Controlling Electrostatic Ignition Hazards during Fuel Delivery at Forecourts

Size: px
Start display at page:

Download "Controlling Electrostatic Ignition Hazards during Fuel Delivery at Forecourts"

Transcription

1 Controlling Electrostatic Ignition Hazards during Fuel Delivery at Forecourts Graham Hearn 1, Ulrich von Pidoll 2 & Jeremy Smallwood 3 1 Wolfson Electrostatics 2 Physikalisch -Technische Bundesanstalt (PTB) 3 Electrostatics Solutions Ltd. The use of electrically insulating synthetic materials, such as plastics, for fuel pipelines and other fuel handling components is now becoming widespread. In the case of buried pipelines in filling station forecourts the use of these materials offers superior corrosion resistance and increased longevity. This in turn reduces the risk of pollution due to fuel leakage. It is well reported that the flow of fuel under certain conditions in both metal and plastic pipes can produce significant levels of electrostatic charge on the fuel. Pipe systems in modern filling stations generally contain both plastic pipe lengths and metal components such as in-line valves and couplings on which electrostatic charge can accumulate. Non-conductive pipework properly installed with grounded metal fittings and capped electrofusion coupler terminals should not create electrostatic ignition hazards. Over the last year or so a small number of fires have occurred around offset fill pipes at various petroleum forecourt refuelling sites in Europe. Initially these were blamed on either static electricity or thermite reaction. A joint investigation by Exxon and Wolfson Electrostatics [1] has shown the most likely cause to be an electrostatic discharge between an electrofusion coupler (EFC) and nearby metal flange. Measurements performed during a repeat of the delivery operation at the site however produced no significant readings of static electricity. Work undertaken independently by the three authors of this article has highlighted a number of factors influencing the levels of electrostatic hazard and these are discussed in this article. The influence on electrostatic ignition hazards due to the introduction of new alcohol-based biofuels such as E85 is considered. This article analyses the conditions necessary for electrostatic ignition and draws important conclusions with regard to the parameters influencing the degree of hazard present. Hazard Analysis There are five general conditions necessary for an electrostatic ignition hazard to be present: 1. Sensitive flammable atmosphere 2. Generation of electrostatic charge 3. Accumulation of charge 4. Electrostatic discharge (ESD) 5. Sufficient discharge energy for ignition If all of the above conditions exist, an ignition hazard will be present, if any of the conditions are removed, the hazard is obviated. As a belt and braces approach attempts are often made to remove more than one of these conditions, however the extent to which any mitigating measures can be applied in practice often involve other considerations which will inevitably include cost and practicality. Is a flammable atmosphere present? Petroleum spirit vapour has a flashpoint of around -43C and is flammable within the range of about 1-6% by volume with air. At most times within a pipe system and

2 storage tank, there is insufficient oxygen to support combustion ie the atmosphere is over-rich. During tanker delivery, a flammable atmosphere may be established around the end of the fill pipe. Similarly flammable petrol vapour concentrations may exist due to fuel spills and within fill-boxes and chambers. This of course applies equally to metal and plastic systems. E85 which is 85% ethanol and 15% petrol has a reported flashpoint of < -20C [3]. It has a wider flammable range than that of petrol of around 2-26% by volume [3]. Due to the fact that the gas phase of E85 contains much more petrol vapour than ethanol vapour, its upper explosion point is strongly dependent on the filling level of the tank (the so called effect of ullage space ). An almost full tank of E85 has a non flammable gas atmosphere above its liquid phase at temperatures higher than 0C, this temperature raises to 18C when the tank has become 99% empty [3,4]. Because of this effect E85 may produce flammable atmospheres in a wider set of circumstances than petrol. Diesel which has a flashpoint in excess of 60C will not produce a flammable atmosphere under normal conditions and is not considered at risk from static electricity at any time during delivery. However mixing diesel with small amounts of petrol, for example when filling diesel into a road tanker containing residual petrol from the last filling, may produce an explosive atmosphere even in a diesel tank. For all fuels the sensitivity to (spark) ignition varies significantly over the flammable range and is easiest to ignite at a concentration roughly midway between the upper and lower flammable limits. At or near this concentration, the ignition energy is very low and vapour ignitions may occur as the result of sparks from charged, ungrounded metal or electrostatic brush discharges from highly-charged insulating surfaces. Charge generation due to fuel flow During fuel delivery it has been estimated that litres is transferred in 10-12minutes. This corresponds to fuel flows of between 7 and 9 litres per second and moderate velocities in the pipe of around 0.3 metres per second. The electrostatic charge that is generated in fuel being pumped along pipes arises from the presence in parts per million (or billion) of ions in the fuel. Positive or negative ions selectively attach themselves to any interfacial surface in contact with the fuel, such as the inner wall of the pipe, due to selective chemical adsorption (and possibly ionic injection from the pipe wall) [2]. As a consequence, the inside surface of the pipe acquires a unipolar charge and ions of the opposite polarity in the fuel are attracted to it. A charged layer then extends from the wall into the fuel of a thickness that increases with decreasing fuel conductivity, the net charge in the pipe being zero when the fuel is at rest. When the fuel flows, the ions in the boundary layer tend to be carried along, while the opposite charge on the wall dissipates to earth at a rate depending primarily on the pipe material's conductivity. This implies that there will be a significant difference between charging behaviour in metal and plastic pipes. Any filters, valves and elbows will generally increase the amount of charge, due to greater interfacial charge separation, higher fuel velocities and increased turbulence. Similarly, the presence of free water in the fuel can also increase the charge concentration, again due to the charge separation arising from the large interfacial area of the emulsified mixtures. Petrol and Diesel are known to produce high levels of charging under certain conditions.

3 The conductivity of market-place petrol can vary from ps.m -1 [3]. Experiments have shown that the highest charge generation occurs at a conductivity of 5-50 ps.m - 1 [5]. Being alcohol-based, the conductivity of E85 is several orders of magnitude higher than traditional fuels and is unlikely to generate hazardous levels of static electricity due to flow through plastic pipes. The presence of filters and flame arrestors in the pipe may increase static charge generation and charging levels are likely to increase if the filter or flame arrestor becomes partially blocked with particulate materials and impurities. Entrained air and immiscible impurities could also increase electrostatic charge generation. According to CLC/TR [6] typical charge densities of 10 µc.m -3 in liquid due to flow in a pipe can be increased tenfold to around 100 µc.m -3 by a blocked strainer. This level of increase would correspond to a similar tenfold increase in voltages induced on ungrounded metal parts such as electrofusion couplers. In addition to the electrostatic charging mechanisms associated with fuel flow, there is also the possibility of electrostatic charge generation by friction with the external pipe wall and other components of the system, such as the walls of plastic chambers and sumps. In such cases, the charge generation mechanism could be frictional contact with a maintenance workers clothing. Charge accumulation With plastic pipe systems, as with metal pipework, the primary source of charge generation is due to the flow of fuel through the pipe, as discussed above. With metal systems the charge on the metalwork will normally be conducted safely to earth. With plastic systems, electrostatic charge can accumulate on the pipe wall and associated ungrounded metallic components, such as the heating coils in electro-fusion couplings, metal valves and other metal fittings. This represents the principal difference between plastic piping systems and earthed metal systems from an electrostatic point of view. Totally buried insulating plastic pipes usually do not create dangerous discharges inside and outside of the pipe. However, in an excavated, unburied or partly buried system extra care must be taken. In chambers and fill boxes, small sections of the pipe are not buried. The metal components present in a fill box (e.g. valves and other fittings) usually have enough capacitance, to produce incendive sparks when charged by influence of fuel flowing through insulating pipes. For this reason, all conductive objects in chambers and fill boxes should be sufficiently earthed and the surface of charged objects should not exceed the limits given in [6]. Furthermore, the electrical connections of electrofusion couplers should be tightly closed using plastic caps [6]. The forecourt ground surface of a filling station is normally made of a dissipative material with a leakage resistance to earth of less than 10 8 Ohms, e.g. concrete [6]. As tyres are usually sufficiently conductive to provide a leakage path to ground, the delivery road tanker parked on the forecourt is normally earthed via its tyres. Faults in the manufacturing process of modern tyres however can occasionally lead to highly insulating tyres. As a consequence, the leakage path to earth of the road tanker cannot be guaranteed [7].

4 Electrostatic discharges There are essentially two types of electrostatic discharges (ESD) that can occur during fuel delivery: spark and brush discharges. With regard to ignition hazard the characteristics of these two discharges are very different. (a) (b) Figure 1 (a) Spark discharge between a charged metal object and a grounded metal electrode (b) brush discharge from a grounded metal electrode to a highly charged dielectric sheet. Figure 1 (a) shows a spark between two metal objects at different potential. Figure 1 (b) shows a brush discharge between a highly charged dielectric and an approaching earthed electrode. Figure 2 compares the discharge waveforms for the two. The spark discharge current in (a) looks like a damped sine wave whereas the brush discharge current (b) is a single broad pulse. It is important when comparing the waveforms in figure 2 to note that the y-axis for (a) has been compressed and that the spark current is 20 times greater. Generally sparks produce a higher current density than brush discharges resulting in higher temperatures and are therefore more likely to cause ignition. (a) (b)

5 Figure 2 (a) Waveform of the current and its integral of a spark discharge between a charged pulse capacitor (93,3 pf at 7 kv) and a grounded metal electrode (b) same for a brush discharge from a grounded metal electrode to a highly charged dielectric sheet. Ignition of fuel vapour Spark discharges from charged, isolated metal components constitute a strong ignition hazard if they have sufficient energy. Metal components in a fill-box are generally earthed. Any unearthed items such as EFC heating coils and clips can only store small amounts of electrical energy and need a high potential to have sufficient energy to ignite an optimum fuel-air mix. Even if these conditions are met, a nearby ground is required to provide the spark gap. To constitute an ignition source a brush discharge will require not only a highly charged electrically-insulating surface but a grounded metal electrode to initiate the discharge. Figure 1 (b) illustrates how the energy of a brush discharge is concentrated close to the ground electrode and it is this region of the discharge most capable of providing the source of ignition. A few millimetres away from the ground, the discharge becomes diffuse and non-incendive. Brush-like discharges inside pipes have been recorded, especially for fluorinated pipes, but they are normally not incendive because of the over-rich or too-lean atmosphere inside pipes. These discharges may be hazardous if an optimised fuel-air concentration were to exist [7]. Flame arrester Measurement wire Possible site of spark? Grounded metal flange Electrofusion coupler Figure 3. All the conditions necessary for ignition? Flammable atmosphere due to residual vapour in the fill box; charge generation due to fuel flow; accumulation on the heating coil of an electrofusion coupler; spark to nearby grounded metal flange. Summary of conclusions 1. Static electricity has been blamed for fires that have occurred around offset fill pipes during tanker delivery. Non-conductive pipework properly installed (grounded metal fittings and capped electrofusion coupler terminals) should not create electrostatic ignition hazards.

6 2. If static electricity is the cause of these fires it is almost certain to be the result of sparks from ungrounded metal fittings or electrofusion couplers igniting residual fuel vapour in the box outside the pipes. If air is present in the pipe, brush discharges may present an ignition hazard. Brush discharges from a buried plastic pipe surface are unlikely to produce sufficient current density in the discharge to cause ignition. 3. Incidents of fire have also been blamed on thermite reactions between aluminium fittings and corroded steel but like static electricity this ignition source has not been ratified. 4. Within a normally-functioning pipe system (plastic or metal) there is insufficient oxygen present to support or propagate combustion. Furthermore. air does not enter the inlet pipe of a fill pipe in modern European installations. The installation is under pressure (35mbar) causing vapour to come out of the fill after disconnection rather than air going in. This will tend to leave an explosive atmosphere just outside the pipe rather than inside. 5. The alcohol-based fuels E50 E100 have a much higher electrical conductivity than petrol and Diesel and will not generate hazardous static potentials in pipe systems assuming they are in contact with an earth point somewhere in the tank system. 6. Flame arresters similar to those in place at the site of the incidents in Hungary [1] (Figure 3) may increase the level of charge generation during fuel flow and may therefore increase the ignition risk. Fire prevention The precise cause of the recent flash fires during fuel delivery cannot be considered certain on the basis of the available evidence. However some recommendations of preventative action can be considered. The ignitions were probably caused by an electrostatic discharge external to the fill pipes. Fuel or vapour may well have been present due to spillage or vapour release. It was found that some vapour leakage could occur from the Stage 1 and fill connections on opening, and through a connection that was not vapour tight. If the possibility of fuel or vapour in the vicinity of the fill pipes can be excluded then the risk of fire from this cause may be eliminated. Reliable exclusion of fuel vapour would be perhaps the best way of removing the risk of ignition outside the pipe. There appears to be little if any risk of ignition inside the pipe if it is either buried or air intake is avoided. It has been suggested that filling the box with sand to above the pipes and sealing the top layer against fuel ingress. This may be one way of successfully removing the possibility of a flammable mixture near the pipes. This procedure would have added benefit in effectively grounding electrofusion couplers in contact with the sand, in all but the driest conditions. Furthermore, if by some chance vapour did accumulate and a spark could ignite it, the sand would prevent the propagation of flame. In any location where a flammable atmosphere can occur, it is important to ground all conductive objects of significant size. Electrofusion couplers may be significant in this context. Additionally it is important that a long term reliable earth connection to these items is achieved.

7 Another approach is to electrically insulate the heating coil terminals in the coupler by some means to prevent electrostatic discharge. This is likely to be effective if a reliable seal is obtained for example by a tight fitting cap or peg. Figure 4 is a photograph of a properly installed underground fill pipe, with grounded metal connectors and capped electrofusion couplers. In this situation, steps 3 and 4 of the five hazard conditions (charge accumulation and ESD) are removed. Ground wire Capped terminals Figure 4. Properly installed underground fill pipe with grounded fitting and caps fitted to electrofusion coupler terminals. With alcohol based fuels E50-E100 it is postulated that fuel flow will not result in significant electrostatic potentials. However with existing installations the presence of a sensitive flammable atmosphere may still exist. Furthermore due to their wider flammable range and different ignition properties, these fuels may be somewhat easier to ignite. With this in mind, precautions against electrostatic discharges from other sources e.g. relating to the grounding of the vehicle and personnel must be in place. References [1] Wolfson Electrostatics report R436/JMS for Exxon Mobil dated 1 February 2006 [2] Feleci, N. J., (1984). J. Electrostatics, 15, [3] Brandes, E., PTB Braunschweig, section 3.41, Safety data of E50, E60, E85 and E>85, unpublished datasheet dated [4] Vaivads, R. H., Bardon, M. F. Rao, V. K. and Battista, V., Flammability Tests of Alcohol/Gasoline Vapours, SAE Technical paper , [5] von Pidoll, U., Krämer, H. and Bothe, H., Avoidance of electrostatic hazards during refuelling of motorcars, J. of Electrostatics 40&41 (1997), [6] CENELEC Technical report TR50404, Code of practice for the avoidance of hazards due to static electricity, [7] von Pidoll, U., Electrostatic ignition hazards in motor cars occurrence, detection and prevention. Proceedings ESA/IEEE Joint Meeting on Electrostatics, , University of Arkansas, Little Rock,

Summary of risks with conductive and nonconductive plastic pipes at retail petrol stations

Summary of risks with conductive and nonconductive plastic pipes at retail petrol stations Summary of risks with conductive and nonconductive plastic pipes at retail petrol stations Introduction Harold Walmsley, Harold Walmsley Electrostatics Ltd, 23/01/2010 This note summarises my views on

More information

FLAMMABLE LIQUIDS COMPLIANCE NOTE

FLAMMABLE LIQUIDS COMPLIANCE NOTE Issued by: Heather Rice Page: 1 of 7 COMPLIANCE NOTE INTRODUCTION This document provides additional guidance to support the Arrangement on Flammable Liquids (Ref No. CYC/HS/A27) CONTENTS Section Topic

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

International Safety Guide Chapter 3 for Inland Navigation Tank-barges and Terminals. Chapter 3 STATIC ELECTRICITY

International Safety Guide Chapter 3 for Inland Navigation Tank-barges and Terminals. Chapter 3 STATIC ELECTRICITY Chapter 3 STATIC ELECTRICITY This Chapter describes hazards associated with the generation of static electricity during the loading and discharging of cargo and during tank cleaning, dipping, ullaging

More information

GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS

GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS September 2007 Replaces the July 2004 edition 1. Purpose Purpose of present Guideline is to specify conditions for the safe handling of flammable

More information

Newson Gale. Is it ever Safe to use Plastic Drums and Containers in Hazardous areas? White Paper. Author Details:

Newson Gale. Is it ever Safe to use Plastic Drums and Containers in Hazardous areas? White Paper. Author Details: White Paper Is it ever Safe to use Plastic Drums Author Details: Mike O Brien, Head of Product Marketing for If you have any questions relating to the topics discussed in this article, you can contact

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

Modelling of Electrostatic Ignition Hazards in Industry: too Complicated, not Meaningful or only of Academic Interest?

Modelling of Electrostatic Ignition Hazards in Industry: too Complicated, not Meaningful or only of Academic Interest? A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 31, 2013 Guest Editors: Eddy De Rademaeker, Bruno Fabiano, Simberto Senni Buratti Copyright 2013, AIDIC Servizi S.r.l., ISBN 978-88-95608-22-8; ISSN

More information

Fire & Explosion Risks in Service Stations

Fire & Explosion Risks in Service Stations Fire & Explosion Risks in Service Stations Petrol Vapour Petrol gives off highly flammable vapour even at very low temperatures. Because of the flammability of petrol vapours, service stations carry a

More information

No. 8940. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CAR RIAGE OF DANGEROUS GOODS BY ROAD (ADR). DONE AT GENEVA ON 30 SEPTEMBER 1957'

No. 8940. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CAR RIAGE OF DANGEROUS GOODS BY ROAD (ADR). DONE AT GENEVA ON 30 SEPTEMBER 1957' 1975 United Nations Treaty Series Nations Unies Recueil des Traités 435 [TRANSLATIN TRADUCTIN] No. 8940. EURPEAN AGREEMENT CNCERNING THE INTERNATINAL CAR RIAGE F DANGERUS GDS BY RAD (ADR). DNE AT GENEVA

More information

B2005/0028. An examination of the myths and facts about fires caused by stat ic electricity and exploding mobile phones

B2005/0028. An examination of the myths and facts about fires caused by stat ic electricity and exploding mobile phones RESEARCH PAPER B2005/0028 STATIC FIRES AT RETAIL PETROL STATIONS An examination of the myths and facts about fires caused by stat ic electricity and exploding mobile phones 1 ISBN 1 921092 08 4 June 2005

More information

Wilkins Safety Group

Wilkins Safety Group H & S Guidance - Flammable Liquids See also: other pages INTRODUCTION Flammable liquids are liquids with a flashpoint of 55ºC or below and hence includes all liquids that are classified as flammable, highly

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

R044-001. Safety of machinery Guidance and recommendations for the avoidance of hazards due to static electricity

R044-001. Safety of machinery Guidance and recommendations for the avoidance of hazards due to static electricity R044-001 Safety of machinery Guidance and recommendations for the avoidance of hazards due to static electricity Page 2 Contents Page Foreword... 4 Clause 1 Scope... 5 2 Definitions... 5 3 General... 6

More information

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders STORE HAZARDOUS SUBSTANCES SAFELY Suitable containers incompatibles gas cylinders Oxy-Acetylene welding flammable substances 35 36 STORE HAZARDOUS SUBSTANCES SAFELY STORE HAZARDOUS SUBSTANCES SAFELY Storing

More information

LCT 1025 (08/08) Copyright 2008 Harleysville Mutual Insurance Company Page 1 of 5 All rights reserved

LCT 1025 (08/08) Copyright 2008 Harleysville Mutual Insurance Company Page 1 of 5 All rights reserved Bonding and Grounding of Flammable Liquid Containers Provided by Harleysville s Risk Control Department 800-523-6344 ext 8100 www.harleysvillegroup.com/riskcontrol Summary The movement of volatile liquids,

More information

Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A.

Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A. Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A. Properties of hydrogen Hydrogen is an odorless, colorless gas. With molecular

More information

Controlling Static Electricity in Modern Buildings

Controlling Static Electricity in Modern Buildings Controlling Static Electricity in Modern Buildings Graham Hearn Wolfson Electrostatics The problem of static electricity in commercial offices and stores is a relatively modern phenomenon. It represents

More information

During Various Aluminum Fabricating Operations

During Various Aluminum Fabricating Operations Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations F-1 Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations SCOPE

More information

OSHA Office of Training and Education 1

OSHA Office of Training and Education 1 Flammable and Combustible Liquids OSHA Office of Training and Education 1 Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and

More information

Recommended Fuel Piping Specification For UPP Piping, UL-971

Recommended Fuel Piping Specification For UPP Piping, UL-971 Recommended Fuel Piping Specification For UPP Piping, UL-971 1.0 General The primary delivery piping system shall be for suction or pressure applications and have semi-rigid coaxial type double wall construction,

More information

ADMINISTRATIVE SERVICES MANUAL

ADMINISTRATIVE SERVICES MANUAL Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of

More information

List of Frequently Utilized Storage Tank Standards and Practices

List of Frequently Utilized Storage Tank Standards and Practices List of Frequently Utilized Storage Tank Standards and Practices Below is a list of frequently used storage tank standards and practices from organizations that are referenced in 25 PA Code, Chapter 245.

More information

BP WIND ENERGY POLICIES AND PROCEDURES

BP WIND ENERGY POLICIES AND PROCEDURES BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials

More information

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Grounding and Bonding Against Static Electricity Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Objectives Identify Sources of Ignition. Identify Hazards associated

More information

Emergency Response Guide

Emergency Response Guide Emergency Response Guide Honda Fuel Cell Vehicle Prepared for Fire Service, Law Enforcement, Emergency Medical, and Professional Towing Personnel by American Honda Motor Co., Inc. Contents Key Components...2

More information

Ethanol Vehicle and Infrastructure Codes and Standards Citations

Ethanol Vehicle and Infrastructure Codes and Standards Citations Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and

More information

Pressure Vessels (Air Compressors) and LPG Tanks

Pressure Vessels (Air Compressors) and LPG Tanks Pressure Vessels (Air Compressors) and LPG Tanks 1. Identification of Workplace Hazard Any container, tank or vessel that contains pressurized material is a potential hazard to employees due to the force

More information

Safety Storage Cabinets

Safety Storage Cabinets Safety Storage Cabinets Safe storage of flammables? The workplace without a fire resistant Safety Storage Cabinet Dangers, risks and your disadvantages... STORAGE ROOM Transport/working time - Increased

More information

SOLAR PV SYSTEM MAINTENANCE GUIDE

SOLAR PV SYSTEM MAINTENANCE GUIDE SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013

More information

Explosions Involving Nonconductive Flammable Liquids

Explosions Involving Nonconductive Flammable Liquids Explosions Involving Nonconductive Flammable Liquids Almost every firefighter and responder has been introduced to the classic fire triangle. For a fire to occur, all three elements (a fuel, oxygen, and

More information

Presented by: Rich Perry Marsh Risk Consulting

Presented by: Rich Perry Marsh Risk Consulting Flammable and Combustible Liquids Presented by: Rich Perry Marsh Risk Consulting What s the Big Deal? Flammable and combustible liquids are easily ignited Ignite with explosive force Burn readily and give

More information

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated

More information

Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation

Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation No. 2008-02-I-IA (September 2008) Key Lessons for Safe Handling and Storage of Flammables Ensure that equipment, such as fill

More information

Flammable and Combustible Liquids. Slide 1 (of 23)

Flammable and Combustible Liquids. Slide 1 (of 23) Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids

More information

Safe use of liquefied petroleum gas (LPG) at small commercial and industrial bulk installations

Safe use of liquefied petroleum gas (LPG) at small commercial and industrial bulk installations Safe use of liquefied petroleum gas (LPG) at small commercial and industrial bulk installations When the risks are properly identified and managed, LPG can be safely used as a fuel source for many applications.

More information

PRECAUTIONS ON TANKER AND TERMINAL DURING CARGO HANDLING

PRECAUTIONS ON TANKER AND TERMINAL DURING CARGO HANDLING Chapter 24 PRECAUTIONS ON TANKER AND TERMINAL DURING CARGO HANDLING This Chapter provides guidance on precautions to be observed by both tanker and shore when cargo handling, ballasting, bunkering, tank

More information

Compressed Gas Cylinder Safety

Compressed Gas Cylinder Safety ISC Compressed Gas Cylinder Safety Training page 1 Compressed Gas Cylinder Safety This training program is adapted from the online OSHA training program on the Oklahoma State University OSHA training web

More information

A Practical Guide to Free Energy Devices

A Practical Guide to Free Energy Devices A Practical Guide to Free Energy Devices Part PatE21: Last updated: 15th January 2011 Author: Patrick J. Kelly This patent describes methods for altering HHO gas so that it can be used in vehicle engines

More information

The safe use and handling of FLAMMABLE LIQUIDS

The safe use and handling of FLAMMABLE LIQUIDS The safe use and handling of FLAMMABLE LIQUIDS The safe use and handling of FLAMMABLE LIQUIDS HSE BOOKS Crown copyright 1996 Applications for reproduction should be made in writing to: Copyright Unit,

More information

Site and Storage Conditions for Class 3.1 Flammable Liquids

Site and Storage Conditions for Class 3.1 Flammable Liquids Site and Storage Conditions for Class 3.1 Flammable Liquids Introduction Contents Introduction... 1 SITE AND STORAGE CONDITIONS...2 Part 1 General Flammability Conditions...2 Part 2 Conditions Relating

More information

Petroleum (Consolidation) Regulations 2014

Petroleum (Consolidation) Regulations 2014 Petroleum (Consolidation) Regulations 2014 Introduction of new Petroleum Regulations On 1 October 2014 the Petroleum (Consolidation) Regulations 2014 are scheduled to come into force. Who do the Regulations

More information

Application Note AN1

Application Note AN1 TAKING INVENTIVE STEPS IN INFRARED. MINIATURE INFRARED GAS SENSORS GOLD SERIES UK Patent App. No. 799A USA Patent App. No. 9/78,7 World Patents Pending SENSOR OVERVIEW Application Note AN The Dynament

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000

Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000 Gas Standards and Safety Guidance Note January 2015 (GN106) Version 1.0 GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000 A guide to assist in the design of biogas

More information

Controlling fire and explosion risks in the workplace

Controlling fire and explosion risks in the workplace Controlling fire and explosion risks in the workplace A brief guide to the Dangerous Substances and Explosive Atmospheres Regulations Introduction to DSEAR This leaflet provides a brief introduction to

More information

Failure Analysis Associates. Cell Phone Usage At Gasoline Stations

Failure Analysis Associates. Cell Phone Usage At Gasoline Stations Failure Analysis Associates Cell Phone Usage At Gasoline Stations Cell Phone Usage At Gasoline Stations Prepared for Motorola Corporation 2001 N. Division St. Harvard, IL 60033 Prepared by Exponent Failure

More information

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:

More information

ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion

ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion Annex 17, page 1 ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16 Part B Prevention of fire and explosion Regulation 4 Probability of ignition 1 The existing paragraph 5.5 is replaced

More information

Oxy-Fuel Gas Welding. Given a functional oxy-fuel gas unit, instruction and demonstration of use, each student will be able to:

Oxy-Fuel Gas Welding. Given a functional oxy-fuel gas unit, instruction and demonstration of use, each student will be able to: I. Competencies Oxy-Fuel Gas Welding Given a functional oxy-fuel gas unit, instruction and demonstration of use, each student will be able to: A. Identify the major parts of the oxy-fuel gas unit. B. Pass

More information

Electrical Classification

Electrical Classification Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to

More information

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for

More information

Case Study. Barton Solvents Static Spark Ignites Explosion Inside Flammable Liquid Storage Tank. U.S. Chemical Safety and Hazard Investigation Board

Case Study. Barton Solvents Static Spark Ignites Explosion Inside Flammable Liquid Storage Tank. U.S. Chemical Safety and Hazard Investigation Board Case Study U.S. Chemical Safety and Hazard Investigation Board Barton Solvents Static Spark Ignites Explosion Inside Flammable Liquid Storage Tank No. 2007-06-I-KS Issues Nonconductive flammable liquids

More information

Portable petrol storage containers

Portable petrol storage containers Portable petrol storage containers The Petroleum (Consolidation) Regulations 2014 (PCR), which came into force on 1 October 2014, apply to the following: workplaces that store petrol where petrol is dispensed,

More information

JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS

JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS 1 JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES

More information

FIRE SAFETY GUIDANCE NOTE Risk Assessments for Petrol Filling Stations Required Under Fire Safety Legislation

FIRE SAFETY GUIDANCE NOTE Risk Assessments for Petrol Filling Stations Required Under Fire Safety Legislation FIRE SAFETY GUIDANCE NOTE Risk Assessments for Petrol Filling Stations Required Under Fire Safety Legislation Number: GN75 This Guidance Note provides information on the legislation relating to risk assessments

More information

Notes. Material 1. Appropriate Flammable Liquids

Notes. Material 1. Appropriate Flammable Liquids 29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female

More information

Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems

Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems Technical Bulletin Gas & Air Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems 1. Introduction Norit GL 50 is a powdered activated carbon widely used for the removal of

More information

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008 HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2

More information

MATERIAL SAFETY DATA SHEET. PRODUCT IDENTIFIER Carbon Dioxide, Refrigerated Liquid

MATERIAL SAFETY DATA SHEET. PRODUCT IDENTIFIER Carbon Dioxide, Refrigerated Liquid SECTION I- Product Information* MANUFACTURER: EPCO Carbon Dioxide Products, Inc. OFFICE PHONE: 1-800-259-3726 24-HOUR EMERGENCY: 1-800-259-8095 SHIPPING NAME: Carbon Dioxide, Refrigerated Liquid UN NUMBER:

More information

MOTOR FUEL DISPENSING SAFETY

MOTOR FUEL DISPENSING SAFETY STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.

More information

5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment

5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment Two Documents are used for the Classification of Combustible Dusts and Hazardous Locations: NFPA 499-Recommended Practices for the Classification of Combustible Dusts and Hazardous Locations for Electrical

More information

Compressed Gas Cylinder Program

Compressed Gas Cylinder Program Department of Environmental Health & Safety Procedures Compressed Gas Cylinder Program March 2010 Compressed Gas Cylinder Program Page 1 of 8 Table of Contents I. Introduction II. III. IV. Policy Scope

More information

53403500 - Injector Max Machine

53403500 - Injector Max Machine 53403500 - Injector Max Machine Operating Instructions Contents Page Introduction Operating Instructions Fuel Injection Cleaner - Petrol Operating Instructions Fuel Injection Cleaner - Diesel 3 Operating

More information

Sample Written Program. For. Flammable Liquids

Sample Written Program. For. Flammable Liquids Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

CATHODIC PROTECTION SYSTEM DESIGN

CATHODIC PROTECTION SYSTEM DESIGN CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of

More information

Ethanol-Water Phase Separation White Paper

Ethanol-Water Phase Separation White Paper Ethanol-Water Phase Separation White Paper Samir Jain Background The use of ethanol as a fuel in the United States has significantly increased over the past decade. Today, greater than 80% of all retail

More information

1.0 Purpose... 4. 2.0 Definitions...4. 3.0 Hot Work Operations. 5

1.0 Purpose... 4. 2.0 Definitions...4. 3.0 Hot Work Operations. 5 HOT WORK PROGRAM Introduction The University of Kentucky recognizes a potential for fire from hot work operations. For that reason this program should be implemented in all departments at the University

More information

International Maritime Dangerous Goods (IMDG) Special Provision 961 and 962

International Maritime Dangerous Goods (IMDG) Special Provision 961 and 962 SP961 and SP962 International Maritime Dangerous Goods (IMDG) Special Provision 961 and 962 Since 2010 when the International Maritime Organization decided to re-regulate vehicles, the applicability and

More information

RADIANT PLASMA 4700 Plasma Spark Generator

RADIANT PLASMA 4700 Plasma Spark Generator RADIANT PLASMA 4700 Plasma Spark Generator Installation Guide / User Manual A S P A R K O F F R E S H A I R Aquapulser.com Contents 1 Introduction 2 1.1 About the Product....................................

More information

Experiences from introduction of ethanol buses and ethanol fuel stations

Experiences from introduction of ethanol buses and ethanol fuel stations SUPPORTED BY THE EUROPEAN UNION Experiences from introduction of ethanol buses and ethanol fuel stations June 2007, La Spezia, Madrid, Rotterdam, Stockholm, Sao Paulo BEST Deliverable No D 2.1 and D 2.2

More information

Certain specific properties of compressed gases make them highly useful in various research activities.

Certain specific properties of compressed gases make them highly useful in various research activities. GAS CYLINDER SAFETY Introduction Certain specific properties of compressed gases make them highly useful in various research activities. These gases, however, can be dangerous if not handled in an appropriate

More information

SELECTION, APPLICATION AND MAINTENANCE

SELECTION, APPLICATION AND MAINTENANCE DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine

More information

Flammability : A safety guide for users

Flammability : A safety guide for users Best Practice Guidelines n 4 version 3, June 2013 Flammability : A safety guide for users Safe working with industrial solvents CONTENTS FOREWORD... 5 PART 1 General advice for handling flammable solvents...

More information

Risk Assessment Based Environmental Management Systems for Petroleum Retail Stores

Risk Assessment Based Environmental Management Systems for Petroleum Retail Stores Risk Assessment Based Environmental Management Systems for Petroleum Retail Stores NATO/CCMS Pilot Study Prevention and Remediation In Selected Industrial Sectors: Small Sites in Urban Areas Prof. Cem

More information

METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS

METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS Contents Foreword --------------------------------------------------------------------------------------------------------------------

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

Basic Safety Examination instructions

Basic Safety Examination instructions Name of candidate: This VCA mock examination is only intended for training purposes and is aimed at familiarising candidates with the examination methods. The questions are checked every year for accuracy

More information

Gas-Fired, Residential Storage Type Water Heaters

Gas-Fired, Residential Storage Type Water Heaters Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. Gas-Fired, Residential Storage Type Water Heaters Most inspectors

More information

The Engineering Science of Oil Pipelines

The Engineering Science of Oil Pipelines The Engineering Science of Oil Pipelines From the Keystone XL pipeline project to spills and leaks in existing lines, pipelines are in the news. The SMCC has prepared this backgrounder on crude oil and

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Underground Storage Tanks

Underground Storage Tanks Underground Storage Tanks An Informational and Guidance Document for the University Community. Please contact Yale Environmental Health and Safety for latest Regulatory Requirements. A typical UST installation

More information

GUERNSEY OIL INSTALLATION GUIDELINES

GUERNSEY OIL INSTALLATION GUIDELINES GUERNSEY OIL INSTALLATION GUIDELINES This guidance relates only to liquid oil. For information on the requirements for associated equipment such as the positioning of boilers and flues please refer to

More information

SOLVENT CLEANER MSDS Page 1 of 5 SAFETY DATA SHEET. (To comply with OSHA s Hazard Communication Standard 29CFR 1910.1200/ANSI z400.

SOLVENT CLEANER MSDS Page 1 of 5 SAFETY DATA SHEET. (To comply with OSHA s Hazard Communication Standard 29CFR 1910.1200/ANSI z400. SOLVENT CLEANER MSDS Page 1 of 5 SAFETY DATA SHEET (To comply with OSHA s Hazard Communication Standard 29CFR 1910.1200/ANSI z400.1-1993) 1. PRODUCT & COMPANY IDENTIFICATION Prepared on: Month, Year Manufactured

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

Queen's University Environmental Health and Safety

Queen's University Environmental Health and Safety April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

Flame Conductivity VS Flame Rectification Systems

Flame Conductivity VS Flame Rectification Systems Flame Conductivity VS Flame Rectification Systems There are two basic principles in flame rod detection systems-flame conductivity and flame rectification. Conductivity systems are, for the most part no

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60

More information

Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****

Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H***** Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H***** FM 3046039 Class I Div 1, Groups A, B, C and D Class II Div 1, Groups E, F and G; Class III Class I, Zone 0, AEx ia IIC Ga, Ga/Gb, Gb Document ID:

More information

Installation of Underground LP-Gas Systems

Installation of Underground LP-Gas Systems NPGA #412-94 Installation of Underground LP-Gas Systems SCOPE This bulletin provides guidelines for the installation and inspection of underground LP-Gas systems and outlines song of the unique problems

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

San josé OWNER S MANUAL

San josé OWNER S MANUAL San josé OWNER S MANUAL Assembling & operating manual San josé 30 mbar - PORTABLE GAS BARBECUE 1. 2. 3. Improper installation, adjustment, alteration, service or maintenance can injury or property damage.

More information

PBX Series Quick Fit Connector Bimetallic Steam Traps

PBX Series Quick Fit Connector Bimetallic Steam Traps 6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

G670 Intermittent Pilot Ignition Controls

G670 Intermittent Pilot Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control

More information

Explosion of a gasoline vapour cloud formed in a hydrocarbon loaded effluents storage tank 10 December 1999 Arquata Scrivia Italy

Explosion of a gasoline vapour cloud formed in a hydrocarbon loaded effluents storage tank 10 December 1999 Arquata Scrivia Italy Explosion of a gasoline vapour cloud formed in a hydrocarbon loaded effluents storage tank 10 December 1999 Arquata Scrivia Italy UVCE Storage tank Hydrocarbons Steam coil Corrosion Steam Instrumentation

More information

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant). Fittings for CO 2 Pipe Threads Pipe thread references quoted in this catalogue conform with the requirements specified in the latest issue and amendments of the following ISO Standards: ISO 7-1 (BS21)

More information