Demand response impacts on off-grid hybrid photovoltaic-diesel generator microgrids
|
|
|
- Charla Strickland
- 10 years ago
- Views:
Transcription
1 Volume 3, Issue 3, DOI: /energy Received date 29 May, Accepted date 10 August, Published date 17 August Research article Demand response impacts on off-grid hybrid photovoltaic-diesel generator microgrids Aaron St. Leger* Department of Electrical Engineering and Computer Science, United States Military Academy, West Point, NY10996, USA * Correspondence: [email protected]; Tel: Abstract: Hybrid microgrids consisting of diesel generator set(s) and converter based power sources, such as solar photovoltaic or wind sources, offer an alternative to generator based off-grid power systems. The hybrid approach has been shown to be economical in many off-grid applications and can result in reduced generator operation, fuel requirements, and maintenance. However, the intermittent nature of demand and renewable energy sources typically require energy storage, such as batteries, to properly operate the hybrid microgrid. These batteries increase the system cost, require proper operation and maintenance, and have been shown to be unreliable in case studies on hybrid microgrids. This work examines the impacts of leveraging demand response in a hybrid microgrid in lieu of energy storage. The study is performed by simulating two different hybrid diesel generator PV microgrid topologies, one with a single diesel generator and one with multiple paralleled diesel generators, for a small residential neighborhood with varying levels of demand response. Various system designs are considered and the optimal design, based on cost of energy, is presented for each level of demand response. The solar resources, performance of solar PV source, performance of diesel generators, costs of system components, maintenance, and operation are modeled and simulated at a time interval of ten minutes over a twenty-five year period for both microgrid topologies. Results are quantified through cost of energy, diesel fuel requirements, and utilization of the energy sources under varying levels of demand response. The results indicate that a moderate level of demand response can have significant positive impacts to the operation of hybrid microgrids through reduced energy cost, fuel consumption, and increased utilization of PV sources. Keywords: microgrid; demand response; solar energy; hybrid; cost of energy; off-grid
2 Introduction Diesel generator sets, which are comprised of an internal combustion engine and coupled electric generator and controller, are commonly used in microgrid applications for backup power and off-grid power in remote locations where utility interconnections are not possible. Hybrid microgrids, which add additional DC energy sources via AC coupling to the AC generator through power electronic converters, offer an attractive alternative. Examples of DC sources include fuel cells, photovoltaic (PV) cells, and wind turbines. This hybrid approach has been shown to be economical in many off-grid applications [1 6]. Reducing fuel requirements and providing an alternative to installing uneconomical distribution feeders to remote locations are key components to the economic viability of off-grid hybrid microgrids in comparison to grid-tied system. When grid-tied, hybrid sources of energy can use the grid interface to help balance demand and generation while off-grid hybrid system often require energy storage through batteries or rapid load shedding to maintain system stability. Energy storage, for example battery banks, can be coupled into the hybrid system through a power electronic converter. Energy storage through batteries provides much flexibility in operation of hybrid microgrids but typically exhibit short lifespan (< 10 years) and must be properly controlled to ensure system operation as detailed in [7]. More specifically, state of charge, depth/rate of discharge, and operational temperature are important factors that dictate the reliability and viability of battery storage systems in microgrids. Studies have shown that within 6 24 months, 50 70% of solar PV home systems are not working as expected [8]. The main failure mode in these systems lies within the battery storage system and is the result of improper system design, operation, or maintenance. As a result, it would be advantageous to reduce or eliminate the need of energy storage in hybrid microgrids. Demand response (DR) is an alternative that can help reduce the need of energy storage. The concept of DR is to alter the electric usage by user in response to system operation. In grid-tied applications this is often desirable due to economic incentives [9 11] and research has shown that coupling DR with PV energy sources can be economically viable in such applications [12,13]. In off-grid applications DR could be a viable alternative, or complimentary technology, to reduce the use of battery storage. More specifically, mismatch between supply and demand in microgrids can be overcome by effectively utilizing distributed energy resources and/or encouraging demand side management [14]. Some recent work has been developing DR techniques designed to be coupled with intermittent renewable resources for microgrid applications [ 17]. The work presented here contributes to these ongoing efforts by providing a detailed analysis of the impacts of DR as applied to an off-grid hybrid photovoltaic-diesel generator microgrid. This paper examines and quantifies the impacts of leveraging DR in a hybrid microgrid in lieu of energy storage. Two different hybrid diesel generator PV microgrid topologies for a small residential neighborhood are modeled and simulated with varying levels of demand response. Impacts of DR are quantified through cost of energy, diesel fuel requirements, and utilization of the PV source under varying levels of demand response. The next section discusses the methodology of this work to include hybrid microgrid topologies, demand/dr modeling, PV source and resource modeling, and diesel generator modeling. Additionally, the simulation method and economic analysis are discussed. Results are presented in the next section followed by discussion and conclusion.
3 Methodology This study was performed by modeling and simulating two different hybrid diesel generator-pv microgrid topologies, one with a single diesel generator and one with multiple paralleled diesel generators, for a small residential neighborhood with varying levels of demand response. Simulations were performed using HOMER Energy software [18]. Various system configurations were considered and the optimal configuration, based on cost of energy, was selected for comparison and analysis at each level of demand response. In particular, the base case was compared to the cases with DR in order to quantify the impacts of DR in these systems Hybrid Microgrid Topologies The hybrid microgrid topologies analyzed in this work are shown in Figure 1. Both systems are comprised of diesel generation, electric load, a power electronic converter, and a PV source tied to the DC bus. The primary difference is that the multiple generator topology consists of multiple generators operating in parallel. It is assumed that these generators feature automatic paralleling and synchronization similar to the Advanced Medium Mobile Power Source (AMMPS) [19]. Such capability yields efficiency improvements by turning on and off generators as they are needed and improves generator loading. The single generator topology consists of one diesel generator. These two topologies were selected for study to compare/contrast the efficiency gains of PV sources and DR incorporation between the scenarios. The design decisions for each topology consist of number or size of generators, size of power electronic converter and size of PV array. Multiple Generator Hybrid Topology Single Generator Hybrid Topology 2.2. System Modeling Figure 1. Hybrid photovoltaic-diesel generator microgrid topologies Demand and Demand Response This work focused on analyzing a microgrid as applied to a small residential neighborhood. The demand profile for this was developed based on analysis of prior work and capabilities available
4 363 within the HOMER software package to develop a realistic residential load profile. This profile was then scaled to approximate a neighborhood of 10 residential homes. Prior research has shown that residential load profiles exhibit lowest demand in the early hours of the morning, rise throughout the day with local peaks around hours six and twelve, and peak demand during the evening []. Load factors are typically very low for residential homes and approximated at 0.2 for this work. An example of this general residential load profile is shown in Figure 2. Variations from month to month, from day to day, and from time step to time step were modeled to further develop this into a more realistic representation of a small community load profile. More specifically, the data was varied ±10% day-to-day and ±% from time-step-to-time-step. Additionally, seasonal variation was incorporated. Details on the final load profile are shown in the box-and-whisker plot in Figure 3 on a month by month basis. Peak loading in the summer is representative of expected air conditioner loads during that time. The final scaled load model for this work had an average energy consumption of 0 kwh/d with a peak load of kw. The effects of demand response were simulated by allocating a percentage of this load to be eligible for DR. Power (kw) Time (hour) Figure 2. Sample hourly residential load profile. Figure 3. Monthly residential load.
5 364 Common loads that are candidates for DR, or can be deferred, include water pumps, water heaters, plug-in loads that are non-critical or have internal battery storage, and HVAC systems as discussed in [16]. The DR model used in this work allows for a designated load to be deferred in time. A generalized model for deferrable loads treats each load as a unit of energy that must be met within a certain time period with an associated load profile. For example, a water heater must maintain a certain temperature within the tank. This tank can be viewed as a storage reservoir with a capacity in kwh. Energy can be put into the tank until the maximum temperature is reached (e.g. full capacity) and the load can be deferred until the minimum temperature is reached (e.g. minimum capacity). While this is occurring, the tank is serving the end user based on a specified profile (e.g. providing hot water) which consumes energy. To add energy to the tank a specific load profile, power over time, is modeled. The model used in this work generalizes this concept as a percentage of total load that is available for DR. More specifically, this is modeled based on specifying the daily energy that can be deferred (as a percentage of total daily energy consumption), effective storage capacity of deferred load (in kwh), and the minimum/peak deferred load profile values (in kw). In simulation, the primary load is provided for at all times. The deferrable load is served within specified guidelines. The strategy used for providing energy to the deferrable load is as follows: P P P if P P P E 0 DL,min DL DL,max AC DG L, prim DL P DL 0 otherwise (1) where PDL : is the deferrable load demand in the current time step (kw) P : DL,min is the minimum deferrable load demand (kw) P : DL,max is the maximum deferrable load demand (kw) PL, prim : is the primary load demand in the current time step (kw) EDL PAC PDG : is the energy in the deferrable load tank at the end of the prior time step (kwh) : is the AC power output from the converter in the current time step (kw) : is the power rating of the diesel generator(s) (kw) In other words, the deferred load is provided energy when it is available (generation exceeds primary load demand) or if the load can be deferred no longer as the energy in the load tank has reached zero. For this work, the deferrable load available, and peak power of deferrable load, was designated as a percentage of total load. Storage capacity was set to % of deferrable load. For example, if DR was set to 10% of the load, then the base load was reduced to 180 kwh/d and kw peak while the deferrable load was kwh/d and 4. kw peak. Sensitivity analysis was performed on all the deferrable load parameters and minimal change in system performance was observed with the exception of energy available for deferment. As a result, the data presented in this paper focuses
6 365 on system performance and economics as the quantity of deferrable load increases and holds other parameters fixed Solar PV Generation Solar PV generation has two key components to the model: solar resources available and the PV system energy conversion. Solar resource estimation was obtained from the National Solar Radiation Data Base [21] based on the geographical location of the system. A clearness index and solar radiation profile for various locations are available in this database. For this work the solar resources for Denver, Colorado, were used and can be seen in Figure 4. Denver was used as the location because the solar resources are fairly good (~ 5.5 kwh/m 2 /day average) and exhibits a good location for a hybrid microgrid with PV. The HOMER software used this data and models for the PV panels and inverter to determine how much PV power is generated at every time step of the simulation. More specifically, the AC power output from the PV array/converter combination was calculated at each time step by: where P AC G P P f T T G T AC DC, STC PV 1 c c, STC conv T, STC : is the AC power output from the converter in the current time step (kw) (2) P DC, STC : is the DC power rating of the PV array under standard test conditions (kw) f PV : is the PV derating factor to account for shading, system losses, soiling, ageing, etc. (%) G T : is the average solar radiation incident on the PV array in the current time step (kw/m 2 ) GT, STC : is the average solar radiation incident on the PV array under STC (kw/m 2 ) : is the temperature coefficient of power for the PV array (%/ C) T c : is average PV cell temperature in the current time step ( C) T c, STC : is the PV cell temperature under STC ( C) conv : is the power electronic converter efficiency (%) It is assumed that a maximum power point tracking converter is used. G T was calculated based on panel orientation (latitude tilt, south facing in this work). Temperature data was imported from the surface meteorology and solar energy database [22]. Parameters for the PV panels and converter were chosen based off standard, commercially available, PV panels and converters. PV panel efficiency was 13%, nominal operating cell temperature 47 C, derating factor 80%, and temperature coefficient 0.5%/ C. The inverter efficiency was 90%.
7 366 Figure 4. Monthly average solar global horizontal irradiance data and clearness index Diesel Generation The diesel generator model was developed based on fuel data from commercially available diesel generators [23]. The generators studied in this work varied from 10 kw and, based on available data, exhibit very similar fuel/efficiency characteristics within this power range. Actual fuel consumption and efficiency can vary during operation and can also vary based on generator size, or brand/model of generator. However, the data used in this work is representative of commercially available diesel generators. The efficiency and fuel consumptions curves shown in Figures 5 and 6 respectively are approximations of diesel generator performance in the range of 10 kw. The operational range of the generators were limited between 100% loading, shown by the shaded region in the figures, to increase generator efficiency and prevent wet stacking. Efficiency (%) Output Power (kw) Figure 5. Diesel generator efficiency curve.
8 367 Fuel Consumption (L/hr) Output Power (kw) Figure 6. Diesel generator fuel curve System Simulation The systems shown in Figure 1 were constructed in HOMER and simulated for six different cases. More specifically, a base case with no DR, and five subsequent cases with DR increased by 10% each case for a maximum of 50% of the load available for DR. The time step was ten minutes and a simulation of twenty-five years was conducted for each case. For each time step an energy balance calculation is performed and flows of energy to and from each components of the system is determined. Energy production, energy consumption, diesel fuel consumption, system operating and O&M costs, etc. are calculated at each time step. Additionally, specified constraints are held during all time steps. For this work, 100% of load is served, a 10% operating reserve and % minimum loading constraints were placed on the generators, and a 0% capacity shortage constraint was set. System configurations that fail to meet these constraints were discarded as infeasible. This ensured that all loads would be met and some excess generation capacity is available at all times. Cost effectiveness of all feasible designs is compared in the simulation. The optimal solution, based on lowest cost of energy, is selected as the design choice for each case and was used to compare to other cases with different DR levels. System component costs, both capital and operation and maintenance costs, are enumerated in Table 1. These costs were estimated based on current installed and operational pricing of generators, converters, and PV panels at the time of this writing. The PV panels are expected to last the duration of the simulation time period, while the converter will need to be replaced after approximately fifteen years, and the generator after approximately,000 hours of operation. Table 1. System component costs. Component Capital Cost Operation and Maintenance Cost Diesel Generator Diesel Fuel Photovoltaic Source Power Electronic Converter $500/kW --- $3000/kW $0/kW $0.03/hr + $500/kW/000hr replacement $0.76/L $10/kW/yr $300/kW/yr replacement
9 368 The search space for system configurations included a wide range of PV and converter capacity in 5 kw increments and a wide range of diesel generator capacity in 10 kw increments. Each simulation was checked to ensure the optimal solution did not fall at the edge of the search space. The simulation results include the cost of energy (COE) in $/kwh, capital and operating costs, and diesel generator fuel consumption and hours of operation for each system configuration studied. A summary of these results are shown in Table 2 for the multiple generator base case (no DR). The optimal solution is shown at the top with a COE of $0.371/kWh in this case. A detailed analysis of energy production and consumption was also obtained and is shown in Figure 7. This case had 31% of the load supplied by the PV source and required four 10 kw diesel generators. Note that kwh/yr of excess electricity is generated. The excess generation is due to the minimum loading requirements on diesel generator sets to avoid wet stacking. More specifically, regardless of demand, a certain minimum loading of the diesel generators is required for reliability purposes. As a result, in some cases this minimum loading results in excess energy production. This excess energy can be routed into a dump load to maintain a minimum loading on the generator and/or PV generation can be curtailed to increase generator loading. A detailed analysis of energy production and consumption for the base case with a single generator is shown in Figure 8. The next section provides simulation results on DR impacts in the hybrid microgrids shown in Figure 1. Table 2. Simulation Results for multiple generator base case. PV Capacity (kw) Generator (kw) Converter (kw) COE ($) $0.371 $0.372 $0.374 $0.374 $0.375 $0.375 $0.377 $0.379 $0.382 $0.383 $0.385 $0.386 $0.388 $0.394 $0.5 $0.419 Initial Capital ($) $86,000 $101,000 $88,000 $103,000 $69,000 $84,000 $71,000 $73,000 $99,000 $54,000 $56,000 $52,000 $58,000 $67,000 $82,000 $97,000 Renewable Fraction (%) kW Gen1 Fuel (L),085 14,176,078 14,116 16,497,484 16,441 16,441 14,883 18,055 18,055 18,5 18,055 17,869 17,568 17,395 10kW Gen2 Fuel (L) kW Gen3 Fuel (L) kW Gen4 Fuel (L)
10 369 Figure 7. Energy production and consumption results for multiple generator base case. Figure 8. Energy production and consumption results for single generator base case. 3. Results The simulation results for the single generator system are shown in Tables 3 and 4. Table 3 shows the optimal system configuration in regards to PV, Converter, and generator capacity over a wide range of DR (0 50%). As more load is available for DR, the capacity of all components is reduced. This effectively reduces system cost and improves the utilization of all system resources. This can be more clearly seen from the data in Table 4. For the base case scenario, there exists much excess electricity production (43,421 kwh/yr) and only 13.5% of the consumed energy is provided for by the PV source. The COE for this base case is $0.657/kWh. Dramatic improvements are seen at
11 370 any level of DR as COE, Fuel consumption, excess electricity production all decrease and renewable energy fraction increases as compared to the base case. At modest level of % of DR load, COE has been reduced by 21.16%, fuel consumption reduced by 16.74%, and excess electricity reduced by 75.39% as shown in Table 5. Generally speaking, system performance improves as DR increases. The primary impact of incorporating DR is the reduction of generation capacity, both PV and diesel, which is possible due to better utilization of these resources. This can be seen in the large jumps in performance between 10% and % DR, and 30% and % DR as capacity changes occur for optimal configurations. Simulation results for the multiple generator system are shown in Tables 6 and 7. Table 6 shows the optimal system configuration as DR capability varies. A similar trend in reduction of diesel generator capacity is seen. PV capacity increased as DR is increased as the flexibility of operating four generators allows for better utilization of PV as compared to the single generator case. Also note that the initial starting point is much more economical in comparison to the single generator system. The data in Table 7 shows that appreciable reduction in COE and excess electricity production is achieved with DR while the renewable energy fraction and fuel consumption improvements are also seen. These results are significant but not as substantial as compared to the single generator case. The differences between the two cases are due solely to the generation architecture. At a modest level of % of DR load, COE has been reduced by 6.%, fuel consumption reduced by 6.89%, and excess electricity reduced by 57.10% as shown in Table 8. As before, the primary impacts of DR are the reduction of diesel generation capacity, better utilization of all generation resources. Table 3. Optimal system configurations for singe generator system. Percentage of Load Available for DR 0% 10% % 30% % 50% PV Capacity (kw) Converter Capacity (kw) Diesel Generator Capacity (kw) Table 4. System performance metrics for singe generator system. Percentage of Load Available for DR 0% 10% % 30% % 50% Cost of Energy Fuel Consumption Excess Electricity Production $0.657/kWh $0.653/kWh $0.518/kWh $0.499/kWh $0.397/kWh $0.383/kWh 28,601 L 28,805 L 23,813 L 22,487 L 17,087 L 17,493 L 43,421 kwh/yr 39,230 kwh/yr 14,555 kwh/yr 10,684 kwh/yr 11,169 kwh/yr 4649 kwh/yr Renewable Energy Fraction 13.5% 19.0% 31.0% 36.0% 45.4% 43.5%
12 371 Table 5. System improvement form base case for single generator system. Percentage of Load Available for DR Cost of Energy Reduction Diesel Fuel Reduction Excess Electricity Reduction 10% 0.61% 0.71% 9.65% % 21.16% 16.74% 66.48% 30% 24.05% 21.38% 75.39% % 39.57%.26% 74.28% 50% 41.70% 38.84% 89.29% Table 6. Optimal system configurations for multiple generator system. Percentage of Load Available for DR 0% 10% % 30% % 50% PV Capacity (kw) Converter Capacity (kw) Diesel Generator Capacity (kw) Table 7. System performance metrics for multiple generator system. Percentage of Load Available for DR Cost of Energy Fuel Consumption Excess Electricity Production Renewable Energy Fraction 0% $0.371/kWh 19,128L 7189 kwh/yr 31.0% 10% $0.358/kWh 18,270 L 6034 kwh/yr 33.9% % $0.348/kWh 17,810 L 3084 kwh/yr 35.6% 30% $0.341/kWh 16,241 L 6626 kwh/yr 41.1% % $0.335/kWh,887 L 5559 kwh/yr 42.4% 50% $0.3/kWh,314 L 4607 kwh/yr 43.6%
13 372 Table 8. System improvement form base case for multiple generator system. Percentage of Load Available for DR 10% % 30% % 50% Cost of Energy Reduction 3.50% 6.% 8.09% 9.70% 13.75% Diesel Fuel Reduction 4.49% 6.89%.09% 16.94% 19.94% Excess Electricity Reduction 38.46% 57.10% 7.84% 22.68% 35.92% Sensitivity analysis was performed on solar resources and diesel fuel pricing to see how these affected the impacts of DR, energy pricing, and system configuration. Average solar insolation was varied between 4.0 and 6.5 kwh/m 2 /day and diesel fuel price was varied between $0.56 and $1.26 per liter. Base case results for the single generator system are shown in Figures 9 and 10 while results for the single generator case with % DR are shown in Figures 11 and 12. Figures 9 and 11 provide data on excess electricity and COE, while Figures 10 and 12 highlight renewable energy fraction across the range of solar irradiation and diesel fuel prices simulated. The impacts of DR in terms of COE, excess electricity, and renewable energy fraction were very similar over the simulated range of diesel fuel prices and solar resources. In regards to system configuration, the diesel generator sizes remained at kw and 30 kw for the base case and % DR case respectively for all simulations. However, the PV/inverter capacities did change inversely proportional to solar insolation and directly proportional to diesel fuel price. In other words, the PV capacity can be decreased with better solar resources and increased in scenarios with higher fuel prices. In summary, these results indicate that the impact of DR will be very positive under a wide range of fuel prices and solar resource levels. Figure 9. Sensitivity analysis results showing excess electricity and COE for single generator base case.
14 373 Figure 10. Sensitivity analysis results showing renewable energy fraction for single generator base case. Figure 11. Sensitivity analysis results showing excess electricity and COE for single generator system with % DR.
15 374 Figure 12. Sensitivity analysis results showing renewable energy fraction for single generator system with % DR. 4. Discussion The analysis in this paper focused on demand response impacts in off-grid hybrid PV-diesel generator microgrids as applied to a small residential community. System topologies with a single diesel generator and multiple diesel generators with parallel operation were studied. The primary objective was to analyze the impacts of DR in the absence of energy storage (e.g. batteries). While elimination of energy storage will not be feasible in all microgrid cases, it simplifies system design and increases system operation and reliability. Additionally, it was advantageous to remove energy storage in this analysis to isolate the impacts of DR. The results shown here indicate that the DR can improve the utilization of energy sources, in particular the intermittent PV source, substantially. As a result, fast acting DR or load shedding can be a valuable tool in designing and implementing efficient hybrid microgrids. Large reductions in the cost of energy, linked to reductions in initial capital and operating costs, are observed in both topologies. The single generator system showed the most improvement as it does not exhibit the advantages of paralleling generators. As a result, aggressive demand response/load shedding schemes could be an alternative to a multiple generator system. Future studies will investigate this further and analyze the feasible limits of DR in this application. 5. Conclusion This work analyzed the impacts of demand response in an off-grid hybrid microgrid, containing diesel and photovoltaic generation, as applied to a small residential neighborhood. Prior research has shown the hybrid approach to be economical in off-grid applications and this study was performed by simulating two different hybrid diesel generator-pv microgrid topologies, one with a single diesel generator and one with multiple paralleled diesel generators, with varying levels of demand response. A detailed model of each microgrid was developed along with a cost analysis, to include initial capital and O&M costs. HOMER software was used to perform time domain simulations for each
16 375 case at ten minute intervals over a period of twenty-five years. These simulations determined the optimal system design, defined as lowest cost of energy, for each case and provide data to analyze the impacts of DR in each case. These impacts were quantified through cost of energy reduction, diesel fuel reduction, and increased utilization of the energy sources. The presented results indicate that a moderate level of demand response can have significant positive impacts to the operation of hybrid microgrids as compared to a base case without demand response. For the single generator system and % of the load available for demand response, the cost of energy is reduced by 21.16%, fuel consumption reduced by 16.74%, and excess electricity reduced by 75.39%. For the multiple generator system and % of the load available for demand response, the cost of energy has been reduced by 6.%, fuel consumption reduced by 6.89%, and excess electricity reduced by 57.10%. Sensitivity analysis showed that similar results can be expected across a wide range of solar resource levels and diesel fuel prices. Conflict of Interest All authors declare no conflicts of interest in this paper. References 1. Saito N, Niimura T, Koyanagi K, et al. (09) Trade-off analysis of autonomous microgrid sizing with PV, diesel, and battery storage. Power & Energy Society General Meeting, PES 09. IEEE, Severson B, St. Leger A (13) Feasibility Study of Photovoltaic Panels in Military Temporary Housing Structures. Green Technologies Conference, 13 IEEE: Hasan ASMM, Chowdhury SA (14) Solar diesel hybrid mini-grid design considerations: Bangladesh perspective. 3rd International Conference on the Developments in Renewable Energy Technology (ICDRET). 4. Iqbal Z, Soyumer G, Kazim W (14) Design and implementation of 59 kwp solar hybrid mini-grid in SOLAB, Ras Al Khaimah. Proceedings of the th IEEE Photovoltaic Specialist Conference (PVSC): SinCheng S, Loka P, Polsani K, et al. (14) The expansion opportunity for off-grid PV to go mainstream: Multiple case studies for village electrification and telecom power-up in India. Proceedings of the th IEEE Photovoltaic Specialist Conference (PVSC): Gogula RR () A sustainable hybrid/ off grid power generation systems suitable for a remote coastal area in Oman. Proceedings of the 8th IEEE GCC Conference and Exhibition (GCCCE): Zhixin M, Ling X, Disfani VR, et al. (14) An SOC-Based Battery Management System for Microgrids. Smart Grid, IEEE Transactions on 5: Alex Z, Clark A (14) Optimization of a Solar PV Wind Turbine Hybrid System for the High-Altitude Village of Chala in the Nepal Himalayas. HOMER Workshop, 13. Available from: 9. Weihao H, Zhe C, Bak-Jensen B (10) Optimal Load Response to Time-of-Use Power Price for Demand Side Management in Denmark. Power and Energy Engineering Conference (APPEEC), 10 Asia-Pacific: Chakrabarti B, Bullen D, Edwards C, et al. (12) Demand Response in the New Zealand
17 376 Electricity Market. Transmission and Distribution Conference and Exposition (T&D), 12 IEEE PES: Fuller JC, Schneider KP, Chassin D (11) Analysis of Residential Demand Response and double-auction markets. Power and Energy Society General Meeting, 11 IEEE: Genao C, St Leger A (12) Insight into Demand Response and Photovoltaic Source with Time of Day Pricing. Transmission and Distribution Conference and Exposition (T&D), 12 IEEE PES: St. Leger A, Sobiesk E, Farmer A, et al. (14) Demand response with photovoltaic energy source and Time-of-Use pricing. T&D Conference and Exposition, 14 IEEE PES: Pourmousavi SA, Nehrir MH (11) Demand response for smart microgrid: Initial results. Innovative Smart Grid Technologies (ISGT), 11 IEEE PES: Hakimi SM, Moghaddas-Tafreshi SM (14) Optimal Planning of a Smart Microgrid Including Demand Response and Intermittent Renewable Energy Resources. IEEE Transactions on Smart Grid 5: Smith DM, St.Leger A, Severson B () Automated demand response of thermal load with a photovoltaic source for military microgrids. Power Systems Conference (PSC), Clemson University: Morel J, Morizane Y, Obara S (14) Seasonal shifting of surplus renewable energy in a power system located in a cold region. AIMS Energy 2: HOMER Renewable Energy Software Version the HOMER Microgrid software. Available from: Power Generation, Cummins Advanced Medium Mombile Power Sources. Available from: Jardini JA, Tahan CMV, Gouvea MR, et al. (00) Daily load profiles for residential, commercial and industrial low voltage consumers.ieee Transactions on Power Delivery : National Renewable Energy Laboratory, National Solar Radiation Database. Available from: Atmospheric Science Data Center, Surface Meteorology and Solar Energy Database. Available from: Diesel Service & Supply, Approximate Diesel Fuel Consumption Chart. Available from: Aaron St. Leger, licensee AIMS Press. This is an open access article distributed under the terms of the Creative Commons Attribution License (
Hybrid Micro-Power Energy Station; Design and Optimization by Using HOMER Modeling Software
Hybrid Micro-Power Energy Station; Design and Optimization by Using HOMER Modeling Software Iyad. M. Muslih 1, Yehya Abdellatif 2 1 Department of Mechanical and Industrial Engineering, Applied Science
Design and Simulation of Micro-Power System of Renewables
Design and Simulation of Micro-Power System of Renewables Charles Kim, Ph.D. Howard University, Washington, DC USA Citation: Charles Kim, Lecture notes on Design and Simulation of Micro-Power Systems of
HOMER Software Training Guide for Renewable Energy Base Station Design. Areef Kassam Field Implementation Manager
HOMER Training Guide for Renewable Energy Base Station Design Areef Kassam Field Implementation Manager Solar Table of Contents Introduction Step Step Step Step Solar Step Step Step Step Solar Introduction
Wind-Diesel Hybrid System Options for Alaska. Steve Drouilhet National Renewable Energy Laboratory Golden, CO
Wind-Diesel Hybrid System Options for Alaska Steve Drouilhet National Renewable Energy Laboratory Golden, CO Wind-Diesel Hybrid Power Systems Basic Concept A wind-diesel hybrid system combines wind turbine(s)
Modelling and Simulation of Distributed Generation System Using HOMER Software
Modelling and Simulation of Distributed Generation System Using HOMER Software Bindu U Kansara Electrical Engineering Department Sardar Patel University SICART, Vidyanagar 388 1210, Gujarat, India [email protected]
Design of Grid Connect PV systems. Palau Workshop 8 th -12 th April
Design of Grid Connect PV systems Palau Workshop 8 th -12 th April INTRODUCTION The document provides the minimum knowledge required when designing a PV Grid connect system. The actual design criteria
MICROPOWER SYSTEM MODELING WITH HOMER
CHAPTER 15 MICROPOWER SYSTEM MODELING WITH HOMER TOM LAMBERT Mistaya Engineering Inc. PAUL GILMAN and PETER LILIENTHAL National Renewable Energy Laboratory 15.1 INTRODUCTION The HOMER Micropower Optimization
Photovoltaic Systems II EE 446/646
Photovoltaic Systems II EE 446/646 Components of a grid-connected residential PV system (net meter) The inverter contains: Ground Fault Circuit Interrupter (GFCI) MPPT and Circuitry to disconnect the PV
AC COUPLED HYBRID SYSTEMS AND MINI GRIDS
, Michael; Hermes, Matthias SMA Technologie AG Hannoversche Str. 1-5 34266 Niestetal GERMANY E-mail: [email protected] E-mail: [email protected] 1. INTRODUCTION Distributed supply based on renewable
OFF-GRID ELECTRICITY GENERATION WITH HYBRID RENEWABLE ENERGY TECHNOLOGIES IN IRAQ: AN APPLICATION OF HOMER
Diyala Journal of Engineering Sciences ISSN 1999-8716 Printed in Iraq Second Engineering Scientific Conference College of Engineering University of Diyala 16-17 December. 2015, pp. 277-286 OFF-GRID ELECTRICITY
OFF GRID HYBRID POWER PLANT Discover how to maximize the usage of the renewable energy.
OFF GRID HYBRID POWER PLANT Discover how to maximize the usage of the renewable energy. Introduction by Michele GRECA ( VP for Business Development) [email protected] Presentation by Gaetano
Solar and Wind Energy for Greenhouses. A.J. Both 1 and Tom Manning 2
Solar and Wind Energy for Greenhouses A.J. Both 1 and Tom Manning 2 1 Associate Extension Specialist 2 Project Engineer NJ Agricultural Experiment Station Rutgers University 20 Ag Extension Way New Brunswick,
DETERMINATION OF THE OPTIMUM RENEWABLE POWER GENERATING SYSTEMS FOR AN EDUCATIONAL CAMPUS IN KIRKLARELI UNIVERSITY
Electronic Journal of Vocational Colleges December/Aralık 2011 DETERMINATION OF THE OPTIMUM RENEWABLE POWER GENERATING SYSTEMS FOR AN EDUCATIONAL CAMPUS IN KIRKLARELI UNIVERSITY Cihan GOKCOL 1, Bahtiyar
POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery
POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the
HBOX SOLAR 3A SOLAR POWERED ELECTROLYSER CASE STUDY 03
HBOX SOLAR 3A SOLAR POWERED ELECTROLYSER CASE STUDY 03 Case Study 03 HBox Solar: A Solar-Powered Electrolyser Background ITM Power is a developer of hydrogen energy systems based on electrolysis. There
Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery
Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the
Financial Analysis of Solar Photovoltaic Power plant in India
Financial Analysis of Solar Photovoltaic Power plant in India M. Ganga Prasanna, S. Mahammed Sameer, G. Hemavathi Department of Management Studies MadanapalleInstitute of Technology& Science Post Box No:
Using HOMER Software, NREL s Micropower Optimization Model, to Explore the Role of Gen-sets in Small Solar Power Systems
National Renewable Energy Laboratory Innovation for Our Energy Future A national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Using HOMER Software, NREL s
Energy Systems Integration
Energy Systems Integration Dr. Martha Symko-Davies Director of Partnerships, ESI March 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy,
Optimium Planning of Hybrid Renewable Energy System Using HOMER
International Journal of Electrical and Computer Engineering (IJECE) Vol. 2, No. 1, February 2012, pp. 68~74 ISSN: 2088-8708 68 Optimium Planning of Hybrid Renewable Energy System Using HOMER J. B. Fulzele
TECHNOLOGICAL AND ECONOMIC ASSESSMENT OF PV-DIESEL HYBRID SOLUTIONS VERSUS OTHER TECHNOLOGIES
TECHNOLOGICAL AND ECONOMIC ASSESSMENT OF PV-DIESEL HYBRID SOLUTIONS VERSUS OTHER TECHNOLOGIES Alexander Schies Fraunhofer Institute for Solar Energy Systems ISE PEP Information Workshop: PV- Hybrid Systems
Irradiance. Solar Fundamentals Solar power investment decision making
Solar Fundamentals Solar power investment decision making Chilean Solar Resource Assessment Antofagasta and Santiago December 2010 Edward C. Kern, Jr., Ph.D., Inc. Global Solar Radiation Solar Power is
AC Coupling in Renewable Energy Systems
AC Coupling in enewable Energy Systems Most renewable energy systems are DC coupled Most renewable energy systems are based on DC current, yet these have certain scalability limitations. Higher currents
Control of a Hybrid Energy System
Control of a Hybrid Energy System Michael Snow, B. Eng. P. Eng. Master of Engineering Candidate Supervisors: Tariq Iqbal Neil Bose Outline Introduction Background Problem Design Methodology Research Design
Deep Dive on Microgrid Technologies
March 2015 Deep Dive on Microgrid Technologies 2 3 7 7 share: In the wake of Superstorm Sandy, a microgrid kept the lights on for more than for the more than 60,000 residents of Co-Op City in the northeastern
Centralized vs. distributed power generation in developing countries: what's smarter? Marco Raganella. September the 16 th, Rabat
Centralized vs. distributed power generation in developing countries: what's smarter? Marco Raganella September the 16 th, Rabat PV Competitiveness in Village Powers Strategic Rationale Currently off-grid
How To Use The Csi Ebpp Calculator
CSI EPBB Design Factor Calculator User Guide 1. Guide Overview This User Guide is intended to provide background on the California Solar Initiative (CSI) Expected Performance Based Buydown (EPBB) Design
Selection of Optimum Hybrid Stand Alone Systems
Selection of Optimum Hybrid Stand Alone Systems Belgin Emre TÜRKAY Electrical Engineering Department, İstanbul Technical University, Ayazağa, Turkey turkayb@ itu.edu.tr Abstract-- A development area in
Hybrid and Off grid Systems Princeton Power Systems Inverter Technology Ken McCauley and Alan Cohen Princeton Power Systems
Hybrid and Off grid Systems Princeton Power Systems Inverter Technology Ken McCauley and Alan Cohen Princeton Power Systems Core Technologies High quality, Robust Power Electronics: Grid Tied Inverter
Stand Alone PV System Sizing Worksheet (example)
Stand Alone PV System Sizing Worksheet (example) Application: Stand alone camp system 7 miles off grid Location: Baton Rouge, La Latitude: 31.53 N A. Loads A1 Inverter efficiency 85 A2 Battery Bus voltage
Abstract. Introduction
Performance Testing of Zinc-Bromine Flow Batteries for Remote Telecom Sites David M. Rose, Summer R. Ferreira; Sandia National Laboratories Albuquerque, NM (USA) 871285 Abstract Telecommunication (telecom)
Optimization of Renewable Energy Hybrid System by Minimizing Excess Capacity
Optimization of Renewable Energy Hybrid System by Minimizing Excess Capacity Juhari Ab. Razak, Kamaruzzaman Sopian, Yusoff Ali, Abstract Optimization of renewable energy hybrid system looks into the process
Certified Renewable Energy Project Developer
Certified Renewable Energy Project Developer Project planning and financing with a technology-specific focus Online training on economic indicators, support mechanisms and bankability. Focus on: Photovoltaic,
HYBRID POWER SYSTEMS for TELECOM applications
HYBRID POWER SYSTEMS HYBRID POWER SYSTEMS HYBRID POWER SYSTEM WITH AC GENSET PRAMAC has developed a new solution that allow coupling a traditional AC constant speed diesel genset with an energy storage
Solar Energy. Airports Going Green Aimee Fenlon
Solar Energy Airports Going Green Aimee Fenlon 1 Renewable vs. Non-Renewable Electrical Generation Renewables: Source Advantages Disadvantages Solar PV No CO2; Needs no Fuel Intermittent no power at night,
Additional Solar System Information and Resources
Additional Solar System Information and Resources Background information a. Roughly 400 schools in NJ already have solar systems, producing more than 91 MW, out of approximately 2500 K- 12 schools in NJ.
PERFORMANCE OF MPPT CHARGE CONTROLLERS A STATE OF THE ART ANALYSIS
PERFORMANCE OF MPPT CHARGE CONTROLLERS A STATE OF THE ART ANALYSIS Michael Müller 1, Roland Bründlinger 2, Ortwin Arz 1, Werner Miller 1, Joachim Schulz 2, Georg Lauss 2 1. STECA ELEKTRONIK GMBH, Mammostr.
Sanjeev Choudhary SunEdison Advanced Solutions
Sanjeev Choudhary SunEdison Advanced Solutions Solar Focus 2015 Solar Plus Storage Introduction to SunEdison Topics What makes a viable energy storage market opportunity? SunEdison storage application
Wind Power and District Heating
1 Wind Power and District Heating New business opportunity for CHP systems: sale of balancing services Executive summary - Both wind power and Combined Heat and Power (CHP) can reduce the consumption of
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, [email protected], Armando Altamirano, [email protected] Osama A. Mohammed, [email protected] Energy Systems
Novel simplified hourly energy flow models for photovoltaic power systems
This is the author's version of the work. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purpose or for creating new collective
A Stable DC Power Supply for Photovoltaic Systems
Int. J. of Thermal & Environmental Engineering Volume 12, No. 1 (216) 67-71 A Stable DC Power Supply for Photovoltaic Systems Hussain A. Attia*, Beza Negash Getu, and Nasser A. Hamad Department of Electrical,
Simulations of Hybrid Renewable Energy Systems and Environmental Impact for Qena Al-Gadida City
Simulations of Hybrid Renewable Energy Systems and Environmental Impact for Qena Al-Gadida City Abdelrahman Atallah Z. Saleh 1, Loai S. Nasrat 2, Barakat M. Hasaneen 3, Ibrahim A.I. Nassar 4 1 Department
Storage Battery System Using Lithium ion Batteries
Offices and schools Utilities / Renewable energy Storage Battery System Using Lithium ion Batteries Worldwide Expansion of Storage Battery System s Commercial Buildings Residential The Smart Energy System
SOLAR PV + HOT WATER: An Introduction
SOLAR PV + HOT WATER: An Introduction Myths About Solar Portland doesn t get any sun Almost all of Germany and Japan get less Solar doesn t make financial sense Solar is a great long-term investment Your
Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage
Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,
Solar Power HourSM. Solar educa on for your community.
Solar Power HourSM Solar educa on for your community. 1 Contents About. 1 Commonly Asked Questions.. 2-3 The Solar Site Assessment.. 3-4 Selecting a Solar Installer. 5-7 Certified Installers by State.
AREVA's Energy Storage Solutions
AREVA's Energy Storage Solutions January 28th and 29th, 2015 Kerstin GEMMER-BERKBILEK AREVA Karlstein / Main (Germany) January 29th, 2015 Rising share of renewables in Europe brings necessity to store
SOLAR COOLING WITH ICE STORAGE
SOLAR COOLING WITH ICE STORAGE Beth Magerman Patrick Phelan Arizona State University 95 N. College Ave Tempe, Arizona, 8581 [email protected] [email protected] ABSTRACT An investigation is undertaken of a
STEADYSUN THEnergy white paper. Energy Generation Forecasting in Solar-Diesel-Hybrid Applications
STEADYSUN THEnergy white paper Energy Generation Forecasting in Solar-Diesel-Hybrid Applications April 2016 Content 1 Introduction... 3 2 Weather forecasting for solar-diesel hybrid systems... 4 2.1 The
Solar Photovoltaic Frequently Asked Questions
Table of Contents 1. What is Solar Energy?... 2 2. What are the basic component of a Solar PV system?.2 3. What are the different types of PV systems ATL offers?...2 4. What is the difference between mono-crystalline
EVALUATING SOLAR ENERGY PLANTS TO SUPPORT INVESTMENT DECISIONS
EVALUATING SOLAR ENERGY PLANTS TO SUPPORT INVESTMENT DECISIONS Author Marie Schnitzer Director of Solar Services Published for AWS Truewind October 2009 Republished for AWS Truepower: AWS Truepower, LLC
Simple project evaluation spreadsheet model
Simple project evaluation spreadsheet model Africa Electricity Institute Practitioner Workshop 15 November 2011 -- Dakar, Senegal Chris Greacen Two very different models Used by: Excel financial model
Grid Connected Storage Various Applications Realised with Proven Technologies. Wilhelm van Butselaar Clean Energy Week 2013, Brisbane July 2013
Grid Connected Storage Various Applications Realised with Proven Technologies Wilhelm van Butselaar Clean Energy Week 2013, Brisbane July 2013 Disclaimer IMPORTANT LEGAL NOTICE This presentation does not
Photovoltaic Systems for Village Electrification in Mongolia Techno-Economics Analysis of Hybrid Systems in Rural Community Centers
The International SEC-14, Bangkok, Thailand, 24 Photovoltaic Systems for Village Electrification in Mongolia Techno-Economics Analysis of Hybrid Systems in Rural Community Centers Amarbayar Adiyabat *,
Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites
Power topic #NAPT-5516-EN Technical information from Cummins Power Generation Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites A system-level
A Discussion of PEM Fuel Cell Systems and Distributed Generation
A Discussion of PEM Fuel Cell Systems and Distributed Generation Jeffrey D. Glandt, M. Eng. Principal Engineer, Solutions Engineering May 2011 The information contained in this document is derived from
SOLAR PV-WIND HYBRID POWER GENERATION SYSTEM
SOLAR PV-WIND HYBRID POWER GENERATION SYSTEM J.Godson 1,M.Karthick 2,T.Muthukrishnan 3,M.S.Sivagamasundari 4 Final year UG students, Department of EEE,V V College of Engineering,Tisaiyanvilai, Tirunelveli,
High Fraction Hybrid Solar in Canada s North
High Fraction Hybrid Solar in Canada s North Making $ s and Sense Now! Dave H. Gerwing B.Eng., M.Sc., P. Eng. Sr. Technical Engineer Lockheed Martin Canada [email protected] www.lockheedmartin.ca/renewables
32/1/2013-14/PVSE(Part-II) Ministry of New and Renewable Energy SPV Off Grid Division
Annexure-A 32/1/2013-14/PVSE(Part-II) Ministry of New and Renewable Energy SPV Off Grid Division Scheme: Installation of 10,000 nos. of solar photovoltaic water pumping systems for irrigation purpose implemented
Running on Renewables (Lesson Plan) (Utilizing HOMER: Modeling Software for Hybrid Electric Power Systems)
Running on Renewables (Lesson Plan) (Utilizing HOMER: Modeling Software for Hybrid Electric Power Systems) Suggested Grade Level 9-12 Overview Students utilize software developed by the National Renewable
Yield Reduction due to Shading:
1x4 1x16 10 x CBC Energy A/S x Danfoss Solar Inverters CBC-40W Poly 40 W TLX 1,5k 5 ; 1x11 3x4 0 1,5kW 1536 x CBC Energy A/S 1 x Power-One CBC-40W Poly 40 W TRIO-7,6-TL-OUTD 30 ; 4x14 0 7,6kW Location:
Implementation of the Movable Photovoltaic Array to Increase Output Power of the Solar Cells
Implementation of the Movable Photovoltaic Array to Increase Output Power of the Solar Cells Hassan Moghbelli *, Robert Vartanian ** * Texas A&M University, Dept. of Mathematics **Iranian Solar Energy
Preparatory Paper on Focal Areas to Support a Sustainable Energy System in the Electricity Sector
Preparatory Paper on Focal Areas to Support a Sustainable Energy System in the Electricity Sector C. Agert, Th. Vogt EWE Research Centre NEXT ENERGY, Oldenburg, Germany corresponding author: [email protected]
ALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM 87123 (505) 856-1010 voice & fax NM License 21880 www.allstarelec.
ALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM 87123 (505) 856-1010 voice & fax NM License 21880 www.allstarelec.com On-Site Power System Specialists: Photovoltaics, Wind Turbine
Energy Storage Systems. New solutions for a new energy environment
Energy Storage Systems New solutions for a new energy environment Facilitating the integration of renewable energy The increase in the quantity of electricity produced by renewable sources is creating
Off-grid solar and backup power installations
Off-grid solar and backup power installations A World of Power Problems... Residential Backup Power Grid-Interactive 3-Phase Commercial Buildings with Backup Power Grid-Interactive Residential with Backup
3.0 Results and Discussions
Estimating the cost of electrification technology options to aid electricity access scale up: The case of Ghana F. Kemausuor * 1, I. Adu-Poku 1, E. Adkins 2, A. Brew-Hammond 1 1.0 Introduction 1 The Energy
CHAPTER 7 PERFORMANCE ANALYSIS OF HYBRID RENEWABLE ENERGY SYSTEMS
Chapter 7Performance Analysis of Hybrid Renewable Energy Systems 21 CHAPTER 7 PERFORMANCE ANALYSIS OF HYBRID RENEWABLE ENERGY SYSTEMS 7.1 Hybrid Renewable Energy System Vs Single Renewable Energy System
Half the cost Half the carbon
Half the cost Half the carbon the world s most efficient micro-chp What is BlueGEN? The most efficient small-scale electricity generator BlueGEN uses natural gas from the grid to generate electricity within
The business model of MICRO POWER ECONOMY DIRECTORY. INENSUS GmbH 2011. The business model
INENSUS GmbH TITEL 2011 DIRECTORY 01 The business model of 01 The business model of Micro Power Economy is a strategic tool to establish a market for economically and ecologically viable electrification
Yukon Government Solar Energy Pilot: Performance Monitoring Yukon Government s Energy Solutions Centre. February 2014
Yukon Government Solar Energy Pilot: Performance Monitoring Yukon Government s Energy Solutions Centre February 2014 Contents 1. Project Overview... 3 2. System Specifications... 3 2.1. Yukon Government
The energy self-sufficient family home of the future
The energy self-sufficient family home of the future Fluctuating energy levels, as is often the case with power obtained through photovoltaics (PV), result in only a partial correlation between generation
Understand Hybrid Generator Battery Systems
Understand Hybrid Generator Battery Systems For off-grid applications powered by diesel generators, move to cyclic operation to save costs Telecommunications operators in Africa, India and other developing
GUJARAT TECHNOLOGICAL UNIVERSITY
GUJARAT TECHNOLOGICAL UNIVERSITY ELECTRICAL & ELECTRONICS ENGINEERING (08) & ELECTRICAL ENGINEERING (09) ELECTRICAL POWER GENERATION SUBJECT CODE: 2140908 B.E. 4 th SEMESTER Type of Course: Engineering
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
NOTICE OF INTENT Department of Revenue Policy Services Division. Income Tax Credits for Wind or Solar Energy Systems (LAC: 61:I.
NOTICE OF INTENT Department of Revenue Policy Services Division Income Tax Credits for Wind or Solar Energy Systems (LAC: 61:I.1907) Under the authority of R.S. 47:287.785, R.S. 47:295, R.S. 47:1511, and
Auburn University s Solar Photovoltaic Array Tilt Angle and Tracking Performance Experiment
Auburn University s Solar Photovoltaic Array Tilt Angle and Tracking Performance Experiment Julie A. Rodiek 1, Steve R. Best 2, and Casey Still 3 Space Research Institute, Auburn University, AL, 36849,
Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems
Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems This Agreement is made and entered into this day of, 20, ( Effective Date ) by and between the Orlando Utilities Commission
Power Management of Cell Sites
International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar
Advanced Electricity Storage Technologies Program. Smart Energy Storage (Trading as Ecoult) Final Public Report
Advanced Electricity Storage Technologies Program Smart Energy Storage (Trading as Ecoult) Final Public Report Introduction Ecoult, working with CSIRO as its principal subcontractor, was provided $1,825,440
Design of a Photovoltaic Data Monitoring System and Performance Analysis of the 56 kw the Murdoch University Library Photovoltaic System
School of Engineering and Information Technology ENG460 Engineering Thesis Design of a Photovoltaic Data Monitoring System and Performance Analysis of the 56 kw the Murdoch University Library Photovoltaic
System Modelling and Online Optimal Management of MicroGrid with Battery Storage
1 System Modelling and Online Optimal Management of MicroGrid with Battery Storage Faisal A. Mohamed, Heikki N. Koivo Control Engineering Lab, Helsinki University of Technology, P.O. Box 5500, FIN-0015
Founded 1900, 8 Nobel Prize Winners Premiere Centre for Science & Engineering
Founded 1900, 8 Nobel Prize Winners Premiere Centre for Science & Engineering Liquid Air Energy Storage a new energy vector and means of large-scale energy storage? Professor Richard A Williams OBE FREng
Corona Department of Water & Power (DWP) Solar Partnership Program Guidelines and Application
Corona Department of Water & Power (DWP) Solar Partnership Program Guidelines and Application DWP s new Solar Partnership Program is available to help offset your investment in a PV system and get you
SOLAR TECHNOLOGY CHRIS PRICE TECHNICAL SERVICES OFFICER BIMOSE TRIBAL COUNCIL
SOLAR TECHNOLOGY CHRIS PRICE TECHNICAL SERVICES OFFICER BIMOSE TRIBAL COUNCIL SOLAR TECHNOLOGY Photovoltaics Funding Options Solar Thermal Photovoltaics 1. What are they and how do they work? 2. The Solar
SIRFN Capability Summary National Renewable Energy Laboratory, Golden, CO, USA
SIRFN Capability Summary National Renewable Energy Laboratory, Golden, CO, USA Introduction The National Renewable Energy Laboratory (NREL) is the U.S. Department of Energy s primary national laboratory
Solar Powered Smart Irrigation System
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 4 (2014), pp. 341-346 Research India Publications http://www.ripublication.com/aeee.htm Solar Powered Smart Irrigation System
Performance Assessment of 100 kw Solar Power Plant Installed at Mar Baselios College of Engineering and Technology
Performance Assessment of 100 kw Solar Power Plant Installed at Mar Baselios College of Engineering and Technology Prakash Thomas Francis, Aida Anna Oommen, Abhijith A.A, Ruby Rajan and Varun S. Muraleedharan
REDUCING UNCERTAINTY IN SOLAR ENERGY ESTIMATES
REDUCING UNCERTAINTY IN SOLAR ENERGY ESTIMATES Mitigating Energy Risk through On-Site Monitoring Marie Schnitzer, Vice President of Consulting Services Christopher Thuman, Senior Meteorologist Peter Johnson,
Glossary of Terms Avoided Cost - Backfeed - Backup Generator - Backup Power - Base Rate or Fixed Charge Baseload Generation (Baseload Plant) -
Glossary of Terms Avoided Cost - The incremental cost Flint Energies would pay for the next kilowatt-hour of power in the open marketplace for energy. Flint Energies Board of Directors sets this Avoided
CERTS Microgrid Research and Lessons Learned
CERTS Microgrid Research and Lessons Learned Advanced Grid Technologies Workshop Microgrid Controls and Management Systems July 9, 2015 Bob Lasseter University of Wisconsin Madison Power System of the
Evaluation of the Solar Hybrid System for Rural Schools in Sabah, Malaysia
Evaluation of the Solar Hybrid System for Rural Schools in Sabah, Malaysia Abdul Muhaimin Mahmud Public Works Department of Malaysia, Kuala Lumpur, Malaysia. Tel: +603 92354399, E-mail: [email protected]
Energy Management in the Greek Islands
21, rue d Artois, F-75008 PARIS C6-303 CIGRE 2012 http : //www.cigre.org Energy Management in the Greek Islands Nikos HATZIARGYRIOU 1,2 Stavros PAPATHANASIOU 2,Isidoros VITELLAS 1, Stavros MAKRINIKAS 1,
Wind and Solar Renewable Energy Applications
Energy Tax Credits Wind and Solar Renewable Energy Applications AN ARRAY OF FEDERAL AND STATE TAX CREDITS have been structured to spur development of both established and emerging renewable energy sources.
EFFICIENT EAST-WEST ORIENTATED PV SYSTEMS WITH ONE MPP TRACKER
EFFICIENT EAST-WEST ORIENTATED PV SYSTEMS WITH ONE MPP TRACKER A willingness to install east-west orientated photovoltaic (PV) systems has lacked in the past. Nowadays, however, interest in installing