commercial gas water heaters
|
|
|
- Erick O’Connor’
- 10 years ago
- Views:
Transcription
1 Instruction Manual commercial gas water heaters American Water Heater Johnson City, TN MODELS BCG3 & ABCG3 SERIES 118/119 INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY Low Lead Content WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor s phone. Follow the gas supplier s instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. Thank you for buying this energy efficient water heater. We appreciate your confidence in our products. Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater. Failure to follow these instructions and safety messages could result in death or serious injury. This manual must remain with the water heater. place these instructions adjacent to heater and notify owner to keep for future reference. PRINTED
2 Table Of Contents Safe Installation, Use and Service... 3 Approvals... 3 General Safety Information Precautions... 5 Grounding Instructions... 5 Hydrogen Gas Flammable... 5 Introduction... 6 Abbreviations Used... 6 Qualifications... 6 Preparing for the Installation... 6 Features And Components... 7 The Eliminator (Self Cleaning System)... 7 High Limit Switch... 7 Electronic Ignition Control... 7 Automatic Flue Damper... 7 Uncrating... 7 Installation Considerations Rough In Dimensions... 8 Locating The Water Heater Clearances NSF Leg Kit...11 Insulation Blanket...11 Hard Water...11 Circulation Pumps High Altitude Installations Installation Requirements Gas Supply Systems Supply Gas Regulator Power Supply Water Temperature Control and Mixing Valves Dishwashing Machines Closed Water Systems Thermal Expansion Temperature-Pressure Relief Valve Contaminated Air Air Requirements Unconfined Space Confined Space Venting Installation Venting Vent Reducer Multiple Heater Manifold Fresh Air Opening for Confined Spaces Outdoor Air Through Two Openings Outdoor Air Through One Opening Outdoor Air Through Two Horizontal Ducts Outdoor Air Through Two Vertical Ducts Air From Other Indoor Spaces Technical Data Venting Mechanical Venting Water Heater Installation Water Line Connections T&P Valve Discharge Pipe Installation Diagrams - Top Inlet/Outlet Usage Heater Wiring Gas Piping Gas Line Leak Testing Purging OPERATION Prior to Start Up Sequence of operation Sequence of Operation Flow Chart Lighting & Operation Labels Adjustments Checking Venting Checking the Input maintenance Venting System Remote Storage Tank Temperature Control Temperature-Pressure Relief Valve Test Anode Rod Inspection Draining and Flushing Recommended Procedure for Periodic Removal or Lime Deposits from the Tank Type Commercial Water Heaters DeLiming Solvents Tank Cleanout Procedure Deliming Using Flo-Jug Method Pilot Burner Main Burner Gas Control Valve service Electrical Servicing Troubleshooting Ignition Module Flue Damper Effikal RVGP-KSF Series Flue Damper Trouble Shooting Guide Troubleshooting Checklist For your information Start up Conditions Operational Conditions Water Piping Diagrams MANIFOLD KITS Notes Warranty
3 Safe Installation, Use and Service The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use, or service this water heater. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which, if not avoided, will result in injury or death. WARNING indicates a potentially hazardous situation which, if not avoided, could result in injury or death. CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage. All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and how to avoid the risk of injury. The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances. This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This water heater can cause low level exposure to some of the substances listed in the Act. APPROVALS Low Lead Content Note: ASME construction is optional on the water heaters covered in this manual. 3
4 General Safety Information Fire or Explosion Hazard Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Avoid all ignition sources if you smell gas. Do not expose water heater controls to excessive gas pressure. Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles. Keep ignition sources away from faucets after extended periods of non-use. Read instruction manual before installing, using or servicing water heater. Fire Hazard For continued protection against risk of fire: Do not install water heater on carpeted floor. Do not operate water heater if flood damaged. Fire and Explosion Hazard Use joint compound or Teflon tape compatible with propane gas. Leak test before placing the water heater in operation. Disconnect gas piping and main gas shutoff valve before leak testing. Install sediment trap in accordance with NFPA 54. CAUTION Property Damage Hazard All water heaters eventually leak. Do not install without adequate drainage. Electrical Shock Hazard Turn off power to the water heater before performing any service. Label all wires prior to disconnecting when performing service. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Failure to follow these instructions can result in personal injury or death. Fire and Explosion Hazard Do not use water heater with any gas other than the gas shown on the rating label. Excessive gas pressure to gas valve can cause serious injury or death. Turn off gas lines during installation. Contact a qualified installer or service agency for installation and service. Jumping out control circuits or components can result in property damage, personal injury or death. Service should only be performed by a qualified service agent using proper test equipment. Altering the water heater controls and/or wiring in any way could result in permanent damage to the controls or water heater and is not covered under the limited warranty. Altering the water heater controls and/or wiring in any way could result in altering the ignition sequence allowing gas to flow to the main burner before the hot surface igniter is at ignition temperature causing delayed ignition which can cause a fire or explosion. Any bypass or alteration of the water heater controls and/or wiring will result in voiding the water heater warranty. 4
5 General Safety Information Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater. Failure to follow these instructions and safety messages could result in death or serious injury. This manual must remain with the water heater. Explosion Hazard Overheated water can cause water tank explosion. Properly sized temperature and pressure relief valve must be installed in the opening provided. Water temperature over 125 F (52 C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury. Feel water before bathing or showering. Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures. CAUTION Improper installation, use and service may result in property damage. Do not operate water heater if flood damaged. Inspect and anode rods regularly, replace if damaged. Install in location with drainage. Fill tank with water before operation. Properly sized thermal expansion tanks are required on all closed water systems. Refer to this manual for installation and service. Verify the power to the water heater is turned off before performing any service procedures. General Safety Information Precautions DO NOT USE THIS water heater IF ANY PART HAS BEEN UNDER WATER. Immediately call a qualified service agency to inspect the water heater and to make a determination on what steps should be taken next. If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualified service agency. 1. External fire. 2. Damage. 3. Firing without water. Hydrogen Gas Flammable Explosion Hazard Flammable hydrogen gases may be present. Keep all ignition sources away from faucet when turning on hot water. GROUNDING INSTRUCTIONS This water heater must be grounded in accordance with the National Electrical Code and/or local codes. These must be followed in all cases. This water heater must be connected to a grounded, permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater, see Figure Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To reduce the risk of injury under these conditions, it is recommended that a hot water faucet served by this water heater be opened for several minutes before using any electrical appliance connected to the hot water system. If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. There should be no smoking or open flame near the faucet at the time it is open.
6 Introduction Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service. Abbreviations Used Abbreviations found in this Instruction Manual include : ANSI - American National Standards Institute ASME - American Society of Mechanical Engineers AHRI - Air-Conditioning, Heating and Refrigeration Institute NEC - National Electrical Code NFPA - National Fire Protection Association UL - Underwriters Laboratory CSA - Canadian Standards Association Qualifications Qualified Installer or Service Agency Installation and service of this water heater requires ability equivalent to that of a Qualified Agency (as defined by ANSI below) in the field involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service. ANSI Z Sec : Qualified Agency - Any individual, firm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction. If you are not qualified (as defined by ANSI above) and licensed or certified as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual. Preparing For The Installation 1. Read the General Safety section, page 4-5 of this manual first and then the entire manual carefully. If you don t follow the safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. This manual contains instructions for the installation, operation, and maintenance of the gas-fired water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety. Since we cannot put everything on the first few pages, READ THE ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER. 2. The installation must conform with these instructions and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or CAN/ CSA-B149.1 the Natural Gas and Propane Installation Code. All documents are available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH NFPA documents are also available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate. 4. Carefully plan the place where you are going to put the water heater. Correct combustion, vent action, and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fires. Examine the location to ensure the water heater complies with the Locating the New Water Heater section in this manual. 5. For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Office of the State Architect, 400 P Street, Sacramento, CA Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR 2.00: State Plumbing Code and 248-CMR
7 FEATURES AND COMPONENTS the eliminator (self-cleaning system) These units include The Eliminator (Self-Cleaning System) installed in the front water inlet, See Figure 1. The Eliminator inlet tube can only be used in the front water inlet connection. Do not install the Eliminator inlet tube in either the top or back inlet water connection. The Eliminator must be oriented correctly for proper function. There is a marked range on pipe nipple portion of the Eliminator, that must be aligned with top of inlet spud. A label above the jacket hole has an arrow that will point to marked portion of pipe nipple if the orientation is correct. If the arrow does not point within the marked range on pipe nipple, adjust the pipe nipple to correct. A pipe union is supplied with the Eliminator to reduce probability of misaligning the Eliminator accidentally while tightening the connection to inlet water supply line. Improper orientation of the Eliminator can cause poor performance of heater and can significantly reduce outlet water temperatures during heavy draws. by creating a spark at the pilot assembly. See Figure 3. Pilot gas is ignited and burns during each running cycle. The main burner and pilot gases are cut off during the OFF cycle. Pilot gas ignition is proven by the pilot sensor. Main burner ignition will not occur if the pilot sensor does not first sense pilot ignition. Note: The Eliminator may have 1, 3 or 7 cross tubes. FIGURE 1. high limit switch The digital thermostat (Figure 2) contains the high limit (energy cutout) switch. The high limit switch interrupts main burner gas flow should the water temperature reach 203 F (95 C). In the event of high limit switch operation, the water heater cannot be restarted unless the water temperature is reduced to approximately 120 F (49 C). The high limit reset button on the front of the control then needs to be depressed. Continued manual resetting of high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation. The following is a possible reason for high limit switch operation: A malfunction in the thermostatic controls would allow the gas control valve to remain open causing water temperature to exceed the thermostat setting. The water temperature would continue to rise until high limit switch operation. Contact your dealer or service agent if continued high limit switch operation occurs. IGNITION module FIGURE 3. AUTOMATIC FLUE DAMPER All units are equipped with an automatic flue damper that reduces heat loss during the OFF cycles. Each automatic flue damper drive assembly is equipped with a Service Switch, as shown in Figure 4 The Service Switch has 2 positions: AUTOMATIC OPERATION and HOLD OPEN DAMPER. For normal operation the switch should be in the AUTOMATIC OPERATION position. If there is a problem with the damper the Service Switch can be placed in the HOLD OPEN DAMPER position. When the switch is placed in the HOLD OPEN DAMPER position the damper disc will rotate to the open position and the heater may be used until vent assembly is repaired or replaced. DO NOT turn the damper disc manually; damage will occur to the drive assembly if operated manually. Refer to TESTING DAMPER OPERATION section of this manual for additional information. DIGITAL THERMOSTAT FIGURE 2. uncrating flue damper FIGURE 4. electronic ignition control Each heater is equipped with a Honeywell ignition module. The solid state ignition control ignites the pilot burner gas The heater is shipped with the flue damper already installed. The wiring conduit runs from the thermostat to the damper drive cover. Before turning unit on, check to make sure the wiring conduit is securely plugged into damper drive. 7
8 installation considerations Rough In Dimensions See Models Below * BCG370T120 Models are approved for 5 (13 cm) venting using a 6 (15 cm) to 5 (13 cm) reducer. FIGURE 5. TABLE 1. BCG370T1205_ THROUGH (A)BCG3100T3998_ MODEL BCG3 70T120 BCG3 80T150 BCG3 80T180 BCG3 100T199 BCG3 80T199 (A)BCG3 100T200 (A)BCG3 100T250 (A)BCG3 65T250 (A)BCG3 100T275 (A)BCG3 65T300 (A)BCG3 85T360 (A)BCG3 100T390 INPUT RATE BTU/ HR. 120,000 BTU/Hr. 35 Kw/Hr 154,000 BTU/Hr 45 Kw/Hr 180,000 BTU/Hr 53 Kw/Hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 250,000 BTU/Hr 72 kw/hr 251,000 BTU/Hr 73 kw/hr 275,000 BTU/Hr 80 kw/hr 305,000 BTU/Hr 89 kw/hr 365,000 BTU/Hr 107 kw/hr 390,000 BTU/Hr 114 kw/hr APPROX. TANK CAP. 71 Gal 268 L 81 Gal 307 L 81Gal 307 L 100 Gal 379 L 81 Gal 307 L 100 Gal 379 L 100 Gal 379 L 65 Gal 246 L 100 Gal 379 L 65 Gal 246 L 85 Gal 322 L 100 Gal 379 L A B C D E F GAS INLET G /2 177 cm 11 cm 151 cm 129 cm 50 cm 48 cm 1/ /2 185 cm 11 cm 169 cm 147 cm 50 cm 48 cm 1/ /2 171 cm 12 cm 157 cm 136 cm 52 cm 53 cm 1/ /2 192 cm 12 cm 178 cm 157 cm 52 cm 53 cm 1/ /2 171 cm 12 cm 157 cm 136 cm 52 cm 53 cm 1/ /2 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1/ /2 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1/ NA 191 cm 12 cm 167 cm 145 cm 51 cm NA 1/2 1/ /2 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1/ NA 191 cm 12 cm 167 cm 145 cm 51 cm NA 1/2 1/ /4 202 cm 12 cm 178 cm 159 cm 57 cm 58 cm 3/ /4 192 cm 12 cm 171 cm 148 cm 68 cm 58 cm 3/4 H cm cm cm cm cm cm cm cm cm cm cm cm VENT DIA. I J cm 71 cm cm 71 cm cm 71 cm cm 71 cm cm 71 cm cm 77 cm cm 77 cm NA 20 cm 70 cm NA cm 77 cm NA 20 cm 70 cm NA cm 70 cm cm 77 cm CONNECTIONS APPROXIMATE INLET OUTLET SHIP WEIGHT TOP FRONT BACK TOP FRONT BACK STD. ASME NA NA NA NA 400 Lbs 182 Kg 470 Lbs 213 Kg 470 Lbs 213 Kg 603 Lbs 273 Kg 470 Lbs 213 Kg 630 Lbs 286 Kg 630 Lbs 286 Kg 750Lbs 341 Kg 630 Lbs 286 Kg 750 Lbs 341 Kg 725 Lbs 329 Kg 760 Lbs 345 Kg NA NA NA NA NA NA NA NA NA NA 725 Lbs 329 Kg 725 Lbs 329 Kg 862 Lbs 391 Kg 725 Lbs 329 Kg 862 Lbs 391 Kg 833 Lbs 379 Kg 874 Lbs 396 Kg 8
9 installation considerations TABLE 2. HEATER PERFORMANCE DATA (A)BCG3 MODELS MODEL BCG3 70T120 BCG3 80T150 BCG3 80T180 BCG3 100T199 BCG3 80T199 (A)BCG3 100T200 (A)BCG3 100T250 (A)BCG3 65T250 (A)BCG3 100T275 (A)BCG3 65T300 (A)BCG3 85T360 (A)BCG3 100T390 INPUT RATE BTUH 120,000 BTU/Hr. 35 Kw/Hr 154,000 BTU/Hr 45 Kw/Hr 180,000 BTU/Hr 53 Kw/Hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 250,000 BTU/Hr 72 kw/hr 251,000 BTU/Hr 73 kw/hr 275,000 BTU/Hr 80 kw/hr 305,000 BTU/Hr 89 kw/hr 365,000 BTU/Hr 107 kw/hr 390,000 BTU/Hr 114 kw/hr APPROX. GAL. CAP. 71 Gal 268 L 81 Gal 306 L 81 Gal 306 L 100 Gal 379 L 81 Gal 306 L 100 Gal 379 L 100 Gal 379 L 65 Gal 246 L 100 Gal 379 L 65 Gal 246 L 85 Gal 322 L 100 Gal 379 L EFF. % RECOVERY RATING CAPACITIES (GPH AND LPH) 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F 130 F 140 F (-)1 C 4 C 10 C 15 C 21 C 27 C 32 C 38 C 43 C 49 C 54 C 60 C TABLE 3. GAS AND ELECTRICAL CHARACTERISTICS Gas Supply Pressure Model Type of Gas Minimum Maximum Gas Manifold Pressure Volts/Hz Amperes All Models Natural 4.5" W.C. (1.12 kpa) 14" W.C. (3.48 kpa) 3.5" W.C. (0.87 kpa) 120/60 <5 All Models Propane 11.0" W.C. (2.74kPa) 14" W.C. (3.48kPa) 10.0" W.C. (2.49 kpa) 120/60 <5 9
10 Installation Considerations locating the water heater CAUTION Property Damage Hazard All water heaters eventually leak. Do not install without adequate drainage. When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible. Fire or Explosion Hazard Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Avoid all ignition sources if you smell gas. Do not expose water heater controls to excessive gas pressure. Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles. Keep ignition sources away from faucets after extended periods of non-use. Read instruction manual before installing, using or servicing water heater. Flammable items, pressurized containers or any other potential fire hazardous articles must never be placed on or adjacent to the heater. Open containers or flammable material should not be stored or used in the same room with the heater. The heater must not be located in an area where it will be subject to freezing. Locate it near a floor drain. The heater should be located in an area where leakage from heater or connections will not result in damage to adjacent area or to lower floors of the structure. When such locations cannot be avoided, a suitable metal drain pan should be installed under heater. Such pans should be fabricated with sides at least 2 deep, with length and width at least 2 greater than diameter of heater and must be piped to an adequate drain. Pan must not restrict combustion air flow. clearances These heaters are approved for installation on combustible flooring in an alcove when the minimum clearance from combustion or non-combustible construction are followed as indicated in Figure 6 and Table 4. In all installations the minimum combustible clearances from draft hood surface or vent piping shall be 6 (152mm). Vent piping passing through a combustible wall or ceiling must be a continuous run (no joints) and retain 6 (152mm) clearance unless an approved reducing thimble is used. A service clearance of 24 (610mm) should be maintained from serviceable parts, such as relief valves, baffles, thermostats, cleanout openings or drain valves. TABLE 4. Installation Clearances There is a risk in using fuel burning appliances such as gas water heaters in rooms, garages or other areas where gasoline, other flammable liquids or engine driven equipment or vehicles are stored, operated or repaired. Flammable vapors are heavy and travel along the floor and may be ignited by the heater s igniter or main burner flames causing fire or explosion. Some local codes permit operation of gas appliances in such areas if they are installed 18 or more above the floor. This may reduce the risk if location in such an area cannot be avoided. Do not install this water heater directly on a carpeted floor. A fire hazard may result. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches in any direction. If the heater is installed in a carpeted alcove, the entire floor shall be covered by the panel. Also, see the DRAINING requirements in MAINTENANCE Section. The heater shall be located or protected so it is not subject to physical damage by a moving vehicle. A (RIGHT SIDE) B (LEFTSIDE) C (BACK) D (CEILING) 70T120 1 (2.54 cm) 1 (2.54 cm) 1 (2.54 cm) 12 (30.48 cm) 80T150 1 (2.54 cm) 1 (2.54 cm) 1 (2.54 cm) 12 (30.48 cm) 80T180 1 (2.54 cm) 1 (2.54 cm) 1 (2.54 cm) 12 (30.48 cm) 100T199 1 (2.54 cm) 1 (2. 54 cm) 1 (2.54 cm) 12 (30.48 cm) 80T199 1 (2. 54 cm) 1 (2. 54 cm) 1 (2. 54 cm) 12 (30.48 cm) 100T200 1 (2. 54 cm) 1 (2. 54 cm) 1 (2. 54 cm) 12 (30.48 cm) 100T250 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 65T250 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 100T275 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 65T300 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 85T360 3 (7.75 cm) 3 (7.75 cm) 3 (7.75 cm) 12 (30.48 cm) 100T390 3 (7.75 cm) 3 (7.75 cm) 3 (7.75 cm) 12 (30.48 cm) 10
11 INSULATION BLANKET Breathing Hazard - Carbon Monoxide Gas Do not obstruct water heater air intake with insulating blanket. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. NSF LEG KIT FIGURE 6. The NSF Leg Kit (part number ) is needed only for applications that must conform to NSF/ANSI Standard 5. Installation of the NSF leg kit will increase the height of the unit and all connection points by 3 inches. See Figure 7. Follow these steps to install the Leg Kit: 1. Unit needs to be lifted in a way not to damage unit or laid on it s side to access the bottom of the legs. 2. Slide leg extension under leg and the bolt up through the bottom hole located in the bottom of the leg. 3. Once in place, screw nut down and secure. 4. Front of leg should line up with front of leg extension as shown to make sure weight of unit is distributed through the leg extension. FIGURE 7. Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. The water heaters covered by this manual meet or exceed the Energy Policy Act standards with respect to insulation and standby heat loss requirements, making an insulation blanket unnecessary. Should you choose to apply an insulation blanket to this heater, you should follow these instructions. See the Features and Components section of this manual for identification of components mentioned below. Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death. DO NOT apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood. DO NOT cover the gas control valve, thermostat or the Temperature-Pressure Relief Valve. DO NOT allow insulation to come within 2 (5 cm) of the burners, to prevent blockage of combustion air flow to the burners. DO NOT allow insulation to come within 9 inches (23 cm) of floor, (within 2 inches (5 cm) of bottom cover) to prevent blockage of combustion air flow to the burners.. DO NOT cover the instruction manual. Keep it on the side of the water heater or nearby for future reference. DO obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels. DO inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow. HARD water Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment. See the Maintenance Section in this manual for sediment and lime scale removal procedures. Circulation pumps A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the water heater. See Water Piping Diagrams in this manual for installation location of circulating pumps. See the Circulation Pump Wiring Diagrams in this manual for electrical hookup information. Install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1. All-bronze circulating pumps are recommended for used with commercial water heaters. Some circulating pumps are manufactured with sealed bearings and do not require further lubrication. Some circulating pumps 11
12 NTROL E must be periodically oiled. Refer to the pump manufacturer s instructions for lubrication requirements. CIRCULATING PUMP WIRING DIAGRAM STORAGE TANK OR BUILDING RECIRCULATION FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE STORAGE TANK OR CIRCULATING LOOP RETURN LINE NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION. L1 HOT L2 NEUTRAL 120 VAC POWER FIGURE 8. CIRC PUMP MOTOR CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH DISHWASHER TOGGLE SWITCH NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION. L1 HOT L2 NEUTRAL 120 VAC POWER FIGURE 9. HIGH ALTITUDE INSTALLATIONS FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR Fire and Explosion Hazard Under no circumstances should the input exceed the rate shown on the water heater s rating label. Overfiring could result in fire or explosion. Gas and carbon monoxide detectors are available. CIRCULATING PUMP WIRING DIAGRAM Breathing DISHWASHER Hazard LOOP - WITH Carbon TOGGLE Monoxide SWITCH Gas DISHWASHER Under no FIELD circumstances SUPPLIED TEMPERATURE should TOGGLE CONTROL INSTALLED IN THE SWITCH the input CIRCULATING exceed the LOOP rate RETURN shownline on the water heater s rating label. NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE Overfiring could result in damage to POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD the water heater and sooting. TO ERRATIC CONTROL SYSTEM OPERATION. L1 HOT Gas and carbon monoxide detectors are available. 120 VAC CIRC Breathing POWER carbon monoxide can cause brain damage or PUMP death. Always read and understand instruction MOTOR manual. L2 NEUTRAL Installations above 2000 feet (610 meters) require replacement of burner orifices in accordance with current edition of the National Fuel Gas Code (ansi z223.1). For Canadian installations consult Canadian Installations Code can/csa b Failure to replace orifices will result in improper and inefficient operation of the water heater resulting in the production of increased levels of carbon monoxide gas in excess of safe limits which could result in serious personal injury or death. You should contact your gas supplier for any specific changes which may be required in your area. As the elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply. Failure to make this reduction would result in an over firing of the heater causing sooting, poor combustion and/or unsatisfactory heater performance. Ratings specified by manufacturers for most appliances apply for elevations up to 2000 feet (610m). For elevations above 2000 feet (610), ratings must be reduced at the rate of 4% for each 1000 feet (305m) above sea level. For example, if a heater is rated at 78,000 Btuh (22.9 Kwh) at sea level, to rate the heater at 4000 feet (1219m), you subtract 4 (once for each thousand feet) x.04 (4% input reduction) x 78,000 (original rating) from the original rating. Therefore, to calculate the input rating at 4,000 feet (1219m): 4 x.04 x 78,000 = 12,480 Btuh (3.7 Kwh), 78,000 (22.9 Kwh) - 12,480 (3.7 Kwh) = 65,520 Btuh (19.2 Kwh). At 6000 feet (1829m) the correct input rating should be 59,280 Btuh (17.4 Kwh). 12
13 Installation Requirements Gas supply Systems Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14 W.C. (1/2 PSI Gauge). These systems do not require pressure regulation. Measurements should be taken to insure that gas pressures are stable and fall within the requirements stated on the water heater rating plate. Readings should be taken with all gas burning equipment off (static pressure) and with all gas burning equipment running at maximum rate (dynamic pressure). The gas supply pressure must be stable within 1.5 W.C. from static to dynamic pressure to provide good performance. Pressure drops that exceed 1.5 W.C. may cause rough starting, noisy combustion or nuisance outages. Increases or spikes in static pressure during off cycles may cause failure to ignite or in severe cases damage to appliance gas valves. If your low pressure system does NOT meet these requirements, the installer is responsible for the corrections. High Pressure building supply systems use pressures that exceed 14 W.C. (1/2 PSI Gauge). These systems must use field supplied regulators to lower the gas pressure to less than 14 W.C. (1/2 PSI Gauge). Water heaters require gas regulators that are properly sized for the water heater input and deliver the rating plate specified pressures. Gas supply systems where pressure exceeds 5 PSI often require multiple regulators to achieve desired pressures. Systems in excess of 5 PSI building pressure should be designed by gas delivery professionals for best performance. Water heaters connected to gas supply systems that exceed 14 W.C. (1/2 PSI Gauge) at any time must be equipped with a gas supply regulator. All models require a minimum gas supply pressure of 4.5" W.C. for natural gas and 11.0" W.C. for propane gas. The minimum supply pressure is measured while gas is flowing (dynamic pressure). The supply pressure should never fall below 4.5" W.C. for natural gas and 11.0" W.C. for propane gas. The supply pressure should be measured with all gas fired appliances connected to the common main firing at full capacity. If the supply pressure drops more than 1.5 W.C. as gas begins to flow to the water heater then the supply gas system including the gas line and/or the gas regulator may be restricted or undersized. See Supply Gas Regulator section and Gas Piping section of this manual. The gas valve on all models has a maximum gas supply pressure limit of 14 W.C. The maximum supply pressure is measured while gas is not flowing (static pressure). SUPPLY GAS REGULATOR The maximum allowable gas supply pressure for this water heater is 14 inches W.C. (3.48 kpa). Install a positive lock-up gas pressure regulator in the gas supply line if inlet gas pressure can exceed 14 inches W.C. (3.48 kpa) at any time. Regulators must be sized/used according to manufacturer s specifications. If a positive lock-up regulator is required follow these instructions: 1. Positive lock-up gas pressure regulators must be rated at or above the input Btu/hr rating of the water heater they supply. 2. Positive lock-up gas pressure regulator(s) should be installed no closer than 3 equivalent feet (1 meter) and no farther than 8 equivalent feet (2.4 meters) from water heater s inlet gas connection. 3. After installing the positive lock-up gas pressure regulator(s) an initial nominal supply pressure setting of 7.0 W.C. while the water heater is operating is recommended and will generally provide good water heater operation. Some addition adjustment maybe required later to maintain a steady gas supply pressure. 4. When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit. Power Supply The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70 or the Canadian Electrical Code, CSA C22.1. WATER TEMPERATURE CONTROL AND Mixing Valves Water temperature over 125 F (52 C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury. Feel water before bathing or showering. Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures. Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the water heater s temperature setting by up to 20 F (11 C). Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm and the physically/mentally disabled. Table 5 shows approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken. In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed at the water heater (see Figure 10) or at the hot water taps to further reduce system water temperature. Mixing valves are available at plumbing supply stores. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer s instructions for installation of the valves. Table 5. Water Temperature F Time for 1st Degree Burn (Less Severe Burns) Time for Permanent Burns 2nd & 3rd Degree (Most Severe Burns) 110 (normal shower temp.) 116 (pain threshold) minutes 45 minutes minute 5 minutes seconds 25 seconds seconds 5 seconds second 2 seconds 154 instantaneous 1 second (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978) 13
14 TEMPERED WATER OUTLET HOT WATER OUTLET 12 TO 15 (30-38 cm) A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion. Contact a local plumbing service agency to have a thermal expansion tank installed. See Water Line Connections on page 21 and the Water Piping Diagrams beginning on page 40. Temperature-pressure relief valve COLD WATER INLET CHECK VALVE TO TANK INLET MIXING VALVE CHECK VALVE Explosion Hazard Temperature-Pressure Relief Valve must comply with ANSI Z CSA 4.4 and ASME code. Dishwashing Machines FIGURE 10. All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kpa and 173 kpa). Flow pressures above 25 pounds per square inch (173 kpa), or below 15 pounds per square inch (103 kpa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in the 180 F (82 C) line to the dishwashing machine and should be adjusted to deliver water pressure between these limits. The National Sanitation Foundation also recommends circulation of 180 F (82 C) water. The circulation flow rate should be just enough to provide 180 F (82 C) water at the point of take-off to the dishwashing machine. Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump. See Water Piping Diagrams in this manual. Note: These water heaters meet the NSF Standard 5 for sanitary installations when used with the leg kit part number Closed Water Systems Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back flow preventers. Devices such as these cause the water system to be a closed system. Thermal Expansion As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion. Properly sized temperaturepressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure. Can cause serious injury or death. This water heater is provided with a properly rated/sized and certified combination Temperature-Pressure Relief Valve (T&P valve) by the manufacturer. The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Pressure Relief Valves for Hot Water Supply Systems, ANSI Z21.22 CSA 4.4, and the code requirements of ASME. If replaced, the new T&P valve must meet the requirements of local codes, but not less than a combination Temperature- Pressure Relief Valve rated/sized and certified as indicated in the above paragraph. The new valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kpa) and a discharge capacity not less than the water heater Btu/hr or kw input rate as shown on the water heater s model rating label. NOTE: In addition to the factory installed Temperature-Pressure Relief Valve on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature- Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for technical assistance in sizing a Temperature-Pressure Relief Valve for remote storage tanks. For safe operation of the water heater, the Temperature-Pressure Relief Valve must not be removed from its designated opening nor plugged. The Temperature-Pressure Relief Valve must be installed directly into the fitting of the water heater designed for the pressure relief valve. Install discharge piping so that any discharge will exit the pipe within 6 inches (15.2 cm) above an adequate floor drain, or external to the building. In cold climates it is recommended that it be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve. 14
15 No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6 (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. CAUTION Water Damage Hazard Temperature-Pressure Relief Valve discharge pipe must terminate at adequate drain. T&P Valve Discharge Pipe Requirements: Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. Shall not be plugged or blocked. Shall not be exposed to freezing temperatures. Shall be of material listed for hot water distribution. Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe. Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. Shall not have any valve or other obstruction between the pressure relief valve and the drain. Contaminated Air Breathing Hazard - Carbon Monoxide Gas Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B To avoid injury, combustion and ventilation air must be taken from outdoors. Do not place chemical vapor emitting products near water heater. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Corrosion of the flue ways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation. Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as hot surface igniters and burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage. Do not store products of this sort near the water heater. Air which is brought in contact with the water heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outdoor sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions). Air requirements Burn hazard. Hot water discharge. Keep clear of Temperature- Pressure Relief Valve discharge outlet. The Temperature-Pressure Relief Valve must be manually operated at least twice a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions in this manual, and replace the Temperature- Pressure Relief Valve with a properly rated/sized new one. NOTE: The purpose of a Temperature-Pressure Relief Valve is to prevent excessive temperatures and pressures in the storage tank. The T&P valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion, see Closed Water Systems and Thermal Expansion on page 14. Breathing Hazard - Carbon Monoxide Gas Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B To avoid injury, combustion and ventilation air must be taken from outdoors. Do not place chemical vapor emitting products near water heater. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided. An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner flame, causing sooting of the combustion chamber, burners and flue tubes and creates a risk of asphyxiation. Do not install the water heater in a confined space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Confined Space section that follows. If you do not understand these instructions or have any questions Never obstruct the flow of ventilation air. If you have any doubts regarding the Temperature-Pressure Relief Valve call the toll or questions at all, call your gas supplier. Failure to provide the free number listed on the back cover of this manual for technical proper amount of combustion air can result in a fire or explosion assistance. and cause property damage, serious bodily injury or death. 15
16 Unconfined Space An Unconfined Space is one whose volume IS NOT LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kw) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space. Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and fireplaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air. Unusually Tight Construction In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows. Confined Space A Confined Space is one whose volume is less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kw) of the total input rating of all appliances installed in the space. Openings must be installed to provide fresh air for combustion, ventilation and dilution in confined spaces. The required size for the openings is dependent on the method used to provide fresh air to the confined space and the total Btu/hr input rating of all appliances installed in the space. Direct Vent Appliances Appliances installed in a Direct Vent configuration that derive all air for combustion from the outdoor atmosphere through sealed intake air piping are not factored in the total appliance input Btu/ hr calculations used to determine the size of openings providing fresh air into confined spaces. Exhaust Fans Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room through the water heater s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of fire or explosion may result. It can also create a risk of asphyxiation. Louvers and Grilles The free areas of the fresh air openings in the instructions that follow do not take in to account the presence of louvers, grilles or screens in the openings. The required size of openings for combustion, ventilation and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size of opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25% free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles shall be fixed in the open position. VENTING INSTALLATION venting THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION. Heater must be protected from freezing downdrafts. Remove all soot or other obstructions from the chimney that will retard a free draft. Type B venting is recommended with these heaters. For typical venting application see TECHNICAL DATA VENTING on pages 19 and 20. This water heater must be vented in compliance with all local codes, the current revision of the National Fuel Gas Code (ANSI-Z223.1) and with the Category I Venting Tables. If any part of the vent system are exposed to ambient temperatures below 40 F it must be insulated to prevent condensation. Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems. Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe. VENT REDUCER Model BCG370T120 is shipped with a 6" to 5" flue outlet adapter. Models (A)BCG3100T250, (A)BCG365T250 and (A) BCG3100T275 are shipped with a 8" to 6" flue outlet adapter. Each adapter fits on top of the installed flue damper. Use only vent reducers supplied with the unit. The venting must comply with the current editions of the NATIONAL FUEL GAS CODE, ANSI Z223.1/ NFPA 54 or NATURAL GAS AND PROPANE INSTALLATION CODE CAN/CSA-B149.1 FIGURE 11. FIGURE
17 Multiple heater manifold Outdoor Air Through One Opening Figure 13 and tables on pages 19 and 20 should be used for horizontally manifolding two or more heaters. Figure 15. FIGURE 13. Fresh Air Openings For Confined Spaces The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confined spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 16 for complete venting installation instructions. Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 14. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50 mm) from the front of the water heater. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following: 1. 1 square inch per 3000 Btu/hr (733 mm 2 per kw) of the total input rating of all appliances located in the enclosure, and 2. Not less than the sum of the areas of all vent connectors in the space. Outdoor Air Through Two Horizontal Ducts Outdoor Air Through Two Openings Figure 14. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 14. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm 2 ). 17 Figure 16. The confined space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 16. Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
18 Outdoor Air Through Two Vertical Ducts The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. Do not refer to these illustrations for the purpose of vent installation. See Venting Installation on page 14 for complete venting installation instructions. When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches. Air From Other Indoor Spaces Figure 18. Figure 17. The confined space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 17. Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18. Each opening shall communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (2200 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm 2 ). 18
19 TABLE 6. TECHNICAL DATA VENTING TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (Figure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. MODEL (A)BCG370T120 Input: 120,000 Btuh Total Vent Height (Feet) Draft Hood: Input Btuh Rise Vent Connector Diameter (inches) 120,000 1 Ft ,000 2 Ft ,000 3 Ft Number of Combined Input in Heaters Thousands of Btuh Manifold and Common Vent Diameter (In inches) MODEL (A)BCG380T150 Input: 154,000 Btuh Total Vent Height (Feet) Draft Hood: Input Btuh Rise Vent Connector Diameter (in inches) 154,000 1 Ft ,000 2 Ft ,000 3 Ft Numbers of Combined Input in Heaters Thousands of Btuh Manifold and Common Vent Diameter (in inches) MODEL BCG380T180, BCG3100T199, BCG380T199, & (A)BCG3100T200 Input: 180,000, 199,000 Btuh Total Vent Height (Feet) Draft Hood: Input Btuh Rise Vent Connector Diameter (in inches) 180,000 1 Ft , ,000 2 Ft , ,000 3 Ft , Number of Combined Input in Heaters Thousands of Btuh Manifold & Common Vent Diameter
20 20
21 Mechanical venting SINGLE UNIT INSTALLATION When mechanical venting of these heaters is desired, the following kits are available. Models with inputs from 120,000 to 200,000 btu/h part number Models with inputs from 250,000 to 390,000 btu/h part number Where an approved power venter is to be installed to operate in conjunction with the water heater thermostat, the following codes must be adhered to. Field wiring should conform to the current edition of the National Electrical Code NFPA 70. For Canadian installations the electrical connections and grounding shall be done in accordance with the current edition of the Canadian Electrical Code CSA C22.1 and/or local codes. VENT INSTALLATION Seal all joints between the power venter and the vent termination. This is to prevent leakage of exhaust products into the room(s) due to positive pressure of blower. The Sequence of Operation description will be the same with mechanical venting except; When the water heater thermostat calls for heat: Thermostat contacts Close and the power venter blower (120 VAC) is energized. Sufficient draft must be established for the Draft Prover Switch (N.O.) to Close. When the draft prover switch Closes the relay coil of the flue damper is energized. water heater installation Water Line Connections The water piping installation must conform to these instructions and to all local code authority having jurisdiction. Good practice requires that all heavy piping be supported. Read and observe all requirements in the following sections before installation of the water piping begins: 1. Water Temperature Control and Mixing Valves on page Dishwashing Machines on page Temperature-Pressure Relief Valve on page Closed Systems and Thermal Expansion on page For multiple water heater installations see Water Piping Diagrams beginning on page 40. Water (potable) Heating And Space Heating 1. All piping components connected to this unit for space heating applications shall be suitable for use with potable water. 2. Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system. 3. This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance. 4. When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagrams beginning on page 40 of this manual for suggested piping arrangements. 5. These water heaters cannot be used in space heating applications only Thermometers (not Supplied) Thermometers should be obtained and field installed as shown in the installation diagrams. Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply. Water Piping Diagrams This manual provides detailed water piping diagrams for typical methods of application for the water heaters, see Water Piping Diagrams beginning on page 40. The water heater may be installed by itself, or with a separate storage tank. When used with a separate storage tank, the circulation may be either by gravity or by means of circulating pump. Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump. See the Water Piping Diagrams beginning on page 40. Note: In addition to the factory installed Temperature-Pressure Relief Valve (T&P valve) on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature-Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for further assistance in sizing a T&P valve for remote storage tanks. T&P Valve Discharge Pipe Explosion Hazard Temperature-Pressure Relief Valve must comply with ANSI Z CSA 4.4 and ASME code. Properly sized temperaturepressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure. Can cause serious injury or death. 21
22 This water heater is provided with a properly rated/sized and certified combination temperature - pressure (T&P) relief valve by the manufacturer. See Temperature-Pressure Relief Valve on pages for information on replacement and other requirements. CAUTION Water Damage Hazard Temperature-Pressure Relief Valve discharge pipe must terminate at adequate drain. Install a discharge pipe between the T&P valve discharge opening and a suitable floor drain. Do not connect discharge piping directly to the drain unless a 6 (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. T&P Valve Discharge Pipe Requirements: Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. Shall not be plugged or blocked. Shall not be exposed to freezing temperatures. Shall be of material listed for hot water distribution. Shall be installed so as to allow complete drainage of both Temperature-Pressure Relief Valve and the discharge pipe. Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. Shall not have any valve or other obstruction between the relief valve and the drain. Installation Diagrams - Top Inlet/Outlet Usage Use of the top inlet water connection requires an inlet dip tube (refer to figure 19). The tube is supplied in the heater. Follow caution labels if applying heat to this fitting. Do not allow pipe dope to contact the plastic tube during installation. Tube Inlet Installation Figure
23 heater wiring All electrical work must be installed in accordance with the current edition of the National Electrical Code ANSI/NFPA No. 70 or Canadian Electrical Code CSA C22.1 and must conform to all local code authority having jurisdiction. AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION. If any of the original wire as supplied with the water heater must be replaced, use only type 105 C thermoplastic or equivalent C type F must be used for the flame sensor and igniter leads. The controls of this water heater are polarity sensitive. Be certain to properly wire the hot and neutral connections. R 24 VAC TO IGNITION CONTROL 24 VAC Y LOWER PROBE BLK DAMPER DRIVE 24 NEUTRAL DAMPER DRIVE E79 LINE IN W BLK ON/OFF SWITCH X BLK W 120 vac NEUTRAL PV MV/PV PV MV MV UPPER PROBE/ECO R W TH TR PROPANE GAS VALVE BL LEGEND: W--WHITE BLK--BLACK BL--BLUE R--RED Y--YELLOW W BL SPARKER PV GND-BURNER 24 V GND 24 V HONEYWELL IGNITION MV MV/PV BLK Y C P M NATURAL GAS VALVE FACTORY WIRED BY INSTALLER IF ANY OF THE ORIGINAL WIRE AS SUPPLIED MUST BE REPLACED, USE ONLY TYPE 105 O C THERMOPLASTIC OR EQUIVALENT. FLAME SENSOR IGNITION CABLE MUST BE 250 O C TYPE F REV 02 FIGURE
24 GAS PIPING Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area. Size the main gas line in accordance with Table 7. The figures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the latest version of the National Fuel Gas Code. Schedule 40 Steel or Wrought Iron Pipe is the preferred material for the gas line of this water heater. It is imperative to follow the sizing recommendations in the latest version of the National Fuel Gas Code if Corrugated Stainless Steel Tubing (CSST) is used as the gas line for this water heater. The heater is not intended for operation at higher than 14.0" W.C.- natural gas, (1/2 pound per square inch gage) supply gas pressure. Exposure to higher supply pressure may cause damage to the gas valve which could result in fire or explosion. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the gas valve must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system, not the heater. Vent blockage may occur during ice storms. Table 7. GAS SUPPLY PIPE LENGTHS (IN FEET) Maximum Equivalent Pipe Length - Natural Gas Only Input rate Schedule 40 Steel or Wrought Iron Pipe (BTU/HR) 1/2" 3/4" 1" 1 1/4" 1 1/2" 120, , , , , , , , , Fitting Type* Equivalent length in feet 45 Ell Ell Tee Natural Gas 0.60 Specific Gravity, 0.50" W.C. Pressure Drop *Screwed Fittings It is important to guard against gas valve fouling from contaminants in gas ways. Such fouling may cause improper operation, fire or explosion. If copper supply lines are used they must be internally tinned and certified for gas service. Before attaching the gas line, be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a sediment trap must be incorporated in the piping (see Figure 21). The sediment trap must be readily accessible and not subject to freezing conditions. Install in accordance with recommendations of serving gas suppliers. Refer to the latest version of the National Fuel Gas Code. To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet. Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compounds to the first two threads. Use compounds resistant to the action of liquefied petroleum gases. Gas Meter Size Natural Gases Only Be sure the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If gas meter is too small, ask the gas company to install a larger meter having adequate capacity. GAS PIPING AND SEDIMENT TRAP INSTALLATION Gas Line Leak Testing FIGURE 21. Fire and Explosion Hazard Use joint compound or Teflon tape compatible with propane gas. Leak test before placing the water heater in operation. Disconnect gas piping and main gas shutoff valve before leak testing. Install sediment trap in accordance with NFPA 54. Any time work is done on the gas supply system perform a leak test to avoid the possibility of fire or explosion. 1. For test pressures exceeding 1/2 psi (3.45 kpa) disconnect the water heater and its Main Gas Shutoff Valve from the gas supply piping system during testing, see Figure 21. The gas supply line must be capped when disconnected from the water heater. 2. For test pressures of 1/2 psi (3.45 kpa) or less, the water heater need not be disconnected, but must be isolated from the supply gas line by closing the Main Gas Shutoff Valve during testing. 3. Coat all supply gas line joints and connections upstream of the water heater with a non-corrosive soap and water solution to test for leaks. Bubbles indicate a gas leak. Do not use matches, candles, flame or other sources of ignition for this purpose. 4. Repair any leaks before placing the water heater in operation. Purging Gas line purging is required with new piping or systems in which air has entered. Purging should be performed per the current edition of NFPA 54 the National Fuel Gas Code. 24
25 OPERATION Fire or Explosion Hazard Gas line purging is required with new piping or systems in which air has entered. To avoid risk of fire or explosion purge discharge must not enter into confined areas or spaces where ignition can occur. The area must be well ventilated and all sources of ignition must be deactivated or removed. Prior to Start Up Read instruction manual before installing, using or servicing water heater. Installation and start up of this water heater requires abilities and skills equivalent to that of a licensed tradesman in the field involved, see Qualifications on page 6. Do not place the water heater in operation if any part has been under water. Immediately call a qualified service technician to inspect the water heater and to replace any part of the control system and any gas control which has been under water. Light the water heater in accordance with the Lighting and Operation Instruction label on the water heater and in this manual on pages 27 and 28. The water heaters covered by this manual are equipped with an electronic control system that automatically sequences the Igniter, the 24 VAC Gas Valve, the Burner ignition, and flame sensing. Before attempting start up, thoroughly study and know the exact Sequence Of Operation. See written Sequence Of Operation on page 25 and Sequence Of Operation Flow Chart on page 26. Be certain that the water heater is full of water, that air is purged from the gas and water lines and that there are no leaks in the gas and water lines. Ensure all inlet water valves are open. Filling The Water Heater Follow these steps to fill the water heater prior to start up. 1. Close the heater drain valve. 2. Open a nearby hot water faucet to permit air in system to escape. 3. Fully open the cold water inlet valve allowing the piping and water heater to fill with water. 4. Close hot water faucet opened in Step 2 as water starts to flow. Read SEQUENCE OF OPERATION section of this manual prior to lighting and operating this water heater. With above conditions satisfied, start the unit in accordance with the instructions on the operating label attached to the heater. For your convenience a copy of the instructions are shown on pages 27 and 28. SEQUENCE OF OPERATION The following information will describe the Sequence of Operation for this water heater. 1. Switch power on to unit. 2. Thermostat calls for heat. 3. Ignition Control performs diagnostic self check on system components. 4. The Ignition Control begins the trial for ignition. 5. The Ignition Control turns on the Spark Igniter and opens the Pilot Gas Valve. 6. The Ignition Control monitors the Flame Sensor during the ignition trial period. 7. If the Ignition Control does not sense the pilot flame during the ignition trial period, the Ignition Control shuts the Pilot Gas Valve and turns off the Spark Igniter. Depending on the water heater model, the Ignition Control will either retry the ignition trial at step 4 or lockout the ignition sequence. If the ignition sequence is locked out, the power to the unit must be cycled to restart the Ignition Control. 8. If the pilot flame is proved during the ignition trial period, the Ignition Control turns off the Spark Ignitor and opens the Main Gas Valve. 9. The Ignition Control allows a 2 second pilot flame stabilization period to insure that the pilot flame is not extinguished by the main burner light-off process. 10. The Ignition Control monitors the Flame Sensor during the heating cycle. If the flame signal is lost, the Ignition Control shuts the Main Gas Valve and Pilot Gas Valve and re-starts the ignition process at step Once the unit is satisfied, the Ignition Control will shut off the Main Gas Valve and the Pilot Gas Valve and the unit will be in standby mode until another call for heat is initiated by the thermostat. See the flow chart on page 26 for more information. 25
26 SEQUENCE OF OPERATION FLOW CHART Description of this flow chart can be found in the SEQUENCE OF OPERATION section found on page 25. IDLE (NOT POWERED) CALL FOR HEAT RECEIVED FROM THERMOSTAT WAIT FOR CALL FOR HEAT TO BE REMOVED POWER TO MODULE AND SELF CHECK ACTIVATE ALARM CONTACT(S) (OPTIONAL) A RETRY DELAY (5 MINUTES) TRIAL FOR IGNITION (TIMER STARTED) SPARK ON OPEN PILOT GAS VALVE RETRY FLAME PROVED? NO CLOSE PILOT GAS VALVE SPARK OFF RETRY OR LOCKOUT MODEL? LOCKOUT (BEFORE TRIAL FOR IGNITION TIMER EXPIRES) YES SPARK OFF OPEN MAIN GAS VALVE FLAME STABILIZATION (2 SECONDS) NO RUN CALL FOR HEAT ENDS? NO FLAME LOST? YES CLOSE MAIN GAS VALVE AND PILOT GAS VALVE A YES CLOSE MAIN GAS VALVE AND PILOT GAS VALVE FLOW CHART 1. 26
27 LIGHTING & OPERATION LABEL FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING FIGURE 22. Label for Natural Gas Models 27
28 FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE FIGURE 23. Label for propane Gas Models 28
29 Adjustments ON INITIAL STARTUP SOME ADJUSTMENTS MAY BE NECESSARY. Check Manifold and inlet gas pressures (see GAS SUPPLY SYSTEMS on page 13 and CHECKING THE INPUT on page ) Check Pilot Burner (See Pilot Burner section on page 34.) TESTING DAMPER OPERATION With the Service Switch in the AUTOMATIC OPERATION position, check the operation of the flue damper three (3) times with the water operating controls for proper operating sequence: The damper disc must be open (in the vertical position) before the ignition and combustion process begins. The damper disc must be in the open position when the main burner is firing. The gas control valve must close and the main burner must have ceased firing before the damper disc begins its return to the closed (horizontal) position. If during testing of the operation of the damper you find that there is a problem with the operation of the water heater when the Service Switch is in the AUTOMATIC OPERATION position: Reset the Service Switch to the HOLD OPEN DAMPER position and check operation again. If the water heater does operate when placed in the HOLD OPEN DAMPER position: Refer to the EFFIKAL RVGP-FSF-SERIES TROUBLESHOOTING GUIDE on page 37. If the water heater does not operate with the Service Switch in either position: Refer to the Troubleshooting Sections and Troubleshooting Checklist. CHECKING VENTING FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS. If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion. CHECKING THE INPUT For installation locations with elevations above 2000 feet, refer to HIGH ALTITUDE INSTALLATIONS section of this manual for input reduction procedure. 1. Attach a pressure gauge or a manometer to the manifold pressure tap on the gas control valve and refer to Table 8, for correct manifold pressure. 2. Use this formula to clock the meter. Be sure that other gas consuming appliances are not operating during this interval. (3600/T) x H = Btuh T = Time in seconds to burn one cubic foot of gas. H = Btu s per cubic foot of gas. Btuh = Actual heater input. Example: T = 15.1 seconds H = 1050 Btu Btuh =? (3600/15.1) x 1050 = 250,000 The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation. 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1or the CAN/ CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Close fireplace dampers. 4. Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so water heater shall operate continuously. 5. Test for draft hood spillage at the relief opening after 5 minutes of main burner operation. 6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use. 7. If improper venting is observed during any of the above tests, the venting system must be corrected. 29 INPUT RATE (BTUH) 120, , , , , , , , , ,000 TABLE 8. APPROXIMATE TIME REQUIRED TO CONSUME 1 CU. FT. OF GAS AT FULL CAPACITY TYPE OF GAS NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE NATURAL PROPANE BTUH PER CU. FT TIME REQ D TO CONSUME 1 CU. FT. OF GAS SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC SEC. 9.7 SEC SEC.
30 Should it be necessary to adjust the gas pressure to the burners to obtain the full input rate, the steps below should be followed: 3. Remove the regulator adjustment sealing cap and adjust the pressure by turning the adjusting screw with a screwdriver. See Figure 24. Clockwise to increase gas pressure and input rate. Counterclockwise to decrease gas pressure and input rate. 4. Clock the meter as in step 2 above. 5. Repeat steps 3 and 4 until the specified input rate is achieved. 6. Turn the gas control knob to PILOT. Remove the pressure gauge and replace the sealing cap and the Allen wrench set screw in the pressure tap opening. FIGURE 24. UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT EXCEED THE INPUT SHOWN ON THE HEATER MODEL AND RATING PLATE. OVERFIRING COULD RESULT IN DAMAGE OR SOOTING OF THE HEATER. 30
31 maintenance venting system Examine the venting system every six months for obstructions and/or deterioration of the vent piping. Remove all soot or other obstructions from chimney which will retard free draft. remote storage tank temperature control The water temperature in the remote storage tank (if used) is controlled by the storage tank temperature control. The sensing element is mounted in the hot water storage tank, see Water Piping Diagram section. A change in water temperature in the storage tank lower than the tank temperature control setting will cause the sensor to activate the circulating pump. The pump then circulates the water through the heater where the thermostat senses the drop in water temperature and activates main burner operation of the water heater. If the storage tank temperature control is out of calibration, replace with new control. SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE Water heater. temperature-pressure relief Valve test Figure 25. If the Temperature-Pressure Relief Valve on water heater weeps or discharges periodically, this may be due to thermal expansion. NOTE: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by "thermal expansion" in a "closed system." See Closed Water Systems and Thermal Expansion on page 12. The Temperature- Pressure Relief Valve is not intended for the constant relief of thermal expansion. Temperature-Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems. DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, SERIOUS INJURY OR DEATH. Burn hazard. Hot water discharge. Keep clear of Temperature- Pressure relief Valve discharge outlet. It is recommended that the Temperature-Pressure Relief Valve should be checked to ensure that it is in operating condition every 6 months. When checking the Temperature-Pressure Relief Valve operation, make sure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot. Use care when operating valve as the valve may be hot. To check the pressure relief valve, lift the lever at the end of the valve several times, see Figure 25. The valve should seat properly and operate freely. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater and drain the water heater, see Draining And Flushing on page 32. Replace the Temperature-Pressure Relief Valve with a properly rated/sized new one, see Temperature- Pressure Relief Valve on pages for instructions on replacement. anode rod inspection explosion hazard Temperature-Pressure relief Valve must comply with AnSI Z CSA 4.4 and ASMe code. Properly sized temperaturepressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure. Can cause serious injury or death. CAUTION Property Damage Hazard Avoid water heater damage. Inspection and replacement of anode rod required. The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifices itself to protect the tank. Instead of corroding tank, 31
32 water ions attack and eat away the anode rod. This does not affect water s taste or color. The rod must be maintained to keep tank in operating condition. Anode rod deterioration depends on water conductivity, not necessarily water condition. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualified technician, and at a minimum should be checked annually after the warranty period. Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank. The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode rod dictates its replacement. Anode replacement is not covered by warranty. NOTE: artificially softened water requires the anode rod to be inspected annually. Draining and flushing Burn harzard. Hot water discharge. Keep hands clear of drain valve discharge. It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup. The water heater should be drained if being shut down during freezing temperatures. See Features And Components in this manual for the location of the water heater components described below. TO DRAIN THE WATER HEATER STORAGE TANK: 1. Turn off the electrical supply to the water heater. 2. Turn off the gas supply at the Main Gas Shutoff Valve if the water heater is going to be shut down for an extended period. 3. Ensure the cold water inlet valve is open. 4. Open a nearby hot water faucet and let the water run until the water is no longer hot. 5. Close the cold water inlet valve to the water heater. 6. Connect a hose to the water heater drain valve and terminate it to an adequate drain. 7. Open the water heater drain valve and allow all the water to drain from the storage tank. 8. Close the water heater drain valve when all water in the storage tank has drained. 9. Close the hot water faucet opened in Step If the water heater is going to be shut down for an extended period, the drain valve should be left open. TO FLUSH THE WATER HEATER STORAGE TANK: 1. Turn off the electrical supply to the water heater. 2. Ensure the cold water inlet valve is open. 3. Open a nearby hot water faucet and let the water run until the water is no longer hot. Then close the hot water faucet. 4. Connect a hose to the drain valve and terminate it to an adequate drain Ensure the drain hose is secured before and during the entire flushing procedure. Flushing is performed with system water pressure applied to the water heater. 6. Open the water heater drain valve to flush the storage tank. 7. Flush the water heater storage tank to remove sediment and allow the water to flow until it runs clean. 8. Close the water heater drain valve when flushing is completed. 9. Remove the drain hose. 10. Fill the water heater - see Filling The Water Heater in this manual. 11. Turn on the electrical supply to place the water heater back in operation. 12. Allow the water heater to complete several heating cycles to ensure it is operating properly. recommended procedure for periodic removal of lime deposits from tank type commercial water heaters The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils. Lime accumulation not only reduces the life of equipment but also reduces efficiency of the heater and increases fuel consumption. The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained. The time between cleaning will vary from weeks to months depending upon water conditions and usage. The depth of lime buildup should be measured periodically. Heaters equipped with cleanouts will have about 2" of lime buildup when the level of lime has reached the bottom of the cleanout opening. A schedule for deliming should then be set up,based on the amount of time it would take for a 1" buildup of lime. It is recommended that the water heater initially be inspected after 6 months. Example 1: Initial inspection after 6 months shows 1/2" of lime accumulation. Therefore, the heater should be delimed once a year. Example 2: Initial inspection after 6 months shows 2" of lime accumulation. Therefore, the heater should be delimed every 3 months. FIGURE 26.
33 deliming solvents UN LIME is recommended for deliming. UN LIME is a patented food grade acid which is safe to handle and does not create the harmful fumes which are associated with other products. UN LIME may be obtained from your dealer, distributor or water heater manufacturer. Order Part Number , 1 gallon, packed 4 gallons per case or Part Number , 5 gallon container. NOTE: Un Lime is not available for use in Canada. Hydrochloric base acids are not recommended for use on glass lined tanks. Observe handling instructions on label of product being used. tank Cleanout Procedure The following practices will ensure longer life and enable the unit to operate at its designed efficiency: 1. Once a month the heater should be flushed. Open drain valve and allow two gallons of water to drain from heater. Inlet water valve should remain open to maintain pressure in tank. 2. A cleanout opening is provided for periodic cleaning of the tank. Gas must be shut off and heater drained before opening cleanout. To clean heater through cleanout opening, proceed as follows: 3. Drain heater. 4. Remove outer cover plate from lower side of heater jacket. 5. Remove six (6) hex head screws securing tank cleanout plate and remove plate. 6. Remove lime, scale, or sediment using care not to damage the glass lining. 7. Inspect cleanout plate gasket, if new gasket is required, replace with part no Install cleanout plate. Be sure to draw plate up tight by tightening screws securely. 9. Replace outer jacket cover plate. In some water areas the sediment might not be removed by this method and may result in the water heater making rumbling or boiling noises. To dissolve and remove these more stubborn mineral deposits, UN LIME Professional Delimer should be used. DELIMING USING FLO-JUG METHOD UN LIME in the 5 gallon size is recommended for deliming of all models. Contact your local dealer, distributor or, water heater manufacturer: Prepare the Water Heater To delime the water heater using the Flo-Jug method, first prepare the heater for deliming. Explosion Hazard Flammable hydrogen gases may be present. Keep all ignition sources away from faucet when turning on hot water. Do not smoke or have open flame or sparks in vicinity of heater. Do not mix UN LIME with other chemicals. Do not allow contact with magnesium, aluminum or galvanized metals. Chemical Hazard Product contains phosphoric acid. Keep out of reach of children. Use rubber or neoprene gloves. Contains phosphoric acid. In case of external contact, flush with cool water. If irritation persists, get medical attention. If swallowed, give 1 or 2 glasses of water or milk and call physician. Get immediate medical attention for eyes. Keep out of reach of children. NOTE: THE USE OF RUBBER OR NEOPRENE GLOVES IS RECOMMENDED, ESPECIALLY IF YOU HAVE ANY OPEN SORES OR CUTS TO AVOID UNNECESSARY IRRITATION OR DISCOMFORT. 1. Turn off fuel and/or power supply to heater. Also, turn off power to any electrical device or equipment, which is attached, or part of the system. 2. Open hot water side of faucet closest to heater and allow water to run until it is cool enough to handle safely. 3. Close cold water inlet valve to heater. 4. Connect hose to drain valve at bottom of heater and start draining heater into suitable floor drain area. 5. Remove pressure relief valve while heater is draining. NOTE: Do not replace pressure relief valve until deliming is completed. Pressure relief valve opening will also act as a vent in case of possible contact between the delimer and the anode rod(s), which may produce flammable hydrogen-air mixtures. 6. If pressure relief valve appears to be limed-up, place it in a clean glass or plastic container adequate in size so that you can pour enough UN LIME into container to cover the valve and allow space for foaming. When foaming stops, run fresh cool water into the container and rinse the pressure relief valve for a few minutes. 7. If heater does not drain completely after a reasonable length of time, turn off the main water supply valve to stop water from entering the tank due to a by-pass problem or defective cold water inlet valve. Also, check for clogged drain valve opening. Heater must be completely drained before introducing UN LIME. 8. Remove the cleanout cover and place a clean plastic bucket next to the cleanout opening. Partially open the cold water inlet valve to allow time to accomplish the following and then close the valve. 33
34 While the water is being run through the tank, insert a stiff wire, copper tube flattened at one end or an opened wire coat hanger through the cleanout opening and scrape out any loose deposits of scale or sediment. This is an economical way to avoid unnecessary usage of the deliming solution. Repeat the opening and closing of the cold water inlet valve as necessary but be sure the heater is completely drained when ready to introduce the UN LIME. Upon completion, reinstall the cleanout cover and use a new cleanout cover gasket (part number ). Remove the drain valve. 9. Install the long plastic male adapter insert fitting into the drain valve opening of heater after applying Teflon tape or paste to threads. Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection. Do not over tighten to avoid damage to threads and fittings. Prepare the Up-N-Down Transfer Kit The next step is the preparation on the Up-N-Down Transfer Kit, if you have not already done so: 1. With the 5 gallon Up-N-Down container in the vertical position, unscrew the plastic vent cap in the handle and pierce the plastic membrane over the vent boss under the cap to allow the container to vent. Note: If your container does not have the vent cap and vent boss, drill a 3/16 hole in the handle. When you have finished deliming you will be able to plug this drilled vent with the stainless steel screw that is supplied with the kit. 2. Remove the container s cap and cut the plastic membrane located in the 3/4 IPT opening in the cap. Take care to not damage the threads. 3. Find the 3/4 male adapter, apply teflon tape to the threaded end and screw it into the 3/4 IPT opening in the cap. 4. Put cap with male adapter back on the container and slide 3/4 hose over end of male adapter and fasten in place using hose clamp provided. Pilot Burner Figure 27. At least once a year, check the pilot burner, Figure 29, and the main burner, Figure 30, for proper operation. See Figure 28 for the location of the Pilot Burner and the Main Burners. For access to pilot, unfasten two screws to burner cover and remove. Locate the burner with pilot and remove screw holding burner to manifold. Unfasten pilot tubing from valve and slide out burner and pilot. Servicing of the pilot burner includes keeping pilot free of lint, cleaning the burner head, the primary air opening and the orifice of the pilot burner. FIGURE 28. Delime using Flo-Jug Method 5. Slide the hose clamp over end of hose and slide hose over the male adapter in the water heater drain opening and secure in place using hose clamp. 6. Lift container to the Pour Position, see Figure 27, being careful to keep the vent in the handle above the liquid level and pour the UN LIME into the heater. 7. Lower container, you may have to place the container on its empty carton to prevent the UN LIME from flowing back into the container. 8. Let UN LIME remain in the heater for 5 minutes and then lower the container to the Drain Position, see Figure Deliming activity is indicated by foaming on the surface of the UN LIME. If there is deliming activity, repeat steps 6 thru 8. Normally, lime removal will be completed within one hour. Severe build-up of lime may take longer than an hour to complete descaling. Note: To check UN LIME for continued use, place some scale or white chalk in a glass with a small amount of UN LIME. If the material is vigorously dissolved by the UN LIME, it can be reused; if not, the UN LIME should be replaced. 34 FIGURE 29. Pilot burner flame is affected by:. 1. Low gas pressure. Adjust pilot flame by means of the pilot gas adjustment located on the gas control valve. See Figure 31. The pilot flame should envelop sensing device with 5/8 (1.6cm) flame, Figure30. Remove pilot adjustment cover screw, Figure 31. Turn inner adjustment screw clockwise to decrease, or counterclockwise to increase pilot flame. Be sure to replace cover screw on gas control valve after adjustment to prevent possible gas leakage. 2. Clogged pilot burner orifice. Clean or replace orifice. A clogged orifice will restrict gas flow.
35 Pilot sensing device must sense a flame before sparking will stop. Loose wires or a draft may cause intermittent or abnormal sparking. To eliminate this condition, first correct loose wiring condition, and then, if necessary, increase pilot flame. Main Burner The main burner, Figure 30, should display the following characteristics: Cause rapid ignition and carry over of flame across entire burner. Give reasonably quiet operation during ignition, burning and extinction. Cause no excessive lifting of flame from burner ports. If the preceding burner characteristics are not evident, check for accumulation of lint or other foreign material that restricts or other foreign material that restricts or blocks air openings to burner or heater. To clean main burners: 1. Remove main burners from unit. 2. Check that burner venturi and ports are free of foreign matter. 3. Clean burners with bristle brush and/or vacuum cleaner DO NOT distort burner ports or pilot location. 4. Reinstall burners in unit. Make sure front and rear of burners are installed correctly in burner support brackets. Also check for good flow of combustion and ventilating air to the unit. Gas Control Valve Figure 31 shows the two types of combination gas control valves used on these heaters. If gas control valve becomes defective, repairs should not be attempted. A new valve should be installed in place of defective one. LP VALVE TYPICAL PILOT AND MAIN BURNER FLAMES NATURAL VALVE FIGURE 30. FIGURE 31. SERVICE The installer may be able to observe and correct certain problems which may arise when the unit is put into operation. HOWEVER, it is recommended that only a qualified service technician or qualified agencys, using appropriate test equipment, be allowed to service the heater. As preliminary step, check wiring against diagram, check for grounded, broken or loose wires. Check all wire ends to be sure that they are making good contact. ELECTRICAL SERVICING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING. 35
36 Troubleshooting IGNITION MODULE Before calling your service agent, the following checklist should be examined to eliminate obvious problems from those requiring replacement or servicing. Check that main manual gas shut-off valve is fully open and that gas service has not been interrupted. Check that after following the water OPERATING INSTRUCTIONS, the Top Knob of the gas control valve is in ON position. Check electrical supply to the water heater for possible blown (or tripped) fusing or power interruption. Is the water temperature in tank below the thermostat dial setting on the thermostat (calling for heat)? It is possible that the high limit (E.C.O.) has functioned to shut off the water heater. See FEATURES - Water Temperature Control for reset procedure. Contact your serviceman if limit continues to function to shut off water heater. Green LED Indicates Next System Action Recommended Service Action Flash Code a OFF No Call for Heat Not applicable None Flash Fast Power up - internal check Not applicable None Heartbeat Norma l startup ignition sequence started (including prepurge) Not applicable None 4 Seconds ON then x flashes Device in run mode. x = flame current to the nearest μ A. 2 5 minute Retry Delay - Pilot flame not detected during trial for ignition Not applicable Initiate new trial for ignition after retry delay completed. 3 Recycle - Flame failed during run Initiate new trial for ignition. Flash code will remain through the ignition trial until flame is proved. 4 Flame sensed out of sequence If situation self corrects within 10 seconds, control returns to normal sequence. If flam e out of sequence remains longer than 10 seconds, control will resume normal operation 1 hour after error is corrected. 6 Control Internal Error Control remains in wait mode. When the fault corrects, control resumes normal operation. 7 Flame rod shorted to ground Control remains in wait mode. When the fault corrects, control resumes normal operation. 8 Low secondary voltage supply Control remains in wait mo de. When the fault corrects, control resumes normal operation. None If system fails to light on next trial for ignition check gas supply, pilot burner, spark and flame sense wiring, flame rod contaminated or out of position, burner ground connection. If system fails to light on next trial for ignition, check gas supply, pilot burner, flame sense wiring, contamination of flame rod, burner ground connection. Check for pilot flame. Replace gas valve if pilot flame present. If no pilot flame, cycle Call for Heat. If error repeats, replace con trol. Cycle Call for Heat. If error repeats, replace control. Check flame sense lead wire for damage or shorting. Check that flame rod is in proper position. Check flame rod ceramic for cracks, damage or tracking. Check transformer and AC line for proper input voltage to the control. Check with full system load on the transformer. a Flash Code Descriptions: - Flash Fast: rapid blinking. - Heartbeat: Constant ½ second bright, ½ second dim cycles. - 4 second solid on pulse followed by x 1 second flashes indicates flame current to the nearest μ A. This is only available in run mode. - A single flash code number signifies that the LED flashes X times at 2H z, remains off for two seconds, and then repeats the sequence. FLUE DAMPER Do not turn damper open manually or motor damage will result, use the service switch. All readings are taken from harness 36 receptacle. Do not push meter leads into harness receptacle. This opens the pins and will create connection problems. See the following EFFIKAL RVGP-KSF-SERIES FLUE DAMPER TROUBLE SHOOTING GUIDE.
37 EFFIKAL RVGP-KSF-SERIES FLUE DAMPER TROUBLE SHOOTING GUIDE Do not turn damper open manually or motor damage will result, use the service switch. All readings are taken from harness receptacle. Do not push meter leads into harness receptacle. This opens the pins and will create connection problems. PIN END VIEW Note: Damper disc shown in open position. Effikal Pinouts Adapter wire & wire colors Function colors in* 1. Brown 24 VAC HOT Black 2. Orange Signal In yellow 3. Yellow Signal Out red 4. Black 24 VAC Common White 24 V.A.C. normal SEQUENCE OF OPERATION A. FLUE DAMPER OPEN OR OPENING (Unit is calling for heat and damper disc should be in vertical position) VOLTAGE ACROSS: 4 & 1 All Times that High Limit is closed 4 & 2 Calling for Heat Open or Opening 4 & 3 During Combustion Damper Open+ WARNING Do not negate the action of any existing safety or operational controls. B. FLUE DAMPER CLOSED (Unit is not calling for heat and damper disc should be in horizontal position) NOTE: POSITION 4 IS COMMON AND POSITION 3 IS HOT 24VAC VOLTAGE ACROSS: 4 & 1 All Times that High Limit is closed NO VOLTAGE ACROSS: 4 & 3 or 4 & 2 1.Thermostat not calling for heat. A abnormal OPERATION A. NOTHING WORKING NO VOLTAGE ACROSS: 4 & 1 1. High Limit has tripped and is OPEN. Determine reason for tripping of high limit 2. Bad Transformer 3. Loose or broken connections 4. Blown fuse or circuit breaker 5. Disconnect switch off 6. Harness not plugged into water heater receptacle B. DAMPER HAS OPENED, NO COMBUSTION VOLTAGE ACROSS: 4 & 1; 4 & 2; 4 & 3: 1. Check for power at ignition module terminals. If 24VAC power is present damper is working properly. 2. Defective component in water heater after the flue damper. 3. If 24 VAC is not present at the ignition module, look for loose or broken connections between damper and ignition module. 4. If the connections from damper to ignition module seem proper, replace damper assembly. If a damper assembly is not available, place the service switch in the hold open position. This should keep the damper in the open position and allow the customer to have automatic heat, until a replacement damper can be installed. C. DAMPER ROTATES CONTINUOUSLY Change the entire damper assembly D. DAMPER STICKS 1. Make sure no screws obstruct the damper blade. 2. Make sure damper pipe assembly is not egg shaped. 3. Make sure damper rod is not rubbing on pipe assembly. See figure on front page of this insert sheet IMPORTANT: DAMPER MUST BE OPEN BEFORE COMBUSTION TAKES PLACE. If all steps have been tried and damper problems persists call Product Service and Support
38 Troubleshooting checklist COMPLAINT Water not hot enough. Insufficient hot water CAUSE Thermostat set too low. Upper and/or lower temperature probe out of calibration. Thermostat set too low. Upper and/or lower temperature probe out of calibration. Main manual gas shutoff valve partially closed. Heater too small for demand. USER Set thermostat dial to a higher temperature. Call qualified service agency. Set thermostat dial to a higher temperature. Call qualified service agency. Open main manual gas shutoff valve to fullest extent. Space usage to give heater time to restore water temperature. REMEDY QUALIFIED SERVICE AGENCY Check continuity and resistance (Ohms) of upper and lower thermostat probes. Replace probes if out of specification. Check continuity and resistance (Ohms) of upper and lower thermostat probes. Replace probes if out of specification.. Heater recovery is slower. Draft hood not installed or one or more baffles. Call qualified service agency. Call qualified service agency. Check gas input. If incorrect, adjust gas pressure or replace main burner orifice. Install draft hood or baffles as furnished with unit. Water temperature too hot. Thermostat set too high. Set thermostat to a lower setting. Heater makes sounds: sizzling. Condensation on outside of tank - normal. Rumbling. Sediment accumulation on bottom of tank. Drain a quantity of water through drain valve. If rumbling persists, call a qualified service agency. Delime heater. Ticking or metallic sounds. Expansion and contractionnormal. Pounding / water hammer. Air chambers in piping have become waterlogged. Thermal expansion tank damaged, improperly charged, or improperly sized. Drain piping system and refill. Heater must be off while this is being done. Check thermal expansion tank charge pressure when the water system pressure is zero. Follow the manufacturer's instructions for proper charging of the thermal expansion tank. Too much primary air. Adjust shutters. Combustion noises. Overtired heater. Incorrect burners or orifice for types of gas used. Call qualified service agency. Check and correct as necessary. Drain valve not closed tightly. If drain valve cannot be closed tightly, replace. Water leaks. If leakage source cannot be corrected or identified, call qualified service agency. Shut off gas supply to heater and close cold water inlet valve to heater. Repair or in case of suspected tank leakage, be certain to confirm before replacing heater. Gas odors. Heater is overtired. Shut off gas supply to heater and call qualified service agency. Check for sooted flue passage. Check for obstructed vent line. Check backdraft or lack of draft. Draft hood may be improperly installed or not sized properly. Possible gas leaks. Shut off gas supply to heater and call gas company at once. 38
39 For Your Information start up conditions SMOKE/ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while. STRANGE SOUNDS Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not necessarily represent harmful or dangerous conditions. Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See Condensation" section in this manual. CONDENSATION Whenever the water heater is filled with cold water, some condensate will form while the burner is on. A water heater may appear to be leaking when in fact the water is condensation. This usually happens when: a. A new water heater is filled with cold water for the first time. b. Burning gas produces water vapor in water heaters, particularly high efficiency models where flue temperatures are lower. c. Large amounts of hot water are used in a short time and the refill water in the tank is very cold. Moisture from the products of combustion condense on the cooler tank surfaces and form drops of water which may fall onto the burner or other hot surfaces to produce a sizzling or frying noise. operational conditions HOT WATER ODOR In each water heater there is installed at least one anode rod for corrosion protection of the tank. Certain water conditions will cause a reaction between this rod and the water. The most common complaint associated with the anode rod is one of a rotten egg smell in the hot water. The smell is a result of four factors which must all be present for the odor to develop: a. A concentration of sulfate in the supply water. b. Little or no dissolved oxygen in the water. c. A sulfate reducing bacteria which has accumulated within the water heater (this harmless bacteria is nontoxic to humans). d. An excess of active hydrogen in the tank. This is caused by the corrosion protective action of the anode rod. Smelly water may be eliminated or reduced in some water heater models by replacing the anode rod(s) with one of less active material, and then chlorinating water heater tank and all water lines. Contact the local water heater supplier or service agency for further information concerning an Anode Rod Replacement Kit and this chlorination treatment. If smelly water persists after anode rod replacement and chlorination treatment, we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem. Do not remove the anode rod leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided. AIR IN HOT WATER FAUCETS HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explosive. To prevent the possibility of injury under these conditions, we recommend the hot water faucet, located farthest away, be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open flame near the faucet at the time it is open. HIGH WATER TEMPERATURE SHUT OFF SYSTEM This water heater is equipped with a manual reset type high limit (Energy Cutout) switch. The high limit switch interrupts the main burner gas flow should water temperature reach 203 F (95 C). In the event of high limit switch operation, the water heater cannot be restarted unless the water temperature is reduced to approximately 120F (49C). The high limit reset button on the front of the thermostat then needs to be depressed. See Figure 2 for the location of the reset button. 39
40 water Piping Diagrams MULTI FLUE - (1 UNIT) WITH VERTICAL STORAGE TANK WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER TO FIXTURES ALT. COLD WATER CONNECTION FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE FULL PORT BALL VALVE PRESSURE RELIEF VALVE CHECK VALVE CIRCULATING PUMP TEMPERATURE GAGE TANK TEMPERATURE CONTROL WATER FLOW SWITCH DRAIN HOT WATER RETURN FROM FIXTURES COLD WATER SUPPLY EXPANSION TANK 40
41 MULTI FLUE - (1 UNIT) WITH HORIZONTAL STORAGE TANK WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER TO FIXTURES ALTERNATE LOCATION FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE FULL PORT BALL VALVE PRESSURE RELIEF VALVE CHECK VALVE CIRCULATING PUMP TEMPERATURE GAGE TANK TEMPERATURE CONTROL WATER FLOW SWITCH DRAIN CIRCULATING PUMP HOT WATER RETURN FROM FIXTURES COLD WATER SUPPLY EXPANSION TANK 41
42 MULTI FLUE - (1 UNIT) WITH MIXING VALVE TWO TEMPERATURE WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER OUTLET TEMPERED WATER OUTLET TEMPERED WATER RETURN HOT COLD WATER SUPPLY COLD HOT WATER RETURN EXPANSION TANK NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). LEGEND TEMPERATURE & PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH 42
43 MULTI FLUE - (2 UNITS) WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER TO FIXTURES NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). LEGEND TEMPERATURE & PRESSURE RELIEF VALVE FULL PORT BALL VALVE PRESSURE RELIEF VALVE CHECK VALVE CIRCULATING PUMP TEMPERATURE GAGE TANK TEMPERATURE CONTROL WATER FLOW SWITCH DRAIN HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK 43
44 MULTI FLUE - (2 UNITS) WITH VERTICAL STORAGE TANK WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN HOT WATER TO FIXTURES ALTERNATE COLD WATER CONNECTION FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK 44
45 MULTI FLUE - (2 UNITS) WITH VERTICAL STORAGE TANK WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN HOT WATER TO FIXTURES ALTERNATE COLD WATER CONNECTION FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK 45
46 LEGEND MULTI FLUE - (2 UNITS) WITH HORIZONTAL STORAGE TANK TEMPERATURE & PRESSURE RELIEF VALVE WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN HOT WATER TO FIXTURES ALTERNATE LOCATION COLD WATER SUPPLY FINISHED FLOOR EXPANSION TANK NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH HOT WATER RETURN FROM FIXTURES 46
47 MULTI FLUE (2 UNITS) TWO TEMPERATURE WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER TO FIXTURES BOOSTER WATER TO FIXTURES 1st HEATER HOT WATER RETURN COLD WATER SUPPLY PRE-HEATED WATER TO BOOSTER BOOSTER HEATER EXPANSION TANK NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE FULL PORT BALL VALVE PRESSURE RELIEF VALVE CHECK VALVE CIRCULATING PUMP TEMPERATURE GAGE TANK TEMPERATURE CONTROL WATER FLOW SWITCH DRAIN BOOSTER WATER RETURN 47
48 LEGEND MULTI FLUE (2 UNITS) WITH BOOSTER TWO TEMPERATURE TEMPERATURE & PRESSURE RELIEF VALVE WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN HOT OUTLET AT STORED TEMPERATURE BOOSTER RETURN (IF USED) PRE-HEATER PRE-HEATER BOOSTED WATER OUTLET COLD WATER SUPPLY TYPICAL BOOSTER HEATER EXPANSION TANK FINISHED FLOOR MUST BE IDENTICAL HEATERS NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH HOT WATER RETURN 48
49 MULTI-FLUE (3 UNITS) WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER TO FIXTURES NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN COLD WATER SUPPLY EXPANSION TANK FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH HOT WATER RETURN 49
50 LEGEND FULL PORT BALL VALVE TEMPERATURE & PRESSURE RELIEF VALVE MULTI-FLUE (3 UNITS) WITH VERTICAL STORAGE TANK CHECK VALVE PRESSURE RELIEF VALVE TEMPERATURE GAGE CIRCULATING PUMP WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. WATER FLOW SWITCH TANK TEMPERATURE CONTROL DRAIN TO FIXTURES HOT WATER HOT WATER RETURN ALT. COLD WATER CONNECTION AOS STORAGE TANK HEATER HEATER HEATER COLD WATER SUPPLY EXPANSION TANK FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. 50
51 MULTI-FLUE (3 UNITS) WITH HORIZONTAL STORAGE TANK WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER TO FIXTURES HEATER HEATER HEATER AOS STORAGE TANK FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN ALTERNATE LOCATION FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK 51
52 MULTI FLUE FLUE (4 UNITS) WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. HOT WATER TO FIXTURES FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. LEGEND TEMPERATURE & PRESSURE RELIEF VALVE FULL PORT BALL VALVE PRESSURE RELIEF VALVE CHECK VALVE CIRCULATING PUMP TEMPERATURE GAGE TANK TEMPERATURE CONTROL WATER FLOW SWITCH DRAIN HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK 52
53 MULTI-FLUE (4 UNITS) WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE & PRESSURE RELIEF VALVE FULL PORT BALL VALVE PRESSURE RELIEF VALVE CHECK VALVE CIRCULATING PUMP TEMPERATURE GAGE WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. TANK TEMPERATURE CONTROL WATER FLOW SWITCH DRAIN HOT WATER TO FIXTURES HOT WATER RETURN ALT. COLD WATER CONNECTION COLD WATER SUPPLY EXPANSION TANK AOS STORAGE TANK HEATER HEATER HEATER HEATER FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. 53
54 LEGEND MULTI-FLUE (4 UNITS) WITH HORIZONTAL STORAGE TANK TEMPERATURE & PRESSURE RELIEF VALVE WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS. PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN HOT WATER TO FIXTURES HEATER HEATER HEATER HEATER AOS STORAGE TANK ALTERNATE LOCATION FINISHED FLOOR NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control. FULL PORT BALL VALVE CHECK VALVE TEMPERATURE GAGE WATER FLOW SWITCH HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK 54
55 manifold kits TWO UNIT MANIFOLD KIT ( ) THREE UNIT MANIFOLD KIT ( ) MODEL BCG370T120 BCG380T150 BCG380T180 BCG3100T199 BCG380T199 (A)BCG3100T200 (A)BCG3100T250 (A)BCG365T250 (A)BCG3100T275 (A)BCG365T300 (A)BCG385T360 (A)BCG3100T390 DIMENSIONS "A" INCHES (CM) (177cm) (185cm) (171cm) (192cm) (171cm) 7 (183cm) 7 (183cm) (191cm) 7 (183cm) (191cm) (202cm) (192cm) FOUR UNIT MANIFOLD KIT ( ) 55
56 notes 56
57 notes 57
58 notes 58
59 Model BCG3 & ABCG Limited Warranty American Water Heater Company, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater. 1. THE TANK If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corrosion from potable water therein, during the first THREE years after initial installation, the warrantor will supply a complete new American water heater of equivalent size and current model. Some government agencies are requiring energy efficient standards for water heaters. In the event regulations prohibit sale of a model of equivalent size and construction, American Water Heater Company will provide a model which complies with the regulations of your area, in which case the consumer will be charged the difference in price between the like replacement and the energy efficient model required. The warranty on the replacement water heater will be limited to the unexpired term of the original warranty. 2. ALL OTHER PARTS If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective in material or workmanship, the warrantor will repair or replace such part or portion at its option. 3. CONDITIONS AND EXCEPTIONS This warranty shall apply only when the water heater is installed in accordance with local plumbing and building codes, ordinances and regulations, the printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, certified by A.G.A./CGA and approved by the American Society of Mechanical Engineers, must have been installed. a. This warranty shall apply only when the heater is: (1) used at temperatures not exceeding the maximum calibrated setting of its thermostat; (2) used at water pressure not exceeding the working pressure shown on the heater; (3) filled with potable water, free to circulate at all times and with the tank free of damaging water sediment or scale deposits; (4) used in a non-corrosive and non-contaminated atmosphere; (5) used with factory approved anode(s) installed; (6) in its original installation location; (7) in the United States, its territories or possessions, and Canada; (8) sized in accordance with proper sizing techniques for commercial and/or residential water heaters; (9) bearing a rating plate which has not been altered, defaced or removed, except as required by the warrantor; (10) used in an open system or in a closed system with properly sized and installed thermal expansion tank; (11) operated with properly installed sediment trap; (12) fired with the fuel for which it was factory built; (13) fired at the factory rated input; (14) operated with the inner and outer combustion chamber doors in place. b. Any accident to the water heater, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, any use of insulation blankets, or any attempt to repair tank leaks will void this warranty. c. This warranty is void if a device acting as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater is connected to, unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times. The relief valve installed on the heater is not an acceptable method. 4. SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other costs. Such costs may include but are not limited to: a. Labor charges for service removal, repair or reinstallation of the water heater or any component part; b. Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and returning the claimed defective heater or part to such distributor. c. All cost necessary or incidental for any material and/or permits required for installation of the replacement heater or part. 5. LIMITATIONS ON IMPLIED WARRANTIES Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state or provincial law are limited to one (1) year duration for the heater or any of its parts. Some states and provinces do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you. 6. CLAIM PROCEDURE Any claim under the warranty should be initiated with the dealer who sold the heater, or with any other dealer handling the warrantor s products. If this is not practicable, the owner should contact: U.S. Customers American Water Heater Company PO Box 1597, 500 Princeton Road Johnson City, TN a. The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the warrantor. b. Dealer replacements are made subject to in-warranty validation by warrantor. 7. DISCLAIMERS NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE HEATER. THE WARRANTOR SHALL NOT BE RE- SPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR IN TORT. a. Some states or provinces do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may not apply to you. b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the heater s rating plate. Model No. Serial No. Date Installed Dealer s Name Dealer s Address Phone No. City and State/Province Zip/PostalCode KEEP THIS WARRANTY POSTED ADJACENT TO THE HEATER FOR FUTURE REFERENCE 59
60 P.O. Box 1597, Johnson City, TN American Water Heater Phone: Fax: Johnson City, TN Copyright 2012 American Water Heater Company. All rights reserved.
Instruction Manual. Series 300, 301. For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER.
500 Tennessee Waltz Parkway Ashland City, TN 37015 Instruction Manual COMMERCIAL GAS WATER HEATERS MODELS BT-80, BT-100 Series 300, 301 INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY
COMMERCIAL GAS WATER HEATERS
Instruction Manual COMMERCIAL GAS WATER HEATERS www.americanwaterheater.com American Water Heater Johnson City, TN 37605 MODELS BCL380T1206NOX, BCL380T1546NOX, BCL380T1806NOX, BCL380T1996NOX, BCL3100T1996NOX,
COMMERCIAL GAS WATER HEATERS
Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENTED GAS MODELS W/HOT SURFACE IGNITION MODEL BTX-80 SERIES 100 500 Tennessee Waltz Parkway Ashland City, TN 37015 Low Lead Content For Your Safety
MODELS BTR(C)120 THRU 500A
MODELS BTR(C)120 THRU 500A COMMERCIAL GAS, GLASS-LINED, TANK-TYPE WATER HEATER INSTALLATION OPERATION MAINTENANCE LIMITED WARRANTY Thank you for buying this energy efficient water heater from A.O. Smith
PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.
Instruction Manual COMMERCIAL GAS WATER HEATERS MODELS CG(N,L)075075, CG(N,L)075100 Series 300, 301 300 Maddox Simpson Parkway Lebanon, TN 37090 Phone: 615-889-8900 Fax: 615-547-1000 Technical Service
Instruction Manual for Residential Manufactured Home Gas Water Heaters
Instruction Manual for Residential Manufactured Home Gas Water Heaters FOR USE ONLY IN MANUFACTURED HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons
PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.
Instruction Manual RESIDENTIAL GAS WATER HEATERS FOR USE ONLY IN MANUFACTURED HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with input rating
Instruction Manual for Residential Gas Water Heaters
Instruction Manual for Residential Gas Water Heaters NOT FOR USE IN MANUFACTURED (MOBILE) HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with
PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.
Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENT/POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION Ashland City, TN 37015 www.hotwater.com For Your Safety AN ODORANT IS ADDED TO THE GAS
Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
RESIDENTIAL GAS WATER HEATERS
Instruction Manual RESIDENTIAL GAS WATER HEATERS NOT FOR USE IN MANUFACTURED (MOBILE) HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with input
Tankless Water Heater
Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not
Water Heater Safety Tips
Instruction Manual for Light Duty Commercial Power Direct Vent Gas Water Heaters ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE HEATER WAS PURCHASED. IF YOU
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
COMMERCIAL GAS WATER HEATERS
Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENTED GAS MODELS W/HOT SURFACE IGNITION MODEL SHE 50 76N SERIES 100 500 Tennessee Waltz Parkway Ashland City, TN 37015 Low Lead Content For Your Safety
INDIRECT WATER HEATER. Installation and Operating Instruction Manual
INDIRECT WATER HEATER Installation and Operating Instruction Manual Maximum supply temperature to heat exchanger must not exceed 180 F (82 C). Safety Warning: Indirect water heaters are heat-producing
ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL
ELECTRIC WATER HEATER A Spanish language version of these instructions is available by contacting the manufacturer listed on the rating plate. La version espanola de estas instruccions se puede obtener
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Instruction Manual. A DIVISION OF A. O. SMITH CORPORATION RENTON, WASHINGTON www.hotwater.com
Instruction Manual Commercial Semi-Instantaneous Water Heaters ALL HWI MODELS INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY A DIVISION OF A. O. SMITH CORPORATION RENTON, WASHINGTON
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
Instantaneous gas water heater
Instantaneous gas water heater Models W 125...T1 installation operation maintenance The Bosch instantaneous water heater is a high efficiency, space saving answer to your water heating needs. All Bosch
Residential Gas Water Heaters. Residential 30, 38, 40 and 50 Gallon
! Warning: This water heater is not suitable for use in manufactured (mobile) homes! Use & Care Manual With Installation Instructions for the Installer Residential Gas Water Heaters The purpose of this
Commercial Gas Water Heaters
UP TO 96% THERMAL EFFICIENCY, DIRECT-VENT FEATURES TM BTH-120 through BTH-500 The A. O. Smith Cyclone Xi family of products represents the industry s most technologically advanced commercial water heaters.
Residential 30, 38, 40, 50 and 60 Gallon
! WARNING: This water heater is not suitable for use in manufactured (mobile) homes! Use & Care Manual With Installation Instructions for the Installer Residential Gas - FVIR Certified Water Heaters Residential
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
INSTALLATION, OPERATION, AND SERVICE MANUAL RESIDENTIAL STORAGE TYPE GAS WATER HEATER
INSTALLATION, OPERATION, AND SERVICE MANUAL RESIDENTIAL STORAGE TYPE GAS WATER HEATER THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION
COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL
COMMERCIAL ELECTRIC WATER HEATER La A version Spanish espanola language de version estas of instrucciones these instructions se puede is available obtener al by escribirle contacting a la the fábrica company
Commercial Gas Water Heaters
CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable
Installation Instructions and Use & Care Guide
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. Do not store or use gasoline or other flammable
LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL
LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATER A Spanish language version of these instructions is available by contacting the company listed on the rating plate. La versión espãnola de estas instrucciones
Water Heaters. Residential 30, 40 and 50 Gallon
! WARNING: This water heater is not suitable for use in manufactured (mobile) homes! Use & Care Manual With Installation Instructions for the Installer Gas Residential Water Heaters Model: HG Series, GG
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Condensing Water Heater Operation Manual Model NPE-180A/ 210A/ 240A NPE-180S/ 210S/ 240S * Lead Free Keep this manual near this water heater for future reference whenever maintenance or service is required.
Water Heaters. Use & Care Manual. Electric Point of Use IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
Electric Point of Use Water Heaters LISTED 786H IMPORTANT SAFETY INSTRUCTIONS Printed in USA Use & Care Manual With Installation Instructions for the Installer The purpose of this manual is twofold: one,
SHC 2.5, SHC 4 MINI-TANK ELECTRIC WATER HEATERS INSTALLATION INSTRUCTIONS FOR THE LICENSED PLUMBER SHC 2.5 SHC 4. English. English
SHC 2.5, SHC 4 MINI-TANK ELECTRIC WATER HEATERS INSTALLATION INSTRUCTIONS FOR THE LICENSED PLUMBER The SHC series is tested and certified by WQA against NSF/ANSI 372 for lead free compliance. SHC 2.5 Table
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
Water Heaters. Residential 30, 40 and 50 Gallon
Residential 30, 40 and 50 Gallon Use & Care Manual With Installation Instructions for the Contractor Gas Residential Water Heaters Model: HG Series, GG Series, GP Series, PG Series, SG Series, SG Series
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS Installation and service must be provided by a qualified installer, service agency or gas supplier Grand Canyon Gas Logs, logs are made
Commercial Gas Water Heater
Commercial Gas Water Heater 3-Year Limited Tank/1-Year Limited Parts Warranty* The Polaris has a high grade 444 stainless steel tank with brass connections for years of dependable, trouble-free service
TANKLESS WATER HEATER USE AND CARE MANUAL
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing death, personal injury, or property damage. For Your Safety! Do not store or use gasoline
HEAVY DUTY STORAGE GAS
Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many
Electric Water Heater
Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.
RESIDENTIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS
RESIDENTIAL GAS-FIRED WATER HEATERS (EQUIPPED WITH FVIR TECHNOLOGY) OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS This water heater IS NOT design certified for installation in a manufactured (mobile)
COMMERCIAL GAS WATER HEATER
Owner s Manual COMMERCIAL GAS WATER HEATER FOR POTABLE WATER HEATING ONLY NOT SUITABLE FOR SPACE HEATING NOT FOR USE IN MOBILE HOMES MODEL NO. CAPACITY 153.338074 74 Gallon (280 Liter) 153.338004 98 Gallon
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
RESIDENTIAL GAS WATER HEATERS
Installation and Operating Manual RESIDENTIAL GAS WATER HEATERS POWER VENTED GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED (MOBILE) HOMES 300 Maddox Simpson Parkway Lebanon, TN 37090
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
COMMERCIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS
COMMERCIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS This water heater IS NOT design certified for installation in a manufactured (mobile) home or for installation
GAS SAFETY PRECAUTIONS
GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier. These instructions must be posted in a prominent location where the unit is to be operated.
Please keep this manual for f uture reference.
GAS WATER/AGUA Congratulations! You've just purchased a new Marey Portable tankless water heater and will soon begin to enjoy the benefits of going tankless. Take the time to thoroughly read and understand
CALIFORNIA PROPOSITION 65 WARNING:
Residential Solar Water Heater USE & CARE MANUAL WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR LISTED 786H The purpose of this manual is twofold: one, for the installing contractor, to provide requirements
TANKLESS WATER HEATER INSTALLATION DIAGRAMS
TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water
COMMERCIAL GAS WATER HEATER GAS-FIRED POWER BURNER FOR DOMESTIC HOT WATER
HIGH EFFICIENCY AHCG3/HCG360T120 thru AHCG3/HCG3100T250 COMMERCIAL GAS WATER HEATER GAS-FIRED POWER BURNER FOR DOMESTIC HOT WATER INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING: If
GAS-FIRED WATER HEATER
GAS-FIRED WATER HEATER A Spanish language version of these instructions is available by contacting the company listed on the rating plate. La version espanola de estas instrucciones se puede obtener al
RESIDENTIAL GAS WATER HEATERS
Instruction Manual RESIDENTIAL GAS WATER HEATERS POWER VENTED GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED (MOBILE) HOMES GAMA certification applies to all residential gas water heaters
NAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
Commercial Gas Water Heaters
POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil
CYCLONE Xi Model BTH 120-250(A) SERIES 100 AND 101
CYCLONE Xi Model BTH 120-250(A) SERIES 100 AND 101 COMMERCIAL GAS WATER HEATER GAS-FIRED POWER BURNER FOR DOMESTIC HOT WATER INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING: If the
American Fireglass Outdoor Fire pit kit information. General instructions/warnings for outdoor gas pan and burner systems
American Fireglass Outdoor Fire pit kit information General instructions/warnings for outdoor gas pan and burner systems We strongly recommend that our burner products be installed by a licensed and certified
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
INSTALLATION & SERVICE MANUAL
INSTALLATION & SERVICE MANUAL POWER VENTED GAS WATER HEATER If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or
Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:
Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,
Instruction Manual. Thank you for buying this energy efficient water heater. We appreciate your confidence in our products.
Instruction Manual COMMERCIAL ELECTRIC WATER HEATERS 500 Tennessee Waltz Parkway Ashland City, TN 37015 MODELS PCE-6/10/17/20 10MSA Series 102 PCE-30/40/50 2OLSA Series 110 & PCE-30/40/52/66/82/120 2ORTA
ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER (EF Series Models)
ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER (EF Series Models) WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal
Installation and Operating Instruction Manual
Electric Mini Tank Water Heaters CMT-1.3 CMT-2.5 CMT-4.0 CMT-ST70 Tempering valve Optionally available Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 3 General
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS HEAT-FLO HOT WATER STORAGE / BOOSTER TANKS MODELS 30-ST, 40-ST, 40L-ST, 60-ST, 60L-ST, 80-ST, 115-ST, 80-ST-C, 115-ST-C FOR SINGLE TANK INSTALLATIONS For
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION As when installing or using any high voltage electrical appliance, basic safety precautions should always
Techtanium Solar Indirect Water Heater Instruction Manual
To the Installer: Please attach these instructions next to the water heater. To the Consumer: Please read these and all component instructions and keep for future reference. Techtanium Solar Indirect Water
OPERATING, INSTALLATION AND SERVICE MANUAL
OPERATING, INSTALLATION AND SERVICE MANUAL COMMERCIAL GAS WATER HEATER WITH FLUE DAMPER AND ELECTRIC IGNITION SYSTEM WITHOUT FAN MOTOR REQUIRES 120V A.C. POWER SUPPLY WARNING: If the information in these
POWER MISER 6 ELECTRIC WATER HEATER
Owner s Manual POWER MISER 6 ELECTRIC WATER HEATER FOR POTABLE WATER HEATING ONLY. NOT SUITABLE FOR SPACE HEATING. MODEL NO. 153.326362 30 Gal. 153.326363 30 Gal. 153.326462 40 Gal. 153.326463 40 Gal.
INSTALLATION INSTRUCTIONS
PRODUCT LITERATURE Lennox Industries Inc. Dallas, Texas INSTALLATION INSTRUCTIONS GWB8-042IE-2, GWB8-075IE-2 GWB8-112IE-2, GWB8-150IE-2 GWB8-187IE-2, GWB8-225IE-2 GAS FIRED BOILER RETAIN THESE INSTRUCTIONS
POWER MISER TM 12 ELECTRIC WATER HEATER
Owner s Manual POWER MISER TM 12 ELECTRIC WATER HEATER FOR POTABLE WATER HEATING ONLY. NOT SUITABLE FOR SPACE HEATING. MODEL NO. 153.321342 30 Gal. 153.321343 30 Gal. 153.321442 40 Gal. 153.321443 40 Gal.
What to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
INSTALLATION, OPERATION, AND SERVICE MANUAL POWER VENT STORAGE TYPE GAS WATER HEATER MODELS PVG/PVCG
INSTALLATION, OPERATION, AND SERVICE MANUAL POWER VENT STORAGE TYPE GAS WATER HEATER MODELS PVG/PVCG THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT
Residential Electric Water Heater
Residential Electric Water Heater Installation Instructions and Use & Care Guide To obtain technical, warranty or service assistance during or after the installation of this water heater, call toll free
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
INSTALLATION & SERVICE MANUAL
SINGLE-WALL INDIRECT WATER HEATER To avoid damage or injury, there must be no materials stored against the indirect water heater and proper care shall be taken to avoid unnecessary contact (especially
CHAPTER 5 WATER HEATERS
PlumbingCode06_ch05 5/29/06 8:12 AM Page 1 CHAPTER 5 WATER HEATERS Water heaters are only a small portion of a plumbing system, but they are important, and they can be dangerous. Many plumbers take water
Mini Tank. Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0. Installation and Operating Instruction Manual
Mini Tank Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0 Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 3 General Information 3/6 Technical
TECHNICAL MANUAL GDS8 & GHS8
TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as
94% CONDENSING TANKLESS WATER HEATER USE AND CARE MANUAL
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing death, personal injury, or property damage. For Your Safety! Do not store or use gasoline