Polychlorinated Biphenyl Inspection Manual
|
|
|
- Winfred Ryan
- 9 years ago
- Views:
Transcription
1 EPA-305-X Polychlorinated Biphenyl Inspection Manual August 2004 Office of Compliance Office of Enforcement and Compliance Assurance U.S. Environmental Protection Agency 1200 Pennsylvania Avenue, NW (MC 2224-A) Washington, D.C
2 Chapter Four Chapter Four Page Transformers Background Transformer Locations Maintenance and Repair of PCB Transformers Manufacturers and Trade Names Capacitors Background Locations Maintenance and Repair Manufacturers and Trade Names Other Electrical Equipment Hydraulic Systems Background Manufacturers and Trade Names Other PCB Equipment Fluorescent Light Ballasts Heat Transfer Systems NaturalGas Pipelines Electric Motors Electromagnets Products Containing PCBs Tables PCB Inspection Manual 4-i August 2004
3 Chapter Four Table 4-1. Table 4-2. Table 4-3. Table 4-4. Table 4-5. Table 4-6. Estimate of the Number of Registered Transformers by Industry Sector Transformer Manufacturers and PCB Fluid Trade Names Capacitor Manufacturers and PCB Fluid Trade Names Hydraulic Fluid Manufacturers and Trade Names TSCA Disposal Requirements for Fluorescent Light Ballasts Heat Transfer Fluid Manufacturers and Trade Names August ii PCB Inspection Manual
4 Chapter Four 4.0 An inspector may encounter several types of PCB-containing equipment during a PCB inspection. This equipment consists chiefly of five major categories: transformers, capacitors, other electrical equipment, hydraulic systems, miscellaneous (e.g., fluorescent light ballasts, heat transfer systems), and other equipment. This chapter provides the inspector with general information on these major categories of regulated PCB equipment for which EPA authorizes certain activities (e.g., servicing and/or use), in accordance with Section 6(e) of TSCA. For each type of PCB equipment discussed, this chapter provides information on the typical economic sectors using the equipment and a list of manufacturers and trade names. This chapter also includes information on inspections relating to specific equipment and the risk of contamination from exposure to such equipment. The sections below summarize those regulations pertaining only to activities authorized for the specific equipment. Section , "Authorizations" describes these authorization provisions. General regulatory requirements (e.g., provisions concerning disposal and storage, marking, and recordkeeping) also apply to authorized uses of such equipment. Inspectors should refer to Chapters Three and Four as well as the regulations when preparing to conduct inspections. Each section in this chapter contains a list of manufacturers and trade names used for PCBs or materials containing PCBs. Appendix E contains a comprehensive listing of PCB manufacturers and the trade names they used for PCB materials. 4.1 Transformers [ (a) and (b)] Background Transformers increase or decrease the voltage level of an electric current. Electrical transformers are often filled with a dielectric liquid that increases the resistance of the unit to arcing and acts as a heat transfer medium, helping to cool the coils. Today, most transformers are filled with mineral oil or silicone. PCBs are chlorinated fire-resistant fluids that meet the definition established in the National Electrical Code (NEC) for askarel, the generic name for non-flammable synthetic chlorinated hydro-carbons used for insulating media. Askarel transformers, containing 40 to 60 Figure 4-1. Two PCB Transformers. PCB Inspection Manual 4-1 August 2004
5 Chapter Four percent PCBs, with the remainder of the fluid being chlorobenzenes, were manufactured in the United States from 1929 to Askarel transformers were made in a variety of sizes, containing from three to 3,000 gallons (average 235 gallons) of liquid. They were generally used in locations where flammability was a concern. Many mineral oil transformers may have been contaminated with PCBs through servicing or at the time of manufacturing. Figure 4-2 shows an oil filled transformer and a non-oil filled transformer. The regulations define PCB and PCBs as any chemical substance that is limited to the biphenyl molecule that has been chlorinated to varying degrees or any combination of substances which contains such substances. The regulations define a PCB Transformer as any transformer containing 500 ppm PCBs or greater. PCB-Contaminated Transformers contain PCBs at concentrations greater than or equal to 50 ppm and less than 500 ppm. The inspector should be aware that the PCB concentration of transformer bushings may differ from the transformer. The inspector should note that regulations pertaining to railroad transformers are separate from those relating to other transformers. Therefore, the information pertaining to railroad transformer regulations, as well as to maintenance, repair, and inspection of railroad transformers, is presented separately, later in this chapter Transformer Locations As of August 28, 1998, owners/operators of PCB Transformers in use, or in storage for reuse, must register those transformers with EPA. Owners/operators of a transformer who failed to register in 1998 are still required to register. This registration is a one-time requirement. When an owner/operator of a company removes PCB Transformers from service and disposes of them, it need not update its original registration. EPA has developed a database of the registered PCB Transformers (the PCB Transformer Registration Database) which can be accessed at Based on a simple analysis of the company names in the October 2001 version of this database, the industries listed in the table below registered the most transformers. The inspector should use the information below only as a general guide to which industries commonly have PCB Transformers, as opposed to an exact count of the transformers in use. Some owners of PCB Transformers may not have registered, while others incorrectly registered. August PCB Inspection Manual
6 Chapter Four Non-Oil Filled Transformer Surge Arrestor Surge Arrestor Oil Filled Transformer Surge Arrestor Figure 4-2. Oil filled and non-oil filled transformers. PCB Inspection Manual 4-3 August 2004
7 Chapter Four Table 4-1. Estimate of the Number of Registered Transformers by Industry Sector Industry Sector Number of Registered Transformers Utilities 10,644 Steel 1,968 Federal 1,805 Metal 1,292 Automotive 1,063 Paper and Paper Products 391 Tire and Rubber 344 Mining 340 Education 308 Transportation 287 Textiles 221 Durable Goods 215 Chemicals and Polymers 208 Cement and Concrete 179 Non-Federal Government 164 Fertilizer and Allied Products 150 Glass 135 Pharmaceutical 113 Oil/Gas/Refinery 111 Building Materials 102 Other 1,814 Grand Total 21,854 PCB Transformers are in use in a wide variety of locations, often including: Utilities! PCB Transformers can be found in: - Distribution substations - Generating facilities (including coal, gas, and nuclear facilities). August PCB Inspection Manual
8 Chapter Four Mines! Transformers are usually located within the power substation that supplies electricity to the entire mine. (See Appendix F for more information regarding the use and distribution of PCBs in underground mines and training and safety issues for inspectors visiting mines.) Industrial and Other Sectors! Industries with high-power requirements or equipment are likely to have PCB Transformers. Likely locations of PCB Transformers include: - In electrical substations - Inside, around, or on top of buildings - In powerhouses that generate and distribute electrical power throughout the facility - In underground vaults.! Transformers can also be found in the broadcasting industry. Commercial Buildings! PCB Transformers often are used inside commercial buildings to meet fire code restrictions or to reduce fire insurance premiums. Most commercial building owners contract the servicing of their transformers to transformer maintenance and repair companies. However, commercial building owners may not own PCB Transformers. The electric utility providing service to the building often owns such units. The inspector should determine who owns and is responsible for the unit.! Neon signs may also contain PCB Transformers and may be found on old or abandoned commercial buildings or in scrap yards. Railroads and Subways! Railroad companies used PCBs in on-board transformers in electric locomotives and self-propelled cars in service in the Northeast Corridor (Washington to Boston). The transformers reduce the high voltage current from overhead lines. Subway systems used PCB Transformers to distribute power to subway cars. Transformers are generally underground Maintenance and Repair of PCB Transformers PCB Transformers (both railroad and others) require periodic maintenance and repair, which may be handled by facility staff or by independent contractors.!! Independent firms may contract to maintain and repair transformers for all types and sizes of industries, including small firms (e.g., commercial buildings). Maintenance divisions of larger industries may operate facilities to maintain and repair transformers. These divisions occasionally service transformers for other firms. PCB Inspection Manual 4-5 August 2004
9 Chapter Four Maintenance operations take place both onsite (at the operating location of the equipment) and offsite (at a special shop or facility operated by the firm or by the contractor).!! Onsite maintenance and repair may involve considerable handling of PCBs, including: - Transport of items such as waste liquids and contaminated rags to storage or disposal. Offsite maintenance may occur in specific facilities used only for transformer maintenance or in shops that handle other maintenance as well. The handling includes: - Removal of the transformer from the operating site - Transport of damaged or leaking equipment - Transport of waste to storage or disposal site - Reinstallation of repaired equipment. PCB Transformer Maintenance PCB Transformers (excluding railroad transformers, which are discussed below) require service periodically and repair when out-of-order. Maintenance includes:! Sampling fluid to test dielectric strength! Topping off fluid (historically a source of PCB contamination)! Replacing gaskets, bushings, insulators, etc., which may involve partial draining of the unit! Removing and filtering the dielectric liquid and refilling the unit! Removing PCB liquid and refilling with replacement dielectric fluid! Generating waste liquid, contaminated rags, equipment, etc., which must be disposed of in accordance with the regulations. Railroad Transformer Maintenance Railroad transformers require additional and more frequent maintenance because of their unique installation and operating circumstances:! On-board transformers are subject to severe conditions (high loads, cramped space) and require a high level of maintenance.! Pumps circulate oil containing PCBs through the transformers, where the oil absorbs heat, to a series of finned radiators which dissipate the heat.! Transformers and the cooling apparatus located in the undercarriage are subject to damage from objects dislodged from the roadbed. Inspectors should be aware that leaks can cause exterior surfaces to become contaminated. August PCB Inspection Manual
10 Chapter Four Maintenance frequently takes place in repair pits, which can become severely contaminated with PCBs. Operations are similar to those listed for other PCB Transformers, but include additional activities, such as:! Repairing/replacing circulating pumps and damaged, leaking cooling systems and radiators! Dismantling/disconnecting cooling systems filled with PCB fluids! Decontaminating the system and equipment surfaces Manufacturers and Trade Names Many manufacturers of PCB askarel liquid identified the substance by a trade name. PCBs have been used since 1929, and many of the early manufacturers have gone out-of-business. PCB Inspection Manual 4-7 August 2004
11 Chapter Four Table 4-2. Transformer Manufacturers and PCB Fluid Trade Names Transformer Manufacturer Allis-Chalmers American Corporation Cornell Dubilier PCB Fluid Trade Name Chlorextol Asbestol Dykanol Electro Engineering Works Envirotech Buell ESCO Manufacturing Company Ferranti-Packard Limited General Electric Askarel* Askarel* Pyranol H.K. Porter Helena Corporation Hevi-Duty Electric ITE Circuit Breaker Company Kuhlman Electric Askarel* Non-flammable Liquid Saf-T-Khul Maloney Electric Mitsubishi Monsanto (fluid only) Niagara Transformer Corporation Power Zone Transformer Research-Cottrell Kennechlor, Santotherm Aroclor Askarel*, EEC-18 EEC-18 Askarel* Standard Transformer Corporation Uptegraff Manufacturing Company Van Tran Electric Wagner Electric Westinghouse No-Flamol Inerteen Nepolin * Generic name for non-flammable insulating liquids. Note: There may be other manufacturers and PCB fluid trade names that are not listed. August PCB Inspection Manual
12 Chapter Four 4.2 Capacitors [ (l)] Background Capacitors regulate the flow of electric current. PCBs were the dielectric fluid used in approximately 95 percent of U.S.-produced, liquid-impregnated capacitors manufactured prior to The regulations require that all capacitors be disposed of as a PCB Capacitor except when a specific capacitor is known not to contain PCBs based on a label or nameplate, manufacturers' literature, or chemical analysis. To assist in this determination, EPA regulations required all non-pcb, large low voltage capacitors, small capacitors, and fluorescent light ballasts manufactured between July 1, 1978, and July 1, 1998, must bear a "No PCBs" label [ (g)]. There are two general types of capacitors containing PCBs: (1) capacitors built into electrical equipment, such as fluorescent lights, televisions, and small motors, which are smaller in size; and (2) capacitors used as separate units in electrical power distribution systems, which are larger in size (see Figure 4-3). The PCB regulatory program under TSCA defines three types of PCB Capacitors in 40 CFR 761.3:! A small capacitor contains less than 1.36 kg (3 pounds) of dielectric fluid.! A large high voltage capacitor contains 1.36 kg (3 pounds) or more of dielectric fluid and operates at 2,000 volts (AC or DC) or above.! A large low voltage capacitor contains 1.36 kg (3 pounds) or more of dielectric fluid and operates below 2,000 volts AC or DC. Figure 4-3. Six large high voltage capacitors. PCB Inspection Manual 4-9 August 2004
13 Chapter Four Locations The following is a list of likely locations, by economic sector, of capacitors. Within these sectors, the capacitors may be located almost anywhere. Electric Utilities! Capacitors are usually located in distribution substations. Manufacturing! Capacitors are: - Located in banks or individually. - Located in underground pump stations. - Used for power factor correction on motor control circuits and as part of the circuitry of electric induction furnaces. - Used for power correction or startups of large motors as used commonly with water pumps for large air conditioning systems or lift stations. - Used for startup of any large motor associated with manufacturing (e.g., drills, saws). Subway Systems Mines! Large capacitors are used: - In conjunction with underground transformers. - On subway cars.! Capacitors are: - Usually located within the power substation that supplies electricity to the entire mine - Located underground in skid-mounted or wheel-mounted power centers or individually - Often installed in control boxes for large electrical motors Maintenance and Repair Facilities replace rather than repair non-functioning capacitors. Short-circuiting units can rupture and leak Manufacturers and Trade Names Several companies manufactured PCB Capacitors in the United States from 1929 until Many of the manufacturers identified the PCB dielectric liquid by trade name. The following list of manufacturers and trade names is not necessarily complete and, therefore, should be used only as a guide. August PCB Inspection Manual
14 Chapter Four Table 4-3. Capacitor Manufacturers and PCB Fluid Trade Names Capacitor Manufacturer PCB Fluid Trade Name Aerovox Hyvol Axel Electronics Capacitor Specialists Cornell Dubilier Dykanol Electrical Utilities Corporation Eucarel Electromagnetic Filter Company Federal Pacific Non-flammable liquid General Electric Pyranol Jard Corporation Clorphen McGraw Edison Elemex Monsanto (fluid only) Aroclor, Capacitor 21, MCS 1489 P.R. Mallory & Company Arclor B R.F. Interonics Sangamo Electric Company Diaclor Sprague Electric Company Clorinol Tobe Deutschmann Labs Universal Manufacturing Corporation Westinghouse Askarel* Inerteen York Electronics * Generic name for non-flammable insulating liquids. PCB Inspection Manual 4-11 August 2004
15 Chapter Four 4.3 Other Electrical Equipment [ (h) and (m)] Other PCB-Contaminated Electrical Equipment includes circuit breakers, reclosers, voltage regulators, switches (including sectionalizers and motor starters), and electromagnets. The inspection guidelines are similar to those for capacitors. Figure 4-4 shows a circuit breaker system and location where PCBcontaminated oil may be found. Operating Linkage Going to Contacts 4.4 Hydraulic Systems [ (e)] Background Hydraulic systems are machines that operate by the force exerted by pressurized and confined liquid. Many steel manufacturing and die casting plants used PCBs in hydraulic systems to reduce fire hazards on machines that handled hot metals. These systems included hydraulic systems for metal dye casting equipment, trim presses, induction hardening machines, heat treating furnaces, forge furnaces, and forge presses. The PCB regulations authorize the use of hydraulic systems containing PCBs below 50 ppm. Owners drained and flushed hydraulic Hydraulic Oil Container systems in an attempt to reduce PCB contamination. However, systems may still be contaminated with residual PCBs that remained after refilling with non-pcb fluid. Hydraulic systems normally leak several times their capacity each year because the fluid is often pressurized to several thousand pounds per square inch causing the system to leak at connection joints and piston rings. August PCB Inspection Manual
16 Chapter Four Manufacturers and Trade Names The following list of hydraulic fluid trade names may not contain all trade names. PCBs have been used since 1929, and many of the early manufacturers have gone out-of-business. Table 4-4. Hydraulic Fluid Manufacturers and Trade Names Manufacturer Hydraulic Fluid Trade Names Monsanto Pydraul A-200 Pydraul 230 Pydraul A-200-B Pydraul AC* Pydraul 230-A Pydraul 280 Pydraul AC-A* Pydraul 312 Pydraul AC-28 Pydraul F-9 Pydraul F-9-A Pydraul 135 Pydraul 312-A Pydraul 540 Pydraul 540-A Pydraul 540-B Pydraul 135-A Pydraul 150 Pydraul 625 Pydraul 625-A Pydraul 150-A Turbinol 153 Santovac 1 Santovac 2 * These were reportedly used as lubricating fluids in some natural gas pipelines as well. 4.5 Other PCB Equipment Fluorescent Light Ballasts Light ballasts are the primary electric components of fluorescent light fixtures and are generally located within the fixture under a metal cover plate. The PCBs are located in the light ballasts small capacitor or in the potting material, the insulating material inside the ballast. Since 1978, EPA has required manufacturers of fluorescent light ballasts to mark ballasts that do not contain PCBs with the statement No PCBs. Inspectors should assume that light ballasts contain PCB small capacitors if they were manufactured before 1978 or do not have a No PCBs statement. Table 4-5 indicates the disposal requirements for fluorescent light ballasts. Please note that after July 1, 1998, fluorescent light ballast manufacturers are no longer required to mark fluorescent light ballasts with the statement No PCBs. PCB Inspection Manual 4-13 August 2004
17 Chapter Four Table 4-5. TSCA Disposal Requirements for Fluorescent Light Ballasts PCB Capacitor PCB Potting Material Labeling, Transportation, and Manifesting for Disposal Disposal Reference in 761 Disposal Options No PCBs label Not regulated under TSCA. N/A Not regulated under TSCA. None* < 50 ppm Not regulated under TSCA. N/A Not regulated under TSCA. Intact and nonleaking or none* > 50 ppm -Is a PCB bulk product waste. -No labeling is required. -Manifesting is required for disposal in accordance with (a); is not required under (b); may be required under (c)..50(b)(2)(ii).62(a)-(c) -TSCA incinerator** -TSCA/RCRA landfill Alternate Destruction Method. -Decontamination ( (d) storage may be required). -Coordinated approval. -State-approved landfill (leach test required). -Risk-based approval. Intact and nonleaking < 50 ppm No labeling or manifesting required..50(b)(2)(i).60(b)(2)(ii) Dispose as municipal solid waste ( 761 Subpart D options). Leaking < 50 ppm or > 50 ppm -Disposal as PCB bulk product waste. -No labeling is required. -Manifesting is required for disposal in accordance with (a); may be required under (c)..62(a) or (c) -TSCA incinerator* -TSCA/RCRA landfill Alternate Destruction Method- -Decontamination ( (d) storage may be required). -Coordinated approval. -Risk-based approval. * "None" means that the capacitor contains no PCB's or was manufactured after ** A TSCA incinerator is one approved by the Regional Administrator or by the Director of NPCD to handle TSCA waste. Source: (EPA PCB Website) Heat Transfer Systems [ (d)] Heat transfer systems use fluids of high heat capacity to remove unwanted heat or to transfer heat from one place to another within a system. They are commonly used to provide heat in chemical manufacturing where temperatures greater than that provided by steam are needed. Heat transfer systems in certain applications used PCBs as a heat transfer fluid. Heat transfer August PCB Inspection Manual
18 Chapter Four systems that contained PCB fluid were refilled with non-pcb fluid approximately 90 percent of the time. Despite this refilling, most systems contained residual PCBs. Leaks usually occur through pump motor seals. Inspectors of facilities using PCB heat transfer fluid should ensure that all systems are below the 50 ppm limit by checking records or sampling (if it is safe to sample). Inspectors should also review disposal records such as manifests for PCB-contaminated fluid drained from the systems to determine if the facility properly stored the fluids for disposal or disposed of the fluids by incineration and visually check for PCB contamination and current releases of PCBs on site due to prior spills or disposal of the PCB fluids. The following is a list of heat transfer fluid manufacturers although it may not contain all trade names. PCBs have been used since 1929, and many of the early manufacturers have gone out-of-business. Table 4-6. Heat Transfer Fluid Manufacturers and Trade Names Manufacturer Geneva Industries Heat Transfer Fluid Trade Names Monsanto FR-1 Monsanto Therminol FR-0 Therminol FR-LO Therminol FR-1 Therminol FR-2 Therminol FR Natural Gas Pipelines [ (i)] A number of gas pipeline companies used PCBs as a working fluid in their compressors between 1950 and the early 1970's. There are several sources of PCBs associated with natural gas transmission pipelines. The use of PCBs in turbine compressors leaked PCBs (Arolcors 1221, 1242 and 1248) into the transmission pipelines and contaminated the existing natural gas pipeline liquids (water and condensate). The condensate fraction consists of heavier hydrocarbons that may be ignitable, BTEX (benzene, toluene, ethyl benzene and xylenes) and naphthalenes. The PCB contamination spread to other interconnected pipeline systems. The improper disposal of PCB contaminated condensate into open pits, via spills and venting caused significant contamination at natural gas companies such as Texas Eastern and Transwestern compressor stations. The historical use of waste oils, contaminated with PCBs, to "fog" or lubricate the old pipelines and use (probably minor) of a Rockwell plug valve sealant/grease containing PCBs (Aroclor 1268) also contaminated existing natural gas pipeline condensate. The use of PCBs (Aroclors 1221, 1242, 1248 and 1254) in reciprocating air compressors and associated blowdowns resulted in onsite surface soil and wastewater drainage system PCB contamination. This use did not result in transmission pipeline PCB contamination. This occurred at Texas Eastern, Tenneco, Columbia Gas, Texas Gas and other companies. PCB Inspection Manual 4-15 August 2004
19 Chapter Four Current regulations (761.30(i)) authorize the use of PCBs in natural gas pipelines at concentrations of less than and greater than 50 ppm PCBs under certain conditions. These (761.30(i)) are the rules that now govern the PCBs that still remain in the various natural gas transmission pipelines. The old PCB/Compliance Monitoring Program (CMP) was terminated when this rule was promulgated in Additional NGP information and details of the 1981 and 1996 PCB CMP are found in Appendix G of this manual Electric Motors In the late 1960s and early 1970s, Reliance Electric for Joy Manufacturing Company manufactured electric motors that contained PCBs. Liquid-filled motors were used because they were smaller and lighter than air-cooled motors. Manufacturers chose a PCB mixture for the liquid because it was non-flammable, provided adequate lubrication, and possessed the best overall combination of electrical properties, chemical stability, and cost. Mining machine electric motors used on certain underground continuous loaders built by Joy contain PCBs as a coolant fluid in the large cutting head motors and traction motors. Previous versions of the regulations established a deadline of January 1, 1982, for phasing-out the use of these motors. The current regulations [ (c)] allow the use of PCB-containing mining equipment only under 50 ppm. Submersible well pump motors manufactured before 1979 may contain up to five ounces of PCB dielectric fluid in their capacitors. PCBs may leak out of these submersible well pump motors during normal wear-and-tear or when the pump suddenly fails due to lightening strikes or electrical failures or shorts. Appendix H contains the manufacturer s models and serial numbers of some of the submersible pump units that contain PCBs Electromagnets [ (h)] Regulations prohibit servicing, including rebuilding, of PCB electromagnets with a PCB concentration of 500 ppm or greater that requires the removal of internal components Products Containing PCBs Other products that may contain PCBs include:! Investment casting wax! Carbonless copy paper! Resins! General sealants and coatings, including windshield sealant and silo sealant! Lubricants, including bridge bearings and additives to transmission fluids! Paint, including marine paint! Electrical cable insulation! Gaskets! Roofing materials. August PCB Inspection Manual
20 Chapter Four Blank Page PCB Inspection Manual 4-17 August 2004
Revisions to the PCB Q and A Manual. (June 2014)
June 2014 Version Revisions to the PCB Q and A Manual (June 2014) About the PCB Question and Answer Manual: The PCB Q and A manual is a living document and is periodically revised and updated. The updates
Rutgers Environmental Health and Safety
Rutgers Environmental Health and Safety PCB Self-Audit (TSCA Program) Facility Name: Rutgers University, Facility Address: Facility EPA Identification Number: Date of Self-Audit Inspection: Campus/Farm/Field
Policies and Procedures Manual Waste Management Plan Policy No. 06:04:00 Page 1 of 12
Page 1 of 12 Revision Responsibility: Director of Facility Services and Safety Responsible Executive Officer: Vice President for Financial & Administrative Services Source / Reference: Tennessee Division
GRU Purchasing Material Group Codes
Title Code Trees and shrubs 10161500 Floral plants 10161600 Non flowering plants 10161800 Fertilizers and plant nutrients and herbicides 10170000 Pest control products 10190000 Minerals and ores and metals
Fact Sheet: Sources of Polychlorinated Biphenyls
Fact Sheet: Sources of Polychlorinated Biphenyls Purpose This fact sheet is intended to help Oregon Department of Environmental Quality (DEQ) project managers and City of Portland stormwater inspectors
Green Seal Best Practices Guide for Fleet Vehicle Maintenance Operations
Green Seal Best Practices Guide for Fleet Vehicle Maintenance Operations June 4, 1996 Green Seal, Inc. 1001 Connecticut Ave. NW, Ste 872 Washington, DC USA 20036-5525 (202) 872-6400 FAX (202) 872-4324
Environmental Compliance Consultation: DOE PCB Questions and Answers Part I
Environmental Compliance Consultation: DOE PCB Questions and Answers Part I Office of Environmental Policy and Guidance, RCRA/CERCLA Division DOE/EH-413-0003 (June 2000) Summary This Environmental Compliance
Pollution Prevention And Best Management Practices For Dry Cleaners Operating In Broward County
FORWARD In 1991, the Broward County Environmental Protection and Growth Management Department, who was then known as the Department of Natural Resource Protection (DNRP), initiated the development of Pollution
Newport News Shipbuilding Contractor Environmental, Health and Safety Resource Manual Waste Management
Newport News Shipbuilding Contractor Environmental, Health and Safety Resource Manual Waste Management Newport News Shipbuilding Page 1 WASTE MANAGEMENT 1. Purpose and Scope a. The purpose of this section
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
An Information Booklet Addressing PCB-Containing Materials in the Indoor Environment of Schools and Other Public Buildings
An Information Booklet Addressing PCB-Containing Materials in the Indoor Environment of Schools and Other Public Buildings Prepared by Bureau of Environmental Health Massachusetts Department of Public
Compliance Bulletin Hazardous Waste Lighting Waste reviewed/revised March 2012
Lamp Wastes Many commonly used lamps contain small amounts of mercury and other metals. Such lamps include fluorescent, compact fluorescent, high-pressure sodium, mercury vapor and metal halide lamps.
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
ATTACHMENT 12 CONTAINERS
ATTACHMENT 12 CONTAINERS Attachment 12 - Page 1 Table of Contents Table of Contents List of Tables List of Acronyms 12.1 Applicability 12.2 Description of 12.3 Reserved 12.4 Reserved 12.5 Description of
PCB Cleanups. Kurt Limesand EPA Region 7 Waste Remediation and Permitting. 5/1/13 U.S. Environmental Protection Agency 1
PCB Cleanups Kurt Limesand EPA Region 7 Waste Remediation and Permitting 5/1/13 U.S. Environmental Protection Agency 1 40 CFR Part 761 Polychlorinated Biphenyls (PCBs) Subpart D: Storage and disposal 761.61
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT
GUIDELINES FOR HANDLING WATER-DAMAGED ELECTRICAL EQUIPMENT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 1300 NORTH 17 TH STREET, SUITE 1752 ROSSLYN, VIRGINIA 22209 703 841-3200 703 841-5900 FAX WWW.NEMA.ORG
Evaluating Fire- and Heat-Damaged Electrical Equipment
Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat
PCB STORAGE. 1) 2-drum unit (4 x 2 x 4 ) 2) 4-drum unit (4 x 4 x 4 ) 3) 8-drum unit (8 x 4 x 4 ) 4) 16-drum unit (8 x 8 x 10 )
PCB STORAGE With the exception of utilities, very few PCB owners are choosing to store their PCB wastes on site. The practice of on-site PCB storage was commonplace before Swan Hills opened up in 1996
ENVIRONMENTAL HEALTH & SAFETY/RISK MANAGEMENT Contractor Management (including Sub-Contractors)
ENVIRONMENTAL HEALTH & SAFETY/RISK MANAGEMENT Contractor Management (including Sub-Contractors) Contractors have the responsibility to ensure the health and safety of their workers and that their work
Work Type Definition
Work Type Definition Page 1-6 details the work type definition. In order to become pre-qualified for this work type, please see the Work Type Submittal Requirements on pages 7-8. I. Description A. Work
RAILROAD COMMISSION OF TEXAS APPENDIX C LIST OF E&P WASTES: EXEMPT AND NONEXEMPT
RAILROAD COMMISSION OF TEXAS APPENDIX C LIST OF E&P WASTES: EXEMPT AND NONEXEMPT WASTE MINIMIZATION IN THE OIL FIELD - APPENDIX C NOTES RAILROAD COMMISSION OF TEXAS LIST OF E&P WASTES: EXEMPT AND NON EXEMPT
Facility Support Services
Facility Support Services The Precision Group has a breadth of experience delivering innovative, first class facility support service solutions to clients across the public and private sectors. Our expert
BP WIND ENERGY POLICIES AND PROCEDURES
BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials
FLORIDA HAZARDOUS WASTE MANAGEMENT REGULATIONS THAT DIFFER FROM FEDERAL REQUIREMENTS
FLORIDA HAZARDOUS WASTE MANAGEMENT REGULATIONS THAT DIFFER FROM FEDERAL REQUIREMENTS Chapter 1: Introduction General Notes Lead Agency: Florida Department of Environmental Protection (DEP) Division of
Managing Floor Drains and Flammable Traps
Managing Floor Drains and Flammable Traps Contents: Problem... 1 Solution... 2 Maintenance... 2 Waste Management Options... 2 For More Information... 4 BMP Chart... 5 This fact sheet discusses recommended
Inspections Standard Operating Procedure 5 Aboveground Storage Tanks
Aboveground Storage Tanks Aboveground Storage Tank Inspection This Standard Operating Procedure describes the steps that campus units that manage aboveground oil storage tanks (ASTs) or containers must
REGISTRATION OF INTEREST
A B C Adhesives and Sealants Advertising Air Cargo Transport Air Conditioners Air Conditioning Installation or Maintenance or Repair Services Air Filters Ambulance Services Arborist Services Architectural
Appendix N Framework Spill Prevention, Containment, and Countermeasures Plan Prepared by: Idaho Power Company 1221 W Idaho Street Boise, ID 83702
Appendix N Framework Spill Prevention, Containment, and Countermeasures Plan Prepared by: Idaho Power Company 1221 W Idaho Street Boise, ID 83702 November 2011 TABLE OF CONTENTS 1.0 PURPOSE... 1 2.0 RESPONSIBILITY
POLLUTION PREVENTION FACT SHEET: AUTOMOBILE MAINTENANCE
POLLUTION PREVENTION FACT SHEET: AUTOMOBILE MAINTENANCE Description This pollution prevention measure involves creating a program of targeted outreach and training for businesses involved in automobile
POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT. for
POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT for Michigan State University Engineering and Architectural Services Physical Plant Building, Room 101 East Lansing, Michigan 48824-1326 at Michigan
RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN PERCHLOROETHYLENE
(Adopted January 6, 1978)(Amended August 3, 1979)(Amended July 11, 1980) (Amended August 3, 1990)(Amended December 7, 1990) (Amended November 17, 2000) RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN
ATTACHMENT 1-9 CHWSF CONTAINER MANAGEMENT
1.0 INTRODUCTION ATTACHMENT 1-9 CHWSF CONTAINER MANAGEMENT 1.1 This Attachment provides information about the management of containers in U.S. Army Dugway Proving Ground s (DPG s) Container Storage Building
SUBJECT: Effective Date: Procedure Number: Contractor Environmental Management. 09/03/13 emp11 Procedures
SUBJECT: Effective Date: Procedure Number: Contractor Environmental Management 09/03/13 emp11 Procedures APPLICABILITY/ACCOUNTABILITY: Supersedes: Page Of EMS Procedure-011 1 11 Responsible Authority:
Heavy Duty Equipment Mechanic (Class Code 3743) Task List. Inspection and Diagnosis
Heavy Duty Equipment Mechanic (Class Code 3743) Task List Inspection and Diagnosis In order to verify complaints and determine malfunctions a Heavy Duty Mechanic: 1. Reads operators written trouble reports,
Petroleum Tanks at Municipal Facilities
January/February 2013 Petroleum Tanks at Municipal Facilities This document was reprinted with permission from the New York Association of Towns Talk of the Towns/Topics magazine January/February 2013
Here are some hazardous wastes commonly generated by the marina industry:
Important Note: The following text is excerpted directly from the New York State Department of Environmental Conservation s publication, Environmental Compliance, Pollution Prevention, and Self Assessment
Federal Wage System Job Grading Standard for Powered Support Systems Mechanic, 5378. Table of Contents
Federal Wage System Job Grading Standard for Powered Support Systems Mechanic, 5378 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 GRADES... 2 TITLES... 3 HELPER AND INTERMEDIATE JOBS... 3 NOTE
APPENDIX 1: 8-DIGIT SIC CODES COMPRISING THE GREEN ECONOMY
APPENDIX 1: 8-DIGIT SIC CODES COMPRISING THE GREEN ECONOMY SIC8 SIC8DESC GRSECTOR 1810103 Mats, preseeded: soil erosion, growing of Green building 8510102 Reforestation services Environmental services
EMERGENCY PETROLEUM SPILL WASTE MANAGEMENT GUIDANCE. Hazardous Materials and Waste Management Division (303) 692-3300
EMERGENCY PETROLEUM SPILL WASTE MANAGEMENT GUIDANCE Hazardous Materials and Waste Management Division (303) 692-3300 First Edition January 2014 This guidance is meant to provide general information to
ULTRA 865HD HIGH PERFORMANCE MULTI PURPOSE GREASE
ULTRA 865HD HIGH PERFORMANCE MULTI PURPOSE GREASE Contains penetrants, lubricants and greases All weather Water-resistant Penetrates like an oil, then cures to a thick, water-resistant grease Recommended
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
Winterizing Your Trailer and Storage Ideas
Winterizing Your Trailer and Storage Ideas Basically winterizing is getting the water out of the pipes and tanks so that when it gets cold enough to freeze water, your unit won't be damaged from the expanding
2006 Standard Application Processing Time. 10 months. 14 months
Air and Radiation Management Administration General Permit to Construct - without expanded public review Air Quality Permit to Construct - with expanded public review but limited public interest 11 months
Hazardous Waste Accumulation, Storage, & Labeling
Nadine Deak, Kalamazoo District Office 269-567-3592 or [email protected] Jenny Bennett, Gaylord District Office 989-705-2421 or [email protected] Hazardous Waste Accumulation, Storage, & Labeling
HAZARDOUS WASTE MANAGEMENT PROGRAM. For OTTERBEIN UNIVERSITY. Prepared by: 140 North Otterbein Avenue Westerville, Ohio 43081
HAZARDOUS WASTE MANAGEMENT PROGRAM For OTTERBEIN UNIVERSITY Prepared by: 140 North Otterbein Avenue Westerville, Ohio 43081 Otterbein University 0 TABLE OF CONTENTS 1.0 PURPOSE AND SCOPE... 1 2.0 ROLES
MBJ Environmental Programmes
MBJ Airports Limited Environmental Policy The following is MBJ Airports Limited s (MBJ) Environmental Policy for Sangster International Airport (SIA): Integrate environmental management measures with planning,
Extraction Oil and Gas, LLC. Diamond Valley Central Oil Terminal Waste Management Plan
Extraction Oil and Gas, LLC. Diamond Valley Central Oil Terminal Waste Management Plan Scope: This Extraction Oil and Gas Waste Management Plan has been prepared to provide operations personnel at the
Subject: 2005 Air Conditioning Service Guidelines
Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning
WHEN IS A PERMIT REQUIRED?
WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,
The Lamp Recycling Outreach Project
Training Module (1-hour version) for Generators and Handlers Of Fluorescent and Mercury-Containing Lamps (and Ballasts) (Training required by the Universal Waste Rule) Prepared by: The Lamp Recycling Outreach
understanding medium frequency induction melting furnace and its components
understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA [email protected] INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose
ENVIRONMENTAL QUESTIONNAIRE - REAL ESTATE SECURED LOANS
ENVIRONMENTAL QUESTIONNAIRE - REAL ESTATE SECURED LOANS Borrower: Property Known As: Property Address: City State NC Zip Code INSTRUCTIONS: For all loans, complete pages 1-3, answering all questions. If
Improper storage of fuel on construction sites will increase the risk of water pollution that may occur as a result of leaks or spills.
WQ-10 Best Management Practice (BMP) Water Quality Protection Guideline Secondary Containment Design Standards Fuel Storage on Construction Sites According to the EPA, the majority of water pollution in
JUBILEE TECHNICAL TRAINING CENTRE TAKORADI POLYTECHNIC 2015 TRAINING PROGRAMMES
JUBILEE TECHNICAL TRAINING CENTRE TAKORADI POLYTECHNIC 2015 TRAINING PROGRAMMES Main Courses Duration: 26 weeks 1. NVQ Level 2 Performing Process Operation in Replicating Environment 2. NVQ Level 2 Performing
Waste and Cost Reduction Techniques for Small Parts Cleaners
Waste and Cost Reduction Techniques for Small Parts Cleaners Edited by Ron Still Mechanical components typically need cleaning during repair and maintenance activities, and most maintenance shops use parts
PALM BEACH STATE COLLEGE PERSONAL PROTECTIVE EQUIPMENT (PPE) JOB HAZARD ASSESSMENT
PALM BEACH STATE COLLEGE PERSONAL PROTECTIVE EQUIPMENT (PPE) JOB HAZARD ASSESSMENT Department: Facilities Campus: All Task: Check/Service/Maintain/Repair/Install HVAC Equipment and Systems Job Title(s)
District of Columbia Municipal Regulations UNDERGROUND STORAGE TANKS: GENERAL PROVISIONS 5500 COMPLIANCE WITH OTHER DISTRICT LAWS
CHAPTER 55 UNDERGROUND STORAGE TANKS: GENERAL PROVISIONS Section 5500 Compliance with Other District Laws 5501 Applicability of UST Regulations 5502 Partial Applicability of UST Regulations to Particular
BECHTEL JACOBS COMPANY ORR WASTE CERTIFICATION PROGRAM DOCUMENT CONTROL SYSTEM
BECHTEL JACOBS COMPANY ORR WASTE CERTIFICATION PROGRAM DOCUMENT CONTROL SYSTEM If you print the following document, this page must be attached to the front of the document and you must fill in the information
Waste Oil Collection / Storage
ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park
DIVISION D ELECTRICITY, GAS, WATER AND WASTE SERVICES
The Electricity, Gas, Water and Waste Services Division comprises units engaged in the provision of electricity; gas through mains systems; water; drainage; and sewage services. This division also includes
Florida Department of Environmental Protection
Florida Department of Environmental Protection Background Mobile vehicle and equipment washing involves washing at a location where vehicles are based (such as a trucking company, warehouse, bus station,
Pollution Liability Exposure: Adjustments your automotive business should consider to maintain compliance
: Adjustments your automotive business should consider to maintain compliance Pollution sounds like such a dirty word. And as an automotive service business owner, employee or operator, you might be producing
NSPS Subpart OOOO: Applicability and Compliance Basics
NSPS Subpart OOOO: Applicability and Compliance Basics Kentucky Oil & Gas Association 2013 Western Kentucky Meeting September 12, 2013 Roy Rakiewicz All4 Inc. Rob Flynn Environmental Standards, Inc. www.all4inc.com
Compliance Guidance for Motor Vehicle Waste Disposal Wells in Oregon September 2015
Compliance Guidance for Motor Vehicle Waste Disposal Wells in Oregon September 2015 Underground Injection Control Program 700 NE Multnomah Street Suite 600 Portland, OR 97232 Phone: 503-229-6371 800-452-4011
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY August 2012 SECTION 2 The storage requirements in Directive 055 apply to upstream petroleum facilities, well sites, and pipelines
COMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
APPENDIX G Materials Storage and Handling Guidelines
APPENDIX G Materials Storage and Handling Guidelines 1.0 INTRODUCTION Operations at Austin-Bergstrom International Airport (ABIA) comprise several different industrial activities including aircraft, ground
The potential to adversely affect human
Purpose and Applicability of Regulations The potential to adversely affect human health and the environment is always present when using, storing, and transporting regulated materials. Consequently, numerous
CLASSIFICATION SYSTEM BY FIELD AND SUB-FIELD OF EXPERTISE SUPPLIERS REGISTRY OF GOODS AND SERVICES ENAP GROUP OF COMPANIES I. Suppliers are classified in three groups: Classification Equipments, materials
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
7. Chemical Waste Disposal Procedures
7. Chemical Waste Disposal Procedures Substances that Can and Cannot be Disposed of via Sink Drains or in Regular Solid Refuse Containers 1. It is prohibited to pour down a sink or floor drain, or place
APPENDIX O. Spill Prevention and Emergency Response Plan. G3 Terminal Vancouver Port Metro Vancouver Project Permit Application APPENDIX O
APPENDIX O Spill Prevention and Emergency Response Plan APPENDIX O G3 Terminal Vancouver Port Metro Vancouver Project Permit Application G3 TERMINAL VANCOUVER: PORT METRO VANCOUVER SPILL PREVENTION AND
TRANSFORMING THE UTILITY INDUSTRY
TRANSFORMING THE UTILITY INDUSTRY WITH POWER WHEN AND WHERE YOU NEED IT Emerald Transformer offers nationwide services covering every phase of the transformer life cycle. Focused exclusively on the needs
Indiana Department of Environmental Management. Well Disinfection
Indiana Department of Environmental Management www.in.gov/idem Well Disinfection Why Disinfect? Well disinfection can eliminate or reduce many different kinds harmful bacteria and viruses as well as harmless
TEXAS TECH UNIVERSITY HAZARDOUS WASTE PROGRAM DEPARTMENT OF ENVIRONMENTAL HEALTH AND SAFETY
TEXAS TECH UNIVERSITY HAZARDOUS WASTE PROGRAM DEPARTMENT OF ENVIRONMENTAL HEALTH AND SAFETY 1 TABLE OF CONTENTS I II III IV V VI VII INTRODUCTION CHEMICAL HAZARDOUS WASTE 1. Definition 2. Characteristics
SPILL PREVENTION AND RESPONSE PLAN TEMPLATE FOR BUSINESSES IN DAYTON S SOURCE WATER PROTECTION AREA
SPILL PREVENTION AND RESPONSE PLAN TEMPLATE FOR BUSINESSES IN DAYTON S SOURCE WATER PROTECTION AREA Regulated Substance Management: All Regulated Substances, including chemical wastes, are to be managed
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Material Safety Data Sheet
1. Product & Company Identification: Product Manufacturer: Model: Nominal capacity: LiPo-Akku Conrad Electronic SE LiPo-Akku 3.7V 130mAh 130mAh Nominal voltage: 3.7V Address: Klaus-Conrad-Strasse 1, D-92242
Cat S O SSM. Services. Understanding Your Results. Understanding Your: S O S Oil Reports S O S Oil Results S O S Coolant Reports S O S Coolant Results
Cat S O SSM Services Understanding Your Results Understanding Your: S O S Oil Reports S O S Oil Results S O S Coolant Reports S O S Coolant Results Contents Overview of S O S Oil Reports...4-5 Overview
PBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
Hazardous Waste Determination and Management Plan
Hazardous Waste Determination and Management Plan Prepared By: Triumvirate Environmental Developed: November 2014 Updated: Program Approval Associate Vice President of Public Safety & Administrative Services
Notes. Material 1. Personal Protective Equipment 2.
29CFR 1926.20(b)-Accident Reduction, 29CFR 1926.21- Safety Training & Education 29CFR 1926.20(a)-Unsafe Working Conditions 29 CFR 1910.132-138, the "Personal Protection Equipment" standard. & 20 CFR 1910.134
Wynn s Extended Care
Wynn s Extended Care Every car deserves to receive the very best care... especially yours. How Do You Keep Your Reliable Transportation Reliable? Count on Wynn s Because Wynn s has been caring for cars
How To Get A Building Permit In Florida
MIAMI-DADE COUNTY BUILDING DEPARTMENT PERMIT EXEMPTIONS Please note that the exemptions listed in this section are from Florida Building Code requirements only. Other State and County regulatory departments
Arkansas Natural Gas Severance Marketing Costs
Arkansas Natural Gas Severance Marketing Costs The following lists present various costs by category as "Allowable" or "Disallowed" as marketing costs. While listing many items, this list may not be all
Asbestos WHAT TO DO? Studies of people who were exposed to high levels of asbestos in factories and shipyards, are at increased risk of:
Asbestos WHAT TO DO? What Is Asbestos? Asbestos is mineral fiber. It can be positively identified only with a special type of microscope. There are several types of asbestos fibers. In the past, asbestos
Facilities Maintenance Standards rev 9-1-2015
Facilities Maintenance Standards rev 9-1-2015 Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will
Exhibit A - Scope of Work
Exhibit A - Scope of Work The Emergency Response and Hazardous Waste Management program responds to both emergency and non-emergency chemical spills, releases of regulated and/or hazardous materials, and
KNOWLEDGE AND EMPLOYABILITY AUTO MECHANICS GRADES 8 AND 9
KNOWLEDGE AND EMPLOYABILITY AUTO MECHANICS GRADES 8 AND 9 Knowledge and Employability junior high school occupational programs of study focus on the exploration stage of student understanding and progress.
Underground Storage Tanks
Underground Storage Tanks An Informational and Guidance Document for the University Community. Please contact Yale Environmental Health and Safety for latest Regulatory Requirements. A typical UST installation
MARSHALL UNIVERSITY HAZARDOUS WASTE DISPOSAL SECTION
MARSHALL UNIVERSITY HAZARDOUS WASTE DISPOSAL SECTION TABLE OF CONTENTS POLICY STATEMENT.2 REFERENCE PROCEDURE 3 l.0 Purpose.3 2.0 Scope 3 3.0 Definitions 4 4.0 Responsibilities 5 5.0 Procedure.7 11/16/2005
MAGB HEALTH, SAFETY AND ENVIRONMENT GROUP POLLUTION INCIDENT RESPONSE PLAN
MAGB HEALTH, SAFETY AND ENVIRONMENT GROUP POLLUTION INCIDENT RESPONSE PLAN SCOPE: This guidance sets out best practice for producing a Pollution Incident Response Plan to deal with an environmental incident