1 Instruction Manual commercial gas water heaters American Water Heater Johnson City, TN MODELS BCG3 & ABCG3 SERIES 118/119 INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY Low Lead Content WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor s phone. Follow the gas supplier s instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. Thank you for buying this energy efficient water heater. We appreciate your confidence in our products. Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater. Failure to follow these instructions and safety messages could result in death or serious injury. This manual must remain with the water heater. place these instructions adjacent to heater and notify owner to keep for future reference. PRINTED

2 Table Of Contents Safe Installation, Use and Service... 3 Approvals... 3 General Safety Information Precautions... 5 Grounding Instructions... 5 Hydrogen Gas Flammable... 5 Introduction... 6 Abbreviations Used... 6 Qualifications... 6 Preparing for the Installation... 6 Features And Components... 7 The Eliminator (Self Cleaning System)... 7 High Limit Switch... 7 Electronic Ignition Control... 7 Automatic Flue Damper... 7 Uncrating... 7 Installation Considerations Rough In Dimensions... 8 Locating The Water Heater Clearances NSF Leg Kit...11 Insulation Blanket...11 Hard Water...11 Circulation Pumps High Altitude Installations Installation Requirements Gas Supply Systems Supply Gas Regulator Power Supply Water Temperature Control and Mixing Valves Dishwashing Machines Closed Water Systems Thermal Expansion Temperature-Pressure Relief Valve Contaminated Air Air Requirements Unconfined Space Confined Space Venting Installation Venting Vent Reducer Multiple Heater Manifold Fresh Air Opening for Confined Spaces Outdoor Air Through Two Openings Outdoor Air Through One Opening Outdoor Air Through Two Horizontal Ducts Outdoor Air Through Two Vertical Ducts Air From Other Indoor Spaces Technical Data Venting Mechanical Venting Water Heater Installation Water Line Connections T&P Valve Discharge Pipe Installation Diagrams - Top Inlet/Outlet Usage Heater Wiring Gas Piping Gas Line Leak Testing Purging OPERATION Prior to Start Up Sequence of operation Sequence of Operation Flow Chart Lighting & Operation Labels Adjustments Checking Venting Checking the Input maintenance Venting System Remote Storage Tank Temperature Control Temperature-Pressure Relief Valve Test Anode Rod Inspection Draining and Flushing Recommended Procedure for Periodic Removal or Lime Deposits from the Tank Type Commercial Water Heaters DeLiming Solvents Tank Cleanout Procedure Deliming Using Flo-Jug Method Pilot Burner Main Burner Gas Control Valve service Electrical Servicing Troubleshooting Ignition Module Flue Damper Effikal RVGP-KSF Series Flue Damper Trouble Shooting Guide Troubleshooting Checklist For your information Start up Conditions Operational Conditions Water Piping Diagrams MANIFOLD KITS Notes Warranty

3 Safe Installation, Use and Service The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use, or service this water heater. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which, if not avoided, will result in injury or death. WARNING indicates a potentially hazardous situation which, if not avoided, could result in injury or death. CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage. All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and how to avoid the risk of injury. The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances. This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This water heater can cause low level exposure to some of the substances listed in the Act. APPROVALS Low Lead Content Note: ASME construction is optional on the water heaters covered in this manual. 3

4 General Safety Information Fire or Explosion Hazard Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Avoid all ignition sources if you smell gas. Do not expose water heater controls to excessive gas pressure. Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles. Keep ignition sources away from faucets after extended periods of non-use. Read instruction manual before installing, using or servicing water heater. Fire Hazard For continued protection against risk of fire: Do not install water heater on carpeted floor. Do not operate water heater if flood damaged. Fire and Explosion Hazard Use joint compound or Teflon tape compatible with propane gas. Leak test before placing the water heater in operation. Disconnect gas piping and main gas shutoff valve before leak testing. Install sediment trap in accordance with NFPA 54. CAUTION Property Damage Hazard All water heaters eventually leak. Do not install without adequate drainage. Electrical Shock Hazard Turn off power to the water heater before performing any service. Label all wires prior to disconnecting when performing service. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Failure to follow these instructions can result in personal injury or death. Fire and Explosion Hazard Do not use water heater with any gas other than the gas shown on the rating label. Excessive gas pressure to gas valve can cause serious injury or death. Turn off gas lines during installation. Contact a qualified installer or service agency for installation and service. Jumping out control circuits or components can result in property damage, personal injury or death. Service should only be performed by a qualified service agent using proper test equipment. Altering the water heater controls and/or wiring in any way could result in permanent damage to the controls or water heater and is not covered under the limited warranty. Altering the water heater controls and/or wiring in any way could result in altering the ignition sequence allowing gas to flow to the main burner before the hot surface igniter is at ignition temperature causing delayed ignition which can cause a fire or explosion. Any bypass or alteration of the water heater controls and/or wiring will result in voiding the water heater warranty. 4

5 General Safety Information Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater. Failure to follow these instructions and safety messages could result in death or serious injury. This manual must remain with the water heater. Explosion Hazard Overheated water can cause water tank explosion. Properly sized temperature and pressure relief valve must be installed in the opening provided. Water temperature over 125 F (52 C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury. Feel water before bathing or showering. Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures. CAUTION Improper installation, use and service may result in property damage. Do not operate water heater if flood damaged. Inspect and anode rods regularly, replace if damaged. Install in location with drainage. Fill tank with water before operation. Properly sized thermal expansion tanks are required on all closed water systems. Refer to this manual for installation and service. Verify the power to the water heater is turned off before performing any service procedures. General Safety Information Precautions DO NOT USE THIS water heater IF ANY PART HAS BEEN UNDER WATER. Immediately call a qualified service agency to inspect the water heater and to make a determination on what steps should be taken next. If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualified service agency. 1. External fire. 2. Damage. 3. Firing without water. Hydrogen Gas Flammable Explosion Hazard Flammable hydrogen gases may be present. Keep all ignition sources away from faucet when turning on hot water. GROUNDING INSTRUCTIONS This water heater must be grounded in accordance with the National Electrical Code and/or local codes. These must be followed in all cases. This water heater must be connected to a grounded, permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater, see Figure Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To reduce the risk of injury under these conditions, it is recommended that a hot water faucet served by this water heater be opened for several minutes before using any electrical appliance connected to the hot water system. If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. There should be no smoking or open flame near the faucet at the time it is open.

6 Introduction Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service. Abbreviations Used Abbreviations found in this Instruction Manual include : ANSI - American National Standards Institute ASME - American Society of Mechanical Engineers AHRI - Air-Conditioning, Heating and Refrigeration Institute NEC - National Electrical Code NFPA - National Fire Protection Association UL - Underwriters Laboratory CSA - Canadian Standards Association Qualifications Qualified Installer or Service Agency Installation and service of this water heater requires ability equivalent to that of a Qualified Agency (as defined by ANSI below) in the field involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service. ANSI Z Sec : Qualified Agency - Any individual, firm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction. If you are not qualified (as defined by ANSI above) and licensed or certified as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual. Preparing For The Installation 1. Read the General Safety section, page 4-5 of this manual first and then the entire manual carefully. If you don t follow the safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. This manual contains instructions for the installation, operation, and maintenance of the gas-fired water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety. Since we cannot put everything on the first few pages, READ THE ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER. 2. The installation must conform with these instructions and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or CAN/ CSA-B149.1 the Natural Gas and Propane Installation Code. All documents are available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH NFPA documents are also available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate. 4. Carefully plan the place where you are going to put the water heater. Correct combustion, vent action, and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fires. Examine the location to ensure the water heater complies with the Locating the New Water Heater section in this manual. 5. For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Office of the State Architect, 400 P Street, Sacramento, CA Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR 2.00: State Plumbing Code and 248-CMR

7 FEATURES AND COMPONENTS the eliminator (self-cleaning system) These units include The Eliminator (Self-Cleaning System) installed in the front water inlet, See Figure 1. The Eliminator inlet tube can only be used in the front water inlet connection. Do not install the Eliminator inlet tube in either the top or back inlet water connection. The Eliminator must be oriented correctly for proper function. There is a marked range on pipe nipple portion of the Eliminator, that must be aligned with top of inlet spud. A label above the jacket hole has an arrow that will point to marked portion of pipe nipple if the orientation is correct. If the arrow does not point within the marked range on pipe nipple, adjust the pipe nipple to correct. A pipe union is supplied with the Eliminator to reduce probability of misaligning the Eliminator accidentally while tightening the connection to inlet water supply line. Improper orientation of the Eliminator can cause poor performance of heater and can significantly reduce outlet water temperatures during heavy draws. by creating a spark at the pilot assembly. See Figure 3. Pilot gas is ignited and burns during each running cycle. The main burner and pilot gases are cut off during the OFF cycle. Pilot gas ignition is proven by the pilot sensor. Main burner ignition will not occur if the pilot sensor does not first sense pilot ignition. Note: The Eliminator may have 1, 3 or 7 cross tubes. FIGURE 1. high limit switch The digital thermostat (Figure 2) contains the high limit (energy cutout) switch. The high limit switch interrupts main burner gas flow should the water temperature reach 203 F (95 C). In the event of high limit switch operation, the water heater cannot be restarted unless the water temperature is reduced to approximately 120 F (49 C). The high limit reset button on the front of the control then needs to be depressed. Continued manual resetting of high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation. The following is a possible reason for high limit switch operation: A malfunction in the thermostatic controls would allow the gas control valve to remain open causing water temperature to exceed the thermostat setting. The water temperature would continue to rise until high limit switch operation. Contact your dealer or service agent if continued high limit switch operation occurs. IGNITION module FIGURE 3. AUTOMATIC FLUE DAMPER All units are equipped with an automatic flue damper that reduces heat loss during the OFF cycles. Each automatic flue damper drive assembly is equipped with a Service Switch, as shown in Figure 4 The Service Switch has 2 positions: AUTOMATIC OPERATION and HOLD OPEN DAMPER. For normal operation the switch should be in the AUTOMATIC OPERATION position. If there is a problem with the damper the Service Switch can be placed in the HOLD OPEN DAMPER position. When the switch is placed in the HOLD OPEN DAMPER position the damper disc will rotate to the open position and the heater may be used until vent assembly is repaired or replaced. DO NOT turn the damper disc manually; damage will occur to the drive assembly if operated manually. Refer to TESTING DAMPER OPERATION section of this manual for additional information. DIGITAL THERMOSTAT FIGURE 2. uncrating flue damper FIGURE 4. electronic ignition control Each heater is equipped with a Honeywell ignition module. The solid state ignition control ignites the pilot burner gas The heater is shipped with the flue damper already installed. The wiring conduit runs from the thermostat to the damper drive cover. Before turning unit on, check to make sure the wiring conduit is securely plugged into damper drive. 7

8 installation considerations Rough In Dimensions See Models Below * BCG370T120 Models are approved for 5 (13 cm) venting using a 6 (15 cm) to 5 (13 cm) reducer. FIGURE 5. TABLE 1. BCG370T1205_ THROUGH (A)BCG3100T3998_ MODEL BCG3 70T120 BCG3 80T150 BCG3 80T180 BCG3 100T199 BCG3 80T199 (A)BCG3 100T200 (A)BCG3 100T250 (A)BCG3 65T250 (A)BCG3 100T275 (A)BCG3 65T300 (A)BCG3 85T360 (A)BCG3 100T390 INPUT RATE BTU/ HR. 120,000 BTU/Hr. 35 Kw/Hr 154,000 BTU/Hr 45 Kw/Hr 180,000 BTU/Hr 53 Kw/Hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 250,000 BTU/Hr 72 kw/hr 251,000 BTU/Hr 73 kw/hr 275,000 BTU/Hr 80 kw/hr 305,000 BTU/Hr 89 kw/hr 365,000 BTU/Hr 107 kw/hr 390,000 BTU/Hr 114 kw/hr APPROX. TANK CAP. 71 Gal 268 L 81 Gal 307 L 81Gal 307 L 100 Gal 379 L 81 Gal 307 L 100 Gal 379 L 100 Gal 379 L 65 Gal 246 L 100 Gal 379 L 65 Gal 246 L 85 Gal 322 L 100 Gal 379 L A B C D E F GAS INLET G /2 177 cm 11 cm 151 cm 129 cm 50 cm 48 cm 1/ /2 185 cm 11 cm 169 cm 147 cm 50 cm 48 cm 1/ /2 171 cm 12 cm 157 cm 136 cm 52 cm 53 cm 1/ /2 192 cm 12 cm 178 cm 157 cm 52 cm 53 cm 1/ /2 171 cm 12 cm 157 cm 136 cm 52 cm 53 cm 1/ /2 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1/ /2 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1/ NA 191 cm 12 cm 167 cm 145 cm 51 cm NA 1/2 1/ /2 183 cm 12 cm 165 cm 142 cm 50 cm 58 cm 1/ NA 191 cm 12 cm 167 cm 145 cm 51 cm NA 1/2 1/ /4 202 cm 12 cm 178 cm 159 cm 57 cm 58 cm 3/ /4 192 cm 12 cm 171 cm 148 cm 68 cm 58 cm 3/4 H cm cm cm cm cm cm cm cm cm cm cm cm VENT DIA. I J cm 71 cm cm 71 cm cm 71 cm cm 71 cm cm 71 cm cm 77 cm cm 77 cm NA 20 cm 70 cm NA cm 77 cm NA 20 cm 70 cm NA cm 70 cm cm 77 cm CONNECTIONS APPROXIMATE INLET OUTLET SHIP WEIGHT TOP FRONT BACK TOP FRONT BACK STD. ASME NA NA NA NA 400 Lbs 182 Kg 470 Lbs 213 Kg 470 Lbs 213 Kg 603 Lbs 273 Kg 470 Lbs 213 Kg 630 Lbs 286 Kg 630 Lbs 286 Kg 750Lbs 341 Kg 630 Lbs 286 Kg 750 Lbs 341 Kg 725 Lbs 329 Kg 760 Lbs 345 Kg NA NA NA NA NA NA NA NA NA NA 725 Lbs 329 Kg 725 Lbs 329 Kg 862 Lbs 391 Kg 725 Lbs 329 Kg 862 Lbs 391 Kg 833 Lbs 379 Kg 874 Lbs 396 Kg 8

9 installation considerations TABLE 2. HEATER PERFORMANCE DATA (A)BCG3 MODELS MODEL BCG3 70T120 BCG3 80T150 BCG3 80T180 BCG3 100T199 BCG3 80T199 (A)BCG3 100T200 (A)BCG3 100T250 (A)BCG3 65T250 (A)BCG3 100T275 (A)BCG3 65T300 (A)BCG3 85T360 (A)BCG3 100T390 INPUT RATE BTUH 120,000 BTU/Hr. 35 Kw/Hr 154,000 BTU/Hr 45 Kw/Hr 180,000 BTU/Hr 53 Kw/Hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 199,000 BTU/Hr 58 kw/hr 250,000 BTU/Hr 72 kw/hr 251,000 BTU/Hr 73 kw/hr 275,000 BTU/Hr 80 kw/hr 305,000 BTU/Hr 89 kw/hr 365,000 BTU/Hr 107 kw/hr 390,000 BTU/Hr 114 kw/hr APPROX. GAL. CAP. 71 Gal 268 L 81 Gal 306 L 81 Gal 306 L 100 Gal 379 L 81 Gal 306 L 100 Gal 379 L 100 Gal 379 L 65 Gal 246 L 100 Gal 379 L 65 Gal 246 L 85 Gal 322 L 100 Gal 379 L EFF. % RECOVERY RATING CAPACITIES (GPH AND LPH) 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F 130 F 140 F (-)1 C 4 C 10 C 15 C 21 C 27 C 32 C 38 C 43 C 49 C 54 C 60 C TABLE 3. GAS AND ELECTRICAL CHARACTERISTICS Gas Supply Pressure Model Type of Gas Minimum Maximum Gas Manifold Pressure Volts/Hz Amperes All Models Natural 4.5" W.C. (1.12 kpa) 14" W.C. (3.48 kpa) 3.5" W.C. (0.87 kpa) 120/60 <5 All Models Propane 11.0" W.C. (2.74kPa) 14" W.C. (3.48kPa) 10.0" W.C. (2.49 kpa) 120/60 <5 9

10 Installation Considerations locating the water heater CAUTION Property Damage Hazard All water heaters eventually leak. Do not install without adequate drainage. When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible. Fire or Explosion Hazard Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Avoid all ignition sources if you smell gas. Do not expose water heater controls to excessive gas pressure. Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles. Keep ignition sources away from faucets after extended periods of non-use. Read instruction manual before installing, using or servicing water heater. Flammable items, pressurized containers or any other potential fire hazardous articles must never be placed on or adjacent to the heater. Open containers or flammable material should not be stored or used in the same room with the heater. The heater must not be located in an area where it will be subject to freezing. Locate it near a floor drain. The heater should be located in an area where leakage from heater or connections will not result in damage to adjacent area or to lower floors of the structure. When such locations cannot be avoided, a suitable metal drain pan should be installed under heater. Such pans should be fabricated with sides at least 2 deep, with length and width at least 2 greater than diameter of heater and must be piped to an adequate drain. Pan must not restrict combustion air flow. clearances These heaters are approved for installation on combustible flooring in an alcove when the minimum clearance from combustion or non-combustible construction are followed as indicated in Figure 6 and Table 4. In all installations the minimum combustible clearances from draft hood surface or vent piping shall be 6 (152mm). Vent piping passing through a combustible wall or ceiling must be a continuous run (no joints) and retain 6 (152mm) clearance unless an approved reducing thimble is used. A service clearance of 24 (610mm) should be maintained from serviceable parts, such as relief valves, baffles, thermostats, cleanout openings or drain valves. TABLE 4. Installation Clearances There is a risk in using fuel burning appliances such as gas water heaters in rooms, garages or other areas where gasoline, other flammable liquids or engine driven equipment or vehicles are stored, operated or repaired. Flammable vapors are heavy and travel along the floor and may be ignited by the heater s igniter or main burner flames causing fire or explosion. Some local codes permit operation of gas appliances in such areas if they are installed 18 or more above the floor. This may reduce the risk if location in such an area cannot be avoided. Do not install this water heater directly on a carpeted floor. A fire hazard may result. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches in any direction. If the heater is installed in a carpeted alcove, the entire floor shall be covered by the panel. Also, see the DRAINING requirements in MAINTENANCE Section. The heater shall be located or protected so it is not subject to physical damage by a moving vehicle. A (RIGHT SIDE) B (LEFTSIDE) C (BACK) D (CEILING) 70T120 1 (2.54 cm) 1 (2.54 cm) 1 (2.54 cm) 12 (30.48 cm) 80T150 1 (2.54 cm) 1 (2.54 cm) 1 (2.54 cm) 12 (30.48 cm) 80T180 1 (2.54 cm) 1 (2.54 cm) 1 (2.54 cm) 12 (30.48 cm) 100T199 1 (2.54 cm) 1 (2. 54 cm) 1 (2.54 cm) 12 (30.48 cm) 80T199 1 (2. 54 cm) 1 (2. 54 cm) 1 (2. 54 cm) 12 (30.48 cm) 100T200 1 (2. 54 cm) 1 (2. 54 cm) 1 (2. 54 cm) 12 (30.48 cm) 100T250 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 65T250 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 100T275 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 65T300 2 (5.08 cm) 2 (5.08 cm) 2 (5.08 cm) 12 (30.48 cm) 85T360 3 (7.75 cm) 3 (7.75 cm) 3 (7.75 cm) 12 (30.48 cm) 100T390 3 (7.75 cm) 3 (7.75 cm) 3 (7.75 cm) 12 (30.48 cm) 10

11 INSULATION BLANKET Breathing Hazard - Carbon Monoxide Gas Do not obstruct water heater air intake with insulating blanket. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. NSF LEG KIT FIGURE 6. The NSF Leg Kit (part number ) is needed only for applications that must conform to NSF/ANSI Standard 5. Installation of the NSF leg kit will increase the height of the unit and all connection points by 3 inches. See Figure 7. Follow these steps to install the Leg Kit: 1. Unit needs to be lifted in a way not to damage unit or laid on it s side to access the bottom of the legs. 2. Slide leg extension under leg and the bolt up through the bottom hole located in the bottom of the leg. 3. Once in place, screw nut down and secure. 4. Front of leg should line up with front of leg extension as shown to make sure weight of unit is distributed through the leg extension. FIGURE 7. Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. The water heaters covered by this manual meet or exceed the Energy Policy Act standards with respect to insulation and standby heat loss requirements, making an insulation blanket unnecessary. Should you choose to apply an insulation blanket to this heater, you should follow these instructions. See the Features and Components section of this manual for identification of components mentioned below. Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death. DO NOT apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood. DO NOT cover the gas control valve, thermostat or the Temperature-Pressure Relief Valve. DO NOT allow insulation to come within 2 (5 cm) of the burners, to prevent blockage of combustion air flow to the burners. DO NOT allow insulation to come within 9 inches (23 cm) of floor, (within 2 inches (5 cm) of bottom cover) to prevent blockage of combustion air flow to the burners.. DO NOT cover the instruction manual. Keep it on the side of the water heater or nearby for future reference. DO obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels. DO inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow. HARD water Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment. See the Maintenance Section in this manual for sediment and lime scale removal procedures. Circulation pumps A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the water heater. See Water Piping Diagrams in this manual for installation location of circulating pumps. See the Circulation Pump Wiring Diagrams in this manual for electrical hookup information. Install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1. All-bronze circulating pumps are recommended for used with commercial water heaters. Some circulating pumps are manufactured with sealed bearings and do not require further lubrication. Some circulating pumps 11

12 NTROL E must be periodically oiled. Refer to the pump manufacturer s instructions for lubrication requirements. CIRCULATING PUMP WIRING DIAGRAM STORAGE TANK OR BUILDING RECIRCULATION FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE STORAGE TANK OR CIRCULATING LOOP RETURN LINE NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION. L1 HOT L2 NEUTRAL 120 VAC POWER FIGURE 8. CIRC PUMP MOTOR CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH DISHWASHER TOGGLE SWITCH NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION. L1 HOT L2 NEUTRAL 120 VAC POWER FIGURE 9. HIGH ALTITUDE INSTALLATIONS FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR Fire and Explosion Hazard Under no circumstances should the input exceed the rate shown on the water heater s rating label. Overfiring could result in fire or explosion. Gas and carbon monoxide detectors are available. CIRCULATING PUMP WIRING DIAGRAM Breathing DISHWASHER Hazard LOOP - WITH Carbon TOGGLE Monoxide SWITCH Gas DISHWASHER Under no FIELD circumstances SUPPLIED TEMPERATURE should TOGGLE CONTROL INSTALLED IN THE SWITCH the input CIRCULATING exceed the LOOP rate RETURN shownline on the water heater s rating label. NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE Overfiring could result in damage to POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD the water heater and sooting. TO ERRATIC CONTROL SYSTEM OPERATION. L1 HOT Gas and carbon monoxide detectors are available. 120 VAC CIRC Breathing POWER carbon monoxide can cause brain damage or PUMP death. Always read and understand instruction MOTOR manual. L2 NEUTRAL Installations above 2000 feet (610 meters) require replacement of burner orifices in accordance with current edition of the National Fuel Gas Code (ansi z223.1). For Canadian installations consult Canadian Installations Code can/csa b Failure to replace orifices will result in improper and inefficient operation of the water heater resulting in the production of increased levels of carbon monoxide gas in excess of safe limits which could result in serious personal injury or death. You should contact your gas supplier for any specific changes which may be required in your area. As the elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply. Failure to make this reduction would result in an over firing of the heater causing sooting, poor combustion and/or unsatisfactory heater performance. Ratings specified by manufacturers for most appliances apply for elevations up to 2000 feet (610m). For elevations above 2000 feet (610), ratings must be reduced at the rate of 4% for each 1000 feet (305m) above sea level. For example, if a heater is rated at 78,000 Btuh (22.9 Kwh) at sea level, to rate the heater at 4000 feet (1219m), you subtract 4 (once for each thousand feet) x.04 (4% input reduction) x 78,000 (original rating) from the original rating. Therefore, to calculate the input rating at 4,000 feet (1219m): 4 x.04 x 78,000 = 12,480 Btuh (3.7 Kwh), 78,000 (22.9 Kwh) - 12,480 (3.7 Kwh) = 65,520 Btuh (19.2 Kwh). At 6000 feet (1829m) the correct input rating should be 59,280 Btuh (17.4 Kwh). 12

13 Installation Requirements Gas supply Systems Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14 W.C. (1/2 PSI Gauge). These systems do not require pressure regulation. Measurements should be taken to insure that gas pressures are stable and fall within the requirements stated on the water heater rating plate. Readings should be taken with all gas burning equipment off (static pressure) and with all gas burning equipment running at maximum rate (dynamic pressure). The gas supply pressure must be stable within 1.5 W.C. from static to dynamic pressure to provide good performance. Pressure drops that exceed 1.5 W.C. may cause rough starting, noisy combustion or nuisance outages. Increases or spikes in static pressure during off cycles may cause failure to ignite or in severe cases damage to appliance gas valves. If your low pressure system does NOT meet these requirements, the installer is responsible for the corrections. High Pressure building supply systems use pressures that exceed 14 W.C. (1/2 PSI Gauge). These systems must use field supplied regulators to lower the gas pressure to less than 14 W.C. (1/2 PSI Gauge). Water heaters require gas regulators that are properly sized for the water heater input and deliver the rating plate specified pressures. Gas supply systems where pressure exceeds 5 PSI often require multiple regulators to achieve desired pressures. Systems in excess of 5 PSI building pressure should be designed by gas delivery professionals for best performance. Water heaters connected to gas supply systems that exceed 14 W.C. (1/2 PSI Gauge) at any time must be equipped with a gas supply regulator. All models require a minimum gas supply pressure of 4.5" W.C. for natural gas and 11.0" W.C. for propane gas. The minimum supply pressure is measured while gas is flowing (dynamic pressure). The supply pressure should never fall below 4.5" W.C. for natural gas and 11.0" W.C. for propane gas. The supply pressure should be measured with all gas fired appliances connected to the common main firing at full capacity. If the supply pressure drops more than 1.5 W.C. as gas begins to flow to the water heater then the supply gas system including the gas line and/or the gas regulator may be restricted or undersized. See Supply Gas Regulator section and Gas Piping section of this manual. The gas valve on all models has a maximum gas supply pressure limit of 14 W.C. The maximum supply pressure is measured while gas is not flowing (static pressure). SUPPLY GAS REGULATOR The maximum allowable gas supply pressure for this water heater is 14 inches W.C. (3.48 kpa). Install a positive lock-up gas pressure regulator in the gas supply line if inlet gas pressure can exceed 14 inches W.C. (3.48 kpa) at any time. Regulators must be sized/used according to manufacturer s specifications. If a positive lock-up regulator is required follow these instructions: 1. Positive lock-up gas pressure regulators must be rated at or above the input Btu/hr rating of the water heater they supply. 2. Positive lock-up gas pressure regulator(s) should be installed no closer than 3 equivalent feet (1 meter) and no farther than 8 equivalent feet (2.4 meters) from water heater s inlet gas connection. 3. After installing the positive lock-up gas pressure regulator(s) an initial nominal supply pressure setting of 7.0 W.C. while the water heater is operating is recommended and will generally provide good water heater operation. Some addition adjustment maybe required later to maintain a steady gas supply pressure. 4. When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit. Power Supply The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70 or the Canadian Electrical Code, CSA C22.1. WATER TEMPERATURE CONTROL AND Mixing Valves Water temperature over 125 F (52 C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury. Feel water before bathing or showering. Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures. Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the water heater s temperature setting by up to 20 F (11 C). Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm and the physically/mentally disabled. Table 5 shows approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken. In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed at the water heater (see Figure 10) or at the hot water taps to further reduce system water temperature. Mixing valves are available at plumbing supply stores. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer s instructions for installation of the valves. Table 5. Water Temperature F Time for 1st Degree Burn (Less Severe Burns) Time for Permanent Burns 2nd & 3rd Degree (Most Severe Burns) 110 (normal shower temp.) 116 (pain threshold) minutes 45 minutes minute 5 minutes seconds 25 seconds seconds 5 seconds second 2 seconds 154 instantaneous 1 second (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978) 13

14 TEMPERED WATER OUTLET HOT WATER OUTLET 12 TO 15 (30-38 cm) A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion. Contact a local plumbing service agency to have a thermal expansion tank installed. See Water Line Connections on page 21 and the Water Piping Diagrams beginning on page 40. Temperature-pressure relief valve COLD WATER INLET CHECK VALVE TO TANK INLET MIXING VALVE CHECK VALVE Explosion Hazard Temperature-Pressure Relief Valve must comply with ANSI Z CSA 4.4 and ASME code. Dishwashing Machines FIGURE 10. All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kpa and 173 kpa). Flow pressures above 25 pounds per square inch (173 kpa), or below 15 pounds per square inch (103 kpa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in the 180 F (82 C) line to the dishwashing machine and should be adjusted to deliver water pressure between these limits. The National Sanitation Foundation also recommends circulation of 180 F (82 C) water. The circulation flow rate should be just enough to provide 180 F (82 C) water at the point of take-off to the dishwashing machine. Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump. See Water Piping Diagrams in this manual. Note: These water heaters meet the NSF Standard 5 for sanitary installations when used with the leg kit part number Closed Water Systems Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back flow preventers. Devices such as these cause the water system to be a closed system. Thermal Expansion As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion. Properly sized temperaturepressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure. Can cause serious injury or death. This water heater is provided with a properly rated/sized and certified combination Temperature-Pressure Relief Valve (T&P valve) by the manufacturer. The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Pressure Relief Valves for Hot Water Supply Systems, ANSI Z21.22 CSA 4.4, and the code requirements of ASME. If replaced, the new T&P valve must meet the requirements of local codes, but not less than a combination Temperature- Pressure Relief Valve rated/sized and certified as indicated in the above paragraph. The new valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kpa) and a discharge capacity not less than the water heater Btu/hr or kw input rate as shown on the water heater s model rating label. NOTE: In addition to the factory installed Temperature-Pressure Relief Valve on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature- Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for technical assistance in sizing a Temperature-Pressure Relief Valve for remote storage tanks. For safe operation of the water heater, the Temperature-Pressure Relief Valve must not be removed from its designated opening nor plugged. The Temperature-Pressure Relief Valve must be installed directly into the fitting of the water heater designed for the pressure relief valve. Install discharge piping so that any discharge will exit the pipe within 6 inches (15.2 cm) above an adequate floor drain, or external to the building. In cold climates it is recommended that it be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve. 14

15 No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6 (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. CAUTION Water Damage Hazard Temperature-Pressure Relief Valve discharge pipe must terminate at adequate drain. T&P Valve Discharge Pipe Requirements: Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. Shall not be plugged or blocked. Shall not be exposed to freezing temperatures. Shall be of material listed for hot water distribution. Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe. Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. Shall not have any valve or other obstruction between the pressure relief valve and the drain. Contaminated Air Breathing Hazard - Carbon Monoxide Gas Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B To avoid injury, combustion and ventilation air must be taken from outdoors. Do not place chemical vapor emitting products near water heater. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Corrosion of the flue ways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation. Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as hot surface igniters and burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage. Do not store products of this sort near the water heater. Air which is brought in contact with the water heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outdoor sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions). Air requirements Burn hazard. Hot water discharge. Keep clear of Temperature- Pressure Relief Valve discharge outlet. The Temperature-Pressure Relief Valve must be manually operated at least twice a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions in this manual, and replace the Temperature- Pressure Relief Valve with a properly rated/sized new one. NOTE: The purpose of a Temperature-Pressure Relief Valve is to prevent excessive temperatures and pressures in the storage tank. The T&P valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion, see Closed Water Systems and Thermal Expansion on page 14. Breathing Hazard - Carbon Monoxide Gas Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B To avoid injury, combustion and ventilation air must be taken from outdoors. Do not place chemical vapor emitting products near water heater. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided. An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner flame, causing sooting of the combustion chamber, burners and flue tubes and creates a risk of asphyxiation. Do not install the water heater in a confined space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Confined Space section that follows. If you do not understand these instructions or have any questions Never obstruct the flow of ventilation air. If you have any doubts regarding the Temperature-Pressure Relief Valve call the toll or questions at all, call your gas supplier. Failure to provide the free number listed on the back cover of this manual for technical proper amount of combustion air can result in a fire or explosion assistance. and cause property damage, serious bodily injury or death. 15

16 Unconfined Space An Unconfined Space is one whose volume IS NOT LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kw) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space. Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and fireplaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air. Unusually Tight Construction In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows. Confined Space A Confined Space is one whose volume is less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kw) of the total input rating of all appliances installed in the space. Openings must be installed to provide fresh air for combustion, ventilation and dilution in confined spaces. The required size for the openings is dependent on the method used to provide fresh air to the confined space and the total Btu/hr input rating of all appliances installed in the space. Direct Vent Appliances Appliances installed in a Direct Vent configuration that derive all air for combustion from the outdoor atmosphere through sealed intake air piping are not factored in the total appliance input Btu/ hr calculations used to determine the size of openings providing fresh air into confined spaces. Exhaust Fans Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room through the water heater s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of fire or explosion may result. It can also create a risk of asphyxiation. Louvers and Grilles The free areas of the fresh air openings in the instructions that follow do not take in to account the presence of louvers, grilles or screens in the openings. The required size of openings for combustion, ventilation and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size of opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25% free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles shall be fixed in the open position. VENTING INSTALLATION venting THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION. Heater must be protected from freezing downdrafts. Remove all soot or other obstructions from the chimney that will retard a free draft. Type B venting is recommended with these heaters. For typical venting application see TECHNICAL DATA VENTING on pages 19 and 20. This water heater must be vented in compliance with all local codes, the current revision of the National Fuel Gas Code (ANSI-Z223.1) and with the Category I Venting Tables. If any part of the vent system are exposed to ambient temperatures below 40 F it must be insulated to prevent condensation. Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems. Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe. VENT REDUCER Model BCG370T120 is shipped with a 6" to 5" flue outlet adapter. Models (A)BCG3100T250, (A)BCG365T250 and (A) BCG3100T275 are shipped with a 8" to 6" flue outlet adapter. Each adapter fits on top of the installed flue damper. Use only vent reducers supplied with the unit. The venting must comply with the current editions of the NATIONAL FUEL GAS CODE, ANSI Z223.1/ NFPA 54 or NATURAL GAS AND PROPANE INSTALLATION CODE CAN/CSA-B149.1 FIGURE 11. FIGURE

17 Multiple heater manifold Outdoor Air Through One Opening Figure 13 and tables on pages 19 and 20 should be used for horizontally manifolding two or more heaters. Figure 15. FIGURE 13. Fresh Air Openings For Confined Spaces The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confined spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 16 for complete venting installation instructions. Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 14. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50 mm) from the front of the water heater. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following: 1. 1 square inch per 3000 Btu/hr (733 mm 2 per kw) of the total input rating of all appliances located in the enclosure, and 2. Not less than the sum of the areas of all vent connectors in the space. Outdoor Air Through Two Horizontal Ducts Outdoor Air Through Two Openings Figure 14. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 14. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm 2 ). 17 Figure 16. The confined space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 16. Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.

18 Outdoor Air Through Two Vertical Ducts The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. Do not refer to these illustrations for the purpose of vent installation. See Venting Installation on page 14 for complete venting installation instructions. When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches. Air From Other Indoor Spaces Figure 18. Figure 17. The confined space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 17. Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18. Each opening shall communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (2200 mm 2 per kw) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm 2 ). 18

19 TABLE 6. TECHNICAL DATA VENTING TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (Figure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. MODEL (A)BCG370T120 Input: 120,000 Btuh Total Vent Height (Feet) Draft Hood: Input Btuh Rise Vent Connector Diameter (inches) 120,000 1 Ft ,000 2 Ft ,000 3 Ft Number of Combined Input in Heaters Thousands of Btuh Manifold and Common Vent Diameter (In inches) MODEL (A)BCG380T150 Input: 154,000 Btuh Total Vent Height (Feet) Draft Hood: Input Btuh Rise Vent Connector Diameter (in inches) 154,000 1 Ft ,000 2 Ft ,000 3 Ft Numbers of Combined Input in Heaters Thousands of Btuh Manifold and Common Vent Diameter (in inches) MODEL BCG380T180, BCG3100T199, BCG380T199, & (A)BCG3100T200 Input: 180,000, 199,000 Btuh Total Vent Height (Feet) Draft Hood: Input Btuh Rise Vent Connector Diameter (in inches) 180,000 1 Ft , ,000 2 Ft , ,000 3 Ft , Number of Combined Input in Heaters Thousands of Btuh Manifold & Common Vent Diameter

20 20

Instruction Manual. Series 300, 301. For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER.

Instruction Manual. Series 300, 301. For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER. 500 Tennessee Waltz Parkway Ashland City, TN 37015 Instruction Manual COMMERCIAL GAS WATER HEATERS MODELS BT-80, BT-100 Series 300, 301 INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY

More information

COMMERCIAL GAS WATER HEATERS

COMMERCIAL GAS WATER HEATERS Instruction Manual COMMERCIAL GAS WATER HEATERS www.americanwaterheater.com American Water Heater Johnson City, TN 37605 MODELS BCL380T1206NOX, BCL380T1546NOX, BCL380T1806NOX, BCL380T1996NOX, BCL3100T1996NOX,

More information

PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.

PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING. Instruction Manual RESIDENTIAL GAS WATER HEATERS POWER VENT/POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION MODEL GDHE 50 SERIES 124/125 Complies with SCAQMD Low NOx Rule 1146.2 Ashland City, TN

More information

COMMERCIAL GAS WATER HEATERS

COMMERCIAL GAS WATER HEATERS Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENTED GAS MODELS W/HOT SURFACE IGNITION MODEL BTX-80 SERIES 100 500 Tennessee Waltz Parkway Ashland City, TN 37015 Low Lead Content For Your Safety

More information

MODELS BTR(C)120 THRU 500A

MODELS BTR(C)120 THRU 500A MODELS BTR(C)120 THRU 500A COMMERCIAL GAS, GLASS-LINED, TANK-TYPE WATER HEATER INSTALLATION OPERATION MAINTENANCE LIMITED WARRANTY Thank you for buying this energy efficient water heater from A.O. Smith

More information

PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.

PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER. Instruction Manual COMMERCIAL GAS WATER HEATERS MODELS CG(N,L)075075, CG(N,L)075100 Series 300, 301 300 Maddox Simpson Parkway Lebanon, TN 37090 Phone: 615-889-8900 Fax: 615-547-1000 Technical Service

More information

PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.

PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING. Instruction Manual RESIDENTIAL GAS WATER HEATERS POWER VENT/POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION Complies with SCAQMD Low NOx Rule 1146.2 Ashland City, TN 37015 www.hotwater.com Low Lead

More information

Instruction Manual for Residential Manufactured Home Gas Water Heaters

Instruction Manual for Residential Manufactured Home Gas Water Heaters Instruction Manual for Residential Manufactured Home Gas Water Heaters FOR USE ONLY IN MANUFACTURED HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons

More information

PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.

PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER. Instruction Manual RESIDENTIAL GAS WATER HEATERS FOR USE ONLY IN MANUFACTURED HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with input rating

More information

Instruction Manual for Residential Gas Water Heaters

Instruction Manual for Residential Gas Water Heaters Instruction Manual for Residential Gas Water Heaters NOT FOR USE IN MANUFACTURED (MOBILE) HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with

More information

COMMERCIAL GAS WATER HEATER Glass-Lined Tank-Type Water Heater

COMMERCIAL GAS WATER HEATER Glass-Lined Tank-Type Water Heater COMMERCIAL GAS WATER HEATER Glass-Lined Tank-Type Water Heater INSTALLATION OPERATION SERVICE MAINTENANCE Thank you for buying this energy efficient water heater. We appreciate your confidence in our products.

More information

PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.

PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING. Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENT/POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION Ashland City, TN 37015 www.hotwater.com For Your Safety AN ODORANT IS ADDED TO THE GAS

More information

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10) Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

SL280UHV SERIES GAS FURNACE WARNING

SL280UHV SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could

More information

RESIDENTIAL GAS WATER HEATERS

RESIDENTIAL GAS WATER HEATERS Instruction Manual RESIDENTIAL GAS WATER HEATERS NOT FOR USE IN MANUFACTURED (MOBILE) HOMES GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with input

More information

Tankless Water Heater

Tankless Water Heater Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not

More information

Water Heater Safety Tips

Water Heater Safety Tips Instruction Manual for Light Duty Commercial Power Direct Vent Gas Water Heaters ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE HEATER WAS PURCHASED. IF YOU

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

COMMERCIAL GAS WATER HEATERS

COMMERCIAL GAS WATER HEATERS Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENTED GAS MODELS W/HOT SURFACE IGNITION MODEL SHE 50 76N SERIES 100 500 Tennessee Waltz Parkway Ashland City, TN 37015 Low Lead Content For Your Safety

More information

INDIRECT WATER HEATER. Installation and Operating Instruction Manual

INDIRECT WATER HEATER. Installation and Operating Instruction Manual INDIRECT WATER HEATER Installation and Operating Instruction Manual Maximum supply temperature to heat exchanger must not exceed 180 F (82 C). Safety Warning: Indirect water heaters are heat-producing

More information

ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL

ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL ELECTRIC WATER HEATER A Spanish language version of these instructions is available by contacting the manufacturer listed on the rating plate. La version espanola de estas instruccions se puede obtener

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

Instruction Manual. A DIVISION OF A. O. SMITH CORPORATION RENTON, WASHINGTON www.hotwater.com

Instruction Manual. A DIVISION OF A. O. SMITH CORPORATION RENTON, WASHINGTON www.hotwater.com Instruction Manual Commercial Semi-Instantaneous Water Heaters ALL HWI MODELS INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY A DIVISION OF A. O. SMITH CORPORATION RENTON, WASHINGTON

More information

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................

More information

Instantaneous gas water heater

Instantaneous gas water heater Instantaneous gas water heater Models W 125...T1 installation operation maintenance The Bosch instantaneous water heater is a high efficiency, space saving answer to your water heating needs. All Bosch

More information

Residential Gas Water Heaters. Residential 30, 38, 40 and 50 Gallon

Residential Gas Water Heaters. Residential 30, 38, 40 and 50 Gallon ! Warning: This water heater is not suitable for use in manufactured (mobile) homes! Use & Care Manual With Installation Instructions for the Installer Residential Gas Water Heaters The purpose of this

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters UP TO 96% THERMAL EFFICIENCY, DIRECT-VENT FEATURES TM BTH-120 through BTH-500 The A. O. Smith Cyclone Xi family of products represents the industry s most technologically advanced commercial water heaters.

More information

Residential 30, 38, 40, 50 and 60 Gallon

Residential 30, 38, 40, 50 and 60 Gallon ! WARNING: This water heater is not suitable for use in manufactured (mobile) homes! Use & Care Manual With Installation Instructions for the Installer Residential Gas - FVIR Certified Water Heaters Residential

More information

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459 SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

GAS-FIRED COMMERCIAL WATER HEATER

GAS-FIRED COMMERCIAL WATER HEATER GAS-FIRED COMMERCIAL WATER HEATER WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. - Do not store

More information

INSTALLATION, OPERATION, AND SERVICE MANUAL RESIDENTIAL STORAGE TYPE GAS WATER HEATER

INSTALLATION, OPERATION, AND SERVICE MANUAL RESIDENTIAL STORAGE TYPE GAS WATER HEATER INSTALLATION, OPERATION, AND SERVICE MANUAL RESIDENTIAL STORAGE TYPE GAS WATER HEATER THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION

More information

COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL

COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL COMMERCIAL ELECTRIC WATER HEATER La A version Spanish espanola language de version estas of instrucciones these instructions se puede is available obtener al by escribirle contacting a la the fábrica company

More information

Residential Gas Water Heater with the Flame Guard Safety System Installation Instructions and Use & Care Guide

Residential Gas Water Heater with the Flame Guard Safety System Installation Instructions and Use & Care Guide WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. Do not store or use gasoline or other flammable

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable

More information

Installation Instructions and Use & Care Guide

Installation Instructions and Use & Care Guide WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. Do not store or use gasoline or other flammable

More information

LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL

LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATER A Spanish language version of these instructions is available by contacting the company listed on the rating plate. La versión espãnola de estas instrucciones

More information

RESIDENTIAL GAS WATER HEATERS

RESIDENTIAL GAS WATER HEATERS Instruction Manual RESIDENTIAL GAS WATER HEATERS NOT FOR USE IN MANUFACTURED (MOBILE) HOMES For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER. ALL TECHNICAL AND WARRANTY QUESTIONS:

More information

Water Heaters. Residential 30, 40 and 50 Gallon

Water Heaters. Residential 30, 40 and 50 Gallon ! WARNING: This water heater is not suitable for use in manufactured (mobile) homes! Use & Care Manual With Installation Instructions for the Installer Gas Residential Water Heaters Model: HG Series, GG

More information

Instruction Manual. place these instructions adjacent to heater and notify owner to keep for future reference.

Instruction Manual. place these instructions adjacent to heater and notify owner to keep for future reference. Instruction Manual COMMERCIAL ELECTRIC WATER HEATERS A DIVISION OF A.O. SMITH CORPORATION RENTON, WASHINGTON MODELS DVE-150 THRU DVE-10000 DHE-200 THRU DHE 10000 INSTALLATION - OPERATION - SERVICE - MAINTENANCE

More information

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Condensing Water Heater Operation Manual Model NPE-180A/ 210A/ 240A NPE-180S/ 210S/ 240S * Lead Free Keep this manual near this water heater for future reference whenever maintenance or service is required.

More information

Water Heaters. Use & Care Manual. Electric Point of Use IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

Water Heaters. Use & Care Manual. Electric Point of Use IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Electric Point of Use Water Heaters LISTED 786H IMPORTANT SAFETY INSTRUCTIONS Printed in USA Use & Care Manual With Installation Instructions for the Installer The purpose of this manual is twofold: one,

More information

SHC 2.5, SHC 4 MINI-TANK ELECTRIC WATER HEATERS INSTALLATION INSTRUCTIONS FOR THE LICENSED PLUMBER SHC 2.5 SHC 4. English. English

SHC 2.5, SHC 4 MINI-TANK ELECTRIC WATER HEATERS INSTALLATION INSTRUCTIONS FOR THE LICENSED PLUMBER SHC 2.5 SHC 4. English. English SHC 2.5, SHC 4 MINI-TANK ELECTRIC WATER HEATERS INSTALLATION INSTRUCTIONS FOR THE LICENSED PLUMBER The SHC series is tested and certified by WQA against NSF/ANSI 372 for lead free compliance. SHC 2.5 Table

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural

More information

Water Heaters. Residential 30, 40 and 50 Gallon

Water Heaters. Residential 30, 40 and 50 Gallon Residential 30, 40 and 50 Gallon Use & Care Manual With Installation Instructions for the Contractor Gas Residential Water Heaters Model: HG Series, GG Series, GP Series, PG Series, SG Series, SG Series

More information

INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS

INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS Installation and service must be provided by a qualified installer, service agency or gas supplier Grand Canyon Gas Logs, logs are made

More information

Commercial Gas Water Heater

Commercial Gas Water Heater Commercial Gas Water Heater 3-Year Limited Tank/1-Year Limited Parts Warranty* The Polaris has a high grade 444 stainless steel tank with brass connections for years of dependable, trouble-free service

More information

TANKLESS WATER HEATER USE AND CARE MANUAL

TANKLESS WATER HEATER USE AND CARE MANUAL WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing death, personal injury, or property damage. For Your Safety! Do not store or use gasoline

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Electric Water Heater

Electric Water Heater Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.

More information

RESIDENTIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS

RESIDENTIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS RESIDENTIAL GAS-FIRED WATER HEATERS (EQUIPPED WITH FVIR TECHNOLOGY) OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS This water heater IS NOT design certified for installation in a manufactured (mobile)

More information

COMMERCIAL GAS WATER HEATER

COMMERCIAL GAS WATER HEATER Owner s Manual COMMERCIAL GAS WATER HEATER FOR POTABLE WATER HEATING ONLY NOT SUITABLE FOR SPACE HEATING NOT FOR USE IN MOBILE HOMES MODEL NO. CAPACITY 153.338074 74 Gallon (280 Liter) 153.338004 98 Gallon

More information

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.

More information

Solar Storage Tank Water Heater. Table Of Contents PAGE 2 3-8 3 4 4-5 6-8 9 10-12 10 11 12 12-13 14 15

Solar Storage Tank Water Heater. Table Of Contents PAGE 2 3-8 3 4 4-5 6-8 9 10-12 10 11 12 12-13 14 15 Solar Storage Tank Water Heater Installation Instructions and Use & Care Guide To obtain technical, warranty or service assistance during or after the installation of this water heater, call toll free

More information

RESIDENTIAL GAS WATER HEATERS

RESIDENTIAL GAS WATER HEATERS Installation and Operating Manual RESIDENTIAL GAS WATER HEATERS POWER VENTED GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED (MOBILE) HOMES 300 Maddox Simpson Parkway Lebanon, TN 37090

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

COMMERCIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS

COMMERCIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS COMMERCIAL GAS-FIRED WATER HEATERS OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS This water heater IS NOT design certified for installation in a manufactured (mobile) home or for installation

More information

GAS SAFETY PRECAUTIONS

GAS SAFETY PRECAUTIONS GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier. These instructions must be posted in a prominent location where the unit is to be operated.

More information

Please keep this manual for f uture reference.

Please keep this manual for f uture reference. GAS WATER/AGUA Congratulations! You've just purchased a new Marey Portable tankless water heater and will soon begin to enjoy the benefits of going tankless. Take the time to thoroughly read and understand

More information

RESIDENTIAL GAS WATER HEATERS

RESIDENTIAL GAS WATER HEATERS Installation and Operating Manual RESIDENTIAL GAS WATER HEATERS POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED (MOBILE) HOMES : If the information in these instructions

More information

RESIDENTIAL GAS WATER HEATERS

RESIDENTIAL GAS WATER HEATERS Installation and Operating Manual RESIDENTIAL GAS WATER HEATERS POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED (MOBILE) HOMES For Your Safety AN ODOURANT IS ADDED TO

More information

CALIFORNIA PROPOSITION 65 WARNING:

CALIFORNIA PROPOSITION 65 WARNING: Residential Solar Water Heater USE & CARE MANUAL WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR LISTED 786H The purpose of this manual is twofold: one, for the installing contractor, to provide requirements

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

COMMERCIAL GAS WATER HEATER GAS-FIRED POWER BURNER FOR DOMESTIC HOT WATER

COMMERCIAL GAS WATER HEATER GAS-FIRED POWER BURNER FOR DOMESTIC HOT WATER HIGH EFFICIENCY AHCG3/HCG360T120 thru AHCG3/HCG3100T250 COMMERCIAL GAS WATER HEATER GAS-FIRED POWER BURNER FOR DOMESTIC HOT WATER INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING: If

More information

GAS-FIRED WATER HEATER

GAS-FIRED WATER HEATER GAS-FIRED WATER HEATER A Spanish language version of these instructions is available by contacting the company listed on the rating plate. La version espanola de estas instrucciones se puede obtener al

More information

RESIDENTIAL GAS WATER HEATERS

RESIDENTIAL GAS WATER HEATERS Instruction Manual RESIDENTIAL GAS WATER HEATERS POWER VENTED GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED (MOBILE) HOMES GAMA certification applies to all residential gas water heaters

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER

INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil

More information

Commercial. Gas-Fired Water Heaters. Installation. Start-Up. Maintenance. Parts. Warranty. CG***N73 / CG***N65 Models

Commercial. Gas-Fired Water Heaters. Installation. Start-Up. Maintenance. Parts. Warranty. CG***N73 / CG***N65 Models Commercial Gas-Fired Water Heaters Installation Start-Up Maintenance Parts Warranty CG***N73 / CG***N65 Models A Suffix of X Denotes Model Set for Low NOx Operation This manual must only be used by a qualified

More information

CYCLONE Xi Model BTH 120-250(A) SERIES 100 AND 101

CYCLONE Xi Model BTH 120-250(A) SERIES 100 AND 101 CYCLONE Xi Model BTH 120-250(A) SERIES 100 AND 101 COMMERCIAL GAS WATER HEATER GAS-FIRED POWER BURNER FOR DOMESTIC HOT WATER INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING: If the

More information

American Fireglass Outdoor Fire pit kit information. General instructions/warnings for outdoor gas pan and burner systems

American Fireglass Outdoor Fire pit kit information. General instructions/warnings for outdoor gas pan and burner systems American Fireglass Outdoor Fire pit kit information General instructions/warnings for outdoor gas pan and burner systems We strongly recommend that our burner products be installed by a licensed and certified

More information

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

INSTALLATION & SERVICE MANUAL

INSTALLATION & SERVICE MANUAL INSTALLATION & SERVICE MANUAL POWER VENTED GAS WATER HEATER If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or

More information

Water Heaters. Commercial Gas. Use & Care Manual. With Installation Instructions for the Installer. Commercial 75 Gallon

Water Heaters. Commercial Gas. Use & Care Manual. With Installation Instructions for the Installer. Commercial 75 Gallon VACATION WARM COOLER A B C VERY HOT HOTTER! Warning: This water heater is not suitable for use in manufactured (mobile) homes! Commercial Gas Use & Care Manual With Installation Instructions for the Installer

More information

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number: Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,

More information

Instruction Manual. Thank you for buying this energy efficient water heater. We appreciate your confidence in our products.

Instruction Manual. Thank you for buying this energy efficient water heater. We appreciate your confidence in our products. Instruction Manual COMMERCIAL ELECTRIC WATER HEATERS 500 Tennessee Waltz Parkway Ashland City, TN 37015 MODELS PCE-6/10/17/20 10MSA Series 102 PCE-30/40/50 2OLSA Series 110 & PCE-30/40/52/66/82/120 2ORTA

More information

Energy Smart Residential Electric Water Heater Installation Instructions

Energy Smart Residential Electric Water Heater Installation Instructions Use & Care Guide http://waterheatertimer.org/whirlpool-energy-smart-electric.html Energy Smart Residential Electric Water Heater Installation Instructions and Use & Care Guide To obtain technical, warranty,

More information

ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER (EF Series Models)

ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER (EF Series Models) ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER (EF Series Models) WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal

More information

Installation and Operating Instruction Manual

Installation and Operating Instruction Manual Electric Mini Tank Water Heaters CMT-1.3 CMT-2.5 CMT-4.0 CMT-ST70 Tempering valve Optionally available Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 3 General

More information

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS HEAT-FLO HOT WATER STORAGE / BOOSTER TANKS MODELS 30-ST, 40-ST, 40L-ST, 60-ST, 60L-ST, 80-ST, 115-ST, 80-ST-C, 115-ST-C FOR SINGLE TANK INSTALLATIONS For

More information

Direct Vent Water Heaters

Direct Vent Water Heaters ! Warning: This water heater is not suitable for use in manufactured (mobile) homes! Use & Care Manual With Installation Instructions for the Installer Residential Gas - FVIR Certified Direct Vent Water

More information

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION As when installing or using any high voltage electrical appliance, basic safety precautions should always

More information

Techtanium Solar Indirect Water Heater Instruction Manual

Techtanium Solar Indirect Water Heater Instruction Manual To the Installer: Please attach these instructions next to the water heater. To the Consumer: Please read these and all component instructions and keep for future reference. Techtanium Solar Indirect Water

More information

OPERATING, INSTALLATION AND SERVICE MANUAL

OPERATING, INSTALLATION AND SERVICE MANUAL OPERATING, INSTALLATION AND SERVICE MANUAL COMMERCIAL GAS WATER HEATER WITH FLUE DAMPER AND ELECTRIC IGNITION SYSTEM WITHOUT FAN MOTOR REQUIRES 120V A.C. POWER SUPPLY WARNING: If the information in these

More information

POWER MISER 6 ELECTRIC WATER HEATER

POWER MISER 6 ELECTRIC WATER HEATER Owner s Manual POWER MISER 6 ELECTRIC WATER HEATER FOR POTABLE WATER HEATING ONLY. NOT SUITABLE FOR SPACE HEATING. MODEL NO. 153.326362 30 Gal. 153.326363 30 Gal. 153.326462 40 Gal. 153.326463 40 Gal.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS PRODUCT LITERATURE Lennox Industries Inc. Dallas, Texas INSTALLATION INSTRUCTIONS GWB8-042IE-2, GWB8-075IE-2 GWB8-112IE-2, GWB8-150IE-2 GWB8-187IE-2, GWB8-225IE-2 GAS FIRED BOILER RETAIN THESE INSTRUCTIONS

More information

POWER MISER TM 12 ELECTRIC WATER HEATER

POWER MISER TM 12 ELECTRIC WATER HEATER Owner s Manual POWER MISER TM 12 ELECTRIC WATER HEATER FOR POTABLE WATER HEATING ONLY. NOT SUITABLE FOR SPACE HEATING. MODEL NO. 153.321342 30 Gal. 153.321343 30 Gal. 153.321442 40 Gal. 153.321443 40 Gal.

More information

What to Expect From the Examination. How to Study the Plumbing Codes

What to Expect From the Examination. How to Study the Plumbing Codes Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.

More information

INSTALLATION, OPERATION, AND SERVICE MANUAL POWER VENT STORAGE TYPE GAS WATER HEATER MODELS PVG/PVCG

INSTALLATION, OPERATION, AND SERVICE MANUAL POWER VENT STORAGE TYPE GAS WATER HEATER MODELS PVG/PVCG INSTALLATION, OPERATION, AND SERVICE MANUAL POWER VENT STORAGE TYPE GAS WATER HEATER MODELS PVG/PVCG THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT

More information

Residential Electric Water Heater

Residential Electric Water Heater Residential Electric Water Heater Installation Instructions and Use & Care Guide To obtain technical, warranty or service assistance during or after the installation of this water heater, call toll free

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

INSTALLATION & SERVICE MANUAL

INSTALLATION & SERVICE MANUAL SINGLE-WALL INDIRECT WATER HEATER To avoid damage or injury, there must be no materials stored against the indirect water heater and proper care shall be taken to avoid unnecessary contact (especially

More information

CHAPTER 5 WATER HEATERS

CHAPTER 5 WATER HEATERS PlumbingCode06_ch05 5/29/06 8:12 AM Page 1 CHAPTER 5 WATER HEATERS Water heaters are only a small portion of a plumbing system, but they are important, and they can be dangerous. Many plumbers take water

More information

Mini Tank. Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0. Installation and Operating Instruction Manual

Mini Tank. Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0. Installation and Operating Instruction Manual Mini Tank Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0 Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 3 General Information 3/6 Technical

More information

TECHNICAL MANUAL GDS8 & GHS8

TECHNICAL MANUAL GDS8 & GHS8 TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as

More information

94% CONDENSING TANKLESS WATER HEATER USE AND CARE MANUAL

94% CONDENSING TANKLESS WATER HEATER USE AND CARE MANUAL WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing death, personal injury, or property damage. For Your Safety! Do not store or use gasoline

More information