ENGINEER S LIST OF APPROVED ITEMS POTABLE WATER SYSTEM
|
|
|
- Maud Jordan
- 10 years ago
- Views:
Transcription
1 ENGINEER S LIST OF APPROVED ITEMS POTABLE WATER SYSTEM General 1. All products must be NSF 61 approved for potable water service 2. All products with brass or bronze must be lead free 3. Advanced written approval from the City Engineer is required to use products. Page 1
2 Standard 857 Fire Hydrant and Lateral / Fire Hydrant Location 1. Fire Hydrant a. Use: an active fire protection measure. All areas i. Maximum distance from fire hydrant to all sides of structure: 1. Commercial: 450 feet (300 foot supply, 150 foot hose) 2. Residential: 650 feet (500 foot supply, 150 foot hose) ii. Color: 1. Body: Cotati Green to match existing City fire hydrants. 2. Top/Nozzle Caps: Reflective paint color to match NFPA 291 designation, as follows: a. Light Blue: 1,500 gpm or greater (Class AA) b. Green: 1,000 1,499 gpm (Class A) c. Orange: gpm (Class B) d. Red: Less than 500 gpm (Class C) iii. Testing: All hydrants shall be flow tested in a manner acceptable to the City, including collection of static and residual system pressures. CLOW F75 CLOW F76 Residential (one 4½-inch and one 2½-inch outlets) Commercial (one 4½-inch and two 2½-inch outlets) Page 2
3 Standard 863 3/4 & 1 Water Service For 5/8 x 3/4 & 1 Meters 2. Tracing Wire d. Use: to assist in locating pipes and service lines after they have been buried in the ground. e. Specifications iv. TWHN solid core v. Blue vi. Insulated copper wire #14 vii. Fasten to pipe viii. UL listed, CSA Certified f. Approved Products Pro-Trace 3. Tracing Wire Service Splice a. Use: Splicing the copper service tracer wire into the water main copper tracer wire b. Split Nut Specifications i. High strength bronze alloy split nut with copper pressure bar ii. Sized to accommodate splice of two 14 AWG wires iii. UL listed, CSA Certified c. Splice Protector Specifications i. Clamshell-like outer plastic closure to encapsulate the splice ii. UL Approved iii. Specifically designed for electrical applications up to 600 volts or equivalent by providing a permanent water tight seal. d. Approved Products Split Nut Grainger 6CYZ5 e. Approved Products Splice Protector UraSeal ES200SV 4. Water Service Line a. Use: Customer water service line from water main HPDE Only i. Blue ii. AWWA C901 / ASTM D2737 iii. PE4710 High Density Polyethylene (HDPE) iv. SDR 9 (250 psi pressure class) Page 3
4 Standard 863 3/4 & 1 Water Service For 5/8 x 3/4 & 1 Meters v. Copper Tube Size (CTS) HPDE Only Performance Pipe Driscoplex 5100 Ultraline Centennial CenCore 5. Water Service Insert (HDPE Service Only) a. Use: Insert for connections on both ends of HDPE water service lines i. Stainless Steel A.Y. McDonald 6133T 6. Tapping Service Saddle a. Use: Tap for customer water service line i. Female Iron Pipe Thread (FIPT) ii. 200 psi working pressure iii. Sealed EPDM O-ring outlet iv. Brass or bronze body / flattened silicon bronze double straps (ACP/DIP ONLY) v. Brass or bronze body / 304L stainless steel double straps (C900 ONLY) ACP/DIP Only Mueller BR2B Jones J-979 Ford 202B d. Approved Products C-900 Only Mueller BR2S Jones J-969 Ford 202BSD 7. Ball Corporation Valves f. Use: Customer water service line shut off at water main g. Specifications i. Male Iron Pipe Thread (MIPT) for Service Saddle ii. Copper Tube Size (CTS) Compression Connection for new water services Page 4
5 Standard 863 3/4 & 1 Water Service For 5/8 x 3/4 & 1 Meters iii. Copper Tube Size (CTS) Pack Joint Connection for retrofit water services iv. 100 psi working pressure v. ANSI/AWWA C800 vi. Brass alloy body (ASTM B62) h. Approved Products Mueller B Angle Meter Ball Valves g. Use: Customer water service shut off on both sides of water meter h. Specifications i. Copper Tube Size (CTS) Compression Connection for water service ii. Female Iron Pipe Thread (FIPT) for house side connection iii. Meter swivel nut for meter connections iv. 100 psi working pressure v. ANSI/AWWA C800 vi. Brass alloy body (ASTM B62) i. Approved Products Street Side Mueller B Jones J-1963WSG a. Approved Products House Side Mueller B Jones J-1966W 9. Meter Boxes and Covers a. Use: Vault to access angle meter stops and customer meters i. High density reinforced concrete box ii. Non-settling shoulders iii. Reinforce concrete lid with Probe Hole (Non-Traffic Only) iv. Polypropylene face: ASTM D1693 v. Steel Checker Plate Cover, 6-inch round self-closing reading lid (Traffic Only) Boxes (3/4 Meter) Old Castle Precast B12Box (Christy) Page 5
6 Standard 863 3/4 & 1 Water Service For 5/8 x 3/4 & 1 Meters d. Approved Products Boxes (1 Meter) Old Castle Precast B16Box (Christy) e. Approved Products Lids (3/4 Meter) Old Castle Precast B12P / B12-61G (Traffic) f. Approved Products Lids (1 Meter) Old Castle Precast N16RP / B16-61G (Traffic) Page 6
7 Standard Dual Meter Service 1. U Branch Connection a. Use: Yoke to split service at property line for 2 customer meters i. Copper Tube Size (CTS) Compression Connection for water service ii. Male Iron Pipe Thread (MIPT) for meter connection iii. Bronze / Brass Mueller H Angle Meter Ball Valves a. See Standard 863, House Side Page 7
8 Standard 883 Air And Vacuum / Air Release Valve 1. Air/Vacuum Relief Valve a. Use: Release air, break vacuum on water main line i. Solid cylindrical HDPE floats ii. Barrel: Stainless Steel AISI 304L iii. Top/Bottom Flange: Stainless Steel AISI 304 iv. National Pipe Thread (NPT) screwed inlet/outlet v. Minimum pressure rating: 276 psi Vent-o-mat RBX Angle Ball Valve Inlet to Air/Vacuum Relief Valve a. Use: Shut off for air/vacuum relief valve at utility vault i. Copper Tube Size (CTS) Compression Connection for water service ii. Female Iron Pipe Thread (FIPT) for air/vaccum valve iii. 100 psi working pressure iv. ANSI/AWWA C800 v. Brass alloy body (ASTM B62) Mueller B Tracing Wire Service a. See Engineering approved Standard 863 for details. 4. Tracing Wire Service Splice b. See Engineering approved Standard 863 for details. 5. Water Service Line a. See Engineering approved Standard 863 for details. 6. Water Service Insert (HDPE Service Only) b. See Engineering approved Standard 863 for details. 7. Ball Corporation Valves Mainline shutoff a. See Engineering approved Standard 863 for details. Page 8
9 ENGINEER S LIST OF APPROVED ITEMS SANITARY SEWER SYSTEM General 1. Advanced written approval from the City Engineer is required to use products. Page 9
10 Standard 500 Standard Precast Concrete Manhole For Sanitary Sewer 1. Cover and Frame a. Use: Secure access for sanitary sewer mainhole i. Ductile iron, ASTM A536 ii. Hinged Lid with Sanitary Sewer Badge iii. AASHTO H-20 load rated iv. Elastomeric seating gasket v. Slip resistant, ASTM C1028 vi. Hinge infiltration plug, closed pick holes CertainTeed Pamrex 2. Grade Rings a. Use: Adjust manhole frame to street grade i. Injection molded HDPE, ASTM D4976 ii. AASHTO H-20 load rated LadTech, Inc LadTech Adjusting Rings 3. Expanding Adhesive Sealant a. Use: Water sealant between cone/grade ring and grade ring/manhole frame i. Single component, closed cell, hydrophobic polyurethane ii. Water activated iii. Expanding foam to fill voids iv. Designed for sanitary sewer environment Seal Guard, Inc XSeal 4. Adhesive Tape Wrap a. Use: Water sealant for horizontal concrete and HDPE grade ring joints i. Pre-formed, cold-applied, self adhesive pipe wrap Page 10
11 Standard 500 Standard Precast Concrete Manhole For Sanitary Sewer ii. Elastomer and resin bonded to a woven highly puncture-resistant polymer iii. Adhesive impregnated with an integrated primer iv. Thickness: 50 mil ± 2 mils v. Conforms to ASTM C209 Tapecoat Chase Tapecoat M50 RC 5. Manhole Base, Barrel, and Cone Structure a. Use: Manhole structural components to access sanitary sewer system i. Reinforced precast concrete, ASTM C478 ii. Conforms to type V cement, ASTM C150 iii. Cast in pipe to manhole connectors iv. Match incoming pipe material v. Loading: AASHTO H-20, soil, groundwater. Old Castle Precast Jensen Precast Cook Concrete Products Pirahana Pipe 6. Manhole Interior Coating a. Use: Protective coating to reduce groundwater infiltration and corrosion i. Concrete coating for sanitary sewer environment XYPEX BASF XYPEX Concentrate Tegraproof 7. Pipe to Manhole Connectors a. Use: Connection for sanitary sewer pipe to manhole i. Flexible watertight connector, ASTM C923 ii. Integrally cast in manhole base or barrel, as applicable iii. Nitrile or equivalent if groundwater contamination Page 11
12 Standard 500 Standard Precast Concrete Manhole For Sanitary Sewer A-Lok Products A-Lok X-Cel Compression Connector 8. Manhole Joint Sealing Compound a. Use: Apply two continuous rings at manhole horizontal joints to seal for water i. Low permeability water sealant for horizontal joints ii. Conform to ASTM C990 iii. Designed for sanitary sewer environment iv. Pre-formed, cold applied, adhesive rope-like butyl rubber gasket Henry Company RU 106 RUBR-NEK LTM Hamilton Kent Kent Seal No Manhole Interior Patch Material a. Use: Repair interior, horizontal joints, interior lifting rings vi. Non-shrink vii. Non-metallic viii. Designed for sanitary sewer environment XYPEX Sika Corp Xypex patch and plug SIKA Set Mortar 10. Transition Couplings a. Use: Slip coupling to protect sewer pipe material transitions from differential settlement at manholes i. 304 Stainless steel hardware ii. Nitrile or equivalent if groundwater contamination iii. Designed for sanitary sewer environment Romac 501 Page 12
13 Standard 500 Standard Precast Concrete Manhole For Sanitary Sewer Page 13
08003-1 WATER SERVICE 2
08003_Mar08_2011.pdf Page 1 of 7 INDEX Page 08003-1 WATER SERVICE 2 1.1 Pipe 2 1.1.1 Copper 2 1.1.2 Polyethylene 2 1.2 Valves and Fittings 2 1.2.1 Main Stops 3 1.2.2 Curb Stops 3 1.2.3 Curb Box 3 1.2.4
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials
SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.
SUBDRAINS AND FOOTING DRAIN COLLECTORS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Subdrains B. Subdrain Cleanouts and Outlets C. Footing Drain Collectors D. Storm Sewer Service and Connections 1.02 DESCRIPTION
EXHIBIT "A. Technical Specifications for Water and Sewer Service Lines
EXHIBIT "A Technical Specifications for Water and Sewer Service Lines Water and Sewer Line Bedding and Backfill: Drawings show cross-section of trench, pipe laid on top of 6" min. bedding material, bedding
Section 3510: Reclaimed water Pipes, Valves, and Appurtenances February 11, 2011
STANDARDS AND CONSTRUCTION MANUAL : Reclaimed water Pipes, Valves, and Appurtenances February 11, 2011 PART 1 - GENERAL 1.01 SCOPE OF WORK A. These specifications cover the pipes, fittings, and appurtenances
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
Chapter 6 Material Specifications
Chapter 6 Material Specifications Chapter 6 Material Specifications Materials incorporated in the finished work and used during construction shall be according to the standards and specifications specified
SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE
SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE PART 1: GENERAL 1.01 SECTION INCLUDES PVC pressure pipe and fabricated fittings in nominal sizes 4-inches through 12-inches with cast iron pipe equivalent
INDEX. Sec. No. Items Page Nos.
INDEX Sec. No. Items Page Nos. 1. Types of Pipe............... MSSP- 2 2. Concrete Pipe............... MSSP- 2 thru MSSP-3 3. ABS and PVC Truss Pipe............... MSSP- 3 4. ABS and PVC Solid Wall Pipe...............
Standard Specifications for Installation and Repairs of Water and Sewer Service Lines
Standard Specifications for Installation and Repairs of Water and Sewer Service Lines Effective December 1, 2013 Approved /S/ Kyle Mathis Kyle Mathis City Engineer /S/ Robert Glenn Robert Glenn Water/Wastewater
Mueller. Pipe Repair Products. Saddles Tapping Sleeves Pipe Repair Clamps A complete selection for all types of pipe... all from a single source.
Mueller Pipe Repair Products Saddles Tapping Sleeves Pipe Repair Clamps A complete selection for all types of pipe... all from a single source. SERVICE SADDLES Mueller service saddles, available in bronze,
SECTION 15 AIR RELEASE VALVE ASSEMBLIES. 15-1 General
SECTION 15 AIR RELEASE VALVE ASSEMBLIES 15-1.01 Scope 15-1 General This section describes the requirements for furnishing and installing Air Release Valve Assemblies of the size and type shown on the plans,
MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water
MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water 105 Decker Court, Suite 825, Irving, TX 75062 P: 469-499-1044 F: 469-499-1063 www.plasticpipe.org HDPE
3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.
The following shall serve as the minimum requirements for contractors performing work in relation to the Authority s potable water and sanitary sewer system(s), appurtenances and service connections. General:
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS PART 1: GENERAL 1.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of AW facilities. Closely coordinate construction work
SECTION 15064 PVC PRESSURE PIPE AWWA C900
SECTION 15064 PVC PRESSURE PIPE (AWWA C900) PART 1 GENERAL 1.01 DESCRIPTION This section includes materials, installation, and testing of polyvinyl chloride (PVC) pressure pipe conforming to AWWA C900.
SECTION 33 12 19 FIRE HYDRANTS
SECTION 33 12 19 FIRE HYDRANTS PART 1: GENERAL 1.01 SCOPE A. Fire hydrants. B. Adjustment of fire hydrants and gate valves. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33 00 - Submittals.
September 2012 Brunswick County Engineering Department Revision 1.0. Technical Specification 020.01 GRAVITY SANITARY SEWER SYSTEM
1.0 General Technical Specification 020.01 GRAVITY SANITARY SEWER SYSTEM a) It is the intent of this specification to ensure that all gravity sewer system infrastructure constructed within the service
Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).
Fittings for CO 2 Pipe Threads Pipe thread references quoted in this catalogue conform with the requirements specified in the latest issue and amendments of the following ISO Standards: ISO 7-1 (BS21)
DIVISION 4300 STORM DRAINAGE
DIVISION 4300 STORM DRAINAGE SECTION 4305 STORM SEWER PART 1 - GENERAL 1.01 SCOPE This section covers the construction of storm sewers for the collection and transport of stormwater runoff. 1.02 REFERENCES
Pipe Repair Products A complete selection for all types of pipe
Pipe Repair Products A complete selection for all types of pipe Mueller Service Saddles Manufactured and tested in accordance with ANSI/AWWA C800 & NSF 61 certified. Mueller service saddles, available
STANDARD SPECIFICATION SECTION 15292 POLYVINYL CHLORIDE (PVC) PRESSURE PIPE (AWWA C900)
STANDARD SPECIFICATION SECTION 15292 POLYVINYL CHLORIDE (PVC) PRESSURE PIPE (AWWA C900) PART 1 - GENERAL 1.01 DESCRIPTION This section includes materials, installation, and testing of PVC pressure pipe
SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES
SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with
505.3.6 For a building with a crawl space, see Figure 10. 505-1
505 WATER SERVICE INSTALLATION 505.1 DEFINITION A service line is comprised of the piping and related appurtenances including the connection installed from the Des Moines Water Works water main to the
DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES 33 00 00 SITE UTILITIES
SECTION INCLUDES Domestic Water Fire Water Service Water Well Sanitary Sewer Storm Drains Foundation Drainage RELATED SECTIONS 03 30 00 Concrete 21 00 00 Fire Suppression - Sprinklers 22 00 00 Plumbing
32-02.05 Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.
SECTION 32: SANITARY SEWER INSTALLATION 32-01 SCOPE. The Work shall consist of furnishing and installing sewer mains, manholes, laterals, cleanout fittings and appurtenances; and testing, flushing and
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. Furnish and install all storm drains, including manholes, inlets, service lines and other appurtenant
SECTION 02401 - SANITARY SEWER PIPE
PART 1 - GENERAL 1.1 DESCRIPTION A. The WORK under this Section includes providing all labor, materials, tools and equipment necessary for furnishing and installing sanitary sewer pipe, in accordance with
SECTION 02110 - ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL
SECTION 02110 - ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL PART 1 - GENERAL 1.1 WORK INCLUDED IN THIS SECTION A. The WORK of this Section includes the repair, demolition, and disposal of asbestos
MATERIAL SPECIFICATION MANUAL
MATERIAL SPECIFICATION MANUAL Created Date: 01/25/05 (JJS) Last Revised Date: 11/29/10 (JJS) When working with Pinellas County (EES), suppliers and contractors shall actively follow EES's published material
REFER TO SPECIFICATIONS AND STANDARD PLANS FOR DETAILED WATER METER, METER VAULT, AND SERVICE LINE REQUIREMENTS
GENERAL REQUIREMENTS METER, METER VAULT, AND SERVICE LINE REFER TO SPECIFICATIONS AND STANDARD PLANS FOR DETAILED METER, METER VAULT, AND SERVICE LINE REQUIREMENTS METER & METER VAULT: 1. METER AND RADIOREAD
Style 07 Zero Flex Rigid Coupling. Style 75 Flexible Coupling. Style 77 Flexible Coupling 11. Description
Style 07 Zero Flex Rigid Coupling The unique angled pad design adjusts to standard pipe tolerances to positively clamp the pipe to resist flexural and torsional loads. Working pressures are based on standard
SECTION 15105 DUCTILE IRON PIPE AND FITTINGS
SECTION 15105 DUCTILE IRON PIPE AND FITTINGS PART 1 GENERAL.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of Owner facilities. Closely coordinate construction work and connections
American- Darling 5¼" B-84-B-5.
-5 Sealed Lubrication Chamber Seals operating threads from water and debris which greatly reduces routine maintenance. Top Travel Stop Nut Helps prevent stem buckling and damage to bronze components which
GAS DISTRIBUTION PRODUCTS STEEL SERVICE TEES
GAS DISTRIBUTION PRODUCTS STEEL SERVICE TEES CONTINENTAL INDUSTRIES ABOUT US THE ULTIMATE CONNECTION Our Company Continental Industries, headquartered in Tulsa, Oklahoma, was formed in 1958 and is today
PART C MATERIAL SPECIFICATIONS
REGION OF WATERLOO AND AREA MUNICIPALITIES DESIGN GUIDELINES AND SUPPLEMENTAL SPECIFICATIONS FOR MUNICIPAL SERVICES PART C TABLE OF CONTENTS C.1 GENERAL... 1 C.1.1 Ontario Provincial Standards... 1 C.1.2
SANITARY SEWER SPECIFICATIONS
SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,
SECTION 15056 DUCTILE-IRON PIPE AND FITTINGS
SECTION 15056 PART 1 GENERAL 1.01 DESCRIPTION This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems. A written request to use Ductile
INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
8D.1 BALL ANGLE METER VALVES - 3/4" & 1" P-24258 B-24258 E-24259 B-24259 B-24266 B-24267
BALL ANGLE METER VALVES - 3/4" & " 8D. B-24258 MUELLER 300 Ball Angle Meter Valve MUELLER 0 Conductive Compression Connection for CTS O.D.* tubing x meter swivel nut** adding -3 suffix to catalog number.
Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer
Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer The user may choose to adopt part or all of this Model Specification; however, the user should ensure that all parts
SECTION 03400 PRECAST CONCRETE STRUCTURES
PART 1 GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, and equipment required to install precast concrete manholes, sanitary leaching rings, pump station, valve chamber, structures, frames,
PRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
SECTION 603 SANITARY SEWER FORCE MAINS
SECTION 603 SANITARY SEWER FORCE MAINS 1. GENERAL Pipelines for sanitary sewer force main systems shall conform to the following specifications and shall be installed at the locations indicated on the
SECTION 200: STORM SEWER CONSTRUCTION STANDARDS
SECTION 200: STORM SEWER CONSTRUCTION STANDARDS Page No. Description 200-2 201 GENERAL 200-2 201.1 SPECIFICATIONS 200-2 201.2 CONNECTION TO EXISTING FACILITIES 200-3 202 MATERIALS 200-3 202.1 PIPES 200-4
Engineering Specifications
PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press
CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements
16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
MOBILE AREA WATER AND SEWER SYSTEM. Section 12. Sanitary Sewer Standard Specifications
MOBILE AREA WATER AND SEWER SYSTEM Section 12 Sanitary Sewer Standard Specifications May 31, 2012 TABLE OF CONTENTS 12.01 SCOPE:... 5 12.02 WORK INCLUDED:... 5 12.03 PIPELINE SYSTEM MATERIALS:... 5 A.
City of Virginia Beach Public Utilities HRPDC Regional Construction Standards, 5 TH Edition Amendments May 19, 2014
City of Virginia Beach Public Utilities HRPDC Regional Construction Standards, 5 TH Edition Amendments May 19, 2014 Section Subsection Name Date Modification Division 1 All subsections General Provisions
Specifications for Residential Property Owners Connection to New Public Sewer
Specifications for Residential Property Owners Connection to New Public Sewer Spalding Tract property owners are required to connect to the community sewer system when construction is complete and the
CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS
CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection
Morrison Bros. Co. General Product Specifications
Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage
Hose Clamps & Fittings
All Stainless Steel Marine or Underground Hose Clamps 5/16 HEX HEAD SCREW 60000 SERIES Highly corrosion resistant Use for marine or underground applications Stainless Steel Band, Housing Plated Steel Screw
WATER & SEWER CORROSIVE RESISTANT PRODUCTS
WATER & SEWER CORROSIVE RESISTANT PRODUCTS The Standard of Excellence in the Industry CASING SPACERS COUPLINGS & FLANGE COUPLING ADAPTERS REPAIR CLAMPS DUCTILE IRON SADDLES STAINLESS STEEL SADDLES TAPPING
SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS
SECTION 08000 STORM DRAINAGE 08010 DESIGN A. Location B. Sizing TABLE OF CONTENTS 08020 MATERIALS A. Pipe Materials B. Structure Materials C. Installation D. Inlets and Outlets 08030 INSPECTIONS AND TESTING
SECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
SECTION 15125 HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION
SECTION 15125 HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION PART 1 GENERAL.01 SECTION INCLUDES Furnishing and installing 4 inch through 16 inch high density
Standard Specifications For Private Sewer Laterals
BUILDING SERVICES DEPARTMENT 250 Frank H. Ogawa Plaza, 2nd Floor, Oakland, CA 94612 Inspection Services: 510.238.3443 FAX: 510.238.2263 Standard Specifications For Private Sewer Laterals APPROVED MATERIALS
How To Replace A Reverse Osmosis Water Tank
ALL MODELS REVERSE OSMOSIS WITH NONAIRGAP FAUCET 1. Read all instructions carefully before starting installation. 2. Find the cold water line beneath your sink. The cold water is typically on the right.
Wastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.
SECTION LS 2530 SANITARY SEWERS PART 1 GENERAL 1.1 SUBMITTALS A. General: Submit the following in accordance with The General Conditions. 1. Product data for drainage piping specialties. 2. Shop drawings
PLUMBING VALVES HOUSTON ORLANDO GREENVILLE 800/392-5066 800/327-3022 800/476-2212 TOTAL MAINTENANCE SOLUTIONS
8-1 BRONZE GATE VALVES 125 psi. SWP 200 psi WOG Threaded ends Non-rising stem Solid wedge disc DOMESTIC IMPORT PART # 40300250 1/4 40300260 40300251 3/8 40300261 40300252 1/2 40300262 40300206 3/4 40300263
Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe
Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe 1. GENERAL The following supplemental sewer main specifications are intended to address the installation of high-density polyethylene
LIST PRICE BOOK MALLEABLE CAST IRON PRESS FITTINGS FOR SCH. 10 40 BLACK & GALVANIZED STEEL PIPE
FASTLOCK fittings are not currently approved for use with gas or fire protection applications. FITTINGS FOR STEEL PIPE LIST PRICE BOOK MALLEABLE CAST IRON FITTINGS FOR SCH. 10 40 BLACK & GALVANIZED STEEL
APCO SLOW CLOSING AIR/VACUUM VALVES
BULLETIN 1 JULY 01 APCO SLOW CLOSING AIR/VACUUM VALVES Series 1900 APCO Slow Closing Air/Vacuum s Maximum Air Flow Velocity in Good Pipeline Design The Air/Vacuum operates in the normal fashion allowing
RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
ASTM C76, Class III, Wall B, except as modified herein. Clean natural sand, ASTM C33. Artificial or manufactured sand will not be permitted.
SECTION 3000 - SANITARY SEWERS 3001 SCOPE. This section applies to sanitary sewer construction and shall consist of furnishing all labor, materials, and equipment for the complete installation of sewers
Section 2100-Trenching and Tunneling
SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial
SECTION 02400 - STORM DRAIN SYSTEM
SECTION 02400 - STORM DRAIN SYSTEM CONTENTS: Part 1 - General... 1 1.01 Work Included... 1 1.02 Related Requirements... 1 1.03 Reference Standards... 1 1.04 Quality Assurance... 1 1.05 Measurement And
Sewer Water Pipeline Replacement with CERTA LOK RESTRAINED JOINT PVC PIPE
1.0 GENERAL 1.1 DESCRIPTION This section addresses the procedures to be employed for pipe bursting existing water/sewer pipelines, as identified on the drawings, and replacing with new Restrained Joint
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
08.08 Vic-Check Valves
The check valves are a product of computer-assisted innovative engineering with quality features including a new hydrodynamically efficient profile. The Vic-Check valve utilizes a spring-assisted, single-disc
Copper Meter Resetters
Copper Meter Resetters To Set 5/8", 5/8" x 3/4", 3/4", 1", 1 1 2" & 2" Water Meters 11/12 Table of Contents Page Page Meter Resetters 5/8", 5/8" x 3/4", 3/4", & 1" Horizontal Inlet and Outlet Series 710
SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)
CHAPTER 9 SEWER / STORM DRAIN / IRRIGATION LINES SECTION 9.01 GENERAL This section covers the requirements for piping materials and installation of Lehi City sewer, storm drainage and irrigation collection
Learning Objectives. History of Vacuum Testing for Precast. Vacuum Testing. Terminology and purpose
: It Just Sucks! Presented by: Darryl Cloud Concrete Sealants, Inc. Learning Objectives In this course, you will learn: Terminology for Watertightness Equipment Tips, Tricks, and FAQ s History of Vacuum
ball valves Flomite 71 Series 2-way Integral Panel Mount Ball Valves
2-way Integral Panel Mount Ball Valves Used for quick on-off service with a visual indication of flow, HOKE s 2-way ball valves offer orifice sizes up to 0.25 (6.4mm). Flomite valves feature a floating
Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes
CANTEX INC. 301 Commerce Ste 2700 Fort Worth, Texas 76102 817-215-7000 Fax: 817-215-7001 Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes YOUR FULL
REQUEST FOR QUOTE STANDING OFFER NO. 2016-131 SUPPLY AND DELIVERY OF WATERWORKS FITTINGS
REQUEST FOR QUOTE STANDING OFFER NO. 2016-131 SUPPLY AND DELIVERY OF WATERWORKS FITTINGS Capital Regional District Integrated Water Services 479 Island Highway Victoria, BC V9B 1H7 Tel: 250.474.9600 Fax:
Double-Headed Screw 1. 3/4" FIP x 3/4" MIP x 1/4" hole 2. 3/4" Fip x 3/4" MIP. Feed Water Connector 1. 1/2" FIP x 1/2" MIP x 1/4" OD 2. 3.
Picture Item No. Description RO- 0010 Brass Water Feed 1. 3/4" FIP with 1/4" hole 2. Using on R.O. tank RO- O020 Double-Headed Screw 1. 3/4" FIP x 3/4" MIP x 1/4" hole 2. 3/4" Fip x 3/4" MIP RO- 0030 Brass
Rules and Regulations for Water Service Lines Water Services Department
Rules and Regulations for Water Service Lines Water Services Department MAY 2015 1 These regulations are established to provide for an orderly growth of the City's water system and to assure equitable
SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE
6.01 SCOPE The work covered by this section of the specifications consists of the furnishing of all plant, labor, materials, equipment and supervision and performing all operations involved in the construction
ITEM II - SANITARY GRAVITY SEWER PIPE, FITTINGS, & ACCESSORIES
ITEM II - SANITARY GRAVITY SEWER PIPE, FITTINGS, & ACCESSORIES 2.01 General (c) All sanitary gravity sewers shall be constructed of either PVC or Ductile Iron unless otherwise specified in the Special
OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT
OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT INDEX AMERICAN - DARLING 5-1/4 IN. B-84-B-5 FIRE HYDRANT OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE REPAIRS Operation and Maintenance...
Ford Service Saddles and Tapping Sleeves
THE FORD METER BOX COMPANY, INC. ISO 9001:2008 10002505 Section AA 02/2015 Web Revision 12/17/2015 Ford Service Saddles and Tapping Sleeves Contents Page Recommended Product Application *Steel *C900 Cast
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
TECHNICAL SPECIFICATION
THOMAS - G-FLEX GFLEX TECH SPEC CONNECTING INNOVATION JOHANNESBURG TEL: +27 11 794 7594 CAPE TOWN TEL: +27 21 556 5258 POLOKWANE TEL: 015 298 9142 DESIGNER, MANUFACTURER AND DISTRIBUTOR OF PIPE CONNECTION,
SECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
Guide Specification Precast Concrete Products
Guide Specification Precast Concrete Products This specificaton should be used only by qualified professionals who are competent to evaluate the significance and limiations of the specification and who
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS While its use is not required, this checklist has been prepared to provide the field inspector a summary
Utility Marking Trace Wire Guide
Manufacture product options: Utility Marking Trace Wire Guide The information provided by Copperhead Industries gives you product options to help you choose the correct wire termination points connectors
One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty
One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable
General Guidelines for Repairing Buried PE Potable Water Pressure Pipes
515 General Guidelines for Repairing Buried PE Potable Water Pressure Pipes Introduction Traditional piping systems have gasket-sealed bell and spigot joints every 20 feet, which can be a potential maintenance