1 RE-DEFINING THE GREEN DATA CENTER A Dell Technical White Paper MANAGING THE DATA CENTER BY EFFICIENT USE OF IT RESOURCES By John Pflueger, Ph. D. Dell Data Center Infrastructure

2 CONTENTS EXECUTIVE SUMMARY 2 INTRODUCTION 2 POWER AND CONSUMPTION AND ENERGY EFFICIENCY IN THE DATA CENTER 2 FRAMING THE PROBLEM 4 MANAGING DATA CENTERS FOR PRODUCTIVITY 6 CONCLUSION 13 FIGURES FIGURE 1: PROJECTED DATA CENTER ENERGY USE UNDER FIVE SCENARIOS (U.S. EPA, 2007) 3 FIGURE 2: DELL HISTORICAL SYSTEM PERFORMANCE (CFP2000rates) 5 FIGURE 3: FACTORS IN IMPROVING FACILITY PRODUCTIVITY 6 FIGURE 4: ESTIMATE OF HISTORICAL DATA CENTER PRODUCTIVITY METRICS FOR A SAMPLE DATA CENTER 8 FIGURE 5: COMPARISON OF ESTIMATED AND ADJUSTED ENERGY CONSUMPTION FOR VOLUME SERVERS ( ) 8 FIGURE 6: DM1 STARTING SERVER POPULATION 9 FIGURE 7: PARETO CHART OF DM1 SERVER POPULATION USEFUL Work 9 FIGURE 8: ESTIMATED RELATIVE WORK PER RACK BY DATA CENTER ROW (DM1) 10 FIGURE 9: EVOLUTION OF A DATA CENTER S EXPECTED PRODUCTIVITY OVER TIME 10 FIGURE 10: DATA CENTER IT UTILIZATION ESTIMATES 11 FIGURE 11: ESTIMATED DATA CENTER POWER CONSUMPTION AS A FUNCTION OF UTILIZATION POLICIES 12

3 Executive Summary Server and data center power consumption are concerns for data center owners and managers and for policy-makers. Additionally, societal trends and interest in Green and Sustainable technologies have increased focus on data centers. The IT industry, policy-makers and regulators have been working this issue, focusing on improvements to infrastructure efficiency. While great strides have been made in this area, the potential for further improvement is diminishing. At the same time, we have been learning more about how data centers use resources and the ways in which they convert resources into their end product: information. While the interest and attention on infrastructure efficiency has been warranted, the real issue with data center power consumption has been a general lack of control over how data centers utilize IT assets. If IT utilization rates had been held constant over the past eight years, it is possible that the aggregate power consumption of volume servers in the U.S. would have held close to constant as well. Modeling work at Dell has shown that technologies and policies available to IT managers today have the potential to reverse the trend of declining IT utilization with resultant positive effects on data center power consumption. The Greenest data center is thus, not the one with the best efficiency with respect to delivering power to the IT equipment, but, instead, the one that manages to make the best use of the IT equipment it has commissioned. Introduction Most of us are aware these days of increasing concerns about the cost and availability of energy. We re also aware that we are now living in the Connected Era. Compute power, and our ability to leverage that power, has driven significant productivity and economic growth. It is not unexpected, then, that these two trends are converging. An increasing demand for computation has led to increasing industry power consumption. This in turn, has led to concerns about the sustainability of this computing engine: Can we support our needs for computation with the resources required by our servers and data centers? Industry action to-date has been substantial, but with a strong focus on garnering benefits from improving data center infrastructure efficiency minimizing losses in power distribution and improving facility cooling efficiency. Today, however, available power and cooling products and emergent power and cooling architectures are quickly reaching economic limits on efficiency / performance. In addition, an analysis of Data Center Productivity shows that these benefits, while very important, are only a stepping stone to more significant strategies with a more profound effect on data center performance. The much greater problems are the mechanisms our industry has incorporated into its IT architectures and policies that have led to chronic IT waste. In the future the greenest data center will not necessarily be the one with the most efficient power distribution architecture or the one that best leverages the local environment to minimize power consumption related to cooling equipment. Instead, Green will be defined by the efficiency with which a data center converts its resources into computation. Management of these facilities will focus on minimizing IT waste - solving the problems of poor utilization of IT assets and allocation of resources to relatively less productive equipment. Modern manufacturing facilities go to great lengths to ensure that capital equipment is properly utilized. Why should data centers be any less disciplined? 2 Power and Consumption and Energy Efficiency in the Data Center While data center owners and managers are concerned about the longevity of their data centers and their future ability to implement applications and commission equipment, aggregate server and data center power consumption has drawn the attention of individuals and organizations developing and driving energy policy worldwide. By now, many, if not most, of us are aware of the findings of the EPA s report on Server and Data Center Power Consumption from August of 2007 (U.S. EPA, 2007). One of the conclusions of this report was that, in the U.S. in 2011, servers and data centers could consume 2.5% of all purchased electricity. The figures for server and data center power consumption are staggering. They demand action. In order to determine the correct action, however, we must look at the root cause behind these numbers. In a precursor to the EPA s report in August of 2007, Dr. Jon Koomey published a detailed analysis of aggregate server power consumption (Koomey, 2007). In his executive summary, Dr. Koomey attributes most of the increase in server power consumption to growth in the number of least expensive servers, with only a small part in the growth in aggregate power consumption attributed to increases in power

4 consumption per unit. The implication is that the demand for computation is the root cause of this issue, not inherent runaway issues with individual server power or data center infrastructure waste. This need for computation is, in large part, a reflection of our transition to an economy based on information and computation. In February of this year, the ACEEE released its report on the effect of IT and Communications Technologies on Economic Growth and Economic Energy Efficiency(Laitner & Ehrhardt-Martinez, 2008). Among their findings were a 10:1 savings of energy invested in IT - one kw consumed in IT displaces 10 kw of power consumption elsewhere in the economy. In addition, the ACEEE found that the energy required to produce a dollar s worth of economic output today is less than half of that required in Figure 1: Projected Data Center Energy Use under Five Scenarios (U.S. EPA, 2007) Clearly, the watchword for handling issues around server and data center energy consumption is caution. Our data centers must be able to support our organizations increasing needs for computation. At the same time, public policy must be careful not to place a bottleneck on one of the most important engines for economic growth present in our society and one of the most effective tools in our arsenal for managing society s overall energy consumption. Current Industry and Governmental Efforts These server and data center power consumption issues have triggered strong responses from both industry stakeholders and governments worldwide. Industry efforts have focused on pulling various stakeholders together to identify systemic issues and develop an orchestrated approach to addressing them. Government efforts have focused on communicating high-level guidance to data center owners and operators, but also creating broad incentives (labeling programs) and identifying important overall goals. Both industry and government entities have agreed that both parties need better information on data center power consumption. Industry Efforts Over the past few years, the industry has produced a number of highly visible initiatives aimed at improving server and data center energy consumption. Examples are The Green Grid, the Climate Savers Computing Initiative and 80Plus. 80Plus is an electric-utility incentive program focusing on improving the efficiency of computer power supplies. Climate Savers targets power consumption characteristics and power management features of computing devices, focusing on individual IT components. The Green Grid targets improvements in data center energy efficiency focusing more on the data center as a system. Government and Policy Initiatives Policy-making organizations across the world are driving a number of initiatives in this space as well copying programs demonstrating success in other industries into this space. The EPA s Energy Star program has been focused on both servers and data centers. Similarly, the U.S. Department of Energy is extending its Save Energy Now program into the space as well. Across the Atlantic, the European Commission is developing Codes of Conduct for data centers. We also see significant efforts in China, Japan, and Australia

5 Industry and Government Common Cause In order to provide guidance to data center owners and operators, however, both industry groups and policy-making organizations need means for evaluating these facilities. These organizations are looking for metrics that would enable data center operators to evaluate themselves both against industry averages and other facilities. Frequently, the miles-per-gallon metric applied to motor vehicles is held up as an example of that which is needed for data centers. The industry has developed metrics for evaluating the efficiency with which a data center delivers power to data center equipment. These metrics are very helpful in providing guidance with respect to power consumption, but are only useful for making decisions about facility infrastructure specifically, power distribution and air conditioning equipment and architectures. Focusing on Efficiency Having available metrics on data center infrastructure efficiency (The Green Grid, 2007) has been very helpful to the industry and to policy-makers looking to manage data center power consumption. The consequences are, however, that proposed policies and initiatives are focused on data center infrastructure efficiency. These do help address some of the energy consumption issues in data centers, but over-reliance on these metrics can potentially prevent focus on those areas where the most significant opportunities lay. The most visible goals set for data centers have come from U.S. policy-makers. The Department of Energy, through their Save Energy Now program, has set a goal to improve the data center energy efficiency of 1500 mid-tier and enterprise-class data centers an average of 25% by the beginning of 2011, with 200 enterprise-class data centers improving their data center energy efficiency by 50% (Scheihing, 2008). The proposed EC Code of Conduct for Data Centers (Data Centre Code of Conduct Working Group, 2008) specifically calls out the data center infrastructure efficiency metrics promoted by The Green Grid. A number of the commitments spelled out in this document refer directly to power calculations around the infrastructure metrics. In addition, however, the EC acknowledges that additional metrics will be developed that relate to the efficiency with which IT equipment converts power into computation ( asset efficiency ) and that future versions of the Code of Conduct will be more specific in this area. Framing the Problem The focus on efficiency has been important. There is, and there will continue to be for some time, opportunities to improve data center energy efficiency in updating, and more efficiently operating, power and cooling equipment. The most significant areas for improvement, however, lie within the IT realm. There is far more opportunity in management of IT assets than there is in infrastructure. Power and Cooling: Past, Present, and Future As the industry has only recently begun collecting and analyzing data on data center power consumption, it is difficult to document historical trends. A white paper initially published by APC in 2006 stated that 70% of the input power into a typical data center is either required by cooling equipment or lost in power distribution or (Rasmussen, 2006). Jon Koomey s paper on server and data center power consumption (Koomey, 2007) estimated that half of the power delivered to the facility was lost in power distribution or consumed in cooling. There is strong anecdotal evidence, however, that industry interest in power and cooling has resulted in improvements both to specific data centers and to the industry as a whole. At the component level, there is strong evidence that power distribution component efficiencies have significantly improved (The Green Grid, 2008). At the data center level, the evidence is at least as strong. For example, Microsoft and Google have both been very proactive with respect to managing their data centers. Microsoft has recently reported an annual Power Usage Effectiveness (PUE) of 1.22 for their Chicago facility (Manos, 2008), and Google has recently reported a PUE of 1.15 (Google, 2008). With best-in-class PUEs moving from > 2.0 to 1.15 to 1.25, there is little headroom left for additional improvements. A perfect PUE would be 1.0. This implies that a data center s power distribution network sees zero losses and that no energy is required to cool the equipment in the data center. Clearly,

6 there is a limit to the opportunity for power and cooling components and architectures to improve data center energy efficiency. If we want data centers to continue to improve, we must look elsewhere. Information Technology Whereas power and cooling components and power and cooling architectures have physical performance limitations that are clearly in sight, the limits to Information Technology are not as well understood. Computer performance has been growing exponentially for decades. While Moore s law specifically calls out only the number of transistors that can be placed on an integrated circuit inexpensively, in practice, this has also meant that processor power has increased accordingly. Figure 2 shows the improvement of processor performance over time based on Dell-reported data for the CFP2000 component-level benchmark. Over the past seven years, our products have seen a 32-fold improvement in performance. While even Moore, himself, argues that there are limits to Moore s law (Gruene, 2007 ) (Gardiner, 2007), he also states that Moore s Law has always been believed to be coming to an end within two or three generations out from current manufacturing processes. At least for the foreseeable future, performance will continue to increase exponentially. Figure 2: Dell Historical System Performance (CFP2000rates) The Future for Facility Productivity The focus on the efficient delivery of power to IT equipment has been useful, but given that infrastructure efficiencies are flattening out and processing power continues to improve exponentially, any effort to manage the energy efficiency of the data center must start seriously focusing on IT efficiency as well. Figure 3 shows the expected relationship between Data Center Infrastructure Efficiency (DCiE), IT Productivity and Facility Productivity. As mentioned earlier, the best that can be achieved, with respect to power and cooling efficiency is 100%. This represents a power distribution architecture exhibiting no losses and a cooling architecture that is entirely passive (i.e., no active components requiring power). As the industry approaches this point, power and cooling capital costs can be expected to rise. At some point, there may be little to no economic benefit to further improvement. IT Productivity, on the other hand, should continue to improve as long as the industry s products continue to follow Moore s Law. The conclusion is that facility productivity will quickly start following IT productivity, as opposed to power and cooling efficiency. The Green data center must manage both infrastructure efficiency and IT productivity. Managing for infrastructure efficiency, however, will quickly become focused on meeting a set target one that will not improve greatly over time. Once the equipment is in place and the policies have been set, there will be little change other than operational and environmental maintenance. Managing for IT productivity, however, will mean tracking to a moving target, constantly being aware of technological improvements 5 PUE is Power Usage Effectiveness, defined as Power Delivered to the Facility / Power Delivered to the IT Equipment (The Green Grid, 2007). 5

7 and treating the IT core of the data center as a dynamic entity. The benefits, however, are clear. The data center that manages IT productivity successfully may be significantly more productive, with respect to resources consumed, than a data center that focuses solely on infrastructure efficiency. Managing Data Centers for Productivity While the infrastructure metrics mentioned above are extremely useful to provide insight on, and help manage, facility infrastructure, they provide no guidance as to how to manage the IT equipment within the data center. Understanding the limitations of existing metrics, policy-makers and industry stakeholders alike have been looking for means to measure the output of these facilities metrics that establish the Useful Work produced by the data center. Figure 3: Factors in Improving Facility Productivity Metrics for Data Center Productivity IT productivity should focus on two issues: Utilization of existing IT resources and expected performance per watt of IT assets. These two issues are separate, but related. It is possible to utilize existing assets well but have poor IT productivity. This is common in some older facilities where IT assets are upgraded infrequently. Similarly, a data center that commissions the most up-to-date IT equipment, but does a poor job of utilizing that equipment, leaves a substantial amount of potential productivity on the table. Accordingly, the industry should focus on two metrics to better manage issues around IT productivity: Data Center IT Utilization (DCIU) and Data Center Performance per Watt (DCPpW). Data Center IT Utilization (DCIU) The first of these new metrics, Data Center IT Utilization (DCIU), is meant to represent how much of IT equipments potential is currently being utilized. There are very few systems commissioned in data centers that are running 100% of the time at 100% utilization. DCIU is a measure of how effectively an organization uses those capital assets it has acquired for its data centers. DCIU should not simply be an average of utilization rates for existing equipment, but should, instead, be represented simply as the ratio of the amount of Useful Work produced by the data center and the maximum amount of work that could be produced if the data center were able to maximize all of its components utilization rates in other words: Data Center IT Utilization = (Total Useful Work) (Total Compute Capacity) While Total Useful Work represents the aggregate computation performed in the data center, Total Compute Capacity represents the potential amount of computation available if all compute resources 6 6 IT Productivity is defined by the amount of processing or computation completed compared to the resources consumed by the IT equipment. This document will also define, and refer to this quantity as, Data Center Performance per Watt. 7 Aggregation of Dell-reported benchmark data (CFP2000rates) to SPEC.org (January 2002 to January 2007). The CFP2000 is a component-level benchmark suite for SPEC CPU2000 that measures and compares compute-intensive floating point performance.

8 were being utilized to their full potential. While interesting, this metric remains academic unless there is some means for measuring or estimating Useful Work in the data center and a means for measuring Total Compute Capacity. In addition, for an aggregate IT utilization to have meaning, these two elements to the metric must use the same foundation. I.e., if an industry standard benchmark is used for estimating Total Compute Capacity, that benchmark must be reflected in the approach taken to measure or estimate Useful Work. At Dell, we have been investigating this issue and have developed an initial approach that shows promise. With this approach in hand, more opportunities arise for managing the data center. We can now investigate how IT deployment and operations policies affect the ROI or ROA for Data Center capital expenditures. Data Center Performance per Watt Data Center Performance per Watt works in a manner similar to Data Center IT Utilization. It is not meant to be an average of Performance per Watt measurements or individual components, but must be an aggregate calculation Total Useful Work divided by Facility Power Consumption. Data Center Performance per Watt = (Total Useful Work) (Facility Power Consumption) This is similar to the Data Center Energy Productivity (DCeP) metric proposed by The Green Grid (The Green Grid, 2008) and CUPS, proposed by Emerson (Emerson Network Power, 2008). For purposes of this paper, this metric is referred to as DCPpW as the specifics for calculating this metric differ from the formulation proposed by The Green Grid and CUPS is a generic measurement that is specifically related only to the year in which a server was purchased. Over time, as the industry settles on a standard means for calculating the productivity of data centers, Dell will likely adopt the industry s recommendations. As with DCIU, in order to be meaningful, the DCPpW metric requires an approach to calculating the Useful Work being performed by a system in the data center. Dell has chosen an initial approach and some of the results of that work are presented later in this document. DCPpW also enables new opportunities or approaches with respect to data center management. This is a true productivity number work out divided by resources in. With a means for estimating this, Dell can investigate how different data center decisions affect the use of resources and improve the data center s ability to convert those resources into processing. This will be the core of the Green data center in the future. Where We ve Been Understanding the Past Issues and Real Opportunity Not only are these metrics useful for making day-to-day decisions in the data center, they also provide insights into broader issues associated with server and data center power consumption. Figure 4 shows the evolution of these metrics for a model 5000 ft2 data center, taken from Dell s Data Center Performance Evaluation Tool. The model suggests that, over the last eight years, DCIU for this sample data center has been cut in half. Despite the reduction in asset utilization, however, the data center is still estimated to be up to four times more productive in 2008 as it was in At the same time that the industry has seen this sort of decline in IT utilization, data center power consumption has gone up. According to the EPA s report on server and data center power consumption, volume servers saw an annual increase in power consumption of 17% between 2000 and Figure 5 compares the EPA s growth curve for volume server power consumption with an adjusted curve estimating the power that would have been required by volume servers assuming a constant 12% rate for server utilization. The modeling suggests that, had IT utilization remained flat over this time, a significant fraction of the increase described by the EPA would not have occurred. 8 Data from Dell s facility productivity model 9 The current approach scales a system s expected maximum performance (from published benchmark data), with current CPU utilization and current CPU clock speed (collected in real-time). 10 Power and energy are confusing quantities to many. By definition, power is the rate at which energy is produced or consumed with respect to time. To be meaningful, therefore, the numerator, Work (Performance), must also be a rate. Dell is defining Work as the rate at which operations are completed with respect to time. Using this approach DCPpW could also be defined as a number of operations completed per Joule. 11 Once again, maximum system performance is scaled by current CPU utilization and current CPU clock speed. 12 Internal Dell tool 7

9 Figure 4: Estimate of Historical Data Center Productivity Metrics for a Sample Data Center Clearly then, the data shows that, with respect to data center energy consumption, the issues in the past are the same as the drivers of the future. Issues with IT utilization have made data center energy consumption an issue and future facility productivity will be driven by the productivity of our IT equipment. The focus on power and cooling is important, but if IT waste is not managed, the core problem will be unresolved. Insight into the Data Center It is helpful that these metrics address energy consumption at the macro level, but in order to be useful, they must also provide direct guidance for individual facilities. Without mechanisms that enable data center professionals to manage for productivity, the argument is interesting, but academic. Fortunately, DCIU, DCPpW, and Dell s formulation for an estimate of data center useful work are also useful at the micro level. Figure 5: Comparison of Estimated and Adjusted Energy Consumption for Volume Servers ( ) When we talk to our customers about the challenges they face with respect to energy consumption, we usually hear one or more of a number of separate, though related, issues. Data centers can face very pragmatic issues with the size of their utility bill. They frequently have environmental issues such as thermal hotspots or specific power distribution issues. Occasionally, their suppliers (local utilities) place hard limits on their power consumption. Above all of these, however, the main issue is of facility longevity. A new data center is a large capital expense and IT organizations prefer, whenever possible, to defray or avoid this entirely. In many cases, however, their data centers and the power, cooling and space provided within these data centers, do not seem to co-operate. Appearances, however, are frequently deceiving. Although many data centers appear to be at the limits 13 Calculated through the Dell Data Center Performance Estimation Tool (DC PET, internal Dell tool) Baseline energy consumption data from EPA report on server and data center power consumption (U.S. EPA, 2007); adjusted data calculated from baseline data and DC PET historical server utilization estimates.

10 of their capacity; few data centers are at the limits of their potential. The new metrics for data center productivity will help find this potential both by pointing out areas of remediation in existing data centers and helping data center managers set on-going data center management policy decisions. Understanding an Existing Data Center As part of a larger effort to develop prescriptive responses for legacy data centers, earlier this year Dell created sample infrastructure and IT populations for a typical 5000 ft^2 data center initially constructed and commissioned in 2000 (we refer to this data center as DM1 ). The IT population model was developed by copying existing rack populations from Dell production data centers in Austin and identifying specific servers in the population in such a way as to refer back to existing Dell production equipment. Different sections of DM1 s IT population represent different periods of time during its life. The latest servers in this IT population are Dell 9th generation products, assumed to have been commissioned in Figure 6 shows the breakdown, by server generation, of DM1 s server population. Specific servers were chosen for the IT population and are identified by asset tag in order to guarantee that both real-time system performance data and server configuration information are available for all members of the population. The availability of server performance data, as well as server configuration data (model, processor type, processor clock, memory) enables the estimation of useful work for each server in the population. Figure 6: DM1 Starting Server Population Analysis of the data provides some interesting insights. First, the majority of work in the data center is performed by relatively few servers. Figure 7 shows a Pareto chart of the data. In this dataset, those servers in the top quartile are responsible for about 80% of the data center s processing output. Those servers in the next quartile are performing a little over 10% of the data center s processing. This means that those servers in the third and fourth quartiles are, together, providing less than 10% of the data center s output. Upon a review of this data, it becomes clear that this server population is a strong candidate for consolidation with the intent to improve asset productivity. Figure 7: Pareto Chart of DM1 Server Population Useful Work 9

11 Second, different sections of the data center exhibit significantly different productivity characteristics. Figure 8 provides an estimate of the relative productivity of each row in the data center. In our dataset, we assumed that, as the data center was commissioned, servers were installed starting in row 1. As a result, the lowest numbered rows in this data center were comprised of the oldest equipment. This is a deployment strategy typical of many data centers. The consequence of that strategy, however, is that most of the Useful Work in this data center is being performed in those rows where servers have most recently been commissioned. In this instance, the data suggests that these rows may be a natural target for an effort aimed at improving the overall productivity of this data center G 8G 6G 4G 3G Row Figure 8: Estimated Relative Work per Rack by Data Center Row (DM1) While these insights are focused on a specific server population, they highlight the importance both of having productivity-related metrics and managing to them. With this information, data center managers can design projects that improve the greenness of their data centers by improving the productivity of their server populations. Even though these changes would be applied within the IT population, issues around IT utilization are such that the magnitude of the potential improvement dwarfs the available opportunity in improving infrastructure performance. The Effect of Policy on Productivity The previous example looks at a specific server population at a particular point in time. To firmly grasp the potential impact of managing productivity by managing IT utilization, however, one must look into the future of the data center. The metrics described above provide a means for exploration. Using these metrics, we have developed a model that looks into a data center s future, estimating the processing required by the data center and the server population required to support that processing. Figure 9 shows some of the model s results: the expected change in a data center s productivity, over time, as a function of different operational policies pertaining to virtualization and the replacement of deployed IT hardware. With a re-definition of the Green data center to be one that makes the best use of available resources, as opposed to one that delivers power to IT equipment efficiently, this curve becomes a direct reflection of how Green a data center is at any point-in-time. Figure 9: Evolution of a Data Center s Expected Productivity over Time 15 This assumes equal performance on behalf of the infrastructure with respect to each row. 10

12 The first conclusion is that a data center is a dynamic facility that should constantly improve over time regardless of policy. This is a result of the continuous improvement in performance per watt of servers, generation over generation. The data center of tomorrow should be more efficient and more productive than the data center of today. That being said, however, policy choices do provide environments that enable relatively smaller or relatively larger improvements. A data center that adopts aggressive policies towards implementation of technologies that give it control over IT utilization and policies that guarantee prompt replacement of relatively poor performing equipment could see twice the productivity of a more conservatively managed facility by Figure 10: Data Center IT Utilization Estimates The Effect of Policy on Utilization The main driver for improved productivity is clear: improved IT utilization. Data center professionals have a number of means to exert active control over their utilization of IT equipment, with Virtualization being one of the most popular today. In any case, however, standalone applications running on individual servers frequently hold the data center back. Figure 10 shows the model s expectations with respect to Data Center IT Utilization (DCIU) with respect to different virtualization adoption and hardware refresh scenarios. Even with these policies, momentum in the deployment of equipment will result in a slight decline in IT utilization until As adoption of virtualization continues, however, and hardware refresh policies start to have affect, the IT utilization curve starts climbing again. It is only with an aggressive approach to virtualization, however, that IT utilization may exceed historical levels by In fact, even conservative approaches to virtualization only halt the decline in utilization as any pool of work commissioned in a one-application-per-server use model pulls down the aggregate Data Center IT Utilization. The Effect of Policy on Power Consumption Still, for many individuals, a Green data center is governed by that facilities use of resources. As our model allows us to predict server populations, with reasonable assumptions about future server power consumption and data center infrastructure efficiency, we can estimate a data center s power consumption over time. Figure 11 shows the model s results for our sample data center. The potential exists for this data center to cut its power consumption by more than half by In addition, there s a very clear difference in data center power consumption before and after adoption of virtualization. Prior to the adoption of this technology, control over IT asset utilization was difficult With this technology, however, it becomes possible to manage to IT utilization, instead of accepting it as a result of application commissioning. Once the data center can control IT utilization, it can leverage the improvements in performance that occur with new generations of servers, magnifying the benefits of refreshing legacy hardware. 16 Dell s Data Center Performance Estimation Tool (DC PET), internal Dell tool 17 Aggressive adoption of virtualization implies that, by 2012, 90% of all new work performed by the data center is either performed on virtual machines or represented by scalable applications that enable data center professionals to manage utilization Specifically, energy.

13 Figure 11: Estimated Data Center Power Consumption as a Function of Utilization Policies Future Areas of Investigation The initial areas of investigation of this work involved adoption of virtualization and the speed with which hardware is refreshed. It is the availability of a metric that estimates aggregate data center IT utilization that makes this possible. With this metric, however, there are a number of additional areas where further research would be valuable. Disaster Recovery Continuity of business being important for any organization s vitality, Disaster Recovery may be the most important operational concern of an IT organization. It may, however, significantly affect utilization of IT assets. Until now, we have not had a means for understanding how DR affects the productivity, efficiency or greenness of the data center. With DCIU we can now size the effect of DR decisions on these key data center performance characteristics. Future work in this area should look into a comparison of the protection offered by various DR options and the effects of deploying those options on energy consumption, data center size, server population and total cost of ownership. With a focus on aggregate IT utilization, future DR innovations may enable the same, or greater, level of protection as today while consuming fewer resources in the data center. Cloud Computing Cloud Computing is a hot topic within the industry today. It is a general concept that incorporates a number of technology trends, including Software as a Service (SaaS). One of the themes within Cloud Computing is the disaggregation of hardware and software the user of the software and the executor of the software may bear no relationship to each other. With this disaggregation, another theme arising from Cloud Computing is the notion of commoditization of computation. Maximizing the efficiency of a compute cloud at the node, rack, and facility level is a key source of business value and an important design consideration. (Pike, Schmitt, Frankovsky, & Brannon, February). Those organizations that have the most productive data centers will have a strong advantage over those with which they compete. Other organizations, those considering leveraging the cloud for their computation needs may have to compare the productivity of their own data centers to that of their potential compute suppliers. This is difficult without strong metrics in this area. DCIU and DCPpW may help answer the question as to whether or not the cloud is green. Total and Projected Cost of Ownership In the final analysis, productivity may be important, but many of the potential policy changes (e.g. more frequent hardware refresh) may be hard to justify unless the changes result in lower IT costs. Fortunately, the sorts of analyses that become possible with the metrics described in this document (DCIU, DCPpW) provide a means for estimating the cost consequences of deployment and operations policies High performance computing clusters are, occasionally, an exception to this.

14 In addition, projecting future needs of the data center and future IT costs is easier with a model for estimating the useful work performed by, or required by, the data center. With these types of models, we can look into a data center s future to understand how the policies we set today will affect tomorrow s costs of operations as well. Conclusion If you cannot measure a quantity, you cannot control it. While this maxim was originally tied to the science of physical measurements, this holds true for the data center as well. There are a number of metrics available today for data center professionals to use as they face difficult decisions pertaining to facility planning, equipment deployment and day-to-day operations. At the moment, however, these metrics are focused solely on facility infrastructure. To better control the energy consumption of the world s data centers Dell recommends supplementing the existing infrastructure metrics with new metrics focused on IT assets. The metrics mentioned in this document, Data Center IT Utilization (DCIU) and Data Center Performance per Watt (DCPpW), can provide critical guidance. DCIU tells how well IT equipment is being utilized. DCPpW tells about the overall productivity of the data center. With these metrics/tools in hand, the notion of the Green data center can be revisited. With Productivity as a guide, we find that, while power and cooling are still extremely important, the Greenest data centers may ultimately be the ones that have control over the utilization of their IT assets and are making the best use of the most up-to-date compute servers, storage equipment, and networking equipment. THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL ERRORS AND TECHNICAL INACCURACIES. THE CONTENT IS PROVIDED AS IS, WITHOUT EXPRESS OR IMPLIED WARRANTIES OF ANY KIND. Works Cited Data Centre Code of Conduct Working Group. (2008). Code of Conduct on Data Centres Version 0.8. Retrieved October 28, 2008, from End-use Efficiency Activities at European Commission: sunbird.jrc.it/energyefficiency/pdf/meeting%20data%20centers%20coc%209%20april%202008/ CoC%20DC-v0%208-WORKING-DRAFT.pdf Emerson Network Power. (2008, November). Energy Logic: Calculating and Prioritizing Your Data Center IT Efficiency Actions. Retrieved December 1, 2008, from Emerson Network Power: Gardiner, B. (2007, September 18). IDF: Gordon Moore Predicts End of Moore s Law (Again). Retrieved November 4, 2008, from Epicenter: Google. (2008). Data Center Efficiency Measurements. Retrieved November 4, 2008, from Google: Gruene, W. (2007, September 18). Gordon Moore says Moore s Law will hit fundamental barrier in 10 to 15 years. Retrieved November 7, 2008, from TGDaily: view/33924/135/ Koomey, J. G. (2007, February 15). Estimating Total Power Consumption by Servers in the U.S. and the World. Retrieved October 31, 2008, from AMD Business: svrpwrusecompletefinal.pdf Laitner, J. A., & Ehrhardt-Martinez, K. (2008, February). Information and Communication Technologies: The Power of Productivity. Retrieved October 31, 2008, from American Council for an Energy-Efficienct Technology: Manos, M. (2008, October 20). Out of the Box Paradox. (M. Manos, Ed.) Retrieved November 4, 2008, from LooseBolts: 13

15 Pike, J., Schmitt, T., Frankovsky, F., & Brannon, T. (February, 2008). Creating a Hyper-Efficient Hyper- Scale Data Center. Dell Power Solutions, pp Rasmussen, N. (2006). Electrical Efficiency Modeling for Data Centers - APC White Paper #113. Retrieved October 30, 2008, from APC Product Information: NRAN-66CK3D_R1_EN.pdf Scheihing, P. (2008). DOE Data Center Energy Efficiency Program. Retrieved October 28, 2008, from U.S. DOE Energy Efficiency and Renewable Energy (EERE): saveenergynow/pdfs/doe_data_centers_presentation.pdf The Green Grid. (2008, May 9). A Framework for Data Center Energy Productivity. Retrieved November 7, 2008, from The Green Grid: Framework_for_Data_Center_Energy_Productivity pdf The Green Grid. (2007). The Green Grid Data Center Power Efficiency Metrics: PUE and DCiE. Retrieved October 28, 2008, from The Green Grid: Power_Efficiency_Metrics_PUE_and_DCiE.pdf The Green Grid. (2008). The Green Grid Peer Review of DC Power for Improved Data Center Efficiency by Lawrence Berkeley National Laboratory. Retrieved November 4, 2008, from The Green Grid: U.S. EPA. (2007, August 2). Report to Congress on Server and Data Center Energy Efficiency - Public Law Retrieved October 31, 2008, from ENERGY STAR: partners/prod_development/downloads/epa_datacenter_report_congress_final1.pdf 14

Managing Power Usage with Energy Efficiency Metrics: The Available Me...

Managing Power Usage with Energy Efficiency Metrics: The Available Me... 1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount

More information

Datacenter Efficiency

Datacenter Efficiency EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Measuring Energy Efficiency in a Data Center

Measuring Energy Efficiency in a Data Center The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics

More information

Selecting an Industry-Standard Metric for Data Center Efficiency

Selecting an Industry-Standard Metric for Data Center Efficiency Selecting an Industry-Standard Metric for Data Center Efficiency By Neil Rasmussen White Paper #157 Executive Summary The development of standards for the measurement and specification of data center efficiency

More information

Greener Pastures for Your Data Center

Greener Pastures for Your Data Center W H I T E P A P E R Greener Pastures for Your Data Center 2 Executive Summary Following a green path, once a concept relegated to a small group of environmentalists and the U.S. Environmental Protection

More information

Increasing Energ y Efficiency In Data Centers

Increasing Energ y Efficiency In Data Centers The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Windows Server 2008 R2 Hyper-V Live Migration

Windows Server 2008 R2 Hyper-V Live Migration Windows Server 2008 R2 Hyper-V Live Migration White Paper Published: August 09 This is a preliminary document and may be changed substantially prior to final commercial release of the software described

More information

EX ECUT IV E ST RAT EG Y BR IE F. Server Design for Microsoft s Cloud Infrastructure. Cloud. Resources

EX ECUT IV E ST RAT EG Y BR IE F. Server Design for Microsoft s Cloud Infrastructure. Cloud. Resources EX ECUT IV E ST RAT EG Y BR IE F Server Design for Microsoft s Cloud Infrastructure Cloud Resources 01 Server Design for Cloud Infrastructure / Executive Strategy Brief Cloud-based applications are inherently

More information

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell Solve your IT energy crisis WITH AN ENERGY SMART SOLUTION FROM DELL overcome DATA center energy challenges IT managers share a common and pressing problem: how to reduce energy consumption and cost without

More information

Harmonizing Global Metrics for Data Center Energy Efficiency

Harmonizing Global Metrics for Data Center Energy Efficiency Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

EU Code of Conduct for Data Centre Efficiency

EU Code of Conduct for Data Centre Efficiency EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry

More information

PROJECTING ANNUAL NEW DATACENTER CONSTRUCTION MARKET SIZE. By Christian L. Belady, P.E.

PROJECTING ANNUAL NEW DATACENTER CONSTRUCTION MARKET SIZE. By Christian L. Belady, P.E. PROJECTING ANNUAL NEW DATACENTER CONSTRUCTION MARKET SIZE By Christian L. Belady, P.E. GLOBAL FOUNDATION SERVICES MARCH 2011 Author s Note: this work is intended to be an exercise to estimate the size

More information

Enterprise PC Power Management Tools: Greening IT from the Top Down. By Michael D. Barr Chris Harty Jane Nero

Enterprise PC Power Management Tools: Greening IT from the Top Down. By Michael D. Barr Chris Harty Jane Nero QDI STRATEGIES 20/20 Vision for Marketing Breakthroughs Enterprise PC Power Management Tools: Greening IT from the Top Down By Michael D. Barr Chris Harty Jane Nero Abstract There are approximately 108

More information

Energy Savings in the Data Center Starts with Power Monitoring

Energy Savings in the Data Center Starts with Power Monitoring Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.

More information

Managing Data Center Power and Cooling

Managing Data Center Power and Cooling White PAPER Managing Data Center Power and Cooling Introduction: Crisis in Power and Cooling As server microprocessors become more powerful in accordance with Moore s Law, they also consume more power

More information

Cloud Computing Capacity Planning. Maximizing Cloud Value. Authors: Jose Vargas, Clint Sherwood. Organization: IBM Cloud Labs

Cloud Computing Capacity Planning. Maximizing Cloud Value. Authors: Jose Vargas, Clint Sherwood. Organization: IBM Cloud Labs Cloud Computing Capacity Planning Authors: Jose Vargas, Clint Sherwood Organization: IBM Cloud Labs Web address: ibm.com/websphere/developer/zones/hipods Date: 3 November 2010 Status: Version 1.0 Abstract:

More information

Global Headquarters: 5 Speen Street Framingham, MA 01701 USA P.508.872.8200 F.508.935.4015 www.idc.com

Global Headquarters: 5 Speen Street Framingham, MA 01701 USA P.508.872.8200 F.508.935.4015 www.idc.com WHITE PAPER Solutions for the Datacenter's Thermal Challenges Sponsored by: IBM and Intel Jed Scaramella January 2007 Matthew Eastwood IDC OPINION Global Headquarters: 5 Speen Street Framingham, MA 01701

More information

Optimizing the Performance of Your Longview Application

Optimizing the Performance of Your Longview Application Optimizing the Performance of Your Longview Application François Lalonde, Director Application Support May 15, 2013 Disclaimer This presentation is provided to you solely for information purposes, is not

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

EMC, VNX and ENERGY EFFICIENCY

EMC, VNX and ENERGY EFFICIENCY White Paper EMC, VNX and ENERGY EFFICIENCY Providing industry leadership and customer value Abstract This white paper explains the value EMC places on energy efficiency across the corporation and in particular

More information

20 th Year of Publication. A monthly publication from South Indian Bank. www.sib.co.in

20 th Year of Publication. A monthly publication from South Indian Bank. www.sib.co.in To kindle interest in economic affairs... To empower the student community... Open YAccess www.sib.co.in ho2099@sib.co.in A monthly publication from South Indian Bank 20 th Year of Publication Experience

More information

As a growing number of small- and medium-sized organizations (SMOs),

As a growing number of small- and medium-sized organizations (SMOs), NRDC Issue brief october 2012 ib:12-10-a Is Cloud Computing Always Greener? Finding the Most Energy and Carbon Efficient Information Technology Solutions for Small- and Medium-Sized Organizations As a

More information

Top 5 Reasons to choose Microsoft Windows Server 2008 R2 SP1 Hyper-V over VMware vsphere 5

Top 5 Reasons to choose Microsoft Windows Server 2008 R2 SP1 Hyper-V over VMware vsphere 5 Top 5 Reasons to choose Microsoft Windows Server 2008 R2 SP1 Hyper-V over VMware Published: April 2012 2012 Microsoft Corporation. All rights reserved. This document is provided "as-is." Information and

More information

Manage Your Data: Virtualization for Small Businesses

Manage Your Data: Virtualization for Small Businesses Manage Your Data: Virtualization for Small Businesses July 2012 Contents: Introduction 3 What is Virtualization 4 What Could Virtualization Mean for your Business 5 Is Server Virtualization Right for your

More information

The ROI of Tape Consolidation

The ROI of Tape Consolidation The ROI of Tape Consolidation NOTICE This white paper may contain proprietary information protected by copyright. Information in this white paper is subject to change without notice and does not represent

More information

Identifying Energy Saving Opportunities in the Data Center

Identifying Energy Saving Opportunities in the Data Center Identifying Energy Saving Opportunities in the Data Center Andrew Fanara US EPA ENERGY STAR Product Development Fanara.andrew@epa.gov (206) 553-6377 (Seattle, WA) 1 Data Centers are INFORMATION FACTORIES

More information

Rackspace Cloud Databases and Container-based Virtualization

Rackspace Cloud Databases and Container-based Virtualization Rackspace Cloud Databases and Container-based Virtualization August 2012 J.R. Arredondo @jrarredondo Page 1 of 6 INTRODUCTION When Rackspace set out to build the Cloud Databases product, we asked many

More information

Power Consumption and Cooling in the Data Center: A Survey

Power Consumption and Cooling in the Data Center: A Survey A M a r k e t A n a l y s i s Power Consumption and Cooling in the Data Center: A Survey 1 Executive Summary Power consumption and cooling issues in the data center are important to companies, as evidenced

More information

Application Visibility A Recipe for Conducting Successful Virtualization Projects

Application Visibility A Recipe for Conducting Successful Virtualization Projects Application Visibility A Recipe for Conducting Successful Virtualization Projects White Paper from ManageEngine Web: email: appmanager-support@manageengine.com Table of Contents 1. Introduction 2. Benefits

More information

Capacity planning with Microsoft System Center

Capacity planning with Microsoft System Center Capacity planning with Microsoft System Center Mike Resseler Veeam Product Strategy Specialist, MVP, Microsoft Certified IT Professional, MCSA, MCTS, MCP Modern Data Protection Built for Virtualization

More information

Understanding Date Center. Power Usage Effectiveness

Understanding Date Center. Power Usage Effectiveness Understanding Date Center Power Usage Effectiveness This Dell Technical White Paper explains how to understand Power Usage Effectiveness (PUE) and how it applies to your Data Center. George Richards Dell

More information

BridgeWays Management Pack for VMware ESX

BridgeWays Management Pack for VMware ESX Bridgeways White Paper: Management Pack for VMware ESX BridgeWays Management Pack for VMware ESX Ensuring smooth virtual operations while maximizing your ROI. Published: July 2009 For the latest information,

More information

Is Hyperconverged Cost-Competitive with the Cloud?

Is Hyperconverged Cost-Competitive with the Cloud? Economic Insight Paper Is Hyperconverged Cost-Competitive with the Cloud? An Evaluator Group TCO Analysis Comparing AWS and SimpliVity By Eric Slack, Sr. Analyst January 2016 Enabling you to make the best

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Initial Steps in Capacity Management for the Green Datacenter

Initial Steps in Capacity Management for the Green Datacenter Initial Steps in Capacity Management for the Green Datacenter Stephen Marksamer, Aetna Inc. James Castronovo, Inventa Technologies Table of Contents Introduction... 3 Who Are the Stewards of Green?...

More information

Windows Server 2008 R2 Hyper-V Live Migration

Windows Server 2008 R2 Hyper-V Live Migration Windows Server 2008 R2 Hyper-V Live Migration Table of Contents Overview of Windows Server 2008 R2 Hyper-V Features... 3 Dynamic VM storage... 3 Enhanced Processor Support... 3 Enhanced Networking Support...

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

DELL s Oracle Database Advisor

DELL s Oracle Database Advisor DELL s Oracle Database Advisor Underlying Methodology A Dell Technical White Paper Database Solutions Engineering By Roger Lopez Phani MV Dell Product Group January 2010 THIS WHITE PAPER IS FOR INFORMATIONAL

More information

can you effectively plan for the migration and management of systems and applications on Vblock Platforms?

can you effectively plan for the migration and management of systems and applications on Vblock Platforms? SOLUTION BRIEF CA Capacity Management and Reporting Suite for Vblock Platforms can you effectively plan for the migration and management of systems and applications on Vblock Platforms? agility made possible

More information

Visibility in the Modern Data Center // Solution Overview

Visibility in the Modern Data Center // Solution Overview Introduction The past two decades have seen dramatic shifts in data center design. As application complexity grew, server sprawl pushed out the walls of the data center, expanding both the physical square

More information

IT@Intel. Comparing Multi-Core Processors for Server Virtualization

IT@Intel. Comparing Multi-Core Processors for Server Virtualization White Paper Intel Information Technology Computer Manufacturing Server Virtualization Comparing Multi-Core Processors for Server Virtualization Intel IT tested servers based on select Intel multi-core

More information

Capping Server Cost and Energy Use with Hybrid Cloud Computing

Capping Server Cost and Energy Use with Hybrid Cloud Computing Capping Server Cost and Energy Use with Hybrid Cloud Computing Richard Gimarc Amy Spellmann Mark Preston CA Technologies Uptime Institute RS Performance Connecticut Computer Measurement Group Friday, June

More information

Greener IT Practices. Anthony Suda Network Manager

Greener IT Practices. Anthony Suda Network Manager Greener IT Practices Anthony Suda Network Manager marketing + technology 701.235.5525 888.9.sundog fax: 701.235.8941 2000 44th st s floor 6 fargo, nd 58103 www.sundog.net In our world today, individuals

More information

Server Consolidation for SAP ERP on IBM ex5 enterprise systems with Intel Xeon Processors:

Server Consolidation for SAP ERP on IBM ex5 enterprise systems with Intel Xeon Processors: Server Consolidation for SAP ERP on IBM ex5 enterprise systems with Intel Xeon Processors: Lowering Total Cost of Ownership An Alinean White Paper Published by: Alinean, Inc. 201 S. Orange Ave Suite 1210

More information

DOE Data Center Energy Efficiency Program

DOE Data Center Energy Efficiency Program DOE Data Center Energy Efficiency Program Paul Scheihing U.S. Department of Energy Energy Efficiency and Renewable Energy April 2009 1 DOE Industrial Technologies Program Worki king to improve th e energy

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any

More information

A Microsoft U.S. Public Sector White Paper by Ken Page and Shelly Bird. January 2009. www.microsoft.com/ government

A Microsoft U.S. Public Sector White Paper by Ken Page and Shelly Bird. January 2009. www.microsoft.com/ government Federal Server Core Configuration (FSCC) A high-level overview of the value and benefits of deploying a single, standard, enterprise-wide managed server environment A Microsoft U.S. Public Sector White

More information

Metrics for Computing Performance of Data Center for Instigating Energy Efficient Data Centers

Metrics for Computing Performance of Data Center for Instigating Energy Efficient Data Centers Journal of Scientific & Industrial Research Vol. 73, January 2014, pp. 11-15 Metrics for Computing Performance of Data Center for Instigating Energy Efficient Data Centers Mueen Uddin* 1, Asadullah Shah

More information

Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services

Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services Data Center & IT Infrastructure Optimization Trends & Best Practices Mickey Iqbal - IBM Distinguished Engineer IBM Global Technology Services IT Organizations are Challenged by a Set of Operational Issues

More information

DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused. A Research Report from the Experts in Business-Critical Continuity TM

DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused. A Research Report from the Experts in Business-Critical Continuity TM DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused A Research Report from the Experts in Business-Critical Continuity TM Introduction Data center management is in a stage of

More information

Developing a dynamic, real-time IT infrastructure with Red Hat integrated virtualization

Developing a dynamic, real-time IT infrastructure with Red Hat integrated virtualization Developing a dynamic, real-time IT infrastructure with Red Hat integrated virtualization www.redhat.com Table of contents Introduction Page 3 Benefits of virtualization Page 3 Virtualization challenges

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

Understanding the Business Value of Migrating to Windows Server 2012

Understanding the Business Value of Migrating to Windows Server 2012 WHITE PAPER Understanding the Business Value of Migrating to Windows Server 2012 Sponsored by: Microsoft and Intel Simon Piff February 2015 EXECUTIVE SUMMARY In December 2014, IDC Asia/Pacific undertook

More information

Cloud Computing, Virtualization & Green IT

Cloud Computing, Virtualization & Green IT Cloud Computing, Virtualization & Green IT Cloud computing can change how IT supports business Consider the following: As much as 85% of computing capacity sits idle in distributed computing environments.

More information

Breaking Through the Virtualization Stall Barrier

Breaking Through the Virtualization Stall Barrier Overview... 2 What is the Virtualization Barrier?... 3 Why Should Enterprises Care... 4 Repeatable Practices for Moving Virtualization Forward... 4 Use Case: Running Your Database in the Cloud... 6 Conclusion...

More information

Convergence of Complexity

Convergence of Complexity Convergence of Complexity Optimize Existing Data Center Space Measure And Allocate Energy Cost Plan for new data centers or additional capacity How to make your Data Center Last Longer, Gartner, December

More information

Managing Today s Data Centers Avoiding the Impending Crisis

Managing Today s Data Centers Avoiding the Impending Crisis Managing Today s Data Centers Avoiding the Impending Crisis Steven Yellen Aperture Research Institute EXECUTIVE SUMMARY Organizations are facing an impending data center management crisis. The constant

More information

CASE STUDY ON TEXAS DATA CENTERS AND ENERGY EFFICIENCY

CASE STUDY ON TEXAS DATA CENTERS AND ENERGY EFFICIENCY CASE STUDY ON TEXAS DATA CENTERS AND ENERGY EFFICIENCY PROJECT SCOPE On this project, Austin Energy s (AE) focused on the identification of methods to reduce energy consumption and demand for data centers

More information

How To Value Your Business It

How To Value Your Business It Gain Clarity & Cost Control when Delivering IT Services to the Business A WHITE PAPER BY DAVID S. LINTHICUM Contents Executive Summary 3 Value Shift for Enterprise IT - CIO and Operations Teams 4 Shadow

More information

Data Center Energy Efficiency Looking Beyond PUE

Data Center Energy Efficiency Looking Beyond PUE Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,

More information

Knowledge Base and Research Report

Knowledge Base and Research Report Knowledge Base and Research Report Copyright 2010, GreenWay Collaborative. All Rights Reserved. 46 Kent Hills Lane Wilton, CT Phone: (203) 429-8951 Cell: (203) 246-1156 Contact: Cal Braunstein cbraunstein@rfgonline.com

More information

Optimizing your IT infrastructure. 2012 IBM Corporation

Optimizing your IT infrastructure. 2012 IBM Corporation Optimizing your IT infrastructure 2012 IBM Corporation Please Note: IBM s statements regarding its plans, directions, and intent are subject to change or withdrawal without notice at IBM s sole discretion.

More information

Implementing Hybrid Cloud at Microsoft

Implementing Hybrid Cloud at Microsoft Implementing Hybrid Cloud at Microsoft Published September 2013 The following content may no longer reflect Microsoft s current position or infrastructure. This content should be viewed as reference documentation

More information

Radware ADC-VX Solution. The Agility of Virtual; The Predictability of Physical

Radware ADC-VX Solution. The Agility of Virtual; The Predictability of Physical Radware ADC-VX Solution The Agility of Virtual; The Predictability of Physical Table of Contents General... 3 Virtualization and consolidation trends in the data centers... 3 How virtualization and consolidation

More information

White Paper. Cloud Computing. Effective Web Solution Technology Investment. January 2011. www.k-bc.co.uk

White Paper. Cloud Computing. Effective Web Solution Technology Investment. January 2011. www.k-bc.co.uk White Paper Cloud Computing Effective Web Solution Technology Investment January 2011 www.k-bc.co.uk Cloud Computing The future of effective technology investment The benefit of web solution technology

More information

Managing the Real Cost of On-Demand Enterprise Cloud Services with Chargeback Models

Managing the Real Cost of On-Demand Enterprise Cloud Services with Chargeback Models Managing the Real Cost of On-Demand Enterprise Cloud Services with Chargeback Models A Guide to Cloud Computing Costs, Server Costs, Pricing Plans, and Chargeback Implementation and Systems Introduction

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Maximum performance, minimal risk for data warehousing

Maximum performance, minimal risk for data warehousing SYSTEM X SERVERS SOLUTION BRIEF Maximum performance, minimal risk for data warehousing Microsoft Data Warehouse Fast Track for SQL Server 2014 on System x3850 X6 (95TB) The rapid growth of technology has

More information

How To Optimize Data Center Performance

How To Optimize Data Center Performance Data Center Optimization WHITE PAPER PARC, 3333 Coyote Hill Road, Palo Alto, California 94304 USA +1 650 812 4000 engage@parc.com www.parc.com Abstract Recent trends in data center technology have created

More information

Green HPC - Dynamic Power Management in HPC

Green HPC - Dynamic Power Management in HPC Gr eenhpc Dynami cpower Management i nhpc AT ECHNOL OGYWHI T EP APER Green HPC Dynamic Power Management in HPC 2 Green HPC - Dynamic Power Management in HPC Introduction... 3 Green Strategies... 4 Implementation...

More information

The Trellis Dynamic Infrastructure Optimization Platform

The Trellis Dynamic Infrastructure Optimization Platform Infrastructure Management & Monitoring for Business-Critical Continuity TM The Trellis Dynamic Infrastructure Optimization Platform Delivering Confidence through Connection TM Is Your Data Center Operating

More information

IBM Tivoli Netcool network management solutions for enterprise

IBM Tivoli Netcool network management solutions for enterprise IBM Netcool network management solutions for enterprise The big picture view that focuses on optimizing complex enterprise environments Highlights Enhance network functions in support of business goals

More information

The Green/ Efficiency Metrics Conundrum. Anand Ekbote Vice President, Liebert Monitoring Emerson Network Power

The Green/ Efficiency Metrics Conundrum. Anand Ekbote Vice President, Liebert Monitoring Emerson Network Power The Green/ Efficiency Metrics Conundrum Anand Ekbote Vice President, Liebert Monitoring Emerson Network Power Agenda Green Grid, and Green/ Efficiency Metrics Data Center Efficiency Revisited Energy Logic

More information

WHITE PAPER. Data Center Fabrics. Why the Right Choice is so Important to Your Business

WHITE PAPER. Data Center Fabrics. Why the Right Choice is so Important to Your Business WHITE PAPER Data Center Fabrics Why the Right Choice is so Important to Your Business Introduction Data center fabrics are emerging as the preferred architecture for next-generation virtualized data centers,

More information

It Pays to Know Your Data Center: Saving Money through Increased Efficiency

It Pays to Know Your Data Center: Saving Money through Increased Efficiency It Pays to Know Your Data Center: Saving Money through Increased Efficiency 1 Introduction: Today s Data Center Few enterprises today can deny this truism: their data centers are consuming incredible amounts

More information

managing Cost in the cloud

managing Cost in the cloud managing Cost in the cloud Executive Summary Leveraging cloud computing, specifically Infrastructure-as-a-Service (IaaS), has the potential to substantially lower an organization s infrastructure costs.

More information

10 Practical Tips for Cloud Optimization

10 Practical Tips for Cloud Optimization Real Life in the Cloud The Cloud Sprawl Cloud Control Challenges 1. Transparency 2. Governance. Predictability Cloud Optimization in Action 10 Cloud Optimization Guidelines to Keep in Mind The 11th Guideline:

More information

Cost-effective Strategies for Building the Next-generation Data Center

Cost-effective Strategies for Building the Next-generation Data Center White Paper Cost-effective Strategies for Building the Next-generation Data Center Custom-made servers bearing energy-efficient processors are key to today s cloud computing-inspired architectures. Tom

More information

Energy Efficient MapReduce

Energy Efficient MapReduce Energy Efficient MapReduce Motivation: Energy consumption is an important aspect of datacenters efficiency, the total power consumption in the united states has doubled from 2000 to 2005, representing

More information

solution brief September 2011 Can You Effectively Plan For The Migration And Management of Systems And Applications on Vblock Platforms?

solution brief September 2011 Can You Effectively Plan For The Migration And Management of Systems And Applications on Vblock Platforms? solution brief September 2011 Can You Effectively Plan For The Migration And Management of Systems And Applications on Vblock Platforms? CA Capacity Management and Reporting Suite for Vblock Platforms

More information

icare and the Cloud FOCUS ON PATIENT CARE, NOT SOFTWARE Knowledge Center The Enterprise Cloud EHR

icare and the Cloud FOCUS ON PATIENT CARE, NOT SOFTWARE Knowledge Center The Enterprise Cloud EHR The Enterprise Cloud EHR icare and the Cloud FOCUS ON PATIENT CARE, NOT SOFTWARE Knowledge Center Author: Don Cook Chief Marketing Officer icare.com LLC 2012, icare.com LLC. All rigthts reserved. Las Olas

More information

Application Performance Management

Application Performance Management Application Performance Management Intelligence for an Optimized WAN xo.com Application Performance Management Intelligence for an Optimized WAN Contents Abstract 3 Introduction 3 Business Drivers for

More information

How to Measure Energy Consumption in Your Data Center

How to Measure Energy Consumption in Your Data Center How to Measure Energy Consumption in Your Data Center Gartner RAS Core Research Note G00205428, Rakesh Kumar, 8 September 2010, R3506 02112011 This research outlines a pragmatic approach that should be

More information

Business Startups - Advantages of Using Automation

Business Startups - Advantages of Using Automation CLOUD AUTOMATION How Cloud Automation Can Help You Scale Your IT Services TABLE OF CONTENTS Introduction 03 Business Benefits 07 Administrator Benefits 11 Technical Considerations 14 Conclusion 17 2 INTRODUCTION

More information

Case study: End-to-end data centre infrastructure management

Case study: End-to-end data centre infrastructure management Case study: End-to-end data centre infrastructure management Situation: A leading public sector organisation suspected that their air conditioning units were not cooling the data centre efficiently. Consequently,

More information

How Solace Message Routers Reduce the Cost of IT Infrastructure

How Solace Message Routers Reduce the Cost of IT Infrastructure How Message Routers Reduce the Cost of IT Infrastructure This paper explains how s innovative solution can significantly reduce the total cost of ownership of your messaging middleware platform and IT

More information

Mosaic s IT Director Series. VMware Basics Capacity Planning and Performance Monitoring

Mosaic s IT Director Series. VMware Basics Capacity Planning and Performance Monitoring Mosaic s IT Director Series VMware Basics Capacity Planning and Performance Monitoring VMware Basics Capacity Planning and Performance Monitoring Introduction 3 VMware Complexity 5 VMware Virtual Infrastructure

More information

Smarter Data Centers. Integrated Data Center Service Management

Smarter Data Centers. Integrated Data Center Service Management Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr

More information

Oracle Platform as a Service (PaaS) FAQ

Oracle Platform as a Service (PaaS) FAQ Oracle Platform as a Service (PaaS) FAQ 1. What is Platform as a Service (PaaS)? Platform as a Service (PaaS) is a standardized, shared and elastically scalable application development and deployment platform

More information

How To Find A Sweet Spot Operating Temperature For A Data Center

How To Find A Sweet Spot Operating Temperature For A Data Center Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL

More information

Five Reasons to Make the Move to a Converged Infrastructure

Five Reasons to Make the Move to a Converged Infrastructure A UBM TECHWEB WHITE PAPER SEPTEMBER 2012 Five Reasons to Make the Move to a Converged Infrastructure This is no time for complacency when it comes to data center architecture and operations. Only by moving

More information

You re not alone if you re feeling pressure

You re not alone if you re feeling pressure How the Right Infrastructure Delivers Real SQL Database Virtualization Benefits The amount of digital data stored worldwide stood at 487 billion gigabytes as of May 2009, and data volumes are doubling

More information

REDUCING DATA CENTER POWER CONSUMPTION THROUGH EFFICIENT STORAGE

REDUCING DATA CENTER POWER CONSUMPTION THROUGH EFFICIENT STORAGE NETAPP VISION SERIES REDUCING DATA CENTER POWER CONSUMPTION THROUGH EFFICIENT STORAGE Brett Battles, Cathy Belleville, Susan Grabau, Judith Maurier February 2007 WP-7010-0207 AN EIGHT-POINT PLAN FOR FIGHTING

More information

ATA DRIVEN GLOBAL VISION CLOUD PLATFORM STRATEG N POWERFUL RELEVANT PERFORMANCE SOLUTION CLO IRTUAL BIG DATA SOLUTION ROI FLEXIBLE DATA DRIVEN V

ATA DRIVEN GLOBAL VISION CLOUD PLATFORM STRATEG N POWERFUL RELEVANT PERFORMANCE SOLUTION CLO IRTUAL BIG DATA SOLUTION ROI FLEXIBLE DATA DRIVEN V ATA DRIVEN GLOBAL VISION CLOUD PLATFORM STRATEG N POWERFUL RELEVANT PERFORMANCE SOLUTION CLO IRTUAL BIG DATA SOLUTION ROI FLEXIBLE DATA DRIVEN V WHITE PAPER Maximize IT for Real Business Advantage 3 Key

More information

Data Deduplication: An Essential Component of your Data Protection Strategy

Data Deduplication: An Essential Component of your Data Protection Strategy WHITE PAPER: THE EVOLUTION OF DATA DEDUPLICATION Data Deduplication: An Essential Component of your Data Protection Strategy JULY 2010 Andy Brewerton CA TECHNOLOGIES RECOVERY MANAGEMENT AND DATA MODELLING

More information

Sage ERP I White Paper. Tips for Maximizing the Return on Your ERP Investment

Sage ERP I White Paper. Tips for Maximizing the Return on Your ERP Investment I White Paper Tips for Maximizing the Return on Your ERP Investment Table of Contents Executive Summary... 3 Why Optimize an ERP Investment... 3 Delivering on Business Objectives... 3 Implementation...

More information