DIFFERENTIAL PRESSURE TRANSDUCER DPT-MOD SERIES: DPT-MOD-10 / DPT-MOD-20
|
|
- Rodger Farmer
- 3 years ago
- Views:
Transcription
1 DIFFERENTIAL PRESSURE TRANSDUCER DPT-MOD SERIES: DPT-MOD-10 / DPT-MOD-20 INSTALLATION INSTRUCTIONS INTRODUCTION The DPT-MOD Differential Pressure Transmitter for air conforms to Modbus over serial line protocol, using RTU transmission mode and RS485 interface. The digital output signal is sent over Modbus enabling the DPT-MOD to connect directly to field communication network. DPT-MOD requires less wiring than traditional 3-wire transducers, since multiple devices can be connected on serial line. The Series is comprised of the standard version (DPT-MOD-x) and the DPT-MOD-x-IN version that includes an Input module. The Input module is a fixed expansion board that provides additional external signal conversion into Modbus. The Input module can be installed during or after the DPT-MOD-x is installed. The -IN module has two input channels designed to accept 0 10V, ntc10k, Pt1000, Ni1000/(-LG), and BIN IN (potential free contact) signals. For example, DPT-MOD with input module can read values from one differential pressure-measurement point and two temperature-measurement points. Hence, the DPT-MOD does the work of three transmitters. WARNING READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE. Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE. To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage. To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres. Retain these instructions for future reference. This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by HK Instruments, Inc. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced, knowledgeable, technicians to install this device. APPLICATIONS DPT-MOD series devices are commonly used in HVAC/R systems for: fan, blower and filter monitoring valve and damper control pressure and flow monitoring pressure monitoring in clean rooms SPECIFICATIONS Performance Accuracy: (Pressure over operating temperature range) DPT10-MOD: Ranges <1.0 inwc = ±0.024 inwc <250 Pa = ±6 Pa Ranges 1.0 inwc = ±1.5% FS 250 Pa = ± 1.5% FS DPT30-MOD: ±1.5% FS (Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, and repetition error.) Long Term Stability: (Typical 1 yr.) Without : DPT10-MOD: inwc (8 Pa) DPT30-MOD: inwc (24 Pa) With : DPT10-MOD: inwc (1 Pa) DPT30-MOD: inwc (1 Pa) Thermal Effects: Temperature compensated across the full spectrum of capability. Overpressure: Burst Pressure: 120 inwc Technical Specifications Media Compatibility: Dry air or nonaggressive gases Measuring units: Pascal (Pa) Measuring element: Piezoresistive Environment: Operating Temperature: F ( C) with (-ez) e-zero circuit option F (-5 50 C) Configuration, while using display F (0 50 C) Storage Temperature: F ( C) Humidity: 0 to 95% RH, non condensing Physical Case: Dimensions: 3.54 x 3.79 x 1.4 (90.0 x 98.5 x 36.0 mm) Weight: 5.3 oz (150 g) Mounting: 2 each 11/64 (4.3 mm) screw holes, one slotted Materials: Case: ABS (UL 94 V-0 Approved) Lid: PC (UL 94 V-0 Approved) Protection standard: IP54 / NEMA3 Display: (Configuration only) 1-Line Display Size: 0.80 W x 0.40 H (20.3 x 10.2 mm) Electrical Connections: 5 screw terminal block Wire: 12-24AWG ( mm 2 ) Cable Entry: Strain Relief: M20 X 1.5 Knockout:.787 (20 mm) Pressure Fittings: 3/16 (5.2 mm) barbed brass + High pressure Low pressure Communication Protocol: MODBUS over Serial Line Transmission Mode: RTU Interface: RS485 Byte format (11 bits) in RTU mode: Coding System: 8 bit binary Bits per Byte: 1 start bit, 8 data bits with least significant bit sent first, 1 bit for parity (See Configuration), 1 stop bit Baud rate: selectable in configuration MODBUS Address: addresses selectable in configuration menu. Zero Point Calibration Options: Automatic with (ez) circuit Manual push-button Auto-Zero Via MODBUS write coil : 0.8 sec, 2.0 sec, or 10 sec selectable in configuration menu. Electrical Input: 24VAC or VDC, ±10% Power consumption: < 1.3W Output: via MODBUS Conformance: Meets requirements for CE marking: EMC directive: 2004/108/EC RoHS Directive: 2002/95/EC WEEE Directive: 2002/96/EC Meets safety requirements for electrical equipment for measurement, control, and laboratory use: ETL marking, standard IEC Tested and meets product approval requirements by the NRTL certified testing laboratory. Conforms to ANSI/UL Std Certified to CAN/CSA Std C22.2 No
2 SCHEMATICS INSTALLATION Figure 1 1) Mount the device in desired location, see Step 1. 2) Open the lid and route power and communication cables through strain relief and connect the wires to terminal block, see Step 2. 3) The device is now ready for configuration, see Step 3. WARNING! Apply power after the device is properly wired. A B 24V GND Shield Terminal Block Push Display Configuration Pressure Sensor MOUNTING DEVISE Step 1 1) mounting location (duct, wall, panel). 2) Use the device as a template and mark the screw holes. 3) Mount with appropriate screws (not included). Figure 3 (a) - Surface Mounting DIMENSIONAL DRAWINGS Figure (90.0) 3.03 (77.0) 1.41 (36.0 ) Figure 3 (b) - Mounting Orientation (71.5) (53.0) 3.79 (98.5) 00 = inches (0.0) = millimeter Ø (Ø4.2) YES NO NO Figure 3 (c) - Application Connections Static Pressure Filter/Damper Monitoring Fan/Blower Monitoring Not Connected
3 WIRING Step 2 For CE compliance, a properly grounded shielding cable is required 1) Unscrew strain relief and route cable. 2) Connect the wires as shown in Figure 4. 3) Tighten the strain relief. SELECT DEVICE ADDRESS Step 3.1 1) Activate the Device Address Menu by installing the Jumper, see, Figure 6. 2) Cycle through options to select device Modbus Address. Figure 4 - Wiring Modbus: I/O A Modbus: I/O B + 24V Power Supply GND 24VDC / 24VAC Shield Options: 1 to 247 Figure 6 - Device Address CONFIGURATION Step 3 The device is configured using the /, the Internal Display, and that are installed and removed from the four (4) sets of jumper pins located at the upper right of the opened device, see Figure 1 and Figure 5. SELECT BAUD RATE Step 3.2 1) Activate the Baud Rate Menu by installing the Jumper; see Figure 7. 2) Cycle through the options to select device Baud Rate. Operations: button / : The button / will advance the display though the available choices by Pressing Down or Tilting Up or Back. The button / will only cycle the choices up, if you accidently pass your preferred selection continue to activate the button / until your selection reappears. : are used to select menus for Device Address, Baud Rate, Bit, and. Install the Jumper on the appropriate pins to display the choices. Example: Device Address, see Figure 5. After choice appears in display, remove Jumper and move it to the next menu, when done with the last menu, Response Time, place Jumper in Store position. Figure 7 - Baud Rate Options: 9600, 1920, 3840 Figure 5 - Example > Device Address SELECT PARITY BIT Step 3.3 1) Activate the Bit Menu by installing the Jumper; see Figure 8. 2) Cycle through the options to select device Bit. Gray color indicates that a jumper is installed > Jumper Stored Gray color indicates that a jumper is installed Options: None, Even or Odd Figure 8 - Bit
4 SELECT RESPONSE TIME Step 3.4 1) Activate the Menu by installing the Jumper; see Figure 9. 2) Cycle through the options to select device. 3) Remove Jumper and place in Stored position. Figure 9 - C) Automatic: Zero Point Calibration Note! If the device includes the optional no action is required. circuit, (-ez) is a True Auto Zero function in the form of an automatic zeroing circuit built into the PCB board. The function electronically adjusts the transducer zero point at predetermined time intervals (every 10 minutes). Options: 0.8, 2.0 or 10 The function eliminates all output signal drift due to thermal, electronic or mechanical effects, as well as the need for technicians to remove high- and low-pressure tubes when performing initial or periodic transducer zero point calibration. The adjustment takes 4 seconds. To avoid conflict with the BAS system, the output and display values will freeze to the latest measured value, after which the device returns to its normal measuring mode. ZERO POINT CALIBRATION Step 3.5 Note! Supply voltage must be connected one-hour before the Zero Point Calibration is carried out. There are three options for Zero Point calibration: A) Manual: Push Auto Zero B) MODBUS: via Write coil C) Automatic: via the function Does my transducer have an function? Look at the small gray product-label on the side of the device. If ez is in the model number, then you have the function. A) Manual: Push Auto Zero Note! Supply voltage must be connected one hour before the Zero Point Calibration is carried out. 1) Disconnect both pressure tubes from the pressure ports labeled + and. 2) Push down the / until the LED light (red) turns on and the display reads zeroing (display option only). 3) The zeroing of the device will proceed automatically. Zeroing is complete when the LED turns off, and the display reads 0 (display option only). 4) Reinstall the pressure tubes, ensuring the High pressure tube is connected to the port labeled +, and the Low pressure tube is connected to the port labeled. Note! The zero point should be calibrated via Manual Push Auto Zero, one hour after installation and power is applied, and at least every 12 months during normal operations. B) MODBUS: Zero Point Calibration via Modbus Note! Supply voltage must be connected at least one hour prior to zero point adjustment. 1) Make sure that the system is locked out and not running while performing the zero point calibration, so that there is zero (0) pressure applied to the device. As an alternative, disconnect both pressure tubes from the pressure ports labeled + and. 2) Send the zeroing command via Modbus. Write 1 to register 0x0001. The register 0x0001 state returns back to 0 automatically after zeroing. 3) The zeroing of the device will proceed automatically. Zeroing is complete when the LED turns off, and the display reads 0 (display option only). 4) The system may now be restarted. Reinstall the pressure tubes, if disconnected. Ensure that the High pressure tube is connected to the port labeled +, and the Low pressure tube is connected to the port labeled. MEASURING STATE Step 3.6 The device display will return to the Measuring State when the Jumper is placed in the Stored position. If the pressure tubes are disconnected or the unit is off the display will show kpa. It will take about 5 seconds to return to Measuring State, after zero point calibration or the Jumper is placed in the Stored position. CONNECT PRESSURE TUBE Step 4 1 ) Connect pressure tubes. Connect positive pressure to port labeled + and negative pressure to port -. 2) Close the lid. The device is ready to use. MODBUS FUNCTIONS DPT-MOD supports to the following functions and registers. FUNCTION 04 - Read Input Register Register Parameter Data Type Value Range 3x0001 3x0002 Program version Pressure in Pascals 16 bit 0 1, bit FUNCTION 05 - Write Single Coil 0 2, ,000 Register Parameter Data Type Value Range 0x0001 Zero Point Calibration 0 2,500(Pa) 0 5,000(Pa) Bit 0 0 / 1 On - Off Zero Point Calibration: Write 1 to register 0x0001. The register 0x0001 state returns to 0 automatically after zero point calibration is completed.
5 WARRANTY POLICY WARRANTY COVERAGE: HK Instruments, Inc. (HK) warrants to the original end user of the Products that the Products will, at the date of initial purchase, meet the applicable specification for such Products (as described by HK in its product literature) and, under normal use and service, will be free from any defects in materials or manufacture for (a) one (1) year from date of sale to end user for electromechanical Products and (b) five (5) years from date of manufacture for electronic Products. NO WARRANTY OF PRODUCT SUITABILITY: Neither HK nor the manufacturer of the Products to be sold hereunder( Manufacturer ) makes any warranty that Products are suitable for a particular purpose, application or design. Many states and localities have differing codes or regulations governing the installation and/or use of HK products. HK does not guarantee compliance with such codes or regulations; the end user is solely responsible for safe and correct installation and use of the Products and for compliance with such codes and regulations. EXCLUSION OF IMPLIED WARRANTIES: THE WARRANTY HEREIN IS THE ONLY WARRANTY APPLICABLE TO THE PRODUCTS AND EXCLUDES ALL OTHER WARRANTIES, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, AND ANY IMPLIED WARRANTY ARISING FROM COURSE OF DEALING OR USAGE OF TRADE. REMEDIES FOR NON-CONFORMITY OR BREACH OF WARRANTY: If the Product purchased does not conform to the applicable warranty, HK will provide, at its option, one of the following remedies: (1) repair of the non-conforming Product, (2) replacement with a conforming Product, or (3) refund of the original purchase price. THESE REMEDIES SHALL BE THE EXCLUSIVE AND SOLE REMEDY for any breach of warranty. HK and Manufacturer have no other responsibility or liability for breach of warranty or otherwise. LIMITATION OF LIABILITY: NEITHER HK NOR MANUFACTURER WILL BE LIABLE FOR ANY INCIDENTAL, SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES UNDER ANY CIRCUMSTANCE, INCLUDING WITHOUT LIMITATION ANY DEFECT IN THE PRODUCT PURCHASED. FURTHER LIMITATIONS: The warranty herein does not cover damage caused by lightning, flood or other natural phenomenon; normal wear and tear; accident, improper or careless handling, abnormal use, overloading, improper storage or abuse; incorrect installation, care or reconstruction; or alteration, calibration, reconfiguration, maintenance or installation work done by unqualified personnel. Should Manufacturer alter the structure of any Product in the future, HK and Manufacturer shall not be obligated to make comparable changes to Products already purchased. HK will give a new warranty for Products being replaced or repaired within the warranty period, however only to the expiration of the original Product s warranty period. The warranty includes the repair of a defective part or device, or if needed, a new part or device, but no other costs except as otherwise stated in the HK Distributor Terms and Conditions.
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationTCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...
More informationModel SRMD Setra Remote Monitoring Display
Model SRMD Setra Remote Monitoring Display 1.0 GENERAL INFORMATION Thank you for purchasing the Setra Remote Monitoring Display (SRMD). The SRMD is a digital panel meter with a bright 1 LED display for
More informationSpecifications - Installation and Operating Instructions Ø5 [127.00] 17/64 [6.91] 1-59/64 [48.89]
Bulletin P-DM-1100 Series DM-1000 DigiMag Digital Differential Pressure Gage Specifications - Installation and Operating Instructions PRESSURE CONNECTIONS 21/64 [8.59] LONG Ø5 [127.00] 4-31/64 [113.89]
More informationSOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity
More informationTemp. & humidity Transmitter Instructions
Temp. & humidity Transmitter Instructions AQ3485/AQ3485Y www.aosong.com 1 Product Overview AQ3485/ AQ3485Y outdoor network temperature and humidity transmitter is accurate measurement of relative humidity
More informationPart I - Installation
400 Series Pressure and Differential Pressure Switches Types: H400, H402, H403, H400K, H402K, J400, J402, J403, J400K, J402K UNITED ELECTRIC CONTROLS Installation and Maintenance Instructions Please read
More informationRI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationPIEZOMETER AIRFLOW MEASURING RING
PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer
More information543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
More informationInstallation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.
Installation Instructions Differential Air-pressure Transmitter Catalog Numbers 1414-IPZ10FODAA, 1414-IPZ10FNDAA, 1414-IPD10FNRAA, 1414-CPZ10FODAA, 1414-CPZ10FNDAA, 1414-CPD10PNRAA Topic Page Before Installation
More informationPRODUCT PROFILE FEATURES
PRODUCT PROFILE Pressure Transmitters & Pneumatic Transducer Airflow Transmitter, Differential Air Pressure Transmitter and Differential & Gauge Liquid/Gas Pressure Transmitter FEATURES AIRFLOW TRANSMITTER
More informationWireless Indoor/ Outdoor Thermometer
Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...
More informationaseries A13B Mini Bullet Camera User Manual
aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView
More informationCompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
More informationUser Manual (English)
User Manual (English) Table of Contents General Safety Information...2 Fueltank UNO Components...3 Charging the Fueltank UNO...4 Using the Fueltank UNO...5 Power Saving Mode...6 Checking the Fueltank UNO
More informationHMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
More information2/8.10.01. These vacuum switches are used in measuring ranges between -1 and 0 bar.
CATALOGUE > Release 8.5 > Electronic vacuum switches Series SWM Electronic miniature vacuum switches Series SWM These vacuum switches are used in measuring ranges between -1 and 0 bar. Small dimension
More informationInstruction Manual. T3111 T3111L T3111P T3111Ex
www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs
More informationMini-HDMI Series MINIATURE MULTIMODE FIBER OPTIC HDMI TRANSMISSION SYSTEM
Mini-HDMI Series MINIATURE MULTIMODE FIBER OPTIC HDMI TRANSMISSION SYSTEM BCI reserves the right to make changes to the products described herein without prior notice or consent. No liability is assumed
More informationElectronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
More informationSierra Dual 24 Volt Brushless DC Motor Controller Product Specification
Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification Assembly 025A0215 600A0942 Rev. A May 14, 2012 025A0215 Brushless DC Motor Controller Page 1 Revision History ECN # Date Rev Description
More informationEPM3. Phase Sequence and Motor Rotation Tester. Users Manual
EPM3 Phase Sequence and Motor Rotation Tester Users Manual 1 L1 L2 L3 2 3 A B C CAT 600V 3-PHASE TESTER 5 TEST M1 M2 BATT M3 EPM3 MOTOR ROTATION TESTER EPM3 MOTOR ROTATION DETERMINED WHILE FACING MOTOR
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
More informationDPT-2015 Differential Pressure Transmitter for VAV Box Applications
FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential
More informationINSTALLATION AND OPERATING INSTRUCTIONS
ddcwp_manual_gb_revisions.ai 10/23/06 Page 1 Date: Station 1 2 3 4 5 6 7 8 CUSTOM WATERING PLAN 3 Program Controller Description Program A Program B Program C Duration Duration Duration DDC WP Series Waterproof
More informationABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
More informationTP32MTT.03 TP32MTT.03.1. [ GB ] Probes for soil thermal profile measurement
TP32MTT.03 [ GB ] Probes for soil thermal profile measurement [ GB ] [ GB ] Description Temperature measurement at 7 levels (TP32MTT.03) or 6 levels () In accordance with the requirements of the World
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
More informationDAM Series DAM124 4DIN+8AI+4DO Module Model No.:DAM124 WebSite: www.gsm-m2m.com
DAM Series DAM124 4DIN+8AI+4DO Module Model No.:DAM124 WebSite: www.gsm-m2m.com This handbook has been designed as a guide to the installation and operation of King Pigeon Hi-Tech.Co.,Ltd DAM series. Statements
More informationName of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
More informationProcess modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
More informationWhen any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
More informationINSTRUCTION MANUAL MODEL PCD-88
INSTRUCTION MANUAL MODEL PCD-88 CLOSED CAPTION DECODER LINK ELECTRONICS, INC. 2137 Rust Avenue Cape Girardeau, Missouri 63703 Phone: 573-334-4433 Fax: 573-334-9255 e-mail: sales @ linkelectronics.com website:
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationA-Series Data Loggers PRODUCT MANUAL
A-Series Data Loggers PRODUCT MANUAL Model # s A110, A125, A130, and A150 Contents Model Specifications 2 Connecting to the Computer 3 SpecWare Software 4 Installation and Placement 6 Battery Replacement
More informationINTMOD485-LH Protocol Converter
For Use with L-GAGE LH Series Sensors Features Converts an LH Network to the 485-RTU protocol Supports baud rates up to 230,400 baud Supports LH Networks with up to 32 sensors Model Protocol Conversion
More informationLS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
More informationUser Guide. HDMI Active Cable Extender. DVI-7370c
User Guide HDMI Active Cable Extender DVI-7370c TABLE OF CONTENTS SECTION PAGE PRODUCT SAFETY...1 PRODUCT LIABILITY...1 1.0 INTRODUCTION...2 2.0 SPECIFICATIONS...3 3.0 PACKAGE CONTENTS...4 4.0 CONNECTING
More informationM7250P. PoE Powered. Gigabit Ethernet Media Converter 1000BASE-TX TO 1000BASE-SX/LX. Installation Guide
M7250P PoE Powered Gigabit Ethernet Media Converter 1000BASE-TX TO 1000BASE-SX/LX Installation Guide September 2009 VERSITRON, Inc. 83 Albe Drive - Suite C Newark, DE 19702 www.versitron.com www.versitron.com
More informationMAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
More informationSignal Manager Installation and Operation Manual
Signal Manager Installation and Operation Manual Rev.11/28/2008 Part # 26550007 Table of Contents CHAPTER 1: SYSTEM DESCRIPTION... 3 FUNCTION AND THEORY... 3 CHAPTER 2: SYSTEM INSTALLATION... 4 HARDWARE
More informationSingle Station Remote Alarm
ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation
More informationElectronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
More informationLeak Detection System
Instructions - Parts List Leak Detection System 311200A For detecting leaks in your diaphragm pump system. Not for use in explosive atmospheres. Part No. 234576 120 psi (0.8 MPa, 8 bar) Maximum Air Input
More informationVentostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:
GE Measurement & Control Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low
More informationUser Manual Revision 2.003 English
Document code: MN67120_ENG Revision 2.003 Page 1 of 15 User Manual Revision 2.003 English RS232 / RS485 / Ethernet - Converter (Order Code: HD67120) for Website information: www.adfweb.com?product=hd67120
More informationDTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual
DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR Installation and Operation Manual 1 ENGLISH Safety Instructions 2 Features 2-3 Specifications 3 Installation 4-5 Wiring Diagrams 6-7 Warranty 8
More informationSP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE
SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
More information2-Way Wireless Indoor Siren Installation Guide
2-Way Wireless Indoor Siren Installation Guide For more detailed information please refer to the iconnect Installer Manual provided on our website: www.electronics-line.com Table of Contents 1. Introduction...
More informationUser Manual. Humidity-Temperature Chart Recorder. Model RH520
User Manual Humidity-Temperature Chart Recorder Model RH520 Introduction Congratulations on your purchase of the Extech RH520 Temperature + Humidity Chart Recorder. The RH520 measures and displays Temperature,
More informationWeather Radio Alarm Clock
1200093 User s Guide Weather Radio Alarm Clock Thank you for purchasing your Weather Radio Alarm Clock from RadioShack. Please read this user s guide before installing, setting up, and using your new weather
More informationLCD5500Z / PKP-LCD v3.x Installation Instructions
LCD5500Z / PKP-LCD v3.x Installation Instructions TM Introduction The LCD5500Z / PKP-LCD keypad displays system status using an LCD screen. The keypad can be used on PowerSeries security systems with up
More informationComfort Control Relay Panel (CCRP)
CCRP9 "Commitment to Innovation" OPERATION & INSTALLATION GUIDE FOR Comfort Control Panel (CCRP) Off-Peak System Control 9 Pole CCRP 4 Pole CCRP (Applicable to Software Version 14.0-14.9) "Manufactured
More informationInstallation and Operation Guide for PD5100 Automatic Transfer Switch
Installation and Operation Guide for PD5100 Automatic Transfer Switch Member P r o gr e ssive Dynamics, Inc. 507 Industrial Rd Marshall, MI 49068 www.progressivedyn.com 2012 Progressive Dynamics, Inc.
More informationUser Manual Revision 1.002 English
Document code: MN67075_ENG Revision 1.002 Page 1 of 15 User Manual Revision 1.002 English Modbus RTU / Modbus ASCII - Converter (Order Code: HD67075-A1) for Website information: www.adfweb.com?product=hd67075
More informationIntesisBox KNX Mitsubishi Heavy Industries AC
IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)
More informationIDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765
IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765 The Service Information provides the following information: Precautions and safety information Specifications Performance test procedure Calibration
More informationBMW Multi Tool User Manual
X-Horse Electronics Co., Ltd. Table of Contents 1. Safety Precautions and Warnings... 3 2. General Information... 4 3. Hardware Overview... 5 3.1. Tool Description... 5 3.2. Specifications... 6 3.3. System
More informationName Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage
Description Supports DALI interface driver Programming Supports 0-10V Programmable Driver Programming Supports Other Controllers (TDD-ANPNx, SDD-AAPNx) Off-line programming capability Auto programming
More informationPolyGard Carbon Monoxide CO Transmitter ADTX3 1110
PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 DESCRIPTION CO transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air
More informationMagnetic Stripe Reader-Writer. Magnetic Stripe Reader-Writer. RS232 & USB-RS232 Interface Quickstart Manual
Magnetic Stripe Reader-Writer RS232 & USB-RS232 Quickstart Manual ID TECH 10721 Walker Street Cypress, California 90630 (714) 761-6368 www.idtechproducts.com 80058504-002 Rev. C R01/08 Magnetic Stripe
More informationT0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
More informationOperation and Installation Manual
Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control
More informationVroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR
Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions
More information4 Port VGA Video Audio Switch with RS232 control
4 Port VGA Video Audio Switch with RS232 control VS410RVGAA *actual product may vary from photos DE: Bedienungsanleitung - de.startech.com FR: Guide de l'utilisateur - fr.startech.com ES: Guía del usuario
More informationOverview of Standards for CO Detection Products
Overview of Standards for CO Detection Products Rev 1.1 INTEC Controls 12700 Stowe Dr., Suite 100 Poway, CA 92064 The Right Choice info@inteccontrols.com www.inteccontrols.com Phone: (858) 578-7887 Fax:
More informationSeries 510 Submersible Level Transmitters
Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable
More informationNI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module
DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position
More informationWEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK
WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue
More informationHow To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
More informationInstallation instructions for Series NRX INCOM communications adapter module
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply
More informationUser's Manual. Heavy Duty Dissolved Oxygen Meter Model 407510
User's Manual Heavy Duty Dissolved Oxygen Meter Model 407510 Introduction Congratulations on your purchase of Extech's Heavy Duty Dissolved Oxygen / Temperature Meter which simultaneously displays Dissolved
More informationMIC-WKT and MIC-WKT-IR
MIC-WKT and MIC-WKT-IR Installation Manual Bosch Security Systems EN Installation and Operation Manual MIC-WKTI and MIC-WKT-IR Installation Manual EN 2 MIC-WKT and MIC-WKT-IR Washer Pump Drive Card Kits
More informationINSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
More informationP O W E R S U P P L Y M A N U A L
POWER SUPPLY MANUAL Congratulations on the purchase of your new Corsair power supply. This User Agreement (the Agreement ) is a legal agreement between you ( You ), and Corsair Memory, Inc. ( Corsair ).
More informationBroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
More informationTelephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationCAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual
Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual
More informationIntesisBox KNX LG Air Conditioning
IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit
More informationRIGtalk. Revision 5. Owner s Manual 2012.
RIGtalk Revision 5 Owner s Manual 2012 www.westmountainradio.com 1020 Spring City Drive Waukesha, WI 53186 262-522-6503 sales@westmountainradio.com 2012 West Mountain Radio, All rights reserved. All trademarks
More informationPowerware Relay-Serial Card User s Guide
Powerware Relay-Serial Card User s Guide Special Symbols The following are examples of symbols used on the UPS and accessories to alert you to important information: This symbol indicates that you should
More informationUSER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
More informationHIH-4000 Series Humidity Sensors
HIH-4000 Series Humidity Sensors DESCRIPTION The HIH-4000 Series Humidity Sensors are designed specifically for high volume OEM (Original Equipment Manufacturer) users. Direct input to a controller or
More information2-3 SAS/SATA II HDD Canister USER S MANUAL XC-23D1-SA10-0-R. Document number: MAN-00076-A
2-3 SAS/SATA II HDD Canister XC-23D1-SA10-0-R USER S MANUAL Document number: MAN-00076-A ii Preface Important Information Warranty Our product is warranted against defects in materials and workmanship
More informationInwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
More informationWD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
More informationInHome Water Leak Detection Package
InHome Water Leak Detection Package For Model Numbers ILD10A-L and ILD10A-B Installation Guide / Wiring Diagram For Creating Water Leak Detection-based Events with Line-Powered or Battery-Powered Sensors
More informationApplication/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
More informationKeysight N4877A Clock Data Recovery and Demultiplexer 1:2
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 Getting Started Getting Started with the Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 You only need a few minutes to get started
More informationMIC-BP4 Bi-Phase Converter Card For the MIC400 series camera
MIC-BP4 Bi-Phase Converter Card for the MIC400 PTZ Camera Series Bosch Security Systems EN Installation and Operation Manual BP4 Bi-phase card Installation and Operation Manual AAAEN 2 MIC-BP4 Bi-Phase
More informationAGS. Owner's Manual. Xantrex Automatic Generator Start Control System
AGS Owner's Manual Xantrex Automatic Generator Start Control System TABLE OF CONTENTS INTRODUCTION...3 Main Features...3 Safety Summary...3 THINGS YOU SHOULD KNOW...4 THEORY OF OPERATION...5 System...5
More informationEZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014
EZmoto V2 Product description Rev. 6 10/01/2014 1 Contents 1. Overview... 3 2. Hardware Interface Description... 3 2.1 Main features of the EZmoto... 3 2.2 Hardware block diagram... 4 2.3 Internal Hardware
More informationITEM MODEL QTY. Filter 3910-04 1. ITEM MODEL QTY USB-RS485 Converter (with 3716A-21) 3716A-20 1
Component List Standard ITEM MODEL QTY Main Unit (3716A/3717A) 3716A-00 3717A-00 AC Adapter - 1 Filter 3910-04 1 Joint - 1 Tygon Tube - 1 User s Manual - 1 Settings Software (DVD) 3716A-40 1 1 Optional
More informationPower supply unit Model: PAC-SC50KUA
Building Air Conditioning Control System Power supply unit Model: PAC-SC50KUA Installation Manual Contents 1. Safety precautions... 1 2. Product feature... 2 1. Specification... 2 2. Appearance... 2 3.
More informationTECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)
More informationTEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.
TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection
More informationOptions for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface
Options for ABB drives, converters and inverters User s manual FDPI-02 diagnostics and panel interface Table of contents Table of contents 3 1. FDPI-02 diagnostics and panel interface Safety..............................................
More information