Yale University Design Standards
|
|
|
- Everett Greer
- 10 years ago
- Views:
Transcription
1 Change History Date Description of Change Pages / Sections Modified Change Approver Initials 3/26/13 Add text encouraging discussion of innovation in , A (Summary) SO newly available products. 3/26/13 Add to item: Dual flush Toilet/ flush valve , B. #4b.(Fixture Types, SO Water Closets) 3/26/13 Add check valves on hot and cold water supply lines to , C, #1 (Plumbing Fixtures, SO faucet to avoid short circuiting through faucet. Add hose bib and r.p backflow preventer for cleaning station Manufacturers, Faucets) 3/26/13 Add to both items: Add check valves on hot and cold , B, #4 & #5 (Plumbing SO water supply lines to faucet. Add hose bib and r.p backflow preventer for cleaning station. Fixtures, Manufacturers, Janitor s Sink & Mop Basin) 3/26/13 Add to item: Dual flush Toilets - flush valve , C #16. (Manufacturers, SO Flush valves) 3/26/13 Add 2 nd paragraph: re. combined bottle filler feature , C. (Drinking Fountains SO and Water Coolers, Product Standards) 3/16/13 Remove Tiger Flow from list , E, #3 (Manufacturers, SO Add Grundfos to the list City and Hot Water Pressure Booster Pumping Systems) 3/26/13 Add Maxi-Therm to the lists for both , E #1 & #2 (Manufacturers, Gas Domestic Water Heaters, Gas & Electric) SO Subdivision 15400: Plumbing Fixtures and Equipment 1
2 Section 15410: Plumbing Fixtures Plumbing Fixtures This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. System Design and Performance Requirements C. Manufacturers D. Quality Control This section contains design criteria for plumbing fixtures, including faucets and flush valves. We encourage use of innovative new products: When designers want to use new products, they are required to present to Yale Utilities and Engineering for discussion, review and approval. B. System Design and Performance Requirements Design the plumbing system for safety, longevity, durability, and flexibility. Provide thermostatic mixing and pressure balancing valves for all baths and showers. 1. Fixture Quantities (General) Yale University will tolerate under-fixturing on individual floors or in specific building areas only if horizontal or vertical occupant access to fixtures in other areas is sensible. a. Base quantities on the anticipated maximum, normal-use bui1ding capacity. b. Quantities must be satisfactory to code-enforcing officials and/or funding agencies. Use the quantities listed in Table 1 as a guide for preliminary planning. Subdivision 15400: Plumbing Fixtures and Equipment 2
3 Section 15410: Plumbing Fixtures c. For all new or remodeled building construction, the aim is to satisfy anticipated demand. However, avoid over-fixturing because of the comparatively high cost of these facilities and spaces. d. When comparing proposed quantities to codes or other required standards, be aware that codes and standards usually apply to fixture totals for an entire single-type occupancy building. Therefore, fixture quantities on each floor of such a building need not necessarily meet codes or standards. 2. Fixture Quantities Verify fixture quantities as specified by state and local building codes. a. Office Buildings The OSHA quantities for water closets and urinals listed in Table 1 are satisfactory. Table 1. Fixture Quantities Water Closets, Lavatories, and Urinals Men Women Men & Women Persons WCs Urinals WCs Persons Lavatories Subdivision 15400: Plumbing Fixtures and Equipment 3
4 Section 15410: Plumbing Fixtures b. Research Buildings Per code, fixture quantities should be the same as for office buildings, but only if it is anticipated that all occupants will be in the building as constantly as occupants of an office building. If the building program does not define this constancy, it must be determined for its effect on fixture quantities. If proposed quantities are less than the code requirements, a code exception will be investigated. c. Places Of Assembly Designers may recommend fixture quantities in places of assembly. See the applicable code for minimum requirements. However, provide no less than two of each type of fixture in any one toilet room. d. Libraries Per code, a library, depending on its type, could fall into either the same category as an office building or in the public or semi-public building category. Evaluate each library according to its type and category. Some small libraries can be categorized as classrooms. A large library, such as Sterling Memorial, could fall into a category not covered by code. As a guide for such a separate category, about one sanitary fixture (water closet or urinal) per 50 reader seats (and about the same number of lavatories) should be adequate, if facilities for staff are considered separately. A proposal involving such a separate category should be approved by code or funding authorities prior to incorporation into a building. e. Classroom Buildings Yale University does not yet have an inventory of fixtures (and adequacy of same) in its classroom buildings. Until such an inventory is available, use Table 2 as a guide. The number of fixtures must be approved by code or funding authorities before incorporation into a building. However, unless the anticipated use by either sex is nominal (under 25), provide at least two of each fixture for each sex. Subdivision 15400: Plumbing Fixtures and Equipment 4
5 Section 15410: Plumbing Fixtures Table 2. Classroom Fixtures Men Women Fixture Type Student Stations per Fixture WCs 100 Urinals 110 Lavatories 150 WCs 60 Lavatories 100 f. Other Building Types If fixture quantities are not stated in the building program for other types of buildings, base the quantities on modifications of those developed by the architect and approved by Yale University and code or funding authorities for the types of buildings listed above. g. Counting Fixtures for the Handicapped Include all fixtures provided for the physically handicapped in the fixture count. Wherever "unisex" toilet rooms are used, apply each WC as a deduction from the combined requirement for both sexes before apportioning the remaining needs among such gang toilet rooms as might be designated for each sex. Unisex toilet rooms are preferred, where feasible, for this use. 3. Mounting of Fixtures Hang fixtures on walls wherever possible. Use chair hangers or (as for a battery of lavatories) a less expensive substitute. 4. Fixture Types a. Lavatories Yale University prefers vitreous china lavatories with integral back and front faucets. The minimum size is 20" W x 18" outside. Space is 26" o.c. Subdivision 15400: Plumbing Fixtures and Equipment 5
6 Section 15410: Plumbing Fixtures b. Water Closets Water closets must be elongated, siphon-jet action, with open front white seats. Include flush valves where feasible and specify dual-flush flush valves where appropriate. c. Urinals Urinals (men only) must be vitreous china, siphon-jet action, with flush valves. For standards of quality, see the manufacturers and model numbers listed below under Manufacturers. 5. Plumbing Fittings For lavatory faucets, use fittings that are not self-closing. C. Manufacturers Yale University requires the use of low flow plumbing fixtures. The flush valves for toilets and urinals must be manufactured by the China Manufacturer. The model numbers for low flow fixtures and flush valves must be compatible. Provide the model numbers for all flush valves for toilets and urinals on the shop drawings for the project. Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: 1. Faucets Symmons S-90-2-G-FR for a regular sink, with a centerset single lever, extra-long wrist operation, and grid strainer assembly. S-90-2-G-FR-W for a handicapped sink, with a 4" centerset single lever, extra-long wrist operation, and grid strainer drain assembly. S-93-2 for a kitchen sink with a hose spray. Speakman SC-5772 for a kitchen sink, with a hose spray and an 8" deck fitting. SC-5811 for a mop basin, with an 8" faucet center. Provide integral check valve on hot and on cold water supplies to mop sink faucet. SC-5811-RCP for a slop sink, with an 8" faucet center. Provide integral check valve on hot and on cold water supplies to slop sink faucet. Subdivision 15400: Plumbing Fixtures and Equipment 6
7 Section 15410: Plumbing Fixtures Moen 4420 Kohler Triton T&S No. B-720 POL cold water hose bib for cleaning solution system. Provide with reduced pressure backflow preventer WATTS No American Standard 2. Metering Faucets Symmons S-61-G Kohler S-60-G (for a regular sink temperature selection and 4" centerset grid strainer drain assembly) T&S Laboratory 3. Shower Valves Symmons X Symmons 1-500, for PWG 4. Angle Stops Brasscraft Furiyne Ansonia (Teledyne) A-200 series 5. Janitor s Sink Kohler K-6718, (wall hung K-6673 trap standard adjust for 3" IPS connect c.o. plug strainer s.s. rim guard, black back) American Standard Provide check valve on hot and cold water supplies to Janitor s sink faucet. Provide cold water hose bib T&S Brass No. B-720-POL and reduced pressure backflow preventer WATTS No. 909 for cleaning solution system. 6. Mop Basin Fiat MSB-3624, 36" x 24" x 10" with shelf MSB-2424, 24" x 24" x 10" without shelf Subdivision 15400: Plumbing Fixtures and Equipment 7
8 Section 15410: Plumbing Fixtures Provide check valve on hot and cold water supplies to mop basin faucet. Provide cold water hose bib T&S Brass No. B-720-POL and reduced pressure backflow preventer WATTS No. 909 for cleaning solution system. 7. Dorm Sinks Kohler K-6718 American Standard Dorm Sinks-Cast Iron, Enamel Kohler K-2861 American Standard (dorm sink, wall mount 19" x 17" with 4" faucet center) 9. Dorm Sinks a. Kohler K-6562 (counter top bar) K-2904 (counter top 4") K-2900 (counter top) K-5964 (kitchen single) K-5965 (kitchen single) K-5961 K-3283 b. American Standard (sink 3 hole drill) (faucet center) (4" faucet center metal frame) (basin, 4 hole or drillings, ) (basin, 3 hole or drillings, ) or (kitchen single, basin 3 hole drillings) ELKAY PSR (kitchen double basin, 4 hole drillings) Subdivision 15400: Plumbing Fixtures and Equipment 8
9 Section 15410: Plumbing Fixtures 10. Dorm Sinks, Vitreous China, Handicapped a. Kohler K (handicapped sink) K-2032 (handicapped sink) K-2054 (handicapped sink) b. American Standard (wall mount 27" x 20" with 4" faucet center) (wall mount, back splash, 4" faucet center concealed arm carrier) Wall mount to back splash 4 faucet center concealed arm carrier 11. Urinal, Vitreous China, Regular Use and Handicapped Kohler K-4985 (regular use) American Standard (wall-mount, siphon-jet action, 3/4" top spud inlet, 2" IPS outlet) Kohler K-5014-T (handicapped) American Standard (regular use, wall mount, siphon-jet action, 1/4" top spud inlet, 2" IPS outlet) 12. Toilets, Wall Mount Kohler K-4430-ET (wall mount) American Standard (3.5 gallon) 13. Water Closet, Vitreous China; Regular Use and Handicapped Kohler K-4430-ET (regular use) American Standard (handicapped use, water saving siphon-jet action, 2-1/2" passageway, 1-1/2" top spud) Kohler K-4250 (regular use, floor mount, water-saving siphon-jet action, 2-1/2" passageway, 1-1/2" top spud, 10" 12" roughing in) Kohler K-3420-ET (regular use) American Standard (floor mount, tank type, 1-3/4" passageway, 3/8" IPS water supply, 12" roughing in) Subdivision 15400: Plumbing Fixtures and Equipment 9
10 Section 15410: Plumbing Fixtures Kohler K-3527-EB (handicapped) American Standard (3.5 gallon use, floor mount tank type, 18" high bowl, 3/8" IPS water supply, 10" roughing in) Kohler K-4268 (handicapped) American Standard (regular use, floor mount siphon-jet action, 18" high bowl, water saving, 2-3/4" passageway, 1-1/2" top spud, 12" roughing in) 14. Toilet Tank 15. Tubs Kohler K-2867 Kohler K-4250 (floor mount) Kohler K-4330 (wall hung) Kohler K-4350ET (floor bolted) Kohler, K-3420EB (floor bolted) American Standard (3.5 gallon) 16. Flush Valves Sloan 186 Royal (for regular urinal, 3/4" IPS angle stop, coupling for 3/4" top spud, 1 to 1-1/2" high) Sloan Royal 180 (for handicapped urinal, 1" IPS angle stop, coupling for 1-1/4" top spud, 11-1/2" high) Sloan Royal (for regular and handicapped water closet, 1" IPS angle stop, coupling for 1-1/2" top spud, 11-1/2" high) Sloan Uppercut WES-111 Dual Flush (for regular and handicapped water closet, 1 I.P.S angel stop, coupling for 1-1/2 top spud, 11-1/2 high) 17. Lab Faucets Chicago 876-F3CP-VP Speakman SC-3004 Moen S0003 (spout only, 8132 handles only) Subdivision 15400: Plumbing Fixtures and Equipment 10
11 Section 15410: Plumbing Fixtures D. Quality Control If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards, and listed in the project specifications, do not conflict with commissioning procedures for testing and training. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 11
12 15412 Emergency Plumbing Fixtures This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. System Design and Performance Requirements C. Product Standards D. Manufacturers E. Installation Guidelines F. Quality Control This section contains design criteria for emergency eyewash and shower units. B. System Design and Performance Requirements 1. Design the plumbing system for safety, longevity, durability, and flexibility. 2. Provide a tempered water supply for all emergency showers and eyewashes. 3. Eyewashes must be full-face. C. Product Standards Products shall conform to ANSI standards. D. Manufacturers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: 1. Emergency Showers Speakman Symmons 2. Emergency Eyewash Units Haws Subdivision 15400: Plumbing Fixtures and Equipment 12
13 Section 15412: Emergency Plumbing Fixtures E. Installation Guidelines 1. Install the floor drain beneath the emergency shower. 2. Verify that tempered water has been specified for emergency fixtures. 3. In conjunction with code and standard requirements, emergency showers must be located in adjacent corridors or at the hazard room door exits. The showers are to be accessible, require not more than 10 seconds to reach, and be within a travel distance of no greater than 50 ft from the hazard rooms. 4. Provide emergency showers and eyewash fountains for: Laboratories Boiler rooms Cooling towers Chemical treatment areas Deionizing acid regenerant tank Battery charging rooms Provide additional emergency showers and eyewash fountains in other areas that: have hazardous materials that will be used in the area, and have no other emergency showers and eyewash fountains located within 50 feet of the area. 5. Provide full-size ball valves to isolate emergency showers or eyewash fountains. Lock the valves in the open position. F. Quality Control If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards, and listed in the project specifications, do not conflict with commissioning procedures for testing and training. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 13
14 15415 Drinking Fountains and Water Coolers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. System Design and Performance Requirements C. Product Standards D. Manufacturers Stainless Steel Water Coolers E. Quality Control This section contains design criteria for drinking fountains and water coolers. B. System Design and Performance Requirements Design the plumbing system for safety, longevity, durability, and flexibility. 1. Fixture Quantities (General) Yale University will tolerate under-fixturing on individual floors or in specific building areas only if horizontal or vertical occupant access to fixtures in other areas is sensible. a. Base quantities on the anticipated maximum, normal-use bui1ding capacity. b. Quantities must be satisfactory to code-enforcing officials and/or funding agencies. c. For all new or remodeled building construction, the aim is to satisfy anticipated demand. However, avoid over-fixturing because of the comparatively high cost of these facilities and spaces. d. When comparing proposed quantities to codes or other required standards, be aware that codes and standards usually apply to fixture totals for an entire single-type occupancy building. Therefore, fixture quantities on each floor of such a building need not necessarily meet codes or standards. Subdivision 15400: Plumbing Fixtures and Equipment 14
15 Section 15415: Drinking Fountains and Water Coolers 2. Fixture Quantities Verify fixture quantities as specified by state and local building codes. C. Product Standards Products must conform to ANSI/NSF 61 standards. D. Manufacturers Stainless Steel Water Coolers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: Halsey Taylor Elkay Oasis E. Bottle Filling Stations Where ever possible, water coolers are to be specified with a bottle filling station, like Halsey Taylor s HYDROBOOST, Elkay s EZH2O and Oasis s Aqua Point. F. Quality Control If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards, and listed in the project specifications, do not conflict with commissioning procedures for testing and training. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 15
16 15430 Plumbing Specialties This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. System Design and Performance Requirements C. Manufacturers D. Installation Guidelines E. Quality Control This section contains design criteria for water and drainage piping specialties, including backflow preventers, vacuum breakers, mixing valves, water hammer arrestors, and domestic water meters. B. System Design and Performance Requirements 1. Before design commences, professionals shall contact local water authority for complete requirements. 2. Design the plumbing system for safety, longevity, durability, and flexibility. 3. Install an approved, reduced-pressure, double-check type valve in both the potable and non-potable water supplies. a. Only potable water must supply drinking fountains, lavatories, sinks, janitor closets, safety showers, eyewash stations, and water heaters. b. Non-potable water or potable water is to must supply fire protection systems, toilets, urinals, fume hoods, laboratory sinks, outside hose bibs, and other supplies not for human consumption. c. A check valve must be installed upstream from the reduced-pressure valve to prevent valve dumping every time the main line pressure drops. d. Provide isolation valves between potable water and non-potable water. e. Identify and label gray-water systems. Subdivision 15400: Plumbing Fixtures and Equipment 16
17 Section 15430: Plumbing Specialties C. Manufacturers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: 1. Mixing Valves Speakman Symmons 2. Water Hammer Arrestors Wade JMJ Cord 3. Backflow Preventers Watts D. Installation Guidelines 1. Where reduced-pressure backflow preventers are installed, install a floor drain nearby that will accommodate the full flow from the backflow preventer emergency dump port, if the valve malfunctions. 2. Install a hose bib at least every 100 ft around a building and in the mechanical room. Install a non-freeze type hose bib on the roof, near the air handling units. 3. Use trap primers only when necessary. Install them in accessible locations for maintenance. E. Quality Control If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards, and listed in the project specifications, do not conflict with commissioning procedures for testing and training. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 17
18 15441 Domestic Water Pumps This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. System Design and Performance Requirements C. Submittals D. Product Standards E. Manufacturers F. Materials G. Accessories or Special Features H. Special Requirements Source Control I. Quality Control Testing J. Installation Guidelines K. Quality Control This section includes design criteria for inline, end suction, and water pressure boosters for domestic water pumping systems. B. System Design and Performance Requirements 1. Provide a three-pump system for water booster pumping. Size one pump for approximately 1/3rd of the total water demand. Size each of the other two pumps for approximately two-thirds of the total water demand. Design the system so the smaller pump will run constantly until the water demand exceeds the capacity of the pump, at which point the smaller pump will stop and one of the large pumps will start. When the water demand exceeds the capacity of the larger pump, the smaller pump will automatically restart and operate together with the larger pump to provide the total water demand. The third pump will act as a standby pump. The pumps must be free of cavitation over their operating range. 2. The system must be controlled by a combination of flow or pressure switches and pressure-regulating valves, and must be designed to prevent water hammer. 3. Provide pressure gauges for every pump. 4. Specify that piping and pumps be installed and connections aligned, but not madeup, until inspection by Yale University. All piping must be supported independently of the pumps. Subdivision 15400: Plumbing Fixtures and Equipment 18
19 Section 15441: Domestic Water Pumps 5. In-line, end-suction, and split-case pumps bearing frame and pump internals must be serviceable without disturbing motors or connected piping. 6. Select pumps for an impeller diameter not greater than 90 percent of the maximum pump impeller diameter. 7. Select pump motors to be non-overloading at any point along the pump impeller curve or in combination with other pumps. 8. Provide pressure gauges for every pump, except small so-called boosters" which must have gauge cocks only. 9. Select pumps between 65% and 115% of best efficiency point along the impeller curve. 10. Consider a storage tank to reduce the number of pump starts. C. Submittals Submit the following construction and certification documentation. 1. Construction Documents Submit the following test reports: Installed pump performance test and balance report. Pump alignment report. 2. Product Certificates Signed by Manufacturer Specify that pumps be inspected by the manufacturer's authorized representative who must submit a written report to the engineer with a copy to Yale University stating that the pump has been properly installed, is operating correctly, and the installation is acceptable to the manufacturer in every respect. D. Product Standards Products must conform to the following standards: Hydraulic Institute standards ASME PTC 8.2 and 9 CSA standards UL Motor-Operated Water Pumps Standard Subdivision 15400: Plumbing Fixtures and Equipment 19
20 Section 15441: Domestic Water Pumps E. Manufacturers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: 1. In-Line Pumps Bell & Gossett Taco 2. Booster Pumps Circulator Bell & Gossett (lubricated bearing with oil seals) Taco (sealed bearing) 3. City and Hot Water Pressure Booster Pumping Systems Bell & Gossett (multiple control panel, 2-3 pumps with small tank) Canaris Corporation Grundfos 4. Suction Diffuser Bell & Gossett Taco F. Materials All wetted parts in recirculation hot water pumps and in-line boosters must be of bronze construction (bronze impellers only). G. Accessories or Special Features 1. Couplings Couplings must be approved by the Yale University Facilities group. 2. Strainers 1. For water service, strainers must be the same size as entering pipe size and have a maximum clean pressure drop of one psig. 2. Use pump startup strainer screens for cleaning, and remove them afterwards. Subdivision 15400: Plumbing Fixtures and Equipment 20
21 Section 15441: Domestic Water Pumps 3. Provide a blow-off valve, full size full port ball valve on each strainer. Where feasible and permitted by code, blow-off piping must have plug. 4. Strainer material for use in domestic water systems must be of stainless steel construction. H. Special Requirements Source Control The manufacturer must maintain an inventory of all wearing parts within 50 miles of New Haven, CT. I. Quality Control Testing After factory assembly, the packaged pumping system must be hydrostatically tested and undergo a complete electric and hydraulic test from 0 to 100% design flow at the factory. All controls, pump sequencing devices, alarms and instrumentation must be tested and calibrated for proper operation during factory testing. J. Installation Guidelines 1. Specify that pumps be aligned, doweled, and grouted. 2. Provide pump suction fittings on the suction sides of base-mounted, centrifugal pumps. 3. Provide a pump discharge valve on the discharge sides of each base-mounted centrifugal pump. 4. Support pump fittings with floor-mounted pipe and flange supports. 5. Each pump must be level and re-aligned. Base-mounted pumps must be grouted. 6. Provide a spring-loaded check valve in the pump discharge, in lieu of a swing check valve. 7. If the pump motor is above 15 hp, provide a beam or rail system for removal from a crowded mechanical room. Subdivision 15400: Plumbing Fixtures and Equipment 21
22 Section 15441: Domestic Water Pumps K. Quality Control 1. If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards, and listed in the project specifications, do not conflict with commissioning procedures for testing and training. 2. Specify that at least one final alignment be performed in the field. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 22
23 15445 Sewage and Sump Pumps This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. Submittals C. Product Standards D. Manufacturers E. Special Requirements Source Control F. Installation Guidelines G. Quality Control This section includes design criteria for sewage ejector and sump pumping systems. B. Submittals Submit the following design, construction, and certification documentation. 1. Designer Submittals Submit pump sizing calculations for sewage ejectors and sump pumps. 2. Construction Documents Submit an installed pump performance test and balance report. 3. Product Certificates Signed by Manufacturer Specify that pumps be inspected by the manufacturer's authorized representative who must submit a written report to the engineer with a copy to Yale University stating that the pump has been properly installed, is operating correctly, and the installation is acceptable to the manufacturer in every respect. Subdivision 15400: Plumbing Fixtures and Equipment 23
24 Section 15445: Sewage and Sump Pumps C. Product Standards Products must conform to the following standards: Hydraulic Institute standards ASME PTC 8.2 and 9 CSA standards UL Motor-Operated Water Pumps Standard D. Manufacturers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: 1. Sewage Ejector Pumping System SKB Weil Peabody Barnes KSB 2. Sump Pump Bell & Gossett (vertical flow series 800) Weil E. Special Requirements Source Control The manufacturer must maintain an inventory of all wearing parts within 50 miles of New Haven, CT. F. Installation Guidelines If the pump motor is above 15 hp, provide a beam or rail system for removal from a crowded mechanical room or air handler. When more than one pump is connected to a common discharge, each pump must have independent intake and discharge isolation valves and discharge check valves. All valves and check valves must be serviceable without entering the sump tank or sump pit. Each sump tank or pit shall have an independent high level alarm that goes to the energy management system. Subdivision 15400: Plumbing Fixtures and Equipment 24
25 Section 15445: Sewage and Sump Pumps G. Quality Control If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards, and listed in the project specifications, do not conflict with commissioning procedures for testing and training. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 25
26 15480 Domestic Water Heaters This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. System Design and Performance Requirements C. Submittals D. Product Standards E. Manufacturers F. Quality Control This section contains design criteria for tankless, instantaneous- and storage-type electric, gas, hot water heaters, both household and commercial. B. System Design and Performance Requirements 1. Design the plumbing system for safety, longevity, durability and flexibility. 2. The setpoint temperature for water heaters must be 120 F for general service and 140 F for kitchen dishwasher preheat. Provide mixing valves to distribute water to fixtures at 110 F. 3. Provide a minimum of two central water heaters for dormitories. 4. Provide temperature and pressure gauges at the inlet and outlet of each water heater. 5. Provide a minimum of two central domestic water heaters for each laboratory facility, each supplying 75% of demand. Coordinate with the Yale University Facilities group for other types of facilities for number of water heaters. 6. Use circulated hot water piping system, limiting dead ends to 20 feet. Subdivision 15400: Plumbing Fixtures and Equipment 26
27 Section 15480: Domestic Water Heaters 7. Install lockable-type shutoff valve, with lock, locked in the open position between the expansion tank and cold water supply. 8. Provide a properly sized pressure and temperature relief valve for each domestic water heater. 9. Recirculating pumps in domestic water heating systems must be of bronze construction. C. Submittals Submit the following design and certification documentation. 1. Designer Submittals Submit domestic hot water load calculations for: 180 dish washers Building domestic hot water heaters Kitchen booster hot water system Laundry hot water system 2. Product Certificates Signed by Manufacturer Specify that water heaters be inspected by the manufacturer's authorized representative who shall submit a written report to the engineer with copy to Yale University stating that the water heaters have been properly installed, are operating correctly, and the installation is acceptable to the manufacturer in every respect. D. Product Standards Products must conform to the following standards: ASHRAE 90.1b ASME Subdivision 15400: Plumbing Fixtures and Equipment 27
28 Section 15480: Domestic Water Heaters E. Manufacturers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: 1. High-Recovery, High-Efficiency Gas Water Heaters AO Smith Maxi-Therm PVI 2. High-Recovery, High-Efficiency Electric Water Heaters AO Smith Maxi-Therm PVI F. Quality Control If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards, and listed in the project specifications, do not conflict with commissioning procedures for testing and training. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 28
29 15487 Heat Exchanger Water Heaters This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS B. System Design and Performance Requirements C. Submittals D. Product Standards E. Manufacturers F. Installation Guidelines G. Quality Control This section contains design criteria for steam, hot water, instantaneous, and storagetype water heaters. B. System Design and Performance Requirements 1. Design the plumbing system for safety, longevity, durability and flexibility. 2. Domestic hot water generators must be double wall. 3. Indirect water thermo-max. C. Submittals Submit the following design and certification documentation. 1. Designer Submittals Submit domestic hot water load calculations for: Building domestic hot water heaters Kitchen booster hot water system Laundry hot water system Subdivision 15400: Plumbing Fixtures and Equipment 29
30 Section 15487: Heat Exchanger Water Heaters 2. Product Certificates Signed by Manufacturer Specify that water heaters be inspected by the manufacturer's authorized representative who shall submit a written report to the engineer with copy to Yale University stating that the water heaters have been properly installed, are operating correctly, and the installation is acceptable to the manufacturer in every respect. D. Product Standards Products must conform to the following standards: ASHRAE 90.1b ASME E. Manufacturers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following: 1. Instantaneous Steam Water Heaters (below 20 psi steam pressure) Leslie Armstrong 2. Semi-Instantaneous Steam Water heaters (greater than 20 psi and less than 60 psi steam pressure) Patterson-Kelley 3. Indirect Water Heaters Thermo-Max F. Installation Guidelines 1. Provide pull space for coils. 2. Provide a 2' minimum clearance around the units for maintenance. Subdivision 15400: Plumbing Fixtures and Equipment 30
31 Section 15487: Heat Exchanger Water Heaters G. Quality Control If this portion of the project includes commissioning, verify that insertions in the project specifications have been made that refer to the commissioning procedures in the commissioning specification section. Verify that the systems and equipment identified in this section of the standards and listed in the project specifications do not conflict with commissioning procedures for testing and training. End of Section Subdivision 15400: Plumbing Fixtures and Equipment 31
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
22 12 00 FACILITY POTABLE WATER STORAGE TANKS
DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 50 foot
GENERAL PLUMBING REQUIREMENTS
22 00 00 GENERAL PLUMBING REQUIRMENTS i. 01 81 00 Facility Performance Requirements ii. 22 07 00 Plumbing Insulation iii. 22 10 00 Plumbing Piping iv. 22 40 00 Plumbing Fixtures v. 22 45 00 Emergency Plumbing
Georgia State Amendments to the International Plumbing Code
Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Local Government Assistance Division 60 Executive Park South, N.E. Atlanta, Georgia 30329-2231
A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
GENERAL PLUMBING REQUIREMENTS
22 00 00 GENERAL PLUMBING REQUIRMENTS i. 00 00 07 Design Professional Design Process Requirements ii. 00 00 08 Design Professional Documentation Requirements and Deliverables iii. 01 81 00 Facility Performance
SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES
SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information
Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations
15430 SAFETY SHOWERS AND EYEWASHES
15430 SAFETY SHOWERS AND EYEWASHES PART 1: GENERAL 1.01 RELATED SECTIONS 01005 - ENVIRONMENTAL HEALTH 11600 LABORATORY EQUIPMENT 15020 - LABORATORIES 15130 - PIPING SPECIALITES 15400 - PLUMBING 15420 -
DIVISION 22 PLUMBING. 22 30 00 PLUMBING EQUIPMENT 22 33 00 Domestic Water Heaters
DIVISION 22 PLUMBING 22 00 00 PLUMBING 22 00 50 Design Criteria 22 01 00 General Requirements 22 05 00 Common Work Results 22 06 00 General Duty Valves 22 07 00 Insulation 22 08 00 Commissioning 22 10
Residential Plumbing BCN 1058
Residential Plumbing BCN 1058 CHAPTER 7 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System MICHAEL KNOTEK 74 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System PLUMBING FIXTURES
NYC Department of Education Building Condition Assessment Survey 2014-2015 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004
School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 0004 Time In Last Edited 255 MECHANICAL 205-05-8 09:00AM
Plumbing Code Sections For Commercial Food Facilities
Plumbing Code Sections For Commercial Food Facilities SCOPE The following list of requirements summarizes the plumbing issues that are commonly addressed in commercial retail food facilities by health
Backflow Bulletin #1
Backflow Bulletin #1 FIRE PROTECTION SYSTEMS Chemicals in the System Anti-Freeze, Foam, Corrosion Inhibitors, etc. Chemicals in the System Glycerin Glycerin or similar food-grade non-toxic additive Siamese
Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 [email protected]
Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 [email protected] b 2011 Los Angeles Plumbing Code LAPC changes from 2008 2011 Los Angeles Plumbing Code Consists of the following:
77 ILLINOIS ADMINISTRATIVE CODE, PART 890 (NEW) ILLINOIS PLUMBING CODE (02/04) SUBPART I: WATER SUPPLY AND DISTRIBUTION
SUBPART I: WATER SUPPLY AND DISTRIBUTION Section 890.1110 Quality of Water Supply All premises intended for human habitation or occupancy shall be provided with a potable water supply. The potable water
FLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
PLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
112039.00 224500 EMERGENCY PLUMBING FIXTURES
PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following emergency plumbing fixtures: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Hand-held drench hoses. 5. Combination
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
One of the fundamental design elements that every
Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things
COMPLETE FACILITIES SUPPLY YOUR COMPLETE SOURCE FOR FACILITY MAINTENANCE SUPPLIES. 8801 Virginia Meadows Drive Manassas, Virginia 20109 USA
COMPLETE FACILITIES SUPPLY YOUR COMPLETE SOURCE FOR FACILITY MAINTENANCE SUPPLIES 8801 Virginia Meadows Drive Manassas, Virginia 20109 USA p. f. 703-334-5009 www.facebook.com/pages/complete-facilities-supply/
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
FIRING RANGE PHASE 1 DESIGN 224500-1
FIRING RANGE PHASE 1 DESIGN 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
TANKLESS WATER HEATER INSTALLATION DIAGRAMS
TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 15430 PLUMBING SPECIALTIES
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Roof drains 1. Coordinate location and depth of drains to assure adequate pitch of the drainage area to drain. 2. Overflow system shall be piped
What to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass.
CHAPTER 9 VENTS 901 GENERAL 901.1 Scope The provisions of this chapter shall govern the materials, design, construction, and installation of vents. 901.2 Protection of Trap Seals The protection of trap
A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 22 45 00 - (ADD#2) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
DIVISION 22 PLUMBING. 22 30 00 PLUMBING EQUIPMENT 22 33 00 Domestic Water Heaters
DIVISION 22 PLUMBING 22 00 00 PLUMBING 22 00 50 Design Criteria 22 01 00 General Requirements 22 05 00 Common Work Results 22 06 00 General Duty Valves 22 07 00 Insulation 22 08 00 Commissioning 22 10
5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES
PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES Health Systems Protection Rev. 07/2006 35-05-20/06/07/18 OFFICE OF FOOD PROTECTION 417 FEDERAL ST
Emergency Showers and Eyewashes Mike Adkins Wednesday, October 31, 10:00-11:1511:15 a.m.
Emergency Showers and Eyewashes Mike Adkins Wednesday, October 31, 10:00-11:1511:15 a.m. Safety First! How to Specify Emergency Showers and Eyewashes Presented by Mike Adkins, Guardian Equipment. ASPE
Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector
Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination
SIZING OF WATER PIPING SYSTEM
SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures
PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC
PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. Section:
Plumbing Apprenticeship Program Curriculum
Plumbing Apprenticeship Program Curriculum Plumbing Level One 02101-05 Introduction to the Plumbing Profession (5 Hours) Introduces the trainee to plumbing, starting with the history of plumbing from ancient
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
City of Elk River BASEMENT Office Use Only
City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:
Amendments to the 2012 International Plumbing Code
Amendments to the 2012 International Plumbing Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby
WESLEY BRIAN HUTTON KNOXVILLE, TENNESSEE LICENSED MASTER PLUMBER. Dear: Human Resources
WESLEY BRIAN HUTTON KNOXVILLE, TENNESSEE LICENSED MASTER PLUMBER Dear: Human Resources As you ll see on my enclosed resume, I have the educational background, professional experience, and track record
B. Reference ASME A17.1 for elevator sumps and sump pump requirements. D. ASSE 1003 Performance Requirements for Water Pressure Reducing Valves.
PART 1: GENERAL 1.01 Purpose A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
FAQ and Device/Usage Chart. What Is a Cross-Connection? What Is Backflow Prevention? What Is Backflow?
What Is a Cross-Connection? A cross-connection is a direct arrangement of piping that allows the potable (safe drinking) water pipe to be connected to a pipe supply that contains a contaminant or pollutant.
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
C I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
A. Product Certificates: Submit certificates of performance testing specified in "Source Quality Control" Article.
PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.02
2006 Codes. Please verify the following before calling for inspection
INSPECTION CHECKLIST RESIDENTIAL PLUMBING ROUGH IN 2006 Codes This checklist is intended for use to prepare for an inspection. This is only a general list and is not intended to address all possible conditions.
B. Shop Drawings: Diagram power, signal, and control wiring.
SECTION 224500 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Combination units. 5. Water-tempering equipment. 1.2 SUBMITTALS
WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS
WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS a. New Plumbing and Gas Piping Systems. This code in conjunction with the Plumbing and Fuel Gas Codes of the State of New York shall apply to plumbing
CHAPTER 2: The Plumbing System
CHAPTER 2: The Plumbing System SECTION I: SIZING REQUIREMENTS Establish building dimensions Building height can be determined either by architectural drawings or # of floors times height/floor. (ex: 1
Medical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: Section 1. Article V of Chapter XII of the Los Angeles Municipal Code is added to read:
ORDINANCE NO. 1,;...8_U_8_2_2_ An ordinance adding Article V to Chapter XII, and amending Section 94.103.1.2.9, of the Los Angeles Municipal Code establishing water efficiency requirements for new development
CERT. TO ASSE STD 1016 AND 1017 1016 AND 1017 1016 AND 1017 WT. LBS.
SUBMITTAL DATA/INSTRUCTION SHEET SD/IS 150 EFFECTIVE September 004 Supercedes March 3, 004 AM-1 SERIES TM ANTI-SCALD PROPORTIONAL THERMOSTATIC MIXING DIVERTING VALVE PATENTED, WITH DUAL ASSE 10 CERTIFICATION,
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The
ELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
(a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems.
12.33 - CROSS-CONNECTION CONTROL. (a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems. (b) Definitions. The following definitions shall apply
Plumbing Code in Commercial Kitchens
Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
Schedule of Maintenance Fees
Schedule of Maintenance Fees Effective July 1, 2015 It is the policy of the Housing Authority of Murray not to charge for NORMAL wear and tear. However, the Housing Authority reserves the right in every
BRADLEY HALO EMERGENCY PLUMBING FIXTURES (Short Form Version)
BRADLEY HALO EMERGENCY PLUMBING FIXTURES (Short Form Version) Bradley Halo Emergency Plumbing Fixtures are a new generation in safety equipment, featuring separate supply and waste piping to eye/face wash,
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
Nominal Life Expectancy for Building Components
Nominal Life Expectancy for Building Components Building System Page A. HVAC 2 B. Elevator/Escalator 6 C. Plumbing 7 D. Roofing 8 E. Electrical 10 F. Fire/Life/Safety/Security System 11 G. Interior Finishes
THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494
THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494 1. BEFORE YOU BEGIN IMPORTANT INSTRUCTIONS READ AND SAVE FOR THE CONSUMER WARNING: Risk of scalding or other severe injury. Before completing installation,
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide
Water Circulation Pumps & Circulators Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide Taco Catalog # 100-41 Supersedes: 08/07/15 Effective Date: 09/01/15 Printed in
DESIGN CHECKLIST PROJECT NAME DISCIPLINE DATE TYPE REVIEW REVIEWER DRAWINGS REVIEWED
DESIGN CHECKLIST PROJECT NAME DISCIPLINE DATETYPE REVIEW_ REVIEWER DRAWINGS REVIEWED EVERY ITEM WILL BE REVIEWED AND NOTED FOR COMPLIANCE (C), OR NON- APPLICABILITY (NA). A. GENERAL SECTION 7 PLUMBING
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
When Should Examination Preparation Begin?
Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing
PLUMBING & CROSS-CONNECTION CONTROL
PLUMBING & CROSS-CONNECTION CONTROL. MODULE 4 VII. Typical Retail Food Service Cross-Connections VIII. Air Gaps and Air Breaks for Drains and Waste IX. Grease Interceptors VII. TYPICAL RETAIL FOOD SERVICE
Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25
PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: [email protected], Web: www.paw.eu Installation and Operation Instructions Domestic hot water modules:
ASME Packaged Indirect Fired Water Heater
Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining
CHAPTER 26 PLUMBING CODE
CHAPTER 26 PLUMBING CODE 26.01 PLUMBING CODE The Illinois Plumbing Code as promulgated by the Illinois Department of Public Health at 77 Illinois Administrative Code, Part 890, is hereby adopted as the
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION 1 HOUSEKEEPING 2 CHANGES We will be covering the significant changes to the International Residential Code and the changes common to
ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International
ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?
Water Pressure Reducing Valves
F-23QA 23 Questions and Answers about Water Pressure Reducing Valves $ HOW THEY Save WATER Save ENERGY Save WASTEWATER Save MAINTENANCE Save MONEY ENERGY WATER Conserve Both Automatically with Water Pressure
INTERNATIONAL RESIDENTIAL PLUMBING CODE
INTERNATIONAL RESIDENTIAL PLUMBING CODE RP2-06/07 P2705.1 Proponent: Guy Tomberlin, Fairfax County, Virginia, representing Virginia Plumbing and Mechanical Revise as follows: P2705.1General. The installation
Lot Number. City. Architect Name SUBCONTRACTORS - COMPLETE AND ATTACH LIST ON PAGE 4
New Construction Permit Application Village of Shorewood Building Division One Towne Center Blvd Shorewood, IL 60404 (815)553-2310 Fax (815)744-6766 SUBMISSION CHECKLIST - Complete this application and
Georgia State Amendments to the International Plumbing Code
Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Planning and Environmental Management Division 60 Executive Park South, N.E. Atlanta,
SPECIFICATION DIVISION 22 SECTION DESCRIPTION DIVISION 22 PLUMBING SECTION 220519 - THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY
Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary
All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
Top 10+ Mistakes of DWV plumbing design
Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of
PMA ONLINE TRAINING Venting for Plumbing Systems
PMA ONLINE TRAINING Venting for Plumbing Systems One Hour Continuing Education Venting PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
Carriers, Fixtures & Piping
Regardless of application and/or installation needs, there are fixture supports available to meet even the harshest design requirements. by William M. Smith Over the years, I m sure that each of you in