pool Heating System Installation Manual Read the complete manual before beginning the installation 1. Sizing the System Visit www.techno-solis.com to size the system using the sizing calculator.
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, 1060. Instruction No.
Instruction No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA PIPING GUIDE GF-115-P Modulex Gas Fired Boiler Systems Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909,
IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE
UV100A Ultraviolet Air Treatment System
UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism
INDIRECT WATER HEATER. Installation and Operating Instruction Manual
INDIRECT WATER HEATER Installation and Operating Instruction Manual Maximum supply temperature to heat exchanger must not exceed 180 F (82 C). Safety Warning: Indirect water heaters are heat-producing
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com MASTER MANUFACTURING MASTER GARDNER
123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com MASTER MANUFACTURING MASTER GARDNER Part Number PCD E3 009B MM Rev 1 Nov. 2010 INTRODUCTION The purpose of this manual
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
Installation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.
Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENT/POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION Ashland City, TN 37015 www.hotwater.com For Your Safety AN ODORANT IS ADDED TO THE GAS
Operating instructions
Operating instructions Gas condensing boilers MGK-130 MGK-170 MGK-210 MGK-250 MGK-300 Wolf GmbH Postfach 1380 D-84048 Mainburg Tel. +49 8751/74-0 Fax +49 8751/741600 Internet: www.wolf-heiztechnik.de Document
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions
Gas-Fired, Residential Storage Type Water Heaters
Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. Gas-Fired, Residential Storage Type Water Heaters Most inspectors
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
Installation Instructions 4508 4508S
SYMPHONY Spread Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American Standard faucets. Speed Connect
Product and Safety Information... 2,3 Service and Maintenance Munchkin Operation Primary Water
User Manual TABLE OF CONTENTS Product and Safety Information............................................. 2,3 Service and Maintenance Munchkin Operation Primary Water Section I Combustion Air Prevention
How To Install An Evaporator Coil
EVAPORATOR COIL INSTALLATION INSTRUCTIONS EVAPORATOR COIL SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... System Requirements... Location Requirements... Drain Requirements... INSTALLATION INSTRUCTIONS...
Installation and maintenance instructions. Danfoss Vent
Installation and maintenance instructions Danfoss Vent 1 Unit design... 2 2 Project planning and installation instructions... 3 2.1 Ventilation...3 2.2 Piping installation....3 2.3 Condensation line...4
SELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
COMMERCIAL GAS WATER HEATERS
Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENTED GAS MODELS W/HOT SURFACE IGNITION MODEL BTX-80 SERIES 100 500 Tennessee Waltz Parkway Ashland City, TN 37015 Low Lead Content For Your Safety
SunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 222-F
Technical Data Manual Model Nos. and pricing: see Price List For Natural Gas and Liquid Propane Gas Gas-fired floor-mounted condensing DHW combi-boiler 12 to 125 MBH (3.5 to 37 kw) VITODENS r 222-F Product
Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION As when installing or using any high voltage electrical appliance, basic safety precautions should always
15GAL STEEL OIL DRAIN WITH 110V PUMP
15GAL STEEL OIL DRAIN WITH 110V PUMP OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety
Operator: Save these instructions for future use!
WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE
Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.
EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT ALPKT7- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... INSTALLATION INSTRUCTIONS...
Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 222-F
Technical Data Manual Model Nos. and pricing: see Price List For Natural Gas and Liquid Propane Gas Gas-fired floor-mounted condensing DHW combi-boiler 12 to 125 MBH (3.5 to 37 kw) VITODENS r 222-F Product
Cooling system components, removing and installing
Page 1 of 34 19-1 Cooling system components, removing and installing WARNING! The cooling system is pressurized when the engine is warm. When opening the expansion tank, wear gloves and other appropriate
Vitodens 200, B2HA / B2HB - Product Introduction
- Product Introduction Foil 2, 10/2015 Viessmann Manufacturing Wall Mounted, Gas-Fired Condensing Boiler Foil 3, 10/2015 Viessmann Manufacturing A member of the Viessmann family of heating products Condensing
USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user
For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS Installation and service must be provided by a qualified installer, service agency or gas supplier Grand Canyon Gas Logs, logs are made
OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER
OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER P110 Your battery charger has been engineered and manufactured to Ryobi s high standard for dependability, ease of operation, and operator safety. When properly
Technical Data Manual
Technical Data Manual Model Nos. and pricing: see Price List Vitodens 100-W WB1B Series Wall-Mounted, gas-fired condensing boiler with optional on demand hot water CombiPLUS Kit Heating input: 37 to 118
Installation Operation & Maintenance Manual
www.montigo.com Operation & Maintenance Manual Check local codes and read all instructions prior to installation. EDVPV BF-Series Wall SS Power Gas Fireplace Vent System EDVPV47 EDVPV58 Warning: Improper
prestige Solo 110 Water Boiler * I N S T A L L A T I O N A N D M A I N T E N A N C E * M A N U A L
prestige Solo 110 Water Boiler * I N S T A L L A T I O N A N D M A I N T E N A N C E * M A N U A L Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installation
Please keep this manual for f uture reference.
GAS WATER/AGUA Congratulations! You've just purchased a new Marey Portable tankless water heater and will soon begin to enjoy the benefits of going tankless. Take the time to thoroughly read and understand
I N S T ALLATION INSTRUCTIONS & HOME OWNERS MANUAL IMPORTANT SAFETY INFORMATION
I N S T ALLATION INSTRUCTIONS & HOME OWNERS MANUAL MODELS: HA018240 HA024240 HA027240 HA036240 IMPORTANT SAFETY INFORMATION As when installing or using any high voltage electrical appliance, basic safety
Installation and Operating Instructions Installation Instructions for SS EPE-316L Series
INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This
Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer
Overview READ ENTIRE INSTRUCTIONS BEFORE STARTING INSTALLATION PARTS LIST A. Flush valve B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil
IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
COOLING SYSTEM Section Page
5 COOLING SYSTEM Section Page 5.1 COOLANT PRE-HEATER... 5-3 5.2 COOLANT PUMP NON-EGR ENGINE... 5-7 5.3 COOLANT PUMP EGR ENGINE... 5-13 5.4 FRONT CONNECTOR HOUSING NON-EGR ENGINE... 5-17 5.5 FRONT CONNECTOR
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
RECON WATER HEATER INSTALLATION FORM
RECON WATER HEATER INSTALLATION FORM Please complete ONE (1) form for each SITE and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: [email protected].
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions