1 TAHQ WEBINAR

2 Know which NFPA code you use for the facility 2000, 2003, etc. Have a valve chart for all valves. Looked into ceiling and wanted us to identify the valve he found. Very interested in whether we had any suites. See NFPA for definitions. You can have fewer restrictions than if the area is identified as a corridor.

3 Fire and patient doors must latch. Fire door vertical and horizontal spacing is checked. Corridors are unobstructed. No trash cans, chair without wheels, pull down computer tables that have not been retracted, etc. If you have fire hose connection cabinets where you have removed the hoses, MUST have a letter from the local fire department saying they know and approve.

4 If you have hose connections, make sure you have the proper devices to connect to fire department hoses. (Sizes of connectors) Letter from fire department stating they will have their own tools and connections is best. Run your fire pump on emergency power quarterly or whenever you feel the need to do so. Document the results.

5 Generator testing. Checked the monthly and/or annual testing.( Annual load test as well.) Make sure your testing language is the same: volts, or amps, or watts, etc. Test emergency (battery) light at the generator 1 ½hours annually and 30 seconds monthly. =Replace as needed. Have an emergency outlet at the generator to run any equipment off of it.

6 Exterior fans should have bio hazard symbols on them if they exhaust air from O.R. s, or negative pressure rooms, or any area that could be Infection Control related, etc. Central Sterile Supply Room has to have positive pressure on the clean side doors and negative pressure on the dirty side doors. During construction, must have SMOKE tight barriers, not just plastic sheeting.

7 Exit signs need to be seen from two directions when fire or smoke doors are closed. Make sure all exit signs have the chevrons punched out appropriately. =Don t have one pointing to a closest or wall. Make sure all lights are working. Exit, hallway, etc. Cages over closet and work space areas light bulbs.

8 Any large open treatment areas should have a protective door way nearby. Who checks the negative pressure rooms pressure and where is it documented? Roof is checked for ponding of water, storage of items that could blow off in a wind, and 3 feet of extension for any air intake pipes. (Also the 120 degree bend)

9 Asking students, interns, residents, and physicians about fire code and their responsibilities on how to respond. No food or paper products should be stored under sinks. Cleaning supplies containers only, if anything is allowed. Stairways that exit up for egress, for example from a basement/ground level, should have a sign FROM the first floor going down, that this is not an exit.

10 If the E.R. is considered a suite, may have to move exit signs as well as making doors smoke barriers. (Latching and spacing as a fire door) No chairs may be kept in the fire stairwell. If the O.R. area is to be considered a suite, can have 42 corridor spacing.

11 Ascussions need to be sealed. If an area has been closed or shut down temporarily, make sure the toilets have water in them to keep the seals intact. -Sewer gas into the hospital could result if not done. Make sure all felt astricles are rated. For each smoke compartment there are only 31 hand sanitizer units allowed.

12 If the facility is 100% sprinkled, smoke damper do not require routine maintenance, but must have every six years inspections. (NFPA exception 2) ILSM due anytime there is an L.S. issue identified. -PFI for L.S. is evaluated for ILSM s.

13 When medical gases are interrupted, the lines must be tested and CERTIFIED by the AHJ! Policy must state this. Ensure the duct detectors actually shut down the air handlers.

14 Ensure all electrical circuit boxes have the 3 feet distance around them. Boxes must be marked for: Life Safety: =Fire alarms. =Dampers for fire/smoke suppression. =Sprinkler system alarms. Life Support: =ICU. =E.R. =Emergency plugs. Equipment: =HVAC. =Kitchen. =All others.

15 Gas cylinders, dietary soda machines for example, must have holding chains high up on the bottle, not low. Documents review specifics for the following: Supervisory signals: =Tamper switches =Fire pumps running. =Fire pumps failure.

16 Main Drain test: Record the time to return to static pressure. =Could indicate a blockage. Flow Test List the percent of flow: 90%, 100%. Document for standpipe tasting reviewed Needed every five years. Remove old inspection stickers on equipment once the new one is completed. For the activation hood suppression area signage. Make it similar to the stand off signs for fire extinguishers.

17 Environment of Care Review Sample Questions

18 Security: What is your highest security risk? HazMat Spills: Who handles them? How do you find out about hazards in the workplace? How do you minimize harm from radiation? Show documentation. Are you measuring nitrous oxide in the O.R. s?

19 Show air balance tests in the O.R. s. 15 changes per hour, 3 must be fresh air. Show fire safety inspections: Facility and AHJ s. Show fire drills. One per shift per quarter. Doing double for ILSM areas. How are you preventing bio hazards from getting to patients?

20 If you have them, how are the cooling towers being treated? (Chemicals?) What do you do if you lose potable water? What if it feeds your boilers? Lose sewer, what do you do? Contract company to pump it? If you heat boilers with gas, can you switch to diesel from the generator supply? Know how to do it. (Practice it)

21 Bio medical repairs: Have you done risk assessments? =Show how. What do you consider life support machines. If equipment problem, what do you do? =Sequester the machine away from the area it was used. =Sequester without changing settings. Use an independent testing firm to check out the machine

Department: Manager: Safety Coordinator: Date:

Department: Manager: Safety Coordinator: Date: SAFETY and staff, regardless of hiring status or job position 1 1. Can staff name their department safety coordinator? 2. Is the Department Safety Binder current? 3. Do slip/trip hazards exist? 4. How

More information

CMS/Accreditation Surveys The Physical Environment

CMS/Accreditation Surveys The Physical Environment CMS/Accreditation Surveys The Physical Environment Critical Aspects for 2013 Presenter Robert H. Bartels, CHFM CHSP CHEP SASHE President Safety Management Services, Inc. A program presented by: SAFETY

More information

Environment of Care Fire Safety Management Plan 2014

Environment of Care Fire Safety Management Plan 2014 Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and

More information

Quality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Quality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Generator fire up Generator 1 hour load test Generator 4 hour load test Fire extinguisher integrity checks Fire extinguisher certification Fire drills Fire door integrity Fire signage lighting Fire alarm

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect

More information

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency

More information

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Arizona Health Care Association DISASTER PLANNING AND EMERGENCY MANAGEMENT GUIDE POST INCIDENT DAMAGE ASSESSMENT CHECKLIST

Arizona Health Care Association DISASTER PLANNING AND EMERGENCY MANAGEMENT GUIDE POST INCIDENT DAMAGE ASSESSMENT CHECKLIST It is essential to perform a Basic Damage Assessment (BDA) following an adverse event to help ensure the safety of building occupants as well as prevent additional losses from occurring. This checklist

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures

More information

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use. Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico

More information

How To Understand The Safety Management Program

How To Understand The Safety Management Program ENVIRONMENT OF CARE INTERVIEW QUESTIONS The Survey Team Process The following questions relate to each of the "Environment of Care" sections listed below. The "EC" interview session will be scheduled as

More information

Town of Bellingham Fire Department

Town of Bellingham Fire Department Town of Bellingham Fire Department OFFICE OF THE Fire Prevention Division Captain Robidoux- jrobidoux@bellinghamma.org Lieutenant Bangma- jbangma@bellinghamma.org Fire Safety Inspection Guidelines for

More information

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

Maintaining Fire Protection Systems

Maintaining Fire Protection Systems Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-

More information

Firefighter Review. Instructor Guide

Firefighter Review. Instructor Guide Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing

More information

CANTON FIRE DEPARTMENT

CANTON FIRE DEPARTMENT CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property

More information

2014 Limited Plan Submittal Checklist

2014 Limited Plan Submittal Checklist City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420

More information

PART II: New Construction Inspections and Acceptance Testing Procedures

PART II: New Construction Inspections and Acceptance Testing Procedures Stafford County Fire Marshal s Office Handbook for Building/Fire Code Policies and Guidelines PART II: New Construction Inspections and Acceptance Testing Procedures Phone: 540-658-8648 Fax: 540-658-9128

More information

Safety and Health Office WORKPLACE SAFETY CHECKLIST

Safety and Health Office WORKPLACE SAFETY CHECKLIST Location: Date: Inspected by: Safety and Health Office WORKPLACE SAFETY CHECKLIST WORK ENVIRONMENT Ventilation Removal of fumes and dust Temperature and humidity control Noise levels Vibration Lighting

More information

Mechanical, Plumbing, and Fire Protection Conditions

Mechanical, Plumbing, and Fire Protection Conditions Mechanical, Plumbing, and Fire Protection Conditions Mechanical Conditions The mechanical systems within the building consist of a combination of the original 1926 systems and renovations that occurred

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

Emergency Evacuation Plan: 232 King St.

Emergency Evacuation Plan: 232 King St. Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0

More information

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:

More information

Fire Safety Plan University Stadium

Fire Safety Plan University Stadium Fire Safety Plan University Stadium Building # 53 Safety, Health, Environment Effective: March 14, 2018 Revised: December 2014 Revision: 1 Approved on: Pending Approval WILFRID LAURIER UNIVERSITY Contact:

More information

FIRE SAFETY PLAN FOR KITCHENER, ONTARIO

FIRE SAFETY PLAN FOR KITCHENER, ONTARIO FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address

More information

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems. OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above

More information

Duke University Hospital Fire/Life Safety Management Plan 2007

Duke University Hospital Fire/Life Safety Management Plan 2007 Duke University Hospital Fire/Life Safety Management Plan 2007 Introduction One of the most serious issues facing Duke University Hospital, Medical Center, Duke Clinic and the Health Systems is the threat

More information

City of Columbus Department of Building and Zoning Services

City of Columbus Department of Building and Zoning Services City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning

More information

Walkthrough Inspection Checklist

Walkthrough Inspection Checklist Walkthrough Inspection Checklist This checklist is to aid during an IAQ Walkthrough of the school. The checklist includes considerations both inside and outside the school building: Instructions: 1. Read

More information

Commercial Fire Inspections

Commercial Fire Inspections Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated

More information

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

Facilities Maintenance Standards rev 9-1-2015

Facilities Maintenance Standards rev 9-1-2015 Facilities Maintenance Standards rev 9-1-2015 Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

Beth Israel Deaconess Medical Center Environment of Care Manual

Beth Israel Deaconess Medical Center Environment of Care Manual Beth Israel Deaconess Medical Center Environment of Care Manual Title: Interim Life Safety Measures (ILSM) Plan Policy #: EC39 Purpose: ILSM are fully adhered to in areas where the hospital/site occupants

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

RISK MANAGEMENT QUARTERLY BUILDING REPORT Fire Safety Self -Inspection Checklist

RISK MANAGEMENT QUARTERLY BUILDING REPORT Fire Safety Self -Inspection Checklist RISK MANAGEMENT QUARTERLY BUILDING REPORT Fire Safety Self -Inspection Checklist Quarter: Year Fall Building: Phone: Winter Spring Safety Coordinator: Date: Summer Use the Checklist to conduct your own

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

SAFETY SELF-INSPECTION PROGRAM

SAFETY SELF-INSPECTION PROGRAM Palm Beach State College Florida s First Public Community College SAFETY SELF-INSPECTION PROGRAM PALM BEACH STATE COLLEGE SAFETY SELF-INSPECTION PROGRAM 1. INTRODUCTION An important element of any employee

More information

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

FIRE SAFETY ONLINE TRAINING

FIRE SAFETY ONLINE TRAINING INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency

More information

Notes. Material 1. Appropriate Flammable Liquids

Notes. Material 1. Appropriate Flammable Liquids 29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

Florida Healthcare Engineering Association

Florida Healthcare Engineering Association Life Safety Accreditation Challenges A PRESENTATION FOR Florida Healthcare Engineering Association Dean Samet, Director of Regulatory Compliance dsamet@ssr-inc.com, cell 615-388-0332 Copyright 2011 Smith

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This

More information

Building Permit Application

Building Permit Application Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

city of edmonds development information

city of edmonds development information #B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit

More information

Division 21. Fire Suppression

Division 21. Fire Suppression 21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven

More information

Disaster Prevention and Protection Checklist

Disaster Prevention and Protection Checklist Preservation Services Leaflet 1438 West Peachtree Street, Suite 200/Atlanta, GA 30309 Phone: 404-892-0943/Fax: 404-892-7879 Website: Disaster Prevention and Protection Checklist The inspection

More information

FIRE SAFETY HANDBOOK

FIRE SAFETY HANDBOOK 29 CFR 1960.20, Alternate Standard For Fire Safety In Airport Traffic Control Towers (ATCTs) Fire Prevention Plan (FPP) Emergency Action Plan (EAP) FIRE SAFETY HANDBOOK DEPARTMENT OF TRANSPORTATION FEDERAL

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist #506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the

More information

Automatic fire-extinguishing systems for commercial cooking

Automatic fire-extinguishing systems for commercial cooking Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and

More information

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

SWF Home Inspections

SWF Home Inspections Cover Page SWF Home Inspections Property Inspection Report Inspection prepared for: Mr & Mrs Home Buyer Real Estate Agent: My Favorite Agent - Date of Inspection: 7/4/2013 Age of Home: 2004 Size: 1568

More information

Current as of 11/10/08 1 of 1

Current as of 11/10/08 1 of 1 BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that

More information

KODAK VERSAMARK, INC.

KODAK VERSAMARK, INC. KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF

More information

City of St. Charles Basement Finish or Remodel

City of St. Charles Basement Finish or Remodel City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

Plumbing Code in Commercial Kitchens

Plumbing Code in Commercial Kitchens Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International

More information

SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING

SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING SECTION.3400 - MECHANICAL: ELECTRICAL: PLUMBING 10A NCAC 13D.3401 HEATING AND AIR CONDITIONING Heating and cooling systems shall meet the American Society of Heating, Refrigerating, and Air Conditioning

More information

Oxford House Evacuation Plan SECTION 1. RESPONSIBILITIES. A. COOP Staff

Oxford House Evacuation Plan SECTION 1. RESPONSIBILITIES. A. COOP Staff Oxford House Evacuation Plan SECTION 1. RESPONSIBILITIES A. COOP Staff 1. COOP DIRECTOR will work with the UHDS Safety & Inspection Coordinator (SIC) to establish an emergency operation plan for the building.

More information

Element D Services Plumbing

Element D Services Plumbing Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov

CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.

More information

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management

More information

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13 presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

Housing Quality Standards Inspection Checklist

Housing Quality Standards Inspection Checklist Housing Quality Standards Inspection Checklist To prevent delays, the R.T.A. must be complete and upon submission the unit must be in move in condition or an inspection will not be conducted. A Fair Housing

More information

FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES

FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES Insert Picture of Building FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES Address: Lock Box Location: Fire Safety Plan Location: Approved: Fire Department (dd /mm/yyyy) Building Owner (dd /mm/yyyy) Reviewed

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

MY HOME IN A HOUSING BLOCK A GUIDE FOR RESIDENTS

MY HOME IN A HOUSING BLOCK A GUIDE FOR RESIDENTS MY HOME IN A HOUSING BLOCK A GUIDE FOR RESIDENTS -KESKUSTA One half of Finns live in housing blocks, which is a safe and comfortable way to live. Welcome a board! Buildings and the Finnish climate There

More information

COMPREHENSIVE PROPERTY INSPECTIONS

COMPREHENSIVE PROPERTY INSPECTIONS COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited

More information

NFPA 91 1999 Edition. 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations:

NFPA 91 1999 Edition. 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations: NFPA 91 1999 Edition 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations: 1) Where ducts pass through fire barriers (2) Where a collection system installed

More information