04222 CONCRETE UNIT MASONRY (UNREINFORCED ONLY)

Size: px
Start display at page:

Download "04222 CONCRETE UNIT MASONRY (UNREINFORCED ONLY)"

Transcription

1 04222 CONCRETE UNIT MASONRY (UNREINFORCED ONLY) SPECIFIER: This section replaces You can use it for projects that have only UNREINFORCED concrete masonry. Its only reinforcement is in the horizontal joints. It covers ONLY plain blockwork (no vertical bars; no grouting) for the unreinforced masonry walls, often fire-rated, that are used in interior construction. It will also cover the infrequent occurrence of unreinforced masonry construction at the exterior. Do not use it for walls that contain windows. It is important to distinguish unreinforced and reinforced block walls on the Drawings. Reinforced blockwork is NOT covered in this section. Use instead. NOR is the tie beam-and-tie column-with-masonry method of construction. Use instead. NOR are there provisions for supporting impact-resistant windows and louvers. Use instead. This section can be edited to add block with a textured or patterned face. CSI MasterFormat 2004 number: An optional keynote to the Drawings follows major product titles, for A/Es using National CAD Standard. PART 1 GENERAL 1.1 RELATED REQUIREMENTS A. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially: 1. Devices in concrete for joining with masonry, such dovetail assemblies Concrete framing. Div Welding masonry anchors to steel Insulation beneath interior wall finish at exterior walls Wall vapor barrier (if used). Div Furring supporting interior wall finish at exterior walls Window stools OVERALL STANDARDS A. Perform reinforced concrete masonry work following 1. ACI 530 Building Code Requirements for Masonry and 2. ACI Specification for Masonry Structures, except as more stringently specified herein. 1.3 REFERENCES A. American Society for Testing and Materials (ASTM). Specifications for: 1. A Steel Wire, Plain, for Masonry Joint Reinforcement. 2. A Zinc Coating (Hot Dip) for Iron and Steel Hardware. 3. C55-06 Concrete Brick. 4. C90-06b Loadbearing Concrete Masonry Units. 5. C91-05 Masonry Cement. 6. C Aggregate for Masonry Mortar. 7. C150-04a Portland Cement. 8. C Hydrated Lime. 9. C Mortar for Unit Masonry. project number Concrete Unit Masonry (Unreinforced)

2 10. C Extended Life Mortar for Unit Masonry. 1.4 SUBMITTALS Follow A. Product Data: Submit for fire-rated block, plain block, [textured block,] special shape, cast stone surround, horizontal joint reinforcement, and each metal accessory and plastic accessory with special attention to the weight of galvanizing on steel items. 1.5 MOCKUP A. Sample Wall (only if there is any textured block in the Work): Erect a 6 ft x 4 ft high x 8 in. thick (or full thickness if double-width) sample wall on a 30 in. wide concrete base to serve as a standard of appearance and construction. Remove sample wall and base only when permitted by A/E. PART 2 PRODUCTS Follow Specifier: Select Normal or Medium weight. Check with structural engineer. Type I block (autoclaved, using electric energy) is not specified here because it normally has the moisture content of Type II by the time it is delivered to the worksite in normal humid south Florida weather. 2.1 CONCRETE BLOCK AND CONCRETE BRICK (CMU) [04221.cmu] A. Description: Normal Weight (>125 lb/ft 3 )] [Medium Weight (105 to 125 lb/ft 3 )] loadbearing units including shapes as needed to execute details. 1. Texture: A uniform, medium texture that is neither very smooth nor very coarse. Face surfaces shall have a texture that will bond well to cementitious materials, yet not leave unpainted pits when painted by roller. 2. Linear shrinkage at time of delivery: 0.065% maximum. 3. Solid units. Where shown, provide solid units with <25% voids. 4. Prohibited: Block of non-loadbearing grade; also U-block. 5. Fire rating: As will attain UL fire rating shown for each wall. B. Standards: 1. Concrete Block: ASTM C90, Type II. Do not use ASTM C129 units. 2. Concrete Brick: ASTM C55. Specifier: If there are any decorative-face block in the Work, give a full description below. Name one or more producers products to ensure that you get what you want. Some common styles in addition to split-face are: ribbed, ribbed with split (specify number of ribs), vertically scored (specify number of square- or V-scores), horizontally scored, and ground face. Keep in mind however, that graffiti are very hard to remove from decorative-face block. 2.2 [SPLIT-FACE] [ ] CONCRETE BLOCK [04221.df-cmu] A. Description: Loadbearing units of same weight class, linear shrinkage, and ASTM standard as other block. project number Concrete Unit Masonry (Unreinforced)

3 1. Face description:. 2. Color:. B. Product / Producer: 1., by. 2., by. 3. Equal product in quality and performance as approved after review by A/E and Board. 2.3 MORTAR A. Types and Uses: 1. Type S or RS, with 1800 lb/in 2 compressive strength, for use above grade. 2. Type M or RM, with 2500 lb/in 2 compressive strength, for use only below grade. 3. Mix: Portland cement, lime and sand, or, if proportions and test results are approved by structural engineer of record, portland cement, masonry cement and sand. 4. For filling cells in courses below structural loads, at jambs of openings, and elsewhere as shown on Drawings, Type S or RS may be used unless a mix of compressive strength greater than 1800 lb/in 2 is shown on the Drawings. 5. For sustainability, follow ASTM recommendation that mortar strength always be less than block compressive strength. 6. Compressive strength: Average measure when tested in 28 days. B. Standards: 1. Mortar (site mixed): ASTM C270, S and M. 2. Extended life mortar: ASTM C1142, RS and RM. 2.4 MORTAR INGREDIENTS A. Standards: Use no calcium chloride in any mix. 1. Portland cement: ASTM C150, Type I or II. 2. Hydrated lime: ASTM C206, Type S. 3. Masonry cement: ASTM C Mortar aggregate: ASTM C Mixing water: Potable. 2.5 LINTELS A. Lintels: Precast concrete lintels except where cast-in-place concrete or steel is shown. 1. Precast concrete and CIP concrete lintels shall be of depth and with reinforcing sufficient to support superimposed live and dead loads. 2.6 REINFORCEMENT AND ACCESSORIES A. Horizontal Joint Reinforcement: Welded in. (9 ga) continuous deformed ASTM A951 hot dip galvanized steel side rods with in. (12 ga) cross ties. Width shall be 1-1/4 to 1-3/4 in. less than wall thickness. Provide preformed corner pieces. B. Corrugated and Plain Anchors and Wall Ties in Masonry: Hot-dip galvanized steel; ASTM A153. project number Concrete Unit Masonry (Unreinforced)

4 C. Anchors for Fastening Masonry Walls to Concrete and Structural Steel: 1. Dovetail anchors, fitting the installed dovetail slots, are to be supplied to the blockmason as specified in the Concrete Forming and Accessories section. 2. Where no dovetail slots have been installed in concrete, use anchoring devices such as the following by Heckmann, or equal approved by A/E and Board: 282, 315C, 315D, 316, 317C, fastened to concrete no more than 16 in. oc using shielded 1/4 in. bolts in drilled holes. 3. To fasten to structural steel, use anchoring devices such as the following by Heckmann, or equal approved by A/E and Board: 190, 193. Weld 315, 316, 317B, 320 and 321 to steel. D. In-Wall Flashings: Self-adhering SBS membrane, or 5 oz/ft 2 sheet copper bonded to fiber-reinforced asphalt treated kraft paper. PART 3 EXECUTION Follow EXAMINATION AND PREPARATORY ANCHORING A. Dovetail Anchors: Where masonry walls will abut concrete walls or columns, check to see that properly positioned dovetail slots have been cast into the concrete. Also check to see that sufficient dovetail anchors (fitting the slots) have been furnished for use by the masons to bond the masonry walls to the concrete walls and columns. 1. If dovetail slots in concrete are found to be missing or are not properly positioned and installed, provide instead the specified masonry anchors 16 in. oc to take the place of dovetail slot & anchor bonding of the masonry walls to the concrete structure. 2. Fasten corrugated strap anchors to the concrete and place the corrugated portion in each horizontal masonry mortar joint. B. Other Anchors: Prepare to anchor masonry walls to cast-in-place concrete and structural steel by providing the specified masonry anchors 16 in. oc the full height of each masonry wall along each line of contact. 3.2 INSTALLING MASONRY A. Follow ACI 530 and except as more stringently specified herein. B. Environmental Conditions: 1. Temperature: 40 F. minimum and rising. 2. Weather: Do not lay up masonry during rain. Overnight and when rain is imminent, cover walls and block piles. Design and construct temporary bracing against overturning by wind; remove and repair when no longer needed. C. Worksite Tolerances: Maximum variances permitted from shown dimensions: 1. Bed joint thickness ± 1/8 in. 2. Bed joint, from level, in 10 ft ± 1/4 in. 3. Bed joint, from level, overall ± 1/2 in. 4. Top surface of bearing walls, overall ± 1/4 in. 5. Walls, from plumb line, in 10 ft ± 1/4 in. 6. Walls, from level line, in 20 ft ± 3/8 in. project number Concrete Unit Masonry (Unreinforced)

5 7. Walls, alignment bottom to top ± 1/8 in. 8. Corners, from plan, in any direction ± 1/8 in. 9. Wall waver in plan, from level line, in 20 ft ± 1/2 in. 3.3 LINTELS A. Lintels: 1. Precast concrete lintels are permitted in interior partitions unless cast-in-place is shown. Set lintels in full mortar beds with 8 in. minimum bearing each end. 3.4 REINFORCING A. Horizontal Joint Reinforcement: Provide at least at every second course and at first joint above and below openings, for all masonry, interior or exterior. 1. In walls having concrete filled cores, provide reinforcing in every horizontal joint. 2. At other areas, provide reinforcing in every second block course joint and at first joint above and below openings for exterior and interior masonry. 3. Cut and lap corners and intersections as recommended by reinforcing producer. 4. Make wall and partition joint reinforcing continuous around corners and at intersections following reinforcement producer's published directions. 5. Lap splices in joint reinforcement no less than 6 inches. Reinforcement shall not be continuous through expansion joints. 3.5 ANCHORING A. Corrugated Anchors: Place in every second block course for masonry walls and partitions abutting structural concrete and wherever dovetail anchors cannot be incorporated. Secure each upturned end to concrete with 2 heavy-duty screws in drilled shields. B. Dovetail Anchors: Place in every second block course for masonry walls and partitions that abut cast-in-place concrete, using the concrete s continuous dovetail anchor slots. C. When anchors have been fastened to the concrete or steel structure, place the corrugated portion in the nearest horizontal masonry mortar joint. 3.6 BLOCK LAYING A. Lay masonry plumb, true to line, with level and accurately spaced courses. Lay up units in common bond, unless stack bond is shown in certain areas. 1. Lay up only fully dry units. Cut units without using water. 2. Use masonry saws for cuts that will be exposed in the finished work. 3. Lay corners and reveals plumb and true. Line up vertical joints. 4. Fully bond and interlock masonry courses at corners and intersections. 5. Use concrete brick or soaps to course out walls concealed in the finished work. 6. Do not over-plumb corner and jamb units after they are set in position. If adjustment is needed after mortar starts to harden, remove mortar and replace with fresh mortar. B. Steel Opening Frames: Fill door and other opening frames with mortar and embed the anchor straps in mortar courses as masonry is layed up along jambs. project number Concrete Unit Masonry (Unreinforced)

6 C. Joint Treatment: 1. Joint Thickness: 3/8 in. 2. Joint Tooling: Tool joints until thoroughly compacted, pressing mortar hard against edges of masonry units. 3. Joint finish at block exposed to view: Concave-tooled joints, unless flush floatfinished joints are specifically shown. Do not rout joints or make reveals of any sort. 4. Joint finish at concealed block: Joints struck flush. 5. Point holes in mortar and masonry units in matching color. 6. Cut out and point up defective joints. D. Jointing Methods: 1. Where block cores are specified or shown to be filled with mortar or concrete, lay in full mortar beds with full mortared end joints. 2. Lay all other block with fully mortared joints at vertical and horizontal face shells. 3. Do not furrow mortar beds. Butter-and-shove vertical joints tight. 4. Finish tooled joints smooth and free of tool marks. 5. Joints between masonry and door frames: Rake to 3/8 in. depth suitable to receive a full bead of sealant. 6. Joints around electrical outlets in wet locations: Rake to receive full bead of sealant. 3.7 WALLS A. All Walls: 1. Grout dovetail slots and space between end of masonry units and concrete solid. 2. Wedge full height partitions and walls tight to soffit except for gap for firestopping where deflection can take place. 3. Set precast concrete (or steel) lintels in full beds of mortar with at least 8 in. bearing at each end. 4. Accommodate the forming, reinforcing and placing of cast-in-place concrete lintels, with care to see that concrete leakage does not ruin the look of exposed walls. 5. Fill the first block core in each block that adjoins an opening, and the last block core where a block wall terminates in a free end. 6. Fill voids around pipes, ducts and conduit penetrating walls except for space needed for the specified firestopping. 7. Point up joints solid and flush on both sides of partitions. B. Load Bearing Masonry Walls: 1. Erect walls before reinforced concrete members that bear on walls, as well as tie beams and tie columns within walls, are cast in place. 2. Fill block cores in top course using mortar or concrete where slabs or beams bear on masonry. 3. Close bottoms of top-course cores 8 in. below cast-in-place concrete beams, unless more filled-block courses are shown, to allow concrete to fill cores. Close bottom of course with galvanized steel sheet or heavy duty fiber-reinforced paper. 4. Do not use flush-end type units against columns and cast-in-place concrete walls. Butter both shell ends to columns and walls. C. Non-Load Bearing Masonry Wall and Partition Anchorage: project number Concrete Unit Masonry (Unreinforced)

7 1. Erect masonry after steel and concrete frames are in place, and after concrete floors and roof decks are in place. 2. After forms are stripped, remove slot fillers. 3. At edges of non-bearing interior masonry walls and partitions abutting concrete columns and cast-in-place concrete walls, provide corrugated dovetail type anchors 4. Grout dovetail slots and space between end of masonry units and concrete solid. 5. Point up joints solid and flush on both sides of partitions. D. Partition Heights: 1. Make partitions continuous from floor to underside of structural or fire-rated floor and roof construction above unless otherwise shown. 2. Wedge full height partitions and walls tight to soffit except for gap for firestopping where deflection can take place. 3. Where there are suspended ceilings on both sides of partitions, partitions other than those shown as continuous may be stopped 6 to 10 in. above the ceiling level. 4. Use concrete brick or solid units (soaps) for top masonry course. 5. Point up all joints solid and flush on both sides of walls and partitions. 3.8 FILLING AND GROUTING A. Concrete Fill for Cored Masonry Units: 1. Coordinate masonry work to allow placing of pea rock concrete as indicated and as specified in Concrete section. 2. Fill top courses of concrete masonry walls with concrete before placing or use concrete brick for top courses to assure solid masonry. 3. Pipe chase walls and partitions: Erect after pipes are in place, tested, and accepted. 4. Slots, chases, recesses, openings: Provide as needed for other work or equipment. 5. Setting of items supplied under other sections: Set anchors, bolts, sleeves, access panels, door frames, and other items occurring in masonry as the work proceeds. 6. Steel door frames: Set frames on floor, with floor clips fastened and frames braced in proper position. Grout anchors into masonry joints as walls are erected. B. Fill the Following Voids with Mortar: 1. First cell of blocks abutting door jambs and window frames. 2. Cells of blocks at free ends of partitions and walls. 3. Where necessary for embedment of anchors, and where otherwise shown. 4. Voids around ducts, pipes, conduit, wires, cable trays and other items passing through masonry work, leaving only a small, uniform, smooth aperture to receive firestopping as specified in the Firestopping section. 5. Steel door frames and elevator hoistway door frames in masonry walls and partitions: Grout solid with mortar as masonry is laid. Fill tops of door frames with mortar. /// project number Concrete Unit Masonry (Unreinforced)

LAYING BLOCK AND BRICK

LAYING BLOCK AND BRICK LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

Ver. 2. Guide to. Inspecting Residential Brick Veneer

Ver. 2. Guide to. Inspecting Residential Brick Veneer Ver. 2 Guide to Inspecting Residential Brick Veneer 1. A guide created by industry professionals. The knowledgeable staff at MASONPRO together with technical support from the Masonry Institute of Michigan

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS. Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION

More information

0331 Brick and block construction

0331 Brick and block construction 0331 BRICK AND BLOCK CONSTRUCTION This worksection has been written for Class 1 and 10a buildings that fully conform to the scope of AS 4773.1. If the works include isolated structures, (totally separate

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

RESIDENTIAL MASONRY A BEST PRACTICES GUIDE

RESIDENTIAL MASONRY A BEST PRACTICES GUIDE RESIDENTIAL MASONRY A BEST PRACTICES GUIDE Build With Brick Build With Boral CONTENTS BRICK :01 MASONRY CEMENT :03 MASONRY SAND :04 WALL TIES :05 STEEL LINTELS :07 DRAINAGE WALL SYSTEM :09 FLASHING :11

More information

Superform Products Ltd.

Superform Products Ltd. TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section

More information

Laying the First Course. 1. Excavate the site and construct the footing.

Laying the First Course. 1. Excavate the site and construct the footing. Use QUIKRETE Mortar Mix or Mason Mix lay up a concrete block wall as shown. QUIKRETE Mortar Mix or Mason Mix Concrete block Mason's line Line blocks 4' level brick trowel Jointer Mason's hammer Stiff brush

More information

necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the

necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final

More information

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General

More information

SECTION 02630 STORM DRAINAGE SYSTEM

SECTION 02630 STORM DRAINAGE SYSTEM SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE

More information

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel

More information

Preformed Metal Roofing and Siding

Preformed Metal Roofing and Siding Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision

More information

CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS

CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection

More information

Brick Veneer Construction

Brick Veneer Construction Brick Veneer Construction Check list of suggested tools & support items Claw hammer Tape measure 3/4" [19 or 20] Wood chisel Wood or plastic shims Pry bar Utility knife Caulking and caulking gun Power

More information

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel What is GigaCrete GigaCrete is a family of products based on low carbon footprint Green ceramic binders

More information

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

PROJECT TITLE : 2-STOREY RESIDENCE LOCATION : ALONG DAANG HARI,MOLINO.BACOOR,CAVITE OWNER : CUEVASVILLE REALTY

PROJECT TITLE : 2-STOREY RESIDENCE LOCATION : ALONG DAANG HARI,MOLINO.BACOOR,CAVITE OWNER : CUEVASVILLE REALTY PROJECT TITLE : 2-STOREY RESIDENCE LOCATION : ALONG DAANG HARI,MOLINO.BACOOR,CAVITE OWNER : CUEVASVILLE REALTY GENERAL SPECIFICATIONS These specifications are intended to cover the construction of the

More information

FORM DESIGN. easy to work with, and generally available.

FORM DESIGN. easy to work with, and generally available. Forms play a major role in concrete construction. They give the plastic concrete its shape and hold it until it hardens. Forms protect the concrete, assist in curing it, and support any reinforcing rods

More information

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3. Pages identified with the NMBS Logo as shown above, have been produced by NMBS to assist specifiers and consumers in the application of New Millennium Building Systems Deck products. Pages identified with

More information

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION General 7 www.meadowburke.com 877-518-7665 MB1109 CONCRETE FLOOR SLAB AND CASTING BED CONSTRUCTION Quality Construction Begins at Ground Level Everything

More information

PANELIZED HOME INSTALLATION GUIDELINE

PANELIZED HOME INSTALLATION GUIDELINE PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.

More information

Guide for SOLID CONCRETE BLOCK SEALS

Guide for SOLID CONCRETE BLOCK SEALS Guide for SOLID CONCRETE BLOCK SEALS July, 2006 Mine Safety and Health Administration SOLID CONCRETE BLOCK SEAL Formersection 30 CFR 75.335(a)(1) specifies requirements for seals constructed using solid

More information

Chapter. Restoration of Damaged Structures

Chapter. Restoration of Damaged Structures 5 Chapter Restoration of Damaged Structures Bringing back a damaged structure to its pre-earthquake state and original strength is called restoration. This is the first step of building rehabilitation.

More information

K. D. FRAME ASSEMBLY FOR CLOSED STEEL STUD WALLS...Ins 10. FRAME INSTALLATION DETAILS FOR CLOSED STEEL STUD WALLS...Ins 11

K. D. FRAME ASSEMBLY FOR CLOSED STEEL STUD WALLS...Ins 10. FRAME INSTALLATION DETAILS FOR CLOSED STEEL STUD WALLS...Ins 11 K. D. FRAME ASSEMBLY FOR MASONRY WALLS...........................Ins 2 FRAME INSTALLATION DETAILS FOR MASONRY WALLS......................Ins 3 INSTALLING EXISTING MASONRY WALL ANCHORS IN FRAME..................Ins

More information

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety

More information

LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council. *Corrected March 2014

LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council. *Corrected March 2014 ICC-ES Legacy Report PFC-3700* Issued October 2003 www.icc-es.org (00) 423-57 (52) 99-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code and the 2000 International

More information

Window Installation Instructions

Window Installation Instructions Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for

More information

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment

More information

Section 04810 EXTERIOR STONE VENEER Full Mortar

Section 04810 EXTERIOR STONE VENEER Full Mortar Full Mortar PART 1 GENERAL 1.1 SUMMARY A. Section includes: 1. Portland cement mortar bed 2. Stone Veneer 3. Expansion and control joints. 4. Portland cement and hydraulic mortar and grout. 5. Sealer and

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS 1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

PERIMETER FLASHING. Table of Contents

PERIMETER FLASHING. Table of Contents FM Global Property Loss Prevention Data Sheets 1-49 February 1985 Revised September 2000 Page1of25 PERIMETER FLASHING Table of Contents Page 1.0 SCOPE... 3 1.1 Changes... 3 2.0 LOSS PREVENTION RECOMMENDATIONS...

More information

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS 13.1 13.2 2006 Edition SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL

More information

Technical Notes 3B - Brick Masonry Section Properties May 1993

Technical Notes 3B - Brick Masonry Section Properties May 1993 Technical Notes 3B - Brick Masonry Section Properties May 1993 Abstract: This Technical Notes is a design aid for the Building Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS 402-92) and Specifications

More information

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including general and supplementary conditions and other Division 1

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS

2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS 2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS The LOGIX wall assembly has no need for an additional vapor barrier, the solid concrete core covered with the low permeance EPS (Type II) foam

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER

GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER CHAPTER 25 GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER User note: Code change proposals to this chapter will be considered by the IBC Structural Code Development Committee during the 2016 (Group B)

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

Division 4 Section 04200 Concrete Masonry Specification

Division 4 Section 04200 Concrete Masonry Specification PART 1- GENERAL 1.01 RELATED DOCUMENTS A. Drawings and General Provisions of Contract, including General and Supplementary Conditions and Division 01 Specification sections, apply to work of this section.

More information

H-Stud Area Separation Wall System

H-Stud Area Separation Wall System 12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic

More information

March 14, 2007. Installation of Bay, Bow and Garden Windows

March 14, 2007. Installation of Bay, Bow and Garden Windows March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed

More information

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system

More information

BILL OF QUANTITY FOR THE WORK OF "REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP"

BILL OF QUANTITY FOR THE WORK OF REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP BILL OF QUANTITY FOR THE WORK OF "REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP" Sl. 1 DISMANTLING WORK 1.1 Stripping off worn out plaster (outside and inside) and raking out joints

More information

7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME

7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME 7. Installation Window involves the fixing of window frame at an earlier construction stage and subsequent of the window sashes. This is a highly workmanship dependent process. Only trained and approved

More information

09/07/07 GLASSFIBER REINFORCED CEMENT (GRC) C. S. I. Spec 03500 Master Spec. 03 49 00 Page 1

09/07/07 GLASSFIBER REINFORCED CEMENT (GRC) C. S. I. Spec 03500 Master Spec. 03 49 00 Page 1 C. S. I. Spec 03500 Page 1 PART 1 - GENERAL 1.01 SUMMARY:.01 Provide special glassfiber reinforced cement (GRC) shapes in accordance with the requirements of the contract documents..02 The installing contractor

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

Introduction...COMB-2 Design Considerations and Examples...COMB-3

Introduction...COMB-2 Design Considerations and Examples...COMB-3 SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

Energy Company Obligation (ECO): Technical Monitoring Questions

Energy Company Obligation (ECO): Technical Monitoring Questions Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified

More information

SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS

SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS SECTION 08000 STORM DRAINAGE 08010 DESIGN A. Location B. Sizing TABLE OF CONTENTS 08020 MATERIALS A. Pipe Materials B. Structure Materials C. Installation D. Inlets and Outlets 08030 INSPECTIONS AND TESTING

More information

Issue of the Guidelines on Prevention of Water Seepage in New Buildings

Issue of the Guidelines on Prevention of Water Seepage in New Buildings graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural

More information

AIRPORT SECURITY FENCING. A. American Society for Testing and Materials (ASTM):

AIRPORT SECURITY FENCING. A. American Society for Testing and Materials (ASTM): SECTION 02832 AIRPORT SECURITY FENCING PART 1-GENERAL 1.1 SUMMARY A. Section includes: Construct airport security chain-link fence and gate at specified areas and conforming lines, grades, details indicated

More information

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description

More information

Division 4 Section 047200 Concrete Masonry Specifications

Division 4 Section 047200 Concrete Masonry Specifications Cast Stone Specification This specification encompasses basic requirements for Cast Stone, as manufactured by Building Products Corp, 494 North 33 rd Street East St. Louis, Il 618-874-6282, 800-427-6282,

More information

MANUFACTURED HOUSING USED AS DWELLINGS

MANUFACTURED HOUSING USED AS DWELLINGS MANUFACTURED HOUSING USED AS DWELLINGS SECTION AE101 SCOPE AE101.1 General. These provisions shall be applicable only to a manufactured home used as a single dwelling unit and shall apply to the following:

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.

More information

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE By H P Gupta & D K Gupta DIFFERENT TYPES OF DAMAGES 1.Minor cracks 0.5 to 5 mm wide in load or non-load bearing walls 2.Major

More information

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) 55-1 GENERAL The Contractor shall perform all work required by the plans for construction of pipe for storm drains, precast polymer trench drains

More information

Packaged Terminal Air Conditioner Wall Sleeve Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation

More information

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing 1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize

More information

OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide. GeneralShale.com

OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide. GeneralShale.com OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide GeneralShale.com OLD BRICK ORIGINALS THIN BRICK VENEER Page 2 INTRODUCTION Check local building codes for proper installation guidelines

More information

Manufactured Stone Veneer Installation Instructions

Manufactured Stone Veneer Installation Instructions Manufactured Stone Veneer Installation Instructions Published: 8/14/2008 Revised: 6/25/2010 Table of Contents PART 1 -- INTRODUCTION PART 2 -- MATERIAL REQUIREMENTS PART 3 EXECUTION REQUIREMENTS PART 4

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

ROOF FLASHING SPRINGLOK FLASHING SYSTEM FEATURES & BENEFITS PRODUCT DESCRIPTION

ROOF FLASHING SPRINGLOK FLASHING SYSTEM FEATURES & BENEFITS PRODUCT DESCRIPTION SPRINGLOK SYSTEM PRODUCT DESCRIPTION FEATURES & BENEFITS Fry Reglet offers five flashing systems, each tailored for a particular type of substrate so you can get exactly what you need. SM Surface mounted

More information

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with

More information

DENVER MODEL 30 X 30 SPECIFICATIONS

DENVER MODEL 30 X 30 SPECIFICATIONS DENVER MODEL 30 X 30 SPECIFICATIONS Dimensions: Roof Dimensions 30-0 x 30-0 (4) Columns (Center to Center) 25-6½ x 25-6½ Minimum Clearance 8-0 Roof Height @ Peak Dependent on Col. Ht. Hip Roof 4:12 pitch

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

Dubai Municipality Standard DMS 1: Part 5: 2004

Dubai Municipality Standard DMS 1: Part 5: 2004 Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue

More information

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein

More information

How To Make A House Safe

How To Make A House Safe 1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design

More information

MeltonStone Cast Stone Product Specifications

MeltonStone Cast Stone Product Specifications MeltonStone Cast Stone Product Specifications Section 04-72-00-04 Architectural Cast Stone This specification encompasses basic requirements for Cast Stone, a refined architectural concrete building unit

More information

GYPSUM BOARD AND PLASTER

GYPSUM BOARD AND PLASTER CHAPTER 25 GYPSUM BOARD AND PLASTER SECTION 2501 GENERAL 2501.1 Scope. 2501.1.1 General. Provisions of this chapter shall govern the materials, design, construction and quality of gypsum board, lath, gypsum

More information

Installation Instructions

Installation Instructions Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate

More information

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit. Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden

More information

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS Introduction This inspection guide is organized to follow the EIF System's Installation Guide.

More information

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

WHI 90-Minute Rated Veneered Door Frame Installation Instructions No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

Tremco Fire Protection Systems Group Technical Bulletin

Tremco Fire Protection Systems Group Technical Bulletin Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

Sun Windows General Information Sun New Construction Window Installation Instructions

Sun Windows General Information Sun New Construction Window Installation Instructions Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten

More information

CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS

CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS AN ERGONARMOR COMPANY TECHNICAL INFORMATION SPECIFICATION FOR INSTALLATION 07/11 SUPERSEDES 04/00 PAGE 1 OF 6 CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS 1. SCOPE 1.1 This specification

More information

Architectural Concrete Masonry

Architectural Concrete Masonry 1. Adams Profile Split Face Units (PSF). 2. Adams Profile Split Face Single Score Units (PSF-1). 3. Adams Profile Split Face Double Score Units (PSF-2) 4. Adams Profile Wide Split Rib Four Units (PWSR-4).

More information