Geothermal Installation Manual. Geothermal Installation. Manual
|
|
- Angelica Woods
- 7 years ago
- Views:
Transcription
1 Geothermal Installation Geothermal Installation Manual Manual Water To Water Water To Water January 2013 January Document 2012 Revision 1 Document Revision 1
2 January 2013 ii Spectrum Manufacturing LLC
3 Table of Contents Table of Contents iii Getting Started with the Unit 1 Safety Considerations 3 Electrical 5 January 2013 iii Spectrum Manufacturing LLC
4 Table Of Contents Condensate Drain Setup 16 Duct Work 17 System Piping 21 Importance of Water Quality 26 Desuperheater Installation 28 Smart Relay Features and Functions 30 January 2013 iv Spectrum Manufacturing LLC
5 Table Of Contents Safety Guidelines and Functions 34 Maintenance Requirements 38 Troubleshooting Tips 39 Unit Components 44 January 2013 v Spectrum Manufacturing LLC
6 Table Of Contents Unit Checkout Sheet 50 Strip Heat 51 Heating and Cooling Refrigeration 56 January 2013 vi Spectrum Manufacturing LLC
7 Getting Started with the Unit Initial Inspection Moving and Storage January Spectrum Manufacturing LLC
8 Getting Started With The Unit Model Configuration Nomenclature Tag Type Tag Capacity Tag Configuration WA Water to Air Ton U Up-flow WW Water to Water Ton D Down-flow HFC Hydronic Fan Coil Ton H Horizontal DXFC DX Fan Coil Ton S Split Ton D Domestic HWG Tag Return Air Tag Voltage Tag Desuperheater L Left 1 Single Phase 1 Yes R Right 3 Three Phase 0 No Tag Heat Exchanger Tag Backup Heat Element Tag Warranty C Copper 0 None Year N CuproNickel 1 5 KW 5 5 Year CD Copper Double Wall 2 10 KW ND CuproNickel Double Wall 3 15 KW 4 20 KW January Spectrum Manufacturing LLC
9 Safety Considerations Pre-Installation Location January Spectrum Manufacturing LLC
10 Safety Considerations Equipment Installation January Spectrum Manufacturing LLC
11 Electrical Loop Pumping Flow Centers Electrical Model Voltage Compressor DHW Pump FLA External Loop Pump Total Unit FLA Min Circuit Ampacity (MCA) Max Fuse Min AWG RLA LRA QTY FLA Total WW-024 WW-036 WW-048 WW-060 WW /1 Ø 240/1 Ø 240/1 Ø 240/1 Ø 240/1 Ø Water to Water Electrical Data January Spectrum Manufacturing LLC
12 Electrical Model Voltage Fan Blower Total Unit FLA Min. Circuit Ampacity (MCA) Min. Breaker Size Min AWG FLA HP HFC-024 HFC-036 HFC-048 HFC-060 HFC /1 Ø 240/1 Ø 240/1 Ø 240/1 Ø 240/1 Ø 2.3 1/ / / / Hydronic Fan Coil Electrical Data January Spectrum Manufacturing LLC
13 Electrical Legend WW HFCH HFCV Water to Water Hydronic Fan Coil Horizontal Hydronic Fan Coil Vertical Model Weight (lbs.) Shipping Weight Shipping Dimensions Refrigerant Charge WW 024 WW 036 WW048 WW 060 WW Lbs 6 Oz HFCH 024 HFCH 036 HFCH 048 HFCH 060 HFCH 072 HFCV 024 HFCV 036 HFCV 048 HFCV 060 HFCV 072 Unit Weights/Refrigerant Charge January Spectrum Manufacturing LLC
14 Electrical Wiring Diagram Ladder January Spectrum Manufacturing LLC
15 Electrical Wiring Diagram Pictorial January Spectrum Manufacturing LLC
16 Electrical Wiring Diagram Ladder Air Handler January Spectrum Manufacturing LLC
17 Electrical Wiring Diagram Pictorial Air Handler January Spectrum Manufacturing LLC
18 Electrical SelecTech Motor Connections January Spectrum Manufacturing LLC
19 Electrical Control Connections Wall Stat Connections 24V G Y1 Y2 O AUX Com L Function 24 Volt Fan Circulate Speed Fan Med-High Speed Fan High Speed Reversing Valve (default is energized in Cooling) Auxiliary Heat Common Fault Light Wall Thermostat Connections Aqua Stat Connections 24V Y1 Y2 C NC NO Aqua Stat Connections Function 24 Volt Compressor Operation Compressor Second Stage Common Normally Closed-Energized in Heating Normally Open- Energized in Cooling Note: The Normally Open And Normally Closed terminals are to be used with a Heating and Cooling Aqua Stats or Controller, to avoid Overheating or Freezing the Tank. January Spectrum Manufacturing LLC
20 Electrical Air Handler Connections 240 Volt Fan Breaker Motor Opt. Load Pump GND Air Handler Connections From 24Volt Pan Aux EMH Fan 1 Fan 2 Fan 3 COM GND Air Handler Connections Function Line Voltage From Building Panel Fan Blower Motor Optional Pump Output For Pumping Water To the Air Handler Ground Function Condensate Pan Level Switch Auxiliary Heat Emergency Heat Fan Speed Low Fan Speed Med/High (or where the installer prefers) Fan Speed High (or where the installer prefers Common Ground January Spectrum Manufacturing LLC
21 Electrical January Spectrum Manufacturing LLC
22 Condensate Drain Setup January Spectrum Manufacturing LLC
23 Duct Work Design Requirements Flex Duct Building Cavities and Ducts Static Losses January Spectrum Manufacturing LLC
24 Duct Work Maximum Velocities Location Main Ducts Branch Ducts Supply Outlet Face Velocity Return Grill Face Velocity Filter Grill Face Velocity Supply 900 FPM 600 FPM 700 FPM 500 FPM 300 FPM Maximum Air Velocities Duct Connections Zonal Pressure Relief January Spectrum Manufacturing LLC
25 Duct Work Duct Installation Insulation Air Tightness January Spectrum Manufacturing LLC
26 Duct Work System Air Flow January Spectrum Manufacturing LLC
27 System Piping Open Loop Systems (Ground Water) January Spectrum Manufacturing LLC
28 System Piping January Spectrum Manufacturing LLC
29 System Piping Closed Loop Systems (Ground Loop) January Spectrum Manufacturing LLC
30 System Piping Pressurized Flow Center Installation Non-Pressurized Flow Center Installation January Spectrum Manufacturing LLC
31 System Piping January Spectrum Manufacturing LLC
32 Importance of Water Quality Antifreeze Overview January Spectrum Manufacturing LLC
33 Importance of Water Quality Antifreeze Characteristics Antifreeze Charging January Spectrum Manufacturing LLC
34 Desuperheater Installation Desuperheater Package January Spectrum Manufacturing LLC
35 Desuperheater Installation Desuperheater Piping January Spectrum Manufacturing LLC
36 Smart Relay Features and Functions Sequence of Operations January Spectrum Manufacturing LLC
37 Smart Relay Features and Functions January Spectrum Manufacturing LLC
38 Smart Relay Features and Functions Unit Checkout Sheet Short Cycle Protection January Spectrum Manufacturing LLC
39 Smart Relay Features and Functions Component Delays Manual (24 Volt Disconnect Switch Inside Panel) Electronic Condensate Overflow Protection January Spectrum Manufacturing LLC
40 Safety Guidelines and Functions High Pressure Low Pressure January Spectrum Manufacturing LLC
41 Safety Guidelines and Functions Flow Switch Condensate Overflow Fault Retry Mode Soft Reset January Spectrum Manufacturing LLC
42 Safety Guidelines and Functions Hard Lockout System Checkout Unit Startup January Spectrum Manufacturing LLC
43 Safety Guidelines and Functions January Spectrum Manufacturing LLC
44 Maintenance Requirements Annual Maintenance Lockouts January Spectrum Manufacturing LLC
45 Troubleshooting Tips Troubleshooting Problem/Issue Possible Cause Actions and Corrections Entire unit will not run. Power supply is off Circuit breaker Apply power and close disconnect. reset circuit breaker. Voltage supply low If voltage is below minimum voltage specified on unit data plate, contact local power company. Thermostat/Aquastat Set the fan to On. The fan should run. Set thermostat to Cool and lowest temperature setting, the unit should run in the cooling mode. Set unit to Heat and the highest temperature setting, the unit should run in the heating mode. If neither the blower nor compressor run in all three cases, the thermostat or Aquastat could be wired incorrectly or faulty. To ensure correct wiring or faulty Aquastat, verify 24 volts is available on the low voltage terminal strip in the compressor section between "R" and "C", "Y" and "C", and, if in cooling mode, "O" and "C". When utilizing an air handler, and the blower does not operate, verify 24 volts between terminals "G" and "C". Replace the thermostat if defective. January Spectrum Manufacturing LLC
46 Troubleshooting Tips Problem/Issue Possible Cause Actions and Corrections Compressor does not run. Wiring Check for loose or broken wires at compressor, capacitor, or contactor. PLC reads High Pressure Check Unit Or HARD LOCKOUT HI PRESSURE Safety controls Capacitor Compressor overload open Compressor motor grounded Compressor windings open Discharge pressure too high Check Smart Relay screen for faults. Check capacitor and replace if defective. If the compressor has cooled down and the overload will not reset, replace compressor. Internal winding grounded to the compressor shell. Replace compressor. If compressor burnout has occurred, install suction filter dryer. After compressor has cooled, check continuity of the compressor windings. If the windings are open, replace the compressor. In Cooling mode, check: Lack of or inadequate water flow Entering water temperature too warm Scaled or plugged condenser In Heating mode check: Lack of or inadequate air flow Blower is inoperative, clogged filter or restrictions in ductwork Refrigerant charge High pressure The unit is overcharged with refrigerant. Reclaim refrigerant, evacuate and recharge with factory recommended charge. Check for defective or improperly calibrated high pressure switch. January Spectrum Manufacturing LLC
47 Troubleshooting Tips Problem/Issue Possible Cause Actions and Corrections PLC reads: Low Pressure Check Unit, or HARD LOCKOUT LOW PSI. Suction pressure too low In Cooling mode, check: Lack of or inadequate air flow Entering water temperature too cold Blower is inoperative, clogged filter or restrictions in ductwork In Heating mode check: Lack of or inadequate water flow Entering water temperature too cold Scaled or plugged condenser Check refrigerant charge. Always charge to nameplate. Refrigerant charge Low pressure switch TXV Bulb may be defective/severed, TXV valve stuck shut, or moisture in the refrigerant system The unit is low on refrigerant. Check for refrigerant leaks. Repair, evacuate and recharge with factory recommended charge. Check for defective low pressure switch. TXV bulb and TXV control diaphragm can be replaced after removing the charge, replacing the control device and bulb, and properly recharging the unit to nameplate value. Unit Short Cycles Unit oversized Adjust deadband on aquastats Wiring and controls Loose connections in the wiring or a defective compressor contactor. Insufficient cooling Unit undersized Recalculate heating and or cooling loads. January Spectrum Manufacturing LLC
48 Troubleshooting Tips Problem/Issue Possible Cause Actions and Corrections Insufficient heating Loss of conditioned air by leaks Check for leaks in duct work or look for entering ambient air through doors or windows. Airflow Refrigerant charge Compressor Reversing valve Operating pressures TXV Moisture, noncondensables Lack of adequate air flow or improper distribution of air. Replace dirty filter. Low on refrigerant charge causing poor operation. Check for defective compressor. If discharge is too low and suction pressure is too high, compressor is not pumping properly. Replace compressor. Defective reversing valve creates a bypass of refrigerant from discharge to suction side of compressor. Replace reversing valve. Compare unit operating pressures to a pressure/ temperature chart for the refrigerant used. Check TXV for restriction or defect. Replace if necessary. The refrigerant system may be contaminated with moisture or noncondensables. Reclaim refrigerant, evacuate and recharge with factory recommended charge. NOTE: A liquid line dryer may be required. PLC Reads: HARD LOCKOUT FLOW SWITCH PLC Reads: HARD LOCKOUT PAN LEVEL PLC Reads: HARD LOCKOUT CURRENT SENS Troubleshooting Tips Loss of conditioned air by leaks Inadequate or no water flow Pan level switch Current sensor Check for leaks in duct work or entering ambient air through doors or windows. Check for water flow. Check flow switch by temporarily bypassing it. Make sure all air is purged from lines. Make sure flow center is purged and functional. Check for proper flow direction. Check condensate drain for blockage. Make sure condensate drain is properly installed. Check Pan level switch by temporarily bypassing it. Make sure unit is on a level surface. Refer to compressor does not run. Check current sensor by temporarily bypassing it. January Spectrum Manufacturing LLC
49 Troubleshooting Tips January Spectrum Manufacturing LLC
50 Unit Components Compressor (Copeland) Flow Switch High Pressure Switch Low Pressure Switch Low Voltage Breaker High Voltage Breakers January Spectrum Manufacturing LLC
51 Unit Components Master Contactor Reversing Valve Smart Relay Terminals Transformer Remote Fan Coil Components Pump Relay January Spectrum Manufacturing LLC
52 Unit Components High Voltage Breaker Blower Motor (Selectech) Electric Heater Terminals January Spectrum Manufacturing LLC
53 Unit Components Unit Dimensions January Spectrum Manufacturing LLC
54 Unit Components January Spectrum Manufacturing LLC
55 Unit Components January Spectrum Manufacturing LLC
56 Unit Checkout Sheet Customer Data Name: Address: Date: Phone: Make: Model: Serial #: Refrigerant Charge (OZ): Compressor RLA: Compressor LRA: Blower FLA/HP: Maximum Fuse Size (A): Maximum Circuit Ampacity (A): Operating Conditions Cooling Mode Heating Mode EAT/LAT / / EWT/LWT / / January Spectrum Manufacturing LLC
57 Strip Heat Model KW Amps Min. CFM KS KS SCCR 10 KA 250V MAX. 10KA 250V MAX. Min. Supply Ampacity Max Overcurrent Protection Multi-Feed Single Feed 30 N/A 30 A 50 N/A 50 A KS KA 250V MAX. 80 #1 30 A #2 50 A 80 A KS KA 250V MAX. 100 #1 30 A #2 50 A 100 A 240 Volts Single Phase Note: When using multi-feed, metal jumpers in the screw connection terminals must be removed January Spectrum Manufacturing LLC
58 Strip Heat January Spectrum Manufacturing LLC
59 Strip Heat January Spectrum Manufacturing LLC
60 Strip Heat January Spectrum Manufacturing LLC
61 Strip Heat January Spectrum Manufacturing LLC
62 Heating and Cooling Refrigeration When the Compressor (1) is energized, it starts to pump refrigerant through the system. Because of the compressor increasing the pressure of the refrigerant, it therefore increases the temperature and has compressed it into a high pressure HOT vapor, (Superheated Gas) Then, in systems equipped with a Desuperheater (2), (hot water generator) the high pressure vapor will go through and release some of its superheat into the home's Potable Water. The hot vapor then goes to the Reversing valve (3). In the Heating Cycle, the reversing valve will direct the hot vapor to a Water to Refrigerant Heat Exchanger (4) (Condenser), where it will be condensed to a liquid. This Heat Exchanger is typically connected to an insulated storage tank inside the home. As it travels through the Heat Exchanger, the hot vapor will release its stored heat into the Water from the storage tank. This is considered condensing, (the action of changing a vapor or gas, to a liquid). At the end point of the Water to Refrigerant Heat Exchanger (Condenser), the refrigerant is a high pressure sub-cooled liquid. Sub-cooling is the cooling of liquid refrigerant below its condensing temperature. The high pressure liquid then enters the Expansion Valve (5). This device reduces the pressure from the high side to the low side in a refrigeration system. This is accomplished by metering the liquid refrigerant into the evaporator coil. This rapid decrease in pressure lowers the temperature of the refrigerant considerably. In the Heating Cycle of a, the Evaporator (6) is also a water to refrigerant heat exchanger. This Heat Exchanger is typically connected to a ground loop. The refrigerant at the start point of the evaporator is in a low pressure, cold, vapor and liquid mixture. As it travels through the evaporator (water to refrigerant heat exchanger) it begins to collect heat from the ground water that is also traveling through the coil. As the refrigerant absorbs heat, it will start to vaporize (changing from a liquid to a gaseous state). When it has left the evaporator, the refrigerant is a 100% saturated vapor. At this point, it will enter the compressor to begin the cycle again. January Spectrum Manufacturing LLC
63 Heating and Cooling Refrigeration When the Compressor (1) is energized, it starts to pump refrigerant through the system. Because of the compressor increasing the pressure of the refrigerant, it therefore increases the temperature and has compressed it into a high pressure HOT vapor, (Superheated Gas). Then, in systems equipped with a Desuperheater (2), (hot water generator) the high pressure vapor will go through and release some of its superheat into the home's Potable Water. The hot vapor then goes to the Reversing Valve (3). In the Cooling Cycle, the reversing valve directs the hot vapor to the Water to Refrigerant Heat Exchanger (4) (Condenser) that is connected to the ground water, where it will be condensed to a liquid. As it travels through the Heat Exchanger, the hot vapor will release its stored heat into the Water from the ground. This is considered condensing, (the action of changing a vapor or gas, to a liquid). At the end point of the Water To Refrigerant Heat Exchanger (Condenser) the refrigerant is a high pressure sub-cooled liquid. Sub-cooling is the cooling of liquid refrigerant below its condensing temperature. The high pressure liquid then enters the Expansion Valve (5). This device reduces the pressure from the high side to the low side in a refrigeration system, by metering the liquid refrigerant into the evaporator coil. This rapid decrease in pressure lowers the temperature of the refrigerant considerably. In the Cooling Cycle of a, the Evaporator (6) is also a Water To Refrigerant Heat Exchanger. Because we have directed the HOT vapor to the Ground Water Heat Exchanger for the condensing cycle, the storage tank in the home is now connected to the Evaporator Coil (also a Water to Refrigerant Heat Exchanger). The refrigerant at the start point of the evaporator is in a low pressure, cold, vapor and liquid mixture. As it travels through the evaporator (water to refrigerant heat exchanger) it begins to collect heat from the water that has come from storage tank. As the refrigerant absorbs heat it will start to vaporize (changing from a liquid to a gaseous state). When it has left the evaporator, the refrigerant is a 100% saturated vapor. At this point it will enter the compressor to begin the cycle again. January Spectrum Manufacturing LLC
64 Heating and Cooling Refrigeration January Spectrum Manufacturing LLC
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
More informationTable Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More information543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
More informationIt will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
More informationEngineering Specifications
Engineering Specifications NORDIC W-85-H-B-*S-PD Water to Water Heat Pump Single-Stage R134a Nominal 7.5 Ton With Double Wall Condenser for Domestic Hot Water Production Maritime Geothermal Ltd. P.O. Box
More informationSERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
More informationINSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard
More informationESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
More informationLOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationService Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
More informationCustomized Assessment Blueprint
Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationREFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca
More informationR22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
More informationHeat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
More informationCircuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
More informationWMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility
More informationMiami Heat Pump HP Series Installation Guide
CAUTION- THIS UNIT IS FOR INDOOR USE ONLY!! WARNING BEFORE ANY INSTALLATION OR MAINTANCE IS STARTED PLEASE READ COMPLETE INSTLLATION GUIDE. INSTALLATION START-UP AND SERVICE INSTRUCTION- The HP Water Source
More informationA.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
More informationRefrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
More informationT-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177
T-SERIES Air Conditioners T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177 88043249 TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER...3 HANDLING AND
More informationIndoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
More informationAny Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationTest Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
More informationModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner
More informationCompressor Service & Maintenance Manual
Compressor Service & Maintenance Manual C Series COMPRESSOR (D)C1103 (D)C1203 (D)C2106 (D)C2206 (D)C3210 Copyright 2006 DCI. All Rights Reserved. 92311, Rev. C, 08/13 1 C1000 Series Service & Maintenance
More informationTHERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
More informationHoshizaki America, Inc.
Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1301SAH/3, SWH/3, SRH/3 KM-1400SWH-M, SWH3-M KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3 KMH-2000SWH/3,
More informationMAINTENANCE INSTRUCTIONS. Thermia Robust heat pump
MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................
More informationOwners Manual. Refrigerated Air Dryer. HX75 thru HX2400
Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION
More informationCOMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
More informationEngineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
More informationCDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
More informationHeater and Air Conditioner, Blend Air System, Troubleshooting 83.06
A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationEvaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationHVAC-02, Air Conditioning Troubleshooting and Repair
HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationTroubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
More information14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
More informationHeating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
More informationCOMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
More informationTechnical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
More informationChilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
More informationICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t. www.ice-air.com
80 Hartford Avenue Mount Vernon New York 10553 Tel: 914-668-4700 EXT. 203 Fax: 914-668-5643 www.ice-air.com Wo r l d C l a s s C o m f o r t Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationCentral Air Conditioning Plants
Central Air Conditioning Plants In our department, these plants (Air cooled or water cooled) are commonly available above 10 TR up to 100 TR. These types of plants are more suitable for large installations
More informationRefrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
More informationGeothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationTWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
More informationON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
More informationCharacteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
More informationPackaged Glycol Chiller Systems Operation Manual
Packaged Glycol Chiller Systems Operation Manual ii Pro Refrigeration, Inc Contents 1 Preface iii CUSTOMER SERVICE MANUFACTURE S INFORMATION RECEIVING & UNLOADING WARNINGS & CAUTIONS iii iii iii iii PRO
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationCommissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
More informationFailure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
More informationSPACE COOLERS. P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com. The leader in packaged Space Cooling.
SPACE COOLERS P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com The leader in packaged Space Cooling. 2 Table of Contents Description Space Cooler from Coil Company. A
More informationINSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-234 E Supersedes: 2100-234
More informationDealer Sales & Service Guide
Analog Models w/thermostat or Timerstat Heat Siphon Not Starting 1 BREAKER TRIPPED - Check Breaker Box for correct size breaker Breakers: EX; Domestic model 2.25hp (20amp) 3.25hp (40amp) 5hp (50amp) check
More informationLG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
More informationWON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationGLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
More informationT-Series Air Conditioner T62 Model
INSTRUCTION MANUAL T-Series Air Conditioner T62 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
More informationFan Coil EC Motor Control
Fan Coil EC Motor Control G3 PWM BARD The Enviro-Tec Generation 3 PWM (G3 PWM) board provides a pulse-width modulated (PWM) signal to the EC motor to control fan speed. The board is factory programmed
More informationTransport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.
R Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL for SPLIT SYSTEM Bus Air Conditioning Units T--326 Rev -- OPERATOR S MANUAL BUS AIR CONDITIONING UNITS GEN IV & GEN V CONTENTS
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationScholar QV Heat Pumps & Air Conditioners
MANUFACTURER CERTIFIED TO ARI AS COMPLYING WITH R ARI STANDARD 210 Scholar QV Heat Pumps & Air Conditioners (CSI 15740) MAINTENANCE & SERVICE Model VAI 2, 5, 3, 5, 4 & 5 Tons CAUTION!! Read all instructions
More informationAFE424 SERVICE PARTS
This is the parts list for the AFE. When looking up part numbers, always check the complete model and serial numbers to be certain of ordering the correct parts. The Air Cooled model has also been manufactured
More informationNO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
More informationSingle Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
More informationCOMPRESSOR REPLACEMENT PROCEDURE
R-22 and R-410A COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003F Supersedes 2100-003E File: Volume I,
More informationCONTROLS KITS AND ACCESSORIES. 507240-01 12/2014 Supersedes10/2014
2014 Lennox Industries Inc. Dallas, Texas, USA CONTROLS KITS AND ACCESSORIES 507240-01 12/2014 Supersedes10/2014 Litho U.S.A. Equipment Interface Module Installation Instructions for the Equipment Interface
More informationECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
More informationAerosphere Midibus. Air Conditioning System. Operation Manual. Aerosphere Midibus 05/2013 P.N. 10000038A
Air Conditioning System Operation Manual Aerosphere Midibus 05/2013 P.N. 10000038A To receive the best performance from the air conditioning system, we suggest carefully reading this manual before operating
More informationINSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
More informationFirst irst Co. Products
First irst Co. Products Recommended Maintenance Program PM1193 FIRST OPERATIONS,LP - P.O. Box 270969 - Dallas, Texas 75227 - www.firstco.com Table of Contents Introduction... 3 General Precautions... 3
More informationNSN 4120-01-21 4-3692
*TM 9-4120-388-14 TECHNICAL MANUAL Operator s, Unit, Direct Support, And General Support Maintenance Manual AIR CONDITIONER, VERTICAL, COMPACT, 18,000 BTU/HR 208 VOLT, 3 PHASE, 50/60 HERTZ NSN 4120-01-21
More informationModels: WA182, WA242. Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List... 4. Control Panel.
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE AIR CONDITIONER Models: WA182, WA242 General Notes! Revised and/or additional pages may be issued from time to time.! A complete and current manual consists
More informationInstallation Instructions
05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:
More informationCOMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
More informationINSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount
More informationPROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
More informationCC145. Air Conditioning System. Operation Manual. CC145 Compact Cooler 4/2013 P.N. 10000034A
Air Conditioning System Operation Manual CC145 Compact Cooler 4/2013 P.N. 10000034A To receive the best performance from the air conditioning system, we suggest carefully reading this manual before operating
More informationARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
More informationREAD AND SAVE THESE INSTRUCTIONS. INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC, NEC AND LOCAL ELECTRICAL CODES.
16EC SERIES UPFLOW PACKAGED TERMINAL AIR CONDITIONERS Electric Heating and Cooling Unit Cooling - Only Unit INSTALLATION & OPERATION MANUAL IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. INSTALLATION AND
More informationEXTENDED 10 YEAR LIMITED LIFETIME WARRANTY LIMITED LIFETIME WARRANTY
EXTENDED 10 YEAR LIMITED LIFETIME WARRANTY Spectrum Manufacturing warrants that the heat pumps and air handling equipment (if purchased with a Water to Water System) manufactured by Spectrum Manufacturing
More informationTroubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
More informationName of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
More informationInstallation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
More informationHow To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
More informationFossil fuel heating equipment
Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating
More informationCooling/Heat Pump Convertible Air Handlers
Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way
More informationModel READ / SEAD Self Contained Cooling / Electric Heating Units
Model READ / SEAD Self Contained Cooling / Electric Heating Units Supersedes: 145.31-IOM1 (708) Form 145.31-IOM1 (908) UNIT MODELS READ / SEAD - R410A ELECTRIC HEATING / ELECTRIC COOLING INSTALLATION,
More informationCondensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
More information